Upflow/ Horizontal Downflow /Horizontal Condensing, Direct Vent Gas-Fired Furnace
PUB. NO. 22-1859-01
XT 95TUH1B040A9H21A, TUH1B060A9H31A, TUH1B080A9H31A, TUH1C100A9H41A, TUH1D120A9H51A TDH1B040A9H21A, TDH1B065A9H31A, TDH1C085A9H41A, TDH1D110A9H51A
High Efficiency Single-Stage Fan Assisted Combustion System
TDH1-HDOWNFLOW
DOWNFLOW/HORIZONTAL
TUH1-HUPFLOW
TUH1-HUPFLOW/HORIZONTAL
TDH1-H
© 2011 Trane All Rights Reserved 2 22-1859-01
GeneralFeatures
NATURAL GAS MODELSCentral Heating furnace designs are certified to ANSI Z21.47 / CSA 2.3 for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating condi-tions using American National Stan-dards Institute standards.
SAFE OPERATIONThe Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.
QUICK HEATINGDurable, cycle tested, heavy gauge alu-minized steel heat exchanger quickly transfers heat to provide warm condi-tioned air to the structure. Low energy power vent blower, to increase effi-ciency and provide a positive discharge of gas fumes to the outside.
BURNERSMultiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROLExclusively designed operational pro-gram provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service. Also contains connec-tion points for E.A.C./humidifier.
AIR DELIVERYThe four speed, direct drive blower motor, has sufficient airflow for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.
STYLINGHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchang-er section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient opera-tion due to the excellent acoustical and insulating qualities of fiberglass. Built-in bottom pan and alternate bottom, left or right side return air connection provision.
FEATURES AND GENERAL OPERATIONThe XT95 High Efficiency Gas Furnaces employ a Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access.
a. Low energy power venter
b. Vent proving pressure switch.
Features and Benefits
XT95 Standard Equipment• Powersupply115/1/60
• Convertibletohorizontalwithleftofright airflow
• Type 29-4C™ stainless steel second-ary heat exchanger
• Innerblowerdoors
• ConstanttorqueECMblowermotor
• SiliconNitrideigniterwithadaptiveheat up
• Accessoryhook-upcapability– Hum and EAC
• Quietinduceddraftblower
• Blowerdoorsafetyswitch
• Dualsolenoidcombinationgasvalve®ulator
• PVCventing–1or2pipeventoption
• Left/rightgasconnection
• Selectablecoolingfanoffdelayelimi-nates need for BAY24X045 time delay relay
• Singlewiretwinning
• Integratedsolidstatecontrolwithself-diagnostics
• 24voltfuse
• Manualresetburnerboxlimit
• Optional extended warranties
22-1859-01 3
Contents
General Features 2Features and Benefits 2
XT95 Standard Equipment 2XT95 Optional Equipment 4
General Data 5TUH1B040A9H21A 5TUH1B060A9H31A 5TUH1B080A9H31A 5TUH1C100A9H41A 6TUH1D120A9H51A 6TDH1B040A9H21A 7TDH1B065A9H31A 7TDH1C085A9H41A 7TDH1D110A9H51A 7
Performance Data 8Electrical Data 10Field Wiring 14Twinning Field Wiring 15Dimensions 16
4 22-1859-01
Features and Benefits
XT95 Optional EquipmentComfort Control, XL803, Programmable 7 Day, 3-Ht, 2-Cl ...........................................................................TCONT803AS32DA [ ]Comfort Control, XR402, Electric, 3-Ht, 2-Cl (Non-programmable) ..............................................................TCONT402AN32DA [ ]For additional comfort control choices, see the product catalog or quick select handbookPropane Conversion Kit ........................................................................................................................................BAYLPKT210B [ ]Propane Conversion Kit (stainless steel burners).................................................................................................BAYLPSS210B [ ]Downflow Subbase .................................................................................................................................................BAYBASE205 [ ]Filter Access Door Kit ..............................................................................................................................................BAYFLTR206[ ]Side Filter Rack .......................................................................................................................................................BAYFLTR200 [ ]High Altitude Pressure Switch Kit TUH1B040, TDH1B040, TDH1C085 .......................................................BAYSWT01AHALTA [ ]HighAltitudePressureSwitchKitTUH1B060,TUH1D100,TUH1D120 ......................................................BAYSWT04AHALTA [ ]High Altitude Pressure Switch Kit TUH1B080, TUH1C100, TDH1D110 ...................................................BAYSWT05AHALTA [ ]High Altitude Pressure Switch Kit TUH1C080 ..........................................................................................BAYSWT11AHALTA [ ]HighAltitudePressureSwitchKitTDH1B065 ..........................................................................................BAYSWT12AHALTA [ ]Concentric Vent Kit .........................................................................................................................................BAYAIR30AVENTA [ ]Sidewall Vent Termination Kit ............................................................................................................................... BAYVENT200B [ ]Manufactured/Mobile Home Kit .......................................................................................................................... BAYMFGH100A [ ]
22-1859-01 5
General Data
PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea
level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above
sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor
TUH1B040A9H21AUpflow/Horizontal
40,00038,000
9530-60
DIRECT10 x 7
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/55 - 3000115/1/60
1.00Yes
High Velocity1 - 17x25 - 1in.
2 Round
Alum. Steel
20
2—452—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
2115/1/60
9.7151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
139 / 129
TUH1B060A9H31AUpflow/Horizontal
60,00057,000
9530-60
DIRECT10 x 7
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/15 - 3450115/1/60
1.75Yes
High Velocity1 - 17x25 - 1in.
2 Round
Alum. Steel
20
3—453—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
3115/1/60
10.4151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
150 / 140
TUH1B080A9H31AUpflow/Horizontal
80,00076,000
9535-65
DIRECT10 x 8
14
See Fan Performance Table1/2
1075115/1/60
CentrifugalDirect - 1
1/20 - 3450115/1/60
0.71Yes
High Velocity1 - 17x25 - 1in.
3 Round
Alum. Steel
20
4—454—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
4115/1/60
9.4151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
158 / 148
6 22-1859-01
General Data
TUH1D120A9H51AUpflow/Horizontal
110,000104,500
9540 - 70
DIRECT11 x 10
14
See Fan Performance Table1
1100115/1/60
CentrifugalDirect - 1
1/20 - 3450115/1/60
.71Yes
High Velocity1 - 24x25 - 1in.
3 Round
Alum. Steel
20
6—456—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
6115/1/60
14.1201/2
H x W x D41-3/4x26-1/2x30-1/2
205 / 193
TDH1B040A9H21AUpflow/Horizontal
40,00038,000
9530-60
DIRECT10 x 7
14
See Fan Performance Table1/2
1080115/1/60
CentrifugalDirect - 1
1/55 - 3000115/1/60
1.14Yes
High Velocity1 - 14x20 - 1in.
2 Round
Alum. Steel
20
2—452—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
2115/1/60
9.7151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
145 / 135
TUH1C100A9H41AUpflow/Horizontal
97,00092,105
9535-65
DIRECT11 x 10
14
See Fan Performance Table3/4
1100115/1/60
CentrifugalDirect - 1
1/20 - 3450115/1/60
.71Yes
High Velocity1 - 20x25 - 1in.
3 Round
Alum. Steel
20
5—455—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
11.4151/2
H x W x D41-3/4 x 23 x 30-1/2
171/160
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea
level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above
sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor
PRODUCT SPECIFICATIONS 1
MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
22-1859-01 7
PRODUCT SPECIFICATIONS 1
MODELTYPERATINGS 2Input BTUH 3Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVE 8Diameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HP 5R.P.M.Volts/Ph/HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFLAFILTER — Furnished?Type RecommendedShipped(No.-Size-Thk.)VENT PIPE DIAMETER - Min (in.)67
HEAT EXCHANGERType - Fired - UnfiredGauge (Fired)ORIFICES — MainNat.Gas.Qty.—DrillSizeL.P.GasQty.—DrillSizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)
General Data
TDH1B065A9H31AUpflow/Horizontal
60,00057,000
9525 - 55
DIRECT10 x 8
14
See Fan Performance Table3/4
1075115/1/60
CentrifugalDirect - 1
1/25 - 3200115/1/60
1.35Yes
High Velocity2 - 14x20 - 1in.
2 Round
Alum. Steel
20
4—484—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
4115/1/60
10.0151/2
H x W x D41-3/4 x 19-1/2 x 30-1/2
158 / 148
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea
level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above
sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Constant torque ECM blower motor6 Refer to the Vent Length Table in the Installer's Guide or the Allowable Vent Length label located on the furnace.7 All TUH1 and TDH1 furnace models have a vent outlet diameter that equals 2".8 4 Speed, direct drive X13 style high efficiency DC motor
TDH1C085A9H41ADownflow/Horizontal
80,00076,000
9530-60
DIRECT11 x 10
14
See Fan Performance Table3/4
1075115/1/60
CentrifugalDirect - 1
1/20 - 3450115/1/60
.71Yes
High Velocity2-16x20-1in.
2.5 Round
Alum. Steel
20
5—485—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
5115/1/60
11.4151/2
H x W x D41-3/4 x 23 x 30-1/2
171/160
TDH1D110A9H51BDownflow/Horizontal
110,000104,500
9535-65
DIRECT11 x 10
14
See Fan Performance Table1
1075115/1/60
CentrifugalDirect - 1
1/20 - 3450115/1/60
.71Yes
High Velocity2-16x20-1in.
2.5 Round
Alum. Steel
20
6—486—56
Redundant - Single Stage
Hot Surface IgnitionMultiport Inshot
6115/1/60
14.1201/2
H x W x D41-3/4x26-1/2x30-1/2
205 / 193
8 22-1859-01
Performance Data
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
TUH1B040A9H21A 59 50 44 39 35 32 29
TUH1B060A9H31A 59 53 48 44 41 38
TUH1B080A9H31A 64 59 54 50 47 44 41
TUH1C100A9H41A 66 61 57 53 50 47 45 43
TUH1D120A9H51A 65 60 57 54 51 48 46 44
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins.w.g.)MODEL SPEED TAP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
TUH1B040A9H21A
4 - HIGH - Black 1159 1131 1102 1077 1052 1022 992 961 9303 - MED-HIGH - Blue 938 910 881 851 820 786 751 717 6622 - MED-LOW - Yellow 844 814 783 750 717 681 645 604 563
1 - LOW - Red** 772 732 691 656 621 581 540 497 454
TUH1B060A9H31A
4 - HIGH - Black 1402 1362 1318 1267 1214 1157 1095 1033 9603 - MED-HIGH - Blue** 1199 1174 1149 1127 1099 1075 1028 973 8972 - MED-LOW - Yellow 1104 1080 1053 1031 1002 980 955 931 890
1 - LOW - Red 834 808 770 750 712 677 641 599 566
TUH1B080A9H31A
4 - HIGH - Black 1328 1304 1277 1253 1224 1182 1127 1057 9593 - MED-HIGH - Blue** 1519 1493 1464 1422 1368 1306 1242 1161 10542 - MED-LOW - Yellow 1072 1039 1015 991 956 928 891 858 828
1 - LOW - Red 810 782 759 729 703 668 643 612 582
TUH1C100A9H41A
4 - HIGH - Black 1586 1552 1517 1477 1443 1410 1366 1331 12893 - MED-HIGH - Blue** 1893 1858 1826 1793 1759 1724 1691 1646 15822 - MED-LOW - Yellow 1364 1320 1282 1241 1205 1167 1120 1078 1045
1 - LOW - Red 1107 1060 1003 959 919 863 825 782 730
TUH1D120A9H51A
4 - HIGH - Black 2141 2108 2076 2041 2009 1976 1939 1894 18263 - MED-HIGH - Blue** 2072 2038 2007 1975 1938 1910 1880 1845 17972 - MED-LOW - Yellow 1886 1853 1816 1785 1754 1718 1688 1652 1619
1 - LOW - Red 1647 1609 1573 1540 1497 1465 1429 1391 1358
** = HEATING SPEED TAP
22-1859-01 9
Performance Data
FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins.w.g.)
MODEL SPEED TAP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
TDH1B040A9H21A
4 - HIGH - Black3 - MED-HIGH - Blue2 - MED-LOW - Yellow**1 - LOW - Red
1156935835752
1128859803726
1100859771700
1072828736648
1043797701596
1012757652554
981717602511
917679569471
852641536431
TDH1B065A9H31A
4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red
145513751099838
140413501076799
135213201044773
129912701021744
12321215994706
11741153968675
11011099941628
10251014904599
916934874558
TDH1C085A9H41A
4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red
1795168613951179
1763165513621141
1732161913281094
1701158612891059
1669155412581019
162715251225970
157514941186931
151414581151888
145114151115846
TDH1D110A9H51A
4 - HIGH - Black3 - MED-HIGH - Blue**2 - MED-LOW - Yellow1 - LOW - Red
2105188017561582
2063185317181553
2010181716881509
1951178516471473
1880174716161433
1802170815761397
1721164915461362
1630157915051317
1543149914681282
** = HEATING SPEED TAP
CFM VS. TEMPERATURE RISE
MODELCFM (CUBIC FEET PER MINUTE)
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
TDH1B040A9H21A 59 50 44 39 35 32 29
TDH1B065A9H31A 53 48 44 41 38 35
TDH1C085A9H41A 59 54 50 47 44 41 39
TDH1D110A9H51A 65 60 57 54 51 48 46
10 22-1859-01
Electrical Data
TUH1-H Wiring
From Dwg. D342491
22-1859-01 11
TUH1-H Schematic
Electrical Data
From Dwg. D342491
12 22-1859-01
Electrical Data
TDH1-H Wiring
From Dwg. D342800P01
22-1859-01 13
Electrical Data
TDH1-H Schematic
From Dwg. D342800P01
14 22-1859-01
Field Wiring
SEE NOTE 6
From Dwg. B341437 Rev. 1
FURNACE
TWIN
SEE NOTE 7
B/CB/C
TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES
HUM SEENOTE 5
EAC SEENOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTATNO COOLING
OUTDOOR UNIT (NO TRANSFORMER)
SEE NOTE 6
From drawing B340388 Rv 2
SEE NOTE 8
FURNACE
B/CB/C
TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES
HUM SEENOTE 5
EAC SEENOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)
22-1859-01 15
Twinning Field Wiring
TWIN TWIN
R1 R1
TWINNING CONNECTION DIAGRAMFOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE1 STAGE HEATING ONLY THERMOSTAT1 STAGE HEAT
ONLYTHERMOSTAT
(WITH FAN SWITCH) FURNACE NO. 1 FURNACE NO. 2
BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 3
ISOLATION RELAY(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAYSEE NOTE 4
B/CB/CB/C
From Dwg. 21B341422 Rev. 3
TWIN TWIN
R1
R1
TWINNING CONNECTION DIAGRAMFOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
1 STAGEHEATING / COOLING
THERMOSTAT FURNACE NO. 1 FURNACE NO. 2
BLOWER OPERATION OF UNIT NO. 2 IS SYNCRONIZEDWITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAYSEE NOTE 4
OUTDOOR UNIT(NO TRANSFORMER)
OUTDOOR UNIT(WITH TRANSFORMER)
RC
ISOLATION RELAY(FIELD SUPPLIED)
SEE NOTE 3
B/CB/CB/C
From Dwg. 21B341423 Rev. 2
16 22-1859-01
Dimensions
From
Dw
g. 2
1C34
1884
TU
H1-
H O
UT
LIN
E D
RA
WIN
G(A
LL
DIM
EN
SIO
NS
AR
E IN
INC
HE
S)
NO
TES
: 1.
*U
H1B
080A
9H31
, *U
H1C
100A
9H41
, & *
UH
1D12
0A9H
51R
EQ
UIR
E 3
” DIA
ME
TER
VE
NT
PIP
E.
2. D
IAM
ETE
R O
F V
EN
T P
IPE
MAY
BE
LIM
ITE
D T
O 2
-1/2
”O
R 3
” ON
SO
ME
MO
DE
LS A
T D
IFFE
RE
NT
ALT
ITU
DE
S.
RE
FER
TO
TH
E V
EN
T LE
NG
TH T
AB
LE F
OR
PR
OP
ER
AP
PLI
CAT
ION
.
22-1859-01 17
Dimensions
From
Dw
g. 2
1C34
1885
TD
H1-
H O
UT
LIN
E D
RA
WIN
G(A
LL
DIM
EN
SIO
NS
AR
E IN
INC
HE
S)
Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Trane6200TroupHighwayTyler, TX 75707www.trane.com
Literature Order Number 22-1859-01
File Number 22-1859-01
Supersedes New
Date 11/11