Modscan32
Checking Modbus protocol on drive
ModScan32 is powerful tool, which can emulates Modbus RTU and Modbus ASCII. It can use serial port (COM), parallel port (LPT), Ethernet (TCP/IP) and Infra Red..
It is very useful to test Modbus RTU embedded in our drives.
Using serial port, ModScan32 can access Control / Status Word and all group of parameters.
Modscan runs into a PC and needs a “RS-485 Adapter” to be connected to the drive.
Control / Status Word Addressing
Control / Status Word are addressed as “Coil Status” by Modscan32
Parameters Addressing
Parameters are addressed as “Holding Register” by Modscan32
Communication settings
Looking Control Word
Station Number
C
043
Changing Control Word
Double Click
Looking Parameter 16-30 DC Link Voltage
Station Number
1 word = 16 bits
Changing Preset Reference 0
Double Click
Looking Parameter 3-41 Ramp up Time 1
2 word = 32 bits
Changing Parameter 3-41 Ramp up Time 1
Change scan rate