CNC2 Installation Instructions TG200262 Issue 3, 22-May-2012 1 Installation Instructions CNC2 Communications Node Controller Important: Retain these instructions These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. 1 Dimensions 3 INSTALLATION 3.1 Installation - Mounting 1 UNPACKING 2 STORING It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). CONTENTS 1 Unpacking .....................................................................1 2 Storing ...........................................................................1 3 Installation .....................................................................1 3.1 Installation - Mounting ...................................................1 3.2 Installation - Configuring ...............................................3 4 Disposal .........................................................................4 HO 2 +50 °C +122 °F 0 -10 °C- 14 °F 95 %RH CNC2 Installation Instructions TG200262 J7 J16 Dev B J15 Dev A J8 Lan A ET1 160 mm (6.3”) 151 mm (5.95”) 33 mm (1.3”) Caution: The CNC2 contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit. BS EN100015/1 Basic Specification: protection of electostatic sensitive devices. WARNING: Opening the panel may expose dangerous voltages. Altitude: <2000 m (6562’)
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.
1 Dimensions
3 INsTallaTIoN3.1 Installation - Mounting
1 UNpaCkINg
2 sToRINg
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
Caution: The CNC2 contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of electostatic sensitive devices.
WaRNINg: Opening the panel may expose dangerous voltages.
The CNC2 can be fitted into enclosures and controllers as shown in the table below:
* CNC2 board fits with 3 screws in normal node position or fits in NDP position. Must use NDP position if RDS fitted.
See appropriate enclosure/controller installation instructions for more details about node installation.
151 mm (5.9”)
141
mm
(5.6
”)
4 off 4 mm(0.16”)
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
18 Vac
18 Vac (isolated)
~ ~ 0V
18 18 0
18-0-18 Vac~ ~ 0V
+24 V 0V
24 Vdc~ ~ 0V
J7
J16
Dev B
J15
Dev A
J8
Lan A
ET1
J16
Dev B
J15
Dev A
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
� �
� � �
� � �
� � � � �
� � �
� � � � �
� �
� � � � �
J7
ET1
J16
Dev B
J15
Dev A
J8
Lan A
H O2
0 °C32 °F
+45 °C113 °F
0 %RH 95 %RH
� �
� � �
� � �
� � � � �
� � �
� � � � �
� �
� � � � �
Power consumption <=5 VA
terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)
NETB/NETBB ü
IQ101+/102+ ü
IQ111+ ü
IQ131+ ü
IQ251 ü*IQ250 ü*
IQ241/242 ü
IQ231/233 ü
Operating Altitude: <2000 m (6562’)
O
I
Do NoT sWITCH oN poWeR
Do not connect 230V input power to this connector.
WaRNINg: This apparatus must be earthed (grounded) via input supply earth (ground) terminal. The earth (ground) on this unit is NOT a protective earth (ground), but it is essential that an earth is fitted for functional reasons.
Input power supply: The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit.
WaRNINg: Opening the panel may expose dangerous voltages.
Caution: The CNC2 contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of electostatic sensitive devices.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control system Usa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
4 DIsposal
Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.