CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012 1
Installation Instructions
CNC2Communications Node Controller
Important: Retain these instructions
These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.
1 Dimensions
3 INsTallaTIoN3.1 Installation - Mounting
1 UNpaCkINg
2 sToRINg
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
CoNTeNTs1 Unpacking .....................................................................12 Storing ...........................................................................13 Installation .....................................................................13.1 Installation - Mounting ...................................................1
3.2 Installation - Configuring ...............................................34 Disposal .........................................................................4
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
H O2
+50 °C +122 °F
0-10 °C- 14 °F
95 %RH
CNC2 Installation Instructions TG200262
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
160 mm (6.3”)
151
mm
(5.9
5”)
33 mm (1.3”)
Caution: The CNC2 contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of electostatic sensitive devices.
WaRNINg: Opening the panel may expose dangerous voltages.
Altitude: <2000 m (6562’)
2 CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012
CNC2 Installation Instructions
3 Mount the Node
4 Connecting power
2 Mounting Requirements
3.1 Installation - Mounting (continued)
The CNC2 can be fitted into enclosures and controllers as shown in the table below:
* CNC2 board fits with 3 screws in normal node position or fits in NDP position. Must use NDP position if RDS fitted.
See appropriate enclosure/controller installation instructions for more details about node installation.
151 mm (5.9”)
141
mm
(5.6
”)
4 off 4 mm(0.16”)
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
18 Vac
18 Vac (isolated)
~ ~ 0V
18 18 0
18-0-18 Vac~ ~ 0V
+24 V 0V
24 Vdc~ ~ 0V
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
J16
Dev B
J15
Dev A
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
� �
� � �
� � �
� � � � �
� � �
� � � � �
� �
� � � � �
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
H O2
0 °C32 °F
+45 °C113 °F
0 %RH 95 %RH
� �
� � �
� � �
� � � � �
� � �
� � � � �
� �
� � � � �
Power consumption <=5 VA
terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
NETB/NETBB ü
IQ101+/102+ ü
IQ111+ ü
IQ131+ ü
IQ251 ü*IQ250 ü*
IQ241/242 ü
IQ231/233 ü
Operating Altitude: <2000 m (6562’)
O
I
Do NoT sWITCH oN poWeR
Do not connect 230V input power to this connector.
WaRNINg: This apparatus must be earthed (grounded) via input supply earth (ground) terminal. The earth (ground) on this unit is NOT a protective earth (ground), but it is essential that an earth is fitted for functional reasons.
Input power supply: The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit.
CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012 3
Installation Instructions CNC2
5 Connecting earth
6 Connect Network (lan a)
7 Connect to local Device (Device B - Rs232) (cables not supplied with unit)
3.1 Installation - Mounting (continued)
�
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
� � � � � � � ���
��
� �
�
� � � � � �
� � � � �
� � � � � � � � �
� � � � � � � ���
��
�
��
��
� � � � � � � �
� � � � �
� � � � � � � � �
2 wire
Network Engineering Manual, 92-1735.
additional terminals
4 wire
Polarity independent
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
WaRNINg: This apparatus must be earthed
Dev B
10 Way, Molex, Femalelinks between pins 2-4, 3-5
25 Way, D type, Female
CABLE/EJ100179A001
25 Way, D type, Male
CABLE/58-0750
9 Way, D type, Female
Device Blocal device
(e.g. PC)
J16
PC’s COM port
additional terminals
Terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
Cable 1k2 baud 4k8 baud 9k6 baud 19k2 baud No. of Wires
Belden 9182 1000 m (1090 yds)
1000 m (1090 yds)
1000 m (1090 yds)
700 m (765 yds) 2
Belden 9207 1000 m (1090 yds)
1000 m (1090 yds)
1000 m (1090 yds)
500 m (545 yds) 2
Trend TP/1/1/22/HF/200(Belden 8761)
1000 m (1090 yds)
1000 m (1090 yds)
700 m (765 yds)
350 m (380 yds) 2
Trend TP/2/2/22/HF/200(Belden 8723)
1000 m (1090 yds)
1000 m (1090 yds)
500 m (545 yds)
250 m (270 yds) 4
4 CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012
CNC2 Installation Instructions
8 Connect auxiliary supply output
9 Close enclosure/Controller
3.1 Installation - Mounting (continued)
J16
Dev B
J15
Dev A
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1 24 V
CNC2
24 VI max = 150 mA
aUX
terminal size 0.5 to 2.5 mm2
CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012 5
Installation Instructions CNC2
3 set the Network address(lan a)
1 switch off
4 set Network Baud Rate (Baud a)
2 open enclosure/Controller
3.2 INsTallaTIoN - CoNfIgURINg
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
O
I
� � � � � � �
� �
� � � �
� � � �
NOT SET
SET
e.g.
Address = D
= DCNC2
Address = 2+16+64= 82
/= D /= D
/= D
� � � � � � � � � � � �
� � � � � � � � � � � �
Network Baud Rate = R1move link to set baud rate
e.g 9k6
= R1
= R1
= R1= R1
J16
Dev B
J15
Dev A
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
WaRNINg: Opening the panel may expose dangerous voltages.
Caution: The CNC2 contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of electostatic sensitive devices.
address 1, 4 to 9, 11 to 114
0, 2, 3, 10 or >119
6 CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012
CNC2 Installation Instructions
7 Check Node Controller
6 switch on
5set Device B connector (Rs232) to local Device Baud Rate
3.2 INsTallaTIoN - CoNfIgURINg (continued)
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
O
I
Check supply
CNC2 Faulty
W/DOG
PWR ON(green)
(red)
� � � � � � � � � � � �
� � � � � � � � � � � �
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
Device B (J16) to local device Baud Rate = R2
move link to set baud rate
e.g 19k2
(Baud B)
= R2
CNC2
= R2
CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012 7
Installation Instructions CNC2
9 Close panel/covers
8 Check Network
10 Check system
3.2 INsTallaTIoN - CoNfIgURINg (continued)
O
I
� � � �
�
� � � �
�
� � � � � � � �
� � � � �� � � � � � � �
� � � � �
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
b TXA
a RXA
c OKA
✘
CNC2 Faulty Check network cabling for short circuits with a multimeter (NOT Megger)
Network Address Invalid 0, 2, 3 or >119
OKA OKA CNC2
Check baud ratePower up other nodes until faulty node is found (OK
). Correct fault.
(yellow)
(yellow)
(green)
J16
Dev B
J15
Dev A
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
CNC2 IQ
T=X °C
temperature ?T=X °C
Lan A
8 CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012
CNC2 Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2012 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control system Usa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
4 DIsposal
Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.