Topic: Productivity Tools in Control Builder
Contents
Instructions for Productivity Tools in Control Builder.............................................................................3
Export/Import a Control Module.............................................................................................................5
2 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
This page was intentionally left blank.
Productivity Tools in Control Builder
Instructions for Productivity Tools in Control Builder
9/18/2013 Copyright © 2013 Honeywell International Inc. 3
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Instructions for Productivity Tools in Control Builder
Introduction
This portion of the document contains important information required to perform to ‘Export-Import Control module’ lab.
Procedure
Step Action
1
Read the following IMPORTANT information carefully.
Decide if you will be performing labs for C200E (and Series A I/O modules) OR C300 (and Series C I/O Modules). You can opt for either one but not both.
_______ C200E (and Series A I/O modules)
_______ C300 (and Series C I/O Modules)
2
ATTENTION
You must perform the remaining steps of this lab if you skipped any of the prior lessons of this course, else skip the remaining instructions and proceed to the next lab.
Locate the “GUI_DB_Load” Shortcut on desktop.
1. Double click “GUI_DB_Load” Shortcut to launch the import utility.
2. In Controller drop down select either C200 or C300 Controller (as per the option selected in step#1).
3. In Lesson number drop down select Lesson11.
4. Click the LOAD button.
Productivity Tools in Control Builder
Instructions for Productivity Tools in Control Builder
4 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
3
ATTENTION
If you are facing any of the following situation while loading the data base:
1. Import wrong Lesson Database
2. Error prompt appears while loading data base.
Then students should wait for at least one minute before reloading the database.
4 Open Control Builder if not already open.
Download and activate Controller and control modules.
5 Ensure that the Controller and Control Modules are indicated in green color.
6 Open the Excel Spreadsheet if not already open. Open either from C:\Users\Student\Documents\Tie_Back_New.xls OR by double clicking the shortcut on your desktop.
Proceed to next Lab
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 5
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Export/Import a Control Module
Practice
Objective
• Use the Import and Export functionality of Control Builder to incorporate parts from one Control Builder Project into another Project
• Export the Control Module 11_TI20
• Import Analog Indicator points
• Use Bulk Edit Parameters to change parameter values
Prerequisites
• Experion PKS server or client machine loaded with Experion PKS Engineering Tools
• 11_TI20 CM configured in Control Builder
• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C200E\L11_Productivity tools in CB
• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C300\L11_Prodcutivity tools in CB
• Control Builder running with at least one Project/Monitor tree window open
• SIM_C200E/SIMC300 Controller and IOMs configured
Introduction
A Project file can contain many items, such as IOMs and CMs, for up to 20 controllers. From Control Builder, use the Import/Export tool to copy some or all of one project to another.
• Export - copies the designated portion of a project from Control Builder to a specified directory
• Import - copies the designated CMs into Control Builder’s Project Tab
Productivity Tools in Control Builder
Export/Import a Control Module
6 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Procedure
Export Function Block Configuration
Step Action
1 In Control Builder, click on the Project window, then from the menu bar select File > Export, to call up the dialog box, as shown below.
• Select 11_TI20
ATTENTION
Your point list may be different. The point list contains all items in the current project.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 7
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
2 11_TI20 now appears in the Selected Objects For Export field.
Browse to the path of:
C:\Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\Export
TIP
Create a folder with name Export at given path if not created already.
Double-click Export and click OK.
Productivity Tools in Control Builder
Export/Import a Control Module
8 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
3 Click the Export Button.
• The Exporting Data dialog box appears.
ATTENTION
This dialog box automatically closes if there were no errors during the export.
4 Open Windows Explorer and navigate to the exported CM location:
• C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\Export
• The following files are generated:
Module Name.bcd (In this case, module name is 11_TI20.)
Module Name.cnf.xml
Export.sl
global.gui
global.snl.xml
• The Export.sl is the successful list file. It contains a list of all the exported objects.
ATTENTION
Here, 11_TI20 was successfully exported. You can import this CM to any other Project with the Import facility.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 9
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Import a Control Module
Import copies designated Control Modules from the Import/Export files located in the specified directory (shown in the Import form) to a Control Builder Project.
In this lab, import the Analog Indicator points. These are pre-built CMs and already exported into the following directory:
• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C200E\\L11_Productivity tools in CB
• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C300\\L11_Productivity tools in CB
Productivity Tools in Control Builder
Export/Import a Control Module
10 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
1 From Control Builder, select File>Import to call up the dialog box, as shown below.
ATTENTION
When the above dialog box opens, the Project Tree window automatically closes.
2 Click the Browse button and change the Import path to the following folder:
C:\ Users\Public\Public Documents\Honeywell\Experion PKS\ IXPORT\C200E (C300)\L11_Productivity tools in CB
Click OK.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 11
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
3 Import the Analog Indicator points listed below.
Selection can be made with <SHIFT> select (for contiguous items) or <CTRL> select (for noncontiguous items).
ATTENTION
Select only the following, from the list, to import:
11_PI14, 11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI25, 11_TI26 and 11_TI40.
4 Maintain the Import CEE Assignments checkbox selection. This checkbox imports and assigns the above CMs to the CEESCEFB61 (or SIM_CEEC300).
• If this option is NOT selected, then the imported items are imported as Unassigned.
Productivity Tools in Control Builder
Export/Import a Control Module
12 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
5 Click the Import button.
• The following dialog box appears:
ATTENTION
This dialog box automatically closes after a successful Import.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 13
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
6 Open the Project Tree window and expand the Project.
• CEESCEFB61 (or SIM_CEEC300) with all the imported CMs appears, as shown below.
Productivity Tools in Control Builder
Export/Import a Control Module
14 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Use Bulk Edit Parameters
Step Action
1 Open the Bulk Editor.
• Click Tools > Bulk Edit Parameters > Create Bulk Edit List
2 Click on Show All Points button.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 15
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
3 Select 11_TI21.DACA from the Available Points window then
• Click the arrow button
• 11_TI21.DACA now appears in the Selected Points window
Similarly, select 11_TI22.DACA, 11_TI23.DACA, 11_TI24.DACA and 11_TI26.DACA and move them to the Selected Points window.
ATTENTION
Press <CNTRL> key for selecting multiple points.
Productivity Tools in Control Builder
Export/Import a Control Module
16 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
4 In the Available Parameters window, find and select PVEUHI and PVEXHILM. Select the arrow button.
ATTENTION
Press <CNTRL> key for selecting multiple parameters.
5 For C300 students only (C200E students skip this step):
From ‘Available Points’, select and move the following to ‘Selected Points’:
11_TI21.TI, 11_TI22.TI, 11_TI23.TI, 11_TI24.TI, 11_TI26.TI
6 For C300 students only (C200E students skip this step):
From ‘Available Parameters’ select and move the following to ‘Selected Parameters’:
PVEXEUHI
7 Click the Browse button for the Output Directory.
• Select C:\Users\Student\Documents in the ‘Browse for Folder’ window
• Click OK
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 17
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
8 Select Excel Spread Sheet [.xls] from the Select File Type pull down menu.
Click the Save button.
ATTENTION
If the file already exists in the folder, a prompt will appear asking you to overwrite the existing file. Press YES.
9 Click OK.
10 Close the ‘Create Bulk Edit List’ window.
Productivity Tools in Control Builder
Export/Import a Control Module
18 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
11 Open Windows Explorer and navigate to C:\Users\Student\Documents
• Double click the BulkEdit.xls file
• Result: Excel opens, displaying the points as shown below
Screen capture shown for SIMC300. You will see this only when using SIMC300.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 19
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
12 In the PVEUHI column, select each 100 value and change it to ‘260.
In the PVEXHILM, select each 100 value and change it to ‘260.
ATTENTION
The single quote “ ‘ “ before 260 tells Excel that this value is text.
For C300 students only:
Enter the PVEXEUHI as 260 for each Series C Analog Input channel.
Screen capture shown for SIMC300. You will see this only when using SIMC300.
Productivity Tools in Control Builder
Export/Import a Control Module
20 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
13 Save and close the Excel spreadsheet.
Accept the default “C:\Users\student” file location.
14 In Control Builder, select Tools > Bulk Edit Parameters > Read Bulk Edit List.
• Result: the Read Bulk Edit List tool opens.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 21
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
15 Click the Browse button.
From the “C:\Users\Student\Documents”, select the BulkEdit.xls file.
Click the Open button.
Productivity Tools in Control Builder
Export/Import a Control Module
22 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
1 Select the Update Project option.
Click the Start button.
2 Click the OK button to acknowledge the warning.
3 Close the Bulk Edit tool.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 23
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
4 In Control Builder, verify that PVEUHI changed (to 260) for the five points above (11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI26).
ATTENTION
If necessary, open the Project Tree, and expand the Project.
Productivity Tools in Control Builder
Export/Import a Control Module
24 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
5 Select the 11_PI14, 11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI25, 11_TI26, and 11_TI40 points.
Click the Download button.
Click Continue on the Load dialog window.
Select the checkbox with Automatically change… in the Load dialog box, and click OK to begin the download.
After a successful download, go to the Monitoring Tree window, expand your SCE/CEE and verify that the CMs are activated (green).
ATTENTION
Your Project screen may appear slightly different than the example above.
Productivity Tools in Control Builder
Export/Import a Control Module
9/18/2013 Copyright © 2013 Honeywell International Inc. 25
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
6 In Station, open the Debutanizer_123 graphic and verify that the downloaded points are displaying values. If Debutanizer_123 is already displayed, refresh the display.
• 11_TI40, 11_TI21, and 11_TI23 are shown below
Productivity Tools in Control Builder
Export/Import a Control Module
26 Copyright © 2013 Honeywell International Inc. 9/18/2013
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
7 • 11_TI25, 11_TI24 and 11_TI21 are shown below
• 11_TI22 is shown below
ATTENTION
Your displays may differ.
If values for 11_TI20 are not updating, close and re-open Tie_back_new.xls and verify the following is selected: Tools > Microsoft Excel Data Exchange > Recalculate Every 5 seconds
This file is used for simulation purposes.