DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05 GRAPHIC MIMIC PANEL 7. 1. The graphic mimic panel on DELPHYS door displays information regarding operating status, electrical meas- urements, access to control functions and conĺguration parameters. It includes a colour graphic display and a luminous status bar, and provides access to: mimic panel; measurements, statuses and commands for the subassemblies; programming battery tests and DELPHYS operating modes; assisted startup and switching to manual maintenance bypass procedures; event and battery discharge log; DELPHYS and battery discharge duration statistics; conĺguration menu; list of states and alarms. Display. LEFT/RIGHT button. Scrolls through the available menus/ pages to the right or left. MENU buttons. Access the respective displayed menu. Luminous status bar. ReĻects the general status of DELPHYS. The status bar colours are identical for both single and parallel UPS installations. Green: load protected by inverter (NORMAL mode); - Green Ļashing: battery test in progress. Yellow: load powered off automatic bypass (NORMAL mode). - load powered off manual maintenance bypass; - Red: on: load not powered; - Ļashing: imminent shutdown. - Off: DELPHYS unit or module is isolated from the installation (Q2 or Q3 open) - automatic switch on or bypass procedure in progress. - USB port. WARNING! Do not connect devices to the USB port. This can damage the system. ENTER button. Accesses the currently displayed menu, accept/send commands and conĺgurations to DELPHYS. UP/DOWN button. Scrolls up and down through the available menus/values. SU INVERTER UPS Eco 1025kVA 10:30 ? MIMIC PANEL 7. 39 ENGLISH
20

socomec gp2.0 control panel

Feb 07, 2016

Download

Documents

control panel manual for socomec delphys gp2.0 ups
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

GRAPHIC MIMIC PANEL7. 1.

The graphic mimic panel on DELPHYS door displays information regarding operating status, electrical meas-

urements, access to control functions and con guration parameters. It includes a colour graphic display and a

luminous status bar, and provides access to:

mimic panel;•

measurements, statuses and commands for the subassemblies;•

programming battery tests and DELPHYS operating modes;•

assisted startup and switching to manual maintenance bypass procedures;•

event and battery discharge log;•

DELPHYS and battery discharge duration statistics;•

con guration menu;•

list of states and alarms.•

Display.

LEFT/RIGHT button.Scrolls through the available menus/

pages to the right or left.

MENU buttons.Access the respective displayed menu.

Luminous status bar. Re ects the general status of DELPHYS.

The status bar colours are identical for both single and parallel UPS installations.

Green:•

load protected by inverter (NORMAL mode); -

Green ashing: battery test in progress.•

Yellow:•

load powered off automatic bypass (NORMAL mode). -

load powered off manual maintenance bypass; -

Red:•

on: load not powered; -

ashing: imminent shutdown. -

Off:•

DELPHYS unit or module is isolated from the installation (Q2 or Q3 open) -

automatic switch on or bypass procedure in progress. -

USB port.WARNING!Do not connect devices to the

USB port. This can damage

the system.

ENTER button.Accesses the currently

displayed menu, accept/send

commands and con gurations

to DELPHYS.

UP/DOWN button.Scrolls up and down through

the available menus/values.

SU INVERTERUPS Eco 1025kVA10:30

?

MIMIC PANEL7.

39

ENG

LISH

Page 2: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

MIMIC PANEL OVERVIEW7. 2.

UPPER BAR (always displayed).

CLOCK.Hours and minutes. The symbol “:” ashes once a second to indicate that the software is running.

ALARMS AREA.Present when an alarm is active.Press button DOWN to display the list of alarms.

See “Troubleshooting”.

Total output load (kVA).

Operating modes:Normal (Normal mode), Service, Isolated (unit isolated from the electric distribution plant).

Unit status:Me• ssages displayed: LOAD OFF, ON INVERTER, IMMINENT STOP, ON BATTERY, BATTERY

TEST, ON MAINTENANCE BYPASS, ON AUTO BYPASS, UPS STARTING..., UPS STOP...,

UNIT AVAILABLE.

Priority of colours (from highest to lowest):•

red: load off, imminent stop. -

grey: when powering up or shutting down. -

yellow: load powered of bypass or maintenance bypass in Battery Mode. -

green: load powered of inverter. -

Mimic panel reference.

40

Page 3: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

FLOW DIAGRAM ANIMATION.

Recti er input.

Colour of the bar: blue: active/mains present. -

grey: mains not present. -

Priority of colours of the symbols “~” and “-”(from highest to lowest):

yellow: ON or voltage present and pre-alarm active. -

green: ON or voltage prese - nt and no alarm active.

Recti er output.

Inverter input.

Bypass input.

Unit output.

Static output switch.

Inverter output.

Overload

LOAD LEVEL.

≤ 30% ≤ 40% ≤ 50% ≤ 60% ≤ 70%

≤ 80% ≤ 90% ≤ 100% ≤ 110% ≤ 120% Green

Yellow

41

ENG

LISH

Page 4: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

MESSAGES AREA.Present during automatic shutdown or manual main-tenance bypass procedure.

BATTERY STATUS (unit only)

Battery charging. Colour of bars: green; level reached: light on.

Battery discharging. Colour of bars: yellow.

Battery charged.Colour of bars: green.

≥ 95% ≤ 90% ≤ 85% ≤ 80%

Battery alarm.

Battery general alarm

(symbol turns to yellow)

Battery circuit open

Battery low or end of autonomy.

42

Page 5: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

Units connected in parallel.Green: unit connected or available.•

Yellow: unit connected with active alarm.•

Red: unit switched off or unit imminent stop•

Grey: unit not connected.•

Units connected in parallel.Green: unit connected and available.•

Yellow: unit connected with active alarm.•

Red: unit switched off.•

Grey: unit not connected.•

Use the LEFT/RIGHT button to select the system DELPHYS mimic panel.

Use the LEFT/RIGHT button to select the system unit mimic panel.

PARALLEL CONFIGURATION7. 3.

MENU ICONS.

Menu CONTROL.

MenuMEASUREMENTS.

MenuMONITORING.

Help.

Unit mimic panel. UPS mimic panel.

43

ENG

LISH

Page 6: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

MIMIC PANEL MENU7. 4.

Select one of the four menus.

Scroll through list (up/down) and pages (left/right).

Access menu.

Legend of symbols.

Controls.

Con rm settings.

Measurements.

Cancel.

Monitoring.

Increase.

Help.

Decrease.

Con rm procedure or send command.

Home page (mimic panel).

Log le.

Previous page.

Status.

Reset alarms.

44

Page 7: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

7.5-1

7.5-3

7.5-2

ENTERING PASSWORDS (WHEN REQUIRED)7. 5.

7.5-4 Select the password to be set.

Notes.

Password to con g: protects the MONITORING menu (User Con gurations, UPS Options and Maintenance-UPS setting); if set, generates the •

Contr. password (user modi able).

Password to control: protects the CONTROL menu. Can be set only if the Con g password has been set. •

45

ENG

LISH

Page 8: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

Enter password.7.5-5

Go to previous character

Quit without saving

Type of character:

C Cancel character.

INS Enter character.

1-9 Number

@ Special characters

A-Z Letters

Confi rm passwordGo to next character

Increment value or next letter

Decrement value or previous letter

Select the type of character.

46

Page 9: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

7. MIMIC PANEL

7.5-6

7.5-8

7.5-7

7.5-9

CONTROL menu7. 5.1.

The menu is used to send some immediate commands to activate DELPHYS or various operating modes.

Note.

The access to con guration and control is protected by password.. •

If a control is not available, the related menu will not be displayed. •

MEASURES menu7. 5.2.

This menu is used to display all the measurements relating to the input, output and to the battery.

MONITORING menu7. 5.3.

This menu is used for monitoring, to change user’s con guration parameters, enabling communication options and to display service

information.

Note.

The remote access con guration is protected by password. •

47

ENG

LISH

Page 10: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

8.1-2

8.1-38.1-4

SWITCHING8. 1. ON

8.1-1

Q1

Close Q1.

8.1-5 8.1-6

OPERATING PROCEDURES8.

48

Page 11: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

8. OPERATING PROCEDURES

8.1-8

Follow the instructions to the screen.

Note.

When prompted, press button • to con rm the operation or button to cancel it.

8.1-7

8.2-1 8.2-2

8.2-3 8.2-4

MANUAL MAINTENANCE BYPASS8. 2.

49

ENG

LISH

Page 12: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

8. OPERATING PROCEDURES

Open Q1.8.2-7

Q1

8.2-68.2-5

Follow the instructions to the screen.

Notes.

When prompted, press button • to con rm

the operation or button to cancel it.

8.2-8

Wait a few seconds for shutdown.

8.2.1-2

Switching on from manual maintenance bypass8. 2.1.

8.2.1-1

Q1 Q5

Close Q1 and Q5.

50

Page 13: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

8. OPERATING PROCEDURES

8.2.1-3 8.2.1-4

8.2.1-6

Follow the instructions to the screen.

Notes.

When prompted, press button • to con rm

the operation or button to cancel it.

8.2.1-5

51

ENG

LISH

Page 14: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

MULTILEVEL COMMUNICATION9. 1.

DELPHYS can manage various serial, contact and Ethernet communication channels at the same time. The 2

communication slots available allow the use of signalling accessories and cards.

Each communication channel is independent; simultaneous connections can thus be made to have various

levels of remote signalling and monitoring (see the § 11 "options" for a detailed evaluation of the functionality of

the cards that can be installed in the slots).

The table below shows the possible connections between DELPHYS communication channels and the external

devices.

Communication levels

1 It is possible to use one isolated serial PCB only.

9.1-1

Legend pin RS2321 Reserved

2 RX for RS232

3 TX for RS232

4 Reserved

5 GND for RS232

6 Not connected

7 RTS

8 CTS

9 +12V

5 4 3 2 1

9 8 7 6

SLOT 2SLOT 2

SLOT 1SLOT 1

RJ45RJ45

RS232RS232

Optional Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6ADC card • • • • • •Isolated serial port1 • • • •BHC •

COMMUNICATION9.

52

Page 15: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

DELPHYS UNIT ALARMS10. 1.

Unit imminent stop.•

Unit Overload.•

The load power draw is greater than DELPHYS’s nominal output.

Check the load on the display and disconnect loads not requiring UPS service or distribute the total load over

the three phases.

Overloading results in the load not being powered by DELPHYS for a limited period of time. For further

details, see the technical specifications.

Transfer blocked.•

Switching from UPS unit bypass to inverter may be inhibited by an inverter failure. Reset the alarm and contact

Socomec UPS After-sales Service.

Transfer impossible.•

Switching from UPS unit inverter to bypass is prevented by problems on the auxiliary mains supply: mains sup-

ply out of tolerance, not synchronised,... Ensure that Q4 is closed, that the auxiliary mains supply is available

and that the values are within range.

Insuffi cient resources.•

DELPHYS unit is in overload, with auxiliary mains supply and inverter inhibited. The power supply to the load will

be interrupted if the load is not brought back within range or the auxiliary mains supply fails. Check the load on the

display and disconnect loads not requiring UPS service or distribute the total load over the three phases.

Inverter stopped by overload.•

This alarm is generated when the inverter has reached the maximum permitted overload time. Check DEL-

PHYS’s load and reset the alarms.

Unit stopped by overload.•

This alarm is generated when both the inverter and the bypass have reached the maximum permitted overload

time. Reduce DELPHYS’s load and reset the alarms.

Fan alarm.•

Ventilation system failure. Contact After-sales Service.

Charger alarm.•

This alarm is generated in case of a battery charger fault. Check for other alarms and contact After-sales Service

if necessary.

Operating on battery.•

This alarm is generated when DELPHYS unit is operating on battery power. The input power supply has failed

or is insuf cient (voltage/frequency out of tolerance). Check for the “recti er input supply fault” alarm. If there is

no power failure, check whether upstream protections have tripped and whether Q1 is open.

Battery general alarm.•

General battery alarm due to: battery test failed, maximum battery voltage, battery circuit breaker open, battery

charger failure. Check for other alarms and inspect the batteries.

TROUBLESHOOTING10.

53

ENG

LISH

Page 16: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

This alarm is generated when the battery room temperature, measured with an external sensor, is higher than the per-

mitted maximum. Check the displayed temperature, and check the battery room ventilation/conditioning system.

This alarm is generated when the batteries’ charge is low and DELPHYS is about to switch off. Check for other alarms.

Battery circuit breaker open.

This alarm is generated when the bypass has reached the maximum permitted overload time or in case of prob-

lems when switching from inverter to bypass. Check for other alarms. In case of overload, check DELPHYS’s

load and reset the alarms.

Incorrect con guration parameters. Contact After-sales Service.

The machine room temperature is above the recommended maximum. Check DELPHYS room temperature and

ventilation/conditioning system. If there is a fan alarm, contact After-sales Service.

DELPHYS must be checked periodically by After-sales Service to ensure maximum ef ciency and performance.

If the alarm displays, DELPHYS must be inspected by a quali ed technician.

This alarm is not generated by a failure or fault, but by incorrect use or sizing of DELPHYS system. The alarm

may be tripped by:

Operation for an extended period of time at high temperatures (degradation of the batteries); -

large number of overloads (incorrect sizing); -

continuous battery draining (unstable mains voltage); -

large number of circuit breakers on the bypass (high peak loads). -

DELPHYS PARALLELS SYSTEM ALARMS10. 2.

The load power draw is greater than the system’s nominal output.

Check the load on the display and disconnect loads not requiring UPS service or distribute the total load over

the three phases.

Overloading results in the load not being powered by DELPHYS for a limited period of time. For further

details, see the technical specifications.

Switching from system bypass to inverter may be inhibited by an inverter failure. Reset the alarm and contact

Aftersales Service.

10. TROUBLESHOOTING

54

Page 17: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

Switching from system inverter to bypass is prevented by problems on the auxiliary mains supply: mains supply

out of tolerance, not synchronised, etc. Ensure that Q4 is closed, that the auxiliary mains supply is available and

that the values are within range.

fi•

The system is in overload, with auxiliary mains supply and inverter inhibited. The power supply to the load will

be interrupted if the load is not brought back within range or the auxiliary mains supply fails. Check the load on

the display and disconnect loads not requiring UPS service or distribute the total load over the three phases

In case of a parallel redundant system, loss of redundancy is due to possible problems with one of the units.

Check values and alarms status of all units, and make sure that none of the operating units is overloaded.

Aftersales Service has activated a remote UPS analysis procedure (if the T.SERVICE contract is active).

This alarm is generated if at least one alarm is present on at least one unit. Check the other active alarms for details.

These alarms are generated if at least one alarm is present on unit 1 to 6 respectively. Check the other active

alarms for details.

This alarm is generated if circuit breakers Q5 (bypass) and Q3 (output) are closed at the same time. Check the

position of the circuit breakers.

The phase cycle of the auxiliary mains is incorrect. Swap two input phases or two phases of the auxiliary mains

supply (only for UPS with separate auxiliary mains supply).

The input power supply or auxiliary mains supply has failed or is insuf cient (voltage/frequency out of tolerance).

Check for “recti er input power fault” and “bypass power supply out of tolerance” to identify the failure.

Check that the voltage and frequency values are in range (see technical speci cations).

If there is no input mains supply failure, check whether Upstream protections have tripped or whether circuit

breaker Q1 (input power supply) is open.

If there is no auxiliary mains supply failure, check whether Upstream protections have tripped or whether circuit

breaker Q4 (auxiliary mains supply) is open.

This alarm is generated if at least one alarm is present on the unit. Check the other active alarms for details.

The genset has sent an alarm; check the genset.

This alarm is generated if one of the optional boards is no longer communicating with DELPHYS controller.

Check that the board is correctly mounted and reset the alarms.

An ADC board input has been activated; check the devices connected to the board.

10. TROUBLESHOOTING

55

ENG

LISH

Page 18: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

PREVENTIVE MAINTENANCE10. 3.

All operations on the equipment must be carried out solely by SOCOMEC UPS personnel or by author-

ised service personnel.

Maintenance requires accurate functionality checks of the various electronic and mechanical parts and, if neces-

sary, the replacement of parts subject to wear and tear (batteries, fans and condensers). It is recommended to

carry out periodic specialised maintenance (annually), in order to keep the equipment at the maximum level of ef-

ciency and to avoid the installation being out of service with possible damage/risks. Moreover, attention should

be paid to any requests for preventive maintenance that the equipment may automatically display with alarm/

warning message.

Batteries10. 3.1.

The state of the battery is fundamental to UPS operation.

Thanks to the Expert Battery System, the information relating to the state and the conditions of use of the bat-

tery are processed in real time and the recharging and discharging procedures are selected automatically in

order to optimise battery life expectancy and offer maximum performance.

Furthermore, during the operating life of the battery, DELPHYS™ stores statistics on the conditions of use of

the battery for analysis.

Since the expected life of the batteries is very much dependent on operating conditions (number of charging

and discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.

When replacing the batteries, use the same type and configuration by placing them in the appropriate

containers so as to avoid the risk of acid leakage.

The replaced batteries must be disposed of at authorised recycling and disposal centres.

Do not open the plastic cover of the batteries as they contain harmful substances.

Fans10. 3.2.

The life of the fans used to cool the power parts is dependent on the using and environmental conditions (temperature, dust).

Preventive replacement by an authorised technician is recommended within 5 years (in normal operating conditions).

When needed, fans must be replaced as per specifications by SOCOMEC UPS.

Capacitors.10. 3.3.

The equipment houses electrolytic capacitors (used in the recti er and inverter section) and ltering capacitors

(used in the output section), whose life is dependent on using and environmental conditions.

The average expected life of these components is shown below:

• Electrolytic capacitors: 5 years;

• Filtering capacitors: 7 years.

In any case the effective state of the components is veri ed during preventive maintenance.

10. TROUBLESHOOTING

56

Page 19: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

11.1-1

OUT2

OUT3

IN1IN3OUT1

OUT4

IN1IN2

ADC CARD11. 1.

This card can be con gured to control up to four outputs that are normally closed or normally open and up to

three digital inputs. A maximum of two cards can be installed on each unit.

SERIAL CONNECTION PCB11. 2.

A serial RS232 connector DB9 and an isolated

RS485 connector are available on the card (RTX+

and RTX ).

5 4 3 2 1

9 8 7 6

REMOTE MONITORING VIA WEB SERVER11. 3.

By connecting DELPHYS to a standard LAN network, the operating status of DELPHYS can be monitored from

any PC connected to the network through an html page.

Connect the network cable to the RJ45 port.1.

Con gure the network IP address via the mimic panel.2.

Open your favourite web browser.3.

Type the IP address of DELPHYS to display the synoptic of DELPHYS.4.

1 Reserved 4 Reserved 7 Reserved

2 RX for RS232 5 GND for RS232 8 Reserved

3 TX for RS232 6 Reserved 9 Reserved

11.2-1

RTX–RTX+

57

ENG

LISH

Page 20: socomec gp2.0 control panel

DELPHYS Green Power - Ref.: IOMDELGP0910-GB_05

ISOLATION CONTROLLER11. 4.

This device continually checks the transformer isolation, displaying an alarm message on the mimic panel.

EXTERNAL MANUAL MAINTENANCE BYPASS11. 5.

This device will electrically exclude and isolate DELPHYS (e.g. for maintenance operations) without interrupting

the power supplied to the load.

ACS PCB11. 6.

Synchronises DELPHYS output with an external power source (another UPS, even of a different brand, genera-

tor or transformer).

TEMPERATURE SENSOR11. 7.

This allows control of the temperature in the battery room or inside the battery cabinet.

PROFIBUS11. 8.

On request, DELPHYS can be provided with a Pro bus protocol converter, installation software, con guration

software and user manuals.

GSM MODEM11. 9.

Enables sending of SMS messages regarding the equipment’s operating status.

11.9-1

11.8-1

OPERATING MANUAL

11. OPTIONS

58