Instructions for Productivity Tools in Control Builder
Introduction
This portion of the document contains important information required to perform to ‘Export-Import Control module’ lab.
Procedure
Step Action
1
Read the following IMPORTANT information carefully.
Decide if you will be performing labs for C200E (and Series A I/O modules) OR C300 (and Series C I/O Modules). You can opt for either one but not both.
_______ C200E (and Series A I/O modules)
_______ C300 (and Series C I/O Modules)
2
ATTENTION
You must perform the remaining steps of this lab if you skipped any of the prior lessons of this course, else skip the remaining instructions and proceed to the next lab.
Locate the “GUI_DB_Load” Shortcut on desktop.
1. Double click “GUI_DB_Load” Shortcut to launch the import utility.
2. In Controller drop down select either C200 or C300 Controller (as per the option selected in step#1).
3. In Lesson number drop down select Lesson11.
4. Click the LOAD button.
Productivity Tools in Control Builder
Instructions for Productivity Tools in Control Builder
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Step Action
3
ATTENTION
If you are facing any of the following situation while loading the data base:
1. Import wrong Lesson Database
2. Error prompt appears while loading data base.
Then students should wait for at least one minute before reloading the database.
4 Open Control Builder if not already open.
Download and activate Controller and control modules.
5 Ensure that the Controller and Control Modules are indicated in green color.
6 Open the Excel Spreadsheet if not already open. Open either from C:\Users\Student\Documents\Tie_Back_New.xls OR by double clicking the shortcut on your desktop.
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Export/Import a Control Module
Practice
Objective
• Use the Import and Export functionality of Control Builder to incorporate parts from one Control Builder Project into another Project
• Export the Control Module 11_TI20
• Import Analog Indicator points
• Use Bulk Edit Parameters to change parameter values
Prerequisites
• Experion PKS server or client machine loaded with Experion PKS Engineering Tools
• 11_TI20 CM configured in Control Builder
• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C200E\L11_Productivity tools in CB
• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C300\L11_Prodcutivity tools in CB
• Control Builder running with at least one Project/Monitor tree window open
• SIM_C200E/SIMC300 Controller and IOMs configured
Introduction
A Project file can contain many items, such as IOMs and CMs, for up to 20 controllers. From Control Builder, use the Import/Export tool to copy some or all of one project to another.
• Export - copies the designated portion of a project from Control Builder to a specified directory
• Import - copies the designated CMs into Control Builder’s Project Tab
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
Import a Control Module
Import copies designated Control Modules from the Import/Export files located in the specified directory (shown in the Import form) to a Control Builder Project.
In this lab, import the Analog Indicator points. These are pre-built CMs and already exported into the following directory:
• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C200E\\L11_Productivity tools in CB
• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C300\\L11_Productivity tools in CB
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
6 In Station, open the Debutanizer_123 graphic and verify that the downloaded points are displaying values. If Debutanizer_123 is already displayed, refresh the display.
HPS Automation College written permission required to distribute
Honeywell Confidential and Proprietary
7 • 11_TI25, 11_TI24 and 11_TI21 are shown below
• 11_TI22 is shown below
ATTENTION
Your displays may differ.
If values for 11_TI20 are not updating, close and re-open Tie_back_new.xls and verify the following is selected: Tools > Microsoft Excel Data Exchange > Recalculate Every 5 seconds