- 186 -
CHAPTER SEVENBASIC DIFFERENTIAL PROTECTION1.0Introduction
1.1Differential Protection is a form of protection whereby a
relay operates when the vector difference of two or more similar
electrical quantities exceeds a predetermined amount.
1.2This relay is called a Differential Relay and may take on a
variety of forms depending upon the equipment being protected.
1.3Almost any type of relay when connected in a certain way can
be made to operate as a Differential relay. In other words it is
not so much as the construction of the relay, but the manner in
which the relay is connected in a circuit that makes it a
differential relay.
2.0Basic Differential Relaying2.1The basic scheme of
differential relaying is explained with reference to the diagram
below:-
2.2The protected equipment may be a length of a circuit or a
winding of a generator, or a portion of the bus etc. A C.T is
connected at either end of the protected equipment. The secondaries
of the C.Ts are interconnected as shown with a relay which may be
an over-current relay.
2.3Now suppose current flows through the protected equipment to
an external load or to a fault at X. If the two C.Ts have an
identical ratio, and are properly connected with respect to
polarity, then the secondary induced currents i1 and i2 will merely
circulate between the two C.Ts and no current flows through the
relay.
2.4However if an internal fault should develop in the protected
equipment or between the primaries of the two C.Ts then the
currents I1 and I2 will be different. The current I1 will be the
sum of current I2 and fault current If. Accordingly the C.T
secondary currents will be different and the difference in the
(i1-i2) flows through the relay causing the relay to operate.
2.5This relay which operates on the vector difference of the
current entering and leaving protected equipment is called a
differential relay and the scheme of protection as Differential
Protection.
3.0Types of Differential Protection or RelayingThere are two
basic types of Differential Relaying namely:-
a) Current Differential Relayingb) Voltage Differential
Relaying
3.1Current Differential RelayingThis is also called the current
balance method or circulating current method of Differential
Relaying. The principle of this method has already been described
in paragraph 2.0 above. Most differential relay applications are of
the Current Differential Method and the method is applied for the
protection of Generators, Transformers, Motors and Bus bars.
3.2Voltage Differential RelayingThis is called voltage balance
method or opposed voltage relaying. The two C.Ts at either end of
the protected equipment are cross connected with the relay in
series as shown below:
Let Z be the impedance of the relay coil.
Then voltage drop produced due to secondary current i1 in
Z:V1=i1 Z.
Similarly the voltage dropV2=i2 Z
When current i1 and i2 are equal the voltage drop V1 and V2 are
equal and opposed and the relay does not operate.
The relay operates when the vector difference in the voltage
drop exceeds the pick up value of the relay. Opposed voltage method
of Differential Relaying is generally employed for the protection
of transmission lines and feeders in A.C. wire Pilot Relaying.
4.0Biased Differential Protection or Percentage differential
Protection4.1This is the most extensively used form of differential
protection. It is essentially the same scheme as described in
paragraph 2.0 above except that restraining coils are introduced in
the C.T secondary circuit as shown below:-The differential current
to operate this relay is a variable quantity owning to the effect
of the restraining coil. The differential current in the operating
coil is proportional to (I1 I2).
4.2The development of the percentage differential relay was
necessitated to take care of the following:-
a) Although C.Ts of identical ratios are used, their performance
during through faults when the C.Ts are saturated cannot be ensured
to be the same. The errors introduced may be different with the
result an operating current will flow.
Example:
I1=I2=2100 A
i1=2100 x 5 (3 x 2100 x 5)
300 100 300
=35 1.05
=33.95 A
i2 =2100 x 5 + (6 x 2100 x 5)
300
100300
=35 + 2.1=37.1 A
Difference in currents =i2i1=37.133.95
=3.15 A
This difference in current may be sufficient to cause operation
in the 5A relay unless the pick up value is greater than 3.15
A.
It should also be noted that no two C.Ts however identical they
may be in so far as their secondary currents are concerned will
give exactly the same secondary current for the same primary
current. These discrepancies may be traced to manufacturing
variations and to differences in secondary loading caused by
unequal length of leads between C.T and relay, unequal burden of
meters and instruments connected in one or both secondaries.b)
Another example of an on load tap changing Transformer is taken to
study the effects on the differential circuit.
At normal tap of 330KV/132KV
Primary full load current=80 x 106 _____3 x 330 x 103=140 A
Primary C.T. Ratio
=140/1C.T. secondary current of primaryi1=140 x 1_140
=1.0 A
Secondary full load current
=80 x 106 _____3 x 132 x 103=350 A
Secondary C.T. Ratio=350/1
C.T. secondary current of secondaryi2=350 x 1__350
=1.0A
Since i1 = i2 no current flows in the differential relay and
therefore the relay does not operate. Let us now assume that the
primary incoming voltage is 310 KV and the OLTC gear is operated to
raise the secondary voltage to say 140 KV.
Then primary full load current=80 x 106 _____3 x 310 x 103=149
A
C.T secondary current of primary i1=149.00 x 1 140
i1=1.06 A
Secondary full load current
=80 x 106 _____3 x 140 x 103=330 A
C.T secondary current of secondaryi2=330 x 1__350
=0.94 A
Now the difference in the currents between (i1 and i2)
=(1.06 0.94) A=0.120 A
This current of 0.120A flowing in a 1 A relay may cause
operation of the differential relay unless the pick up value of the
relay is raised to be beyond 0.120 Amps. It is also not practical
to keep on raising the pick up value whenever a tap changing
operation is carried out.
4.3Thus to obviate all these practical difficulties, the
percentage differential relay was developed. The current flowing
through the restraining coil or windings is called the Through
Current and the current flowing through the operating winding is
called the Spill Current.
4.4This spill current necessary to operate the relay expressed
as a percentage of the through current is called the percentage
bias.
% bias=Spill current for relay operation x 100
Through fault current causing it
4.5Bias is provided on both the restraining windings by a plug
setting bridge in electromagnetic relays and in static relays by a
rotary switch. Bias settings are usually from 10% to 80% in
multiples of 10% or 20% to 80% in multiples of 20% or sometimes in
multiples of 15%.
4.6The number of turns on both the restraining windings are
always the same so that in effect it can be considered as one
winding, with the operating coil or winding connected at its mid
point.
Let N be the turns in the restraining winding.
Then the restraining torque produced is:=I1 N+I2 N 2
2
=(I1 + I2) N
2
Or Restraining Torque is I1 + I2 2
4.7The operating characteristic of such a relay is as shown
below:
4.8It can be seen that (I1 + I2)/2 is the average of the two
currents I1 and I2. Specifically the term through current is used
to designate I2 as it is this current which flows in the circuit
from one end to the other and also causes the relay operation.
Hence the characteristic is also plotted with I2 as abscissa
instead of (I1 + I2)/2.
4.9The operating characteristic is a straight line indicating
that the spill or operating current is a fixed percentage of the
through current. Hence the name Percentage Differential
5.0ApplicationPercentage Differential relays are almost always
used as the primary protection device for generators, transformers,
motors and other costly electrical apparatus in industry.
PAGE 192