Page 1: UV-C Manual English June 2010

1

June 2010

K I T C H E N

V E N T I L A T I O N

WAARSCHUWING

ALLEEN OPSTARTEN DOOR

BEVOEGD EN GEKWALIFICEERD

PERSONEEL

WAARSCHUWING

UV-C LUIK ALLEEN OPENEN

DOOR BEVOEGD EN

GEKWALIFICEERD PERSONEEL

Vianen Kitchen Ventilation

Edisonweg 15, 3442 AC Woerden, P.O.Box 163, 3440 AD Woerden, Holland

E-mail: [email protected], Internet: www.vianenkvs.nl

Tel: + 31.348.416300, Fax: +31.348.421595,

WARNING

START UP ONLY BY AUTHORIZED AND QUALIFIED PERSONNEL

W A R N I N G

OPEN UV-C DOOR BY

AUTHORIZED AND QUALIFIED

PERSONNEL ONLY

Page 2: UV-C Manual English June 2010

2

June 2010

Important warning:

UV-C is harmful to the eyes. The

UV-C lamps MUST be off when

servicing or when changing filters.

CHECK THE DISPLAY OF THE

CONTROL CABINET.

Manual – Vianen UV-C System

1. Instructions:

This manual contains important security information and operating instructions. It is

important that the operators read the instruction manual carefully before operating

the Vianen UV-C System.

2. In general:

For security purposes ensure all operators are fully instructed and are familiar with the

operating manual before starting up the system as the manual contains important

information for operating and maintenance of the installation.

This manual is provided with the delivery of the equipment.

Ensure all criteria for secure operation is fully complied with before start up.

Only authorized and qualified personnel may perform installation, operation and

maintenance.

No changes are to be performed to the equipment, without prior consultation with

Vianen B.V., as this can affect the safety of the installation. Vianen B.V. will not be

held responsible for damages caused by unauthorized changes to the installation

and incorrect operation and application by the owners and operating personnel.

N.B. This manual should be accessible at all times to operating personnel.

Page 3: UV-C Manual English June 2010

3

June 2010

3. The Vianen UV-C System

The Vianen UV-C System utilises a Photo Light Oxidation-technique, which produces

ozone through UV-C lamps. The ozone reduces organic substances in the air due to

the oxidation process. The lamps are mounted in a stainless steel frame, which is

installed in the hood behind the grease filters. The protein chains in the fat and

grease are broken down by the intense UV-C radiation allowing the ozone to reduce

the organic substances.

Any leftover of non-reacted ozone automatically turns into oxygen (02).

The ozone produced by the UV-C does not turn into nitrogen oxide (NOx)

Ozone is an environmental-friendly gas, existing in the nature and decomposes in the

atmosphere.

4. Installation of the Vianen UV-C System.

During installation the lamps must be protected from dirt and grease and must be

handled with clean gloves at all times.

4.1 Receiving the delivery.

The packaging of the Vianen UV-C System must be controlled for possible transport

damages. Damages are to be immediately reported to Vianen B.V. Check that the

delivery is complete and in accordance with the packaging list.

4.2 Mechanical installation

The UV-C system is to be installed such that the duct allows a reaction time of a

minimum of two seconds whilst passing through the duct. This is necessary for the

oxidation process. Control the calculation of the air velocity with the length of duct.

N.B. As the UV-C system cleans air using ozone-oxidation no other ducts are to be

connected to the UV-C duct.

4.3 Electrical installation

The electrical installations must conform to local directives.

The location of the control cabinet is designed and constructed for indoor

conditions, and must be installed in a ventilated area, with an ambient temperature

not exceeding 30° C. The control cabinet must be placed where it can be controlled

on a daily basis. A switch must be installed between the main electrical supply and

the control cabinet.

Page 4: UV-C Manual English June 2010

4

June 2010

Control panel: Lay out

On/Off switch; - On - Off

:- When pressed once for longer than 10 seconds the display will

indicate if the lamps are in operation

:- When pressed twice the display will indicate the number of hours the

lamps have been on

:-When pressed for the third time a sub-menu will appear – this is the

configuration menu (AUTHORISED PERSONS ONLY)

Reset switch : Resets messages displayed on screen

Arrow Up : - Changes values of the configuration menu

Arrow Down : - Changes values of the configuration menu

Messages : -During normal working conditions the text UV= 2,3Amps REF=0. Will

display indicating the electrical power consumption (in amps) which

is being used by the UV-C lights

Configuration menu : (authorised persons only).

a. To set the maximum and minimum levels of electrical power press the

arrow up and down

b. With the up and down arrows pressed simultaneously resets the hour

counter

Page 5: UV-C Manual English June 2010

5

June 2010

Errors indicated on the display:

a. FAN-OFF : No current Amps on extraction fan

b. Check Door UVC : Service hatch for UV-C lights is open

c. Check-Filters : Grease filters not in place or complete

d. Check lamps : One or more lamps are broken

(fused - lamps have black ends)

After the system has been running for 7500 hours a warning on the display will

appear “Change Lamps” - this message will remain until 8000 hours are

reached. This is the lifetime of the lamps and the system will automatically

stop if not replaced.

Once the lamps have been replaced the hour counter needs to be reset.

Connection to external signals:

The electrical connection to the fan must be such that the lamps can only operate

when the fan is on and air is passing through the system. This is a very important to

prevent overheating.

Pressure guard for monitoring of the static pressure drop of the grease filters.

Connection of Vianen UV-C system-frames.

The cables from the UV-C system are to be connected in the control cabinet.

4.4 Protection of cables

Appropriate protection of the cables must be ensured at all times.

4.5 Protection during mechanical installation

During installation the Vianen UV-C system must be placed on a secure and flat

surface in a horizontal position. The frames are fragile and must not be subjected to

vibrations and must not be dropped.

4.6 Commissioning

a. Check all the fans are operating correctly

b. Check that there is sufficient ventilation at normal operation level.

c. Check all wiring to the distribution boxes and that they are correctly

connected to the control cabinet

d. Check that all the grease filters are in place

Page 6: UV-C Manual English June 2010

6

June 2010

e. Check that the UV-C lamps are not damaged

5. Operational start-up

Preparation:

The authorised personnel must read and understand the operational instructions. The

personnel must have knowledge of security and safety regulations, and other

relevant (local) directives.

Operational and maintenance instructions:

Lamp frames

The lamps are assembled in a sturdy frame of stainless steel. The frame contains two

special transformers. Each frame has its own connecting cable, which is to be

disconnected prior to installation. Only authorized and skilled electricians may open

the electrical section of the UV-C frames.

UV-C lamps

The lamps must be clean for maximum effect and production of ozone. If not clean

fat will stick on and burn into the lamps with a reduction in the air cleaning capacity.

If necessary spray the lamps with a mild cleaning detergent with a high pH Value

(>13) then carefully wipe the lamps with a soft and damp cloth using gloves for

personal protection. Ensure personal protective clothing is used at all times during

installation and servicing of the system.

Cleaning frequency depends on the stress on the lamps. For example, when the

production in the kitchen is at a higher level than normal the cleaning frequency

must be increased.

At normal operating levels it is expected that the frequency be every second month

and subsequently higher at greater production levels. The type of cooking involved

will also influence the cleaning frequency. A maintenance schedule must be

implemented and maintained once the system has been commissioned and is in

operation.

Page 7: UV-C Manual English June 2010

7

June 2010

6. Changing the UV-C lamps

WARNING

Close down the UV-C system completely before removing the grease filters or

opening the service hatches. The blue UV-C light is harmful to eyes and health.

Required tooling: Phillips screwdriver, mild detergent, water, brush or soft cloth.

The lamps are mounted in stainless steel frames and are connected by a multi

contact in the service box left or right side of the frame.

6.1 Shut down the power to the control cabinet

6.2 Remove the grease filters

6.3 Open both end panels of the stainless steel UV-C frames

6.4 Disconnect the speed clamps on the lamps

6.5 Disconnect the lamps from their contacts by removing the wiring from

the lamps and slide them out from their silicone protection rings

6.6 N.B.: The lamps are very delicate and break easily.

6.7 N.B.: New silicone protection rings must be inserted at every lamp change

6.8 Clean the lamps if necessary with a mild detergent and water and dry

the lamps

6.9 Carefully insert a new lamp and re-connect the speed clamps

6.10 Re-connect the electric wiring

6.11 Close the end panels of the stainless steel UV-C frames

6.12 Close the service hatch

6.13 Replace the grease filters.

Page 8: UV-C Manual English June 2010

8

June 2010

7. Safety Warnings

UV-C lamps are harmful to human eyes. Do not look directly into the lamps If the

eyes are exposed contact a doctor immediately!

UV-C lamps must automatically switch off when the exhaust fan is switched off.

When removing grease filters the UV-C lamps switch off the lamps and exhaust fan

automatically.

Always use the protective safety clothing and glasses.

The lamps must be cleaned at regular intervals according to the maintenance

schedule.

Check the Operational counter (time) on the control cabinet on a regular basis.

The UV-C lamps have a life span of approximately 8000 hours and must be changed

before this point.

If the cooking equipment beneath the UV-C system is changed, Vianen B.V. must be

informed to reset airflow volume and velocity.

Page 9: UV-C Manual English June 2010

9

June 2010

8. The working of the control panel and display

During normal working conditions the display indicates the electrical power

consumption in Amps used by the UV-C lamps and the preset setting. If the power

drops below this value the following error appears on the display:

8.1 Press On/off switch for short time and “Hour counter”appears in the

display

8.2 Press again and power is back.

8.3 Press again for a little longer and the UV-C system switches off.

Page 10: UV-C Manual English June 2010

10

June 2010

The working of the control panel and display

Problem with UV-C lamps refer to Paragraph 6 of this manual section: Changing of

UV-C lamps.

Press reset button for 10 seconds to remove message from display.

Page 11: UV-C Manual English June 2010

11

June 2010

The working of the control panel and display

Ventilator is not working - no power ventilator - check electrical connection.

Page 12: UV-C Manual English June 2010

12

June 2010

The working of the control panel and display

Last grease filter removed or not installed properly

- If not working the possible cause is that the Pressure Sensor is situated

above the arrow in the gutter under the last placed filter in the filter

bank is not activated.

Check that the filter is firmly in position.

Page 13: UV-C Manual English June 2010

13

June 2010

The working of the control panel and display

Check Filters : grease filter bank not complete which causes a pressure difference or

pressure switch is not adjusted correctly / broken.

- The pressure difference switch is situated behind the filter in the electrical part

of the UV-box. For exact position of the difference switch look directly above

the arrow on the gutter next to the grease tray.

- Check if the fan is functioning properly.

Page 14: UV-C Manual English June 2010

14

June 2010

The working of the control panel and display

CHANGE LAMPS :

After 7500 working hours of the lamps this message will appear on the display

Prepare to change lamps in the next 500 hours.

With the reset button message can be removed press reset for more than 10

seconds.

When 8000 hours are reached lamps must to be changed. See paragraph 6 of this

manual . On display the message “Lamps out” will appear this message can only be

removed by resetting the hour counter.

After changing of lamps the hour counter must be reset to zero. See 4.3 electrical

installation of this manual.

Warning: UV-C System will switch off at 8000 hours.

Page 15: UV-C Manual English June 2010

15

June 2010

RESETTING OF THE HOUR COUNTER:

Press OFF/ON button for more than 10 seconds

Entry configuration menu

Press both arrow buttons

Hour counter disappears on display

Press both arrow buttons longer than 3 seconds. Hour counter returns to 0

Page 16: UV-C Manual English June 2010

16

June 2010

POWER LIMIT ADJUSTMENT

To set the limit of the electrical power in Amps first determine the total power

consumption used by all the lamps

Set the limit at minus 10 percent.

Press OFF/ON button for more than 10 seconds

Entry configuration menu

Arrow up higher A Arrow down lower A

Page 17: UV-C Manual English June 2010

17

June 2010

Page 18: UV-C Manual English June 2010

18

June 2010

Page 19: UV-C Manual English June 2010

19

June 2010

Page 20: UV-C Manual English June 2010

20

June 2010

Page 21: UV-C Manual English June 2010

21

June 2010

Page 22: UV-C Manual English June 2010

22

June 2010