  • Truck Engine Driven Refrigeration Units

    Model HT-050 II series

    HT-070 II series

    HT-100 II series

    HT-250 II series

    HT-500 II series

    Model HT-100MB series

    HT-250MB series

    HT-500MB series

    Operation Manual

  • - 1 -

    Introduction

    It is recommend you study the information contained in this manual, as it contains important instructions

    on the correct operation of the unit controls.

    This operating manual is published for informational purpose only and the information being furnished

    should not be considered as all inclusive or meant to cover all contingencies. Performing pre-trip checks

    and enroute inspections on a regular basis will minimize on the road operating problems.

    A closely followed maintenance program will also keep your refrigeration unit fully operational and safe

    at all times.

    Contents

    Safety precaution 2

    First aid 2

    Location of safety decals 3

    Unit description 4

    Unit specification 5-9

    Temperature control SH-710ES 10-14

    Temperature control SH-900/900ES 15-18

    Temperature control SH-900K 19-21

    Temperature control SH-800H 22-24

    Error code and Trouble shooting 25-26

    Pre-trip inspection of refrigeration unit 27-28

    Safety device 28

    Adjust belt tension 29

    Safety countermeasure 30

    Handling refrigeration vehicle 30

    Maintenance inspection schedule 31

    * All specification in this manual can be changed without prior notice.

  • - 2 -

    SAFETY PRECAUTION Always wear safety glasses when working around or using battery acid or refrigerant.

    Never operate the unit with the compressor discharge valve closed.

    Avoid wearing loose clothing and touching parts when the unit is operating.

    Drilling holes in the unit could weaken the structure or cause electrical fires.

    Any work carried out on the unit must be done by a qualified technician.

    Electric Standby

    The unit may start automatically at any time when connected to power, and the on/off switch is in the

    On position.

    Electrical Hazard

    Disconnect the electrical power cable from the all before commencing work on the unit.

    Refrigerant Gas

    Although fluorocarbon refrigerants are classified as safe, observe caution when working with

    refrigerants.

    When released into the atmosphere in the liquid state, fluorocarbons evaporate rapidly freezing

    anything they contact.

    Fluorocarbons tend to displace air and can cause oxygen depletion which in turn could cause

    unconsciousness if released in a confined space.

    Refrigerant Oil

    Do not allow refrigerant oil to contact your eyes.

    Do not allow prolonged contact with skin or clothing.

    Wash thoroughly after use to avoid irritation.

    FIRST AID Refrigerant Gas

    Eyes : Flush immediately with water and seek medial assistance.

    Skin : Flush area with warm water and do not apply heat. Wrap burns with dry, sterile dressing

    and seek medical assistance.

    Inhalation : Move victim to fresh air and if necessary restore breathing. Stay with victim until medical

    assistance arrives.

    Refrigerant Oil

    Eyes : Flush immediately with water at least 25minutes while holding the eyelids open. Seek

    medical assistance.

    Skin : Remove contaminated clothing. Seek medical assistance if irritation is experienced.

    Inhalation : Move victim to fresh air and if necessary restore breathing. Stay with victim until medical

    assistance arrives.

    Ingestion : Do not induce vomiting. Seek medical assistance.

  • - 3 -

    LOCATION OF SAFETY DECALS

    1. Fan Caution

    Located top of the condenser

    2. Power supply(option feature)

    Located on the power receptacle box

    FAN CAUTION

    AC 220/380/415 VOLTS

  • - 4 -

    Condenser Evaporator

    Cab control box

    CompressorUnder-mounted Electric

    standby unit

    LP/HP hoses

    and tubes

    UNIT DESCRIPTION The HwaSung Thermo units HT-050 II, HT-100 II, HT-250 II and HT-500 II are two split units designed

    for fresh and frozen on vans and small to medium trucks. On compressor is powered by the vehicles engine while another one is powered by an electric motor. Models with heating system are also

    available.

  • - 5 -

    SPECIFICATION MODEL HT-050 HT-070 HT-100 HT-250 HT-500

    Cargo Size 3.5~4.5 3.5~5 5~12 8~16 12~20 Operation Compressor is powered by truck engine

    Thermo controller In-cab controls by digital Thermometer

    Refriger-

    ant

    Type R-404A

    Amount(Kg) 1.2Kg 1.5Kg 1.6~2.0Kg 1.8~2.0Kg 2.2Kg

    Comp.

    Model TM-13HD SELTEC TM-15HD TM-16HD

    Origin Japan

    Type Swash plate type

    No. Cylinder 6cylinders

    Displacement 131cc 147cc 163cc

    RPM 700~6000

    Weight(approx.) 4.4kg 4.6kg 4.9kg

    Comp. Oil Jomo Freol Alpha 32TF

    Amount(cc) 180cc 200cc 210cc

    EVA.

    Coil Aluminum. FIN & Copper Tube

    Size(mm) 840*629*1630 840*629*163 1040*669*168 1200*689*170 1300*682*152

    Fan motor DC 12V*6Amp

    2700rpm*2EA

    DC 12V*6Amp

    2700rpm*2EA

    DC 12V*6Amp

    2350rpm*2EA

    DC 12V*6Amp

    *2350rpm*2EA

    DC 12V*6Amp

    *2350rpm*3EA

    Fan AL 230

    *4wings*2EA

    AL 230

    *4wings*2EA

    AL 250

    *5wings*2EA

    PL 300

    *4wings*2EA

    AL 250

    *5wings*3EA

    Case ABS 3.0t ABS 3.0t ABS 3.0t ABS 3.0t Aluminum

    Install Slim/Ceiling Slim/Ceiling Slim/Ceiling Slim/Ceiling Slim/Ceiling

    Weight(approx.) 21kg 21kg 24kg 29kg 34kg

    COND.

    Coil Aluminum. FIN & Copper Tube

    Size(mm) 960*431*220 1090*470*258 1090*470*258 1120*497*395 1120*497*395

    Fan motor DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    Fan AL 250

    *5wings*2EA

    AL 250

    *5wings*2EA

    AL 250

    *5wings*2EA

    AL 250

    *5wings*2EA

    AL 250

    *5wings*2EA

    Case ABS 3.0t ABS 3.0t ABS 3.0t ABS 3.0t ABS 3.0t

    Install Nose(front) mount type

    Weight(approx.) 22kg 25kg 25kg 32kg 34kg

    Defrost Automatic hot gas defrost by microprocessor

  • - 6 -

    MODEL HT-050RT HT-100RT HT-250RT

    Operation Compressor is powered by truck engine or electric standby

    motor

    Thermo controller In-cab controls by digital Thermometer

    Refrigerant Type R-404A R-404A R-404A

    Amount(Kg) 1.2kg 1.6~2.0kg 1.8~2.0kg

    Compressor

    Model TM-13HD TM-15HD TM-15HD

    Origin Japan Japan Japan

    Type Swash plate type Swash plate type Swash plate type

    No. of Cylinder 6 cylinders 6 cylinders 6 cylinders

    Displacement 131cc 147cc 147cc

    RPM 700~6000rpm 700~6000rpm 700~6000rpm

    Weight(approx. ) 4.4 Kg 4.6 Kg 4.6 Kg

    Evaporator

    Type Ceiling / Slim type

    Coil Aluminum. FIN & Copper tube

    Size(mm) 840*659*163 1040*669*168 1200*689*170

    Fan motor DC 12V*6Amp

    *2700rpm*2EA

    DC12V*6Amp*

    2350rpm*2EA

    DC12V*6Amp*

    2350rpm*2EA

    Fan Aluminium230c*

    4blades*2EA

    Aluminium250*

    5blades*2EA

    Aluminium300*

    4blades*2EA

    Case ABS 3.0t ABS 3.0t ABS 3.0t

    Weight(approx. ) 21Kg 24Kg 29Kg

    Condenser

    Coil Aluminum. FIN & Copper tube

    Size(mm) 740*175*830 910*182*840 956*182*910

    Fan motor DC 12V*7Amp*

    2350rpm*2EA

    DC 12V*7Amp*

    2350rpm*2EA

    DC 12V*7Amp*

    2350rpm*2EA

    Fan Plastic300*

    5blades*1EA

    Aluminium250*

    5blades*2EA

    Plastic300*

    5blades*2EA

    Install Roof Top mount type

    Case Aluminum front top grill & side FRP covers

    Weight(approx.) 16Kg 18Kg 18Kg

    Defrost Automatic hot gas defrost by microprocessor

  • - 7 -

    MODEL HT-100ESC HT-250ESC HT-500ESC Operation Compressor is powered by vehicle engine or electric motor

    Thermo controller In-cab controls by digital Thermometer

    Refrigerant Type R-404A R-404A R-404A

    Amount(Kg) 1.6kg 2.0kg 2.0kg

    Compressor

    Model TM-15HD

    Origin Japan

    Type Swash plate type

    No. of Cylinder 6 cylinders

    Displacement 147cc

    RPM 700~6000rpm

    Weight(approx. ) 4.6 Kg

    AC Motor

    Origin Korea(HS Thermo)

    AC Voltage 220/380/415Vac

    Phase Three Phase

    Hertz 50HZ/60HZ

    HP 3HP

    kW 2.2kw

    Weight(approx.) 24kg

    Evaporator

    Type Ceiling/Slim Type

    Coil Aluminum FIN & Copper Type

    Size(mm) 1040*669*168 1200*689*170 1300*682*152

    Fan motor DC 12V*6Amp

    *2350rpm*2EA

    DC 12V*6Amp

    *2350rpm*2EA

    DC 12V*6Amp

    *2350rpm*3EA

    Fan Aluminum 250

    *5wings*2EA

    Plastic 300

    *4wings*2EA

    Aluminum 250

    *5wings*3EA

    Case ABS 3.0t ABS 3.0t ABS 3.0t

    Weight(approx.) 24kg 29kg 34kg

    Condenser

    Coil Aluminum FIN & Copper Tube

    Size(mm) 1148*530*327 1200*540*430 1320*556*460

    Fan motor DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    DC 12V*7Amp

    *2350rpm*2EA

    Fan AL 250*

    5wings*2EA

    AL 250*

    5wings*2EA

    PL.300*

    4wings*2EA

    Install Nose(front) mount type

    Case FRP case Steel front grill & side FRP doors

    Weight(approx.) 86kg 124kg 133kg

    Defrost Automatic hot gas defrost by microprocessor

  • - 8 -

    MODEL HT-100MB HT-250MB HT-500MB

    Operation Compressor is powered by truck engine

    or electric standby motor

    Thermo controller In-cab controls by digital Thermometer

    Ref.

    Type R-404A

    Amount(kg) 1.6kg 2.5kg 2.7kg

    Compressor

    Model TM-15HS TM-15HS/TM-16HS TM-16HS/TM-21HX

    Origin Japan

    Type Swash plate type

    Cylinder 6cylinders

    cc 147cc 147cc/163cc 163cc/215cc

    RPM 700~6000rpm

    Evaporator

    Coil Aluminium. FIN & Copper Tube

    Fan motor DC 12V/24V, 2100rpm, 3EA

    Fan PL.TURBO 240 FAN

    Condenser

    Coil Aluminium. FIN & Copper Tube

    Size(mm) 1418*550*493 1733*565*620 1733*565*620

    Fan motor DC 12V/24V, 2350rpm, 2EA

    Fan AL.5B*250 PL.4B*300 PL.4B*300

    Install Nose(front) mount type

    Case FRP ABS ABS

    Size(mm) 1418*550*493 1733*675*620 1733*675*620

    Weight (approx. kg) 80kg 98kg 102kg

    Defrost Automatic hot gas defrost initiated

    & terminated by cab controller

  • - 9 -

    MODEL HT-250MB ESC HT-500MB ESC

    Operation Compressor is powered by truck engine or electric standby motor

    Thermo controller In-cab controls by digital Thermometer

    Ref. Type R-404A R-404A

    Amount(kg) 2.5kg 2.7kg

    Compressor

    Model TM-15HS/TM-16HS TM-16HS/TM-21HX

    Origin Japan

    Type Swash plate type

    Cylinder 6cylinders

    cc 147cc/163cc 163cc/215cc

    RPM 700~6000rpm

    AC Motor

    Origin Korea(HS Thermo)

    AC Voltage 220V/380V/415V AC

    Phase Single / Three Phase

    Hertz 50HZ / 60HZ

    HP 3HP

    kW 2.2kw

    Weight(approx. kg) 24kg

    Evaporator

    Coil Aluminium. FIN & Copper Tube

    Fan motor DC 12V/24V, 2100rpm, 3EA

    Fan PL.TURBO 240 FAN

    Condenser

    Coil Aluminium. FIN & Copper Tube

    Size(mm) 1733*565*620

    Fan motor DC 12V/24V, 2350rpm, 2EA

    Fan PL.4B*300*45

    Install Nose(front) mount type

    Case ABS

    Weight (approx. kg) 145kg Included A/C Motor 150kg Included A/C Motor

    Defrost Automatic hot gas defrost initiated & terminated by cab controller

  • - 10 -

    TEMERATURE CONTROLS

    Cab control system Model HS710ES (standard export)

    1. Front Panel commands

    Power switch :Power on/off switch for refrigeration unit. Mode/Set :To display target set point, in programming mode it selects a parameter or confirm an operation.

    Def :To start a manual defrost A/C:To start air conditioning(optional feature) Up :To see the max. stored temperature, in programming mode it browses the parameter code, or increase the displayed value.

    Down :To see the min. stored temperature, in programming mode it browses the parameter code, or decrease the displayed value.

    1-1. Description of indicators in the display

    Indicators Mode Function

    On Showing Temperature A(single compartment)

    On Showing Temperature B for second compartment(option)

    On Showing Temperature setting

    On Cooling is started

    On Defrost enabled

    On Air conditioning mode(Option)

    On Electric power engaged(Option)

    On/Flash Trouble with compressor

  • - 11 -

    1-2 Use of Leds

    Led Mode Function

    POWER On Showing power is On. Compressor enabled

    A/C On Showing air conditioning mode(Option)

    COOL On Showing cooling is started

    DEF On Defrost enabled

    SET On Showing temperature is setting with new value

    HEAT On Heating system(option)

    E.S On Electric power engaged

    2. How to start and stop the cab controller

    1> Start the vehicle engine

    2> Press the POWER key to start the refrigeration

    unit. Type of controller will be displayed shortly.

    3> Power led will be on.

    4> Current cargo temperature will be displayed.

    5> If the cargo temperature is higher than set

    temperature, refrigeration unit is running in Cooling

    mode. Cooling indicator will be on.

    6> To stop the controller, press the POWER key

    again.

    2-1 How to change the set point(new temperature)

    1> Press the MODE/SET key once to change the set

    point value.

    2> The current value of the set point will be displayed.

    3> To change the set value, push the UP or DOWN

    key.

    4>To memorize the new set temperature value, push

    the MODE/SET key again.

    5> Cooling led can be On before or after setting.

    ! Cooling indicators can be light on whenever

    temperature is higher than set temperature and will

    be off when it reaches at set point. Condenser and

    evaporator fans will be stopped at the same time of

    cooling off.

  • - 12 -

    2-2 How to start a manual defrost

    1> Press the DEF key and a manual defrost will start

    2> Defrost indicator will be light and DEF led will be

    lighted on.

    3> Press DEF key again to stop the defrost. If not

    pressed, defrost will be stopped depend on the set

    value.

    2-3 How to change the defrost time

    Determines the defrost duration.

    1> Press MODE/SET key more than 6seconds until

    t10 is displayed.

    2> To change the defrost time, push UP or DOWN

    key.

    3> To memorize the new defrost time, push the

    MODE/SET key again.

    4> Defrost time can be set from 00 to 30minutes

    Eg)t05(5min.), t10(10min)

    ! Factory setting : t10(10min)

    2.4 How to change the defrost period

    Determines the time interval between the beginning

    of two defrost cycles.

    1> Press MODE/SET key more than 6seconds until

    t10 is displayed.

    2> Press one more time and d0.0 will be displayed

    3> To change the defrost period, push UP or Down

    key.

    4> To memorize the new defrost period, push

    the MODE/SET key again.

    5> Defrost period can be set from 0.0 to 3.0hours,

    every 30mintues.

    ! Factory setting : d0.0 User has to enter the value.

    Display 0.0 0.3 1.0 1.3 2.0 2.3 3.0

    Value 0 30min. 1hour 1hr & 30min. 2hours 2hrs & 30min 3hours

  • - 13 -

    2-5 How to change the temperature calibration

    Allows to adjust possible offset of the thermostat probe.

    1> Press the MODE/SET key more than 6seconds

    until C0.0 is displayed.

    2> To change the value, push UP or DOWN key.

    3> Press MODE/SET key to memorize the new value.

    4> Temperature calibration range : 9.9

    2-6 How to change the differential

    Intervention differential for set point. Compressor Cut

    In is set point plus differential. Compressor Cut Out is

    when the temperature reaches the set point.

    1> Press the MODE/SET key more than 6seconds.

    2> Press the MODE/SET key again until 02d is displayed.

    3> To change the value, press the UP or DOWN key.

    4> Press the MODE/SET key to memorize the new

    value.

    5> Differential range : 1~9 ! Factory setting : 2

  • - 14 -

    3. How to start Air conditioning(optional feature)

    1> Press the POWER key to start the controller for

    refrigeration unit..

    1> Press the A/C key to start air conditioning. A/C indicator

    will be light on.

    2> Press the A/C key again to stop air conditioning.

    Although Air conditioning is off, refrigeration unit is still running.

    ! If Air conditioning is only necessary to operate, turn off the Power Switch. Then refrigeration unit will be

    stopped and only the air conditioning will be operated.

    4. Electric Standby power input(optional feature)

    Allows the operation of the unit while the

    vehicle engine is off, the refrigeration unit will

    be operated by the standby motor.

    1> Stop the vehicle engine.

    Warning! Electric standby can be damaged if it

    is connected while engine is running.

    2> Connect the plug to the main electricity.

    Warning! Check the AC voltage of refrigeration

    unit and main power before connecting. Electric standby can be damaged if it in connected with

    incorrect voltage.

    3> Push the POWER SWITCH to start the electric standby. Plug indicator will be light on and E.S

    leds also lighted on.

    4> Cooling and Defrost indicators will be light on together for pressure equalization at the

    beginning of start for about 8seconds.

    5> After equalization, defrost indicator will be off and if cooling will be started.

    6> To stop the electric standby, press the power switch off and disconnect the plug.

    5. How to change the equalization time.

    1> Push the UP key more than 6seconds.

    2> F08 will be displayed.

    3> Push UP or DOWN keys to change the value.

    4> Press the MODE/SET key to memorize the new value.

    ! Factory setting : 8seconds

    ! Equalization range : 8~12seconds.

  • - 15 -

    Cab control system Model HS900, 900ES (Hyundai Motor Mighty 2.5ton)

    1. Front Panel commands

    Power switch :Power on/off switch for refrigeration unit. Mode/Set :To display target set point, in programming mode it selects a parameter or

    confirm an operation.

    Def :To start a manual defrost A/C :To start air conditioning(optional feature) Up :To see the max. stored temperature, in programming mode it browses the

    parameter code, or increase the displayed value.

    Down :To see the min. stored temperature, in programming mode it browses the parameter code, or decrease the displayed value.

    1-1. Description of indicators in the displays

    Indicators Mode Function

    On Show ing Temperature A(single compartment)

    On Show ing Temperature B for second compartment(option)

    On Show ing Temperature setting

    On Cooling is started

    On Defrost enabled

    On Air conditioning mode(Option)

    On Electric pow er engaged(Option)

    On/Flash Trouble w ith compressor

  • - 16 -

    2. How to start and stop the cab controller

    1> Start the vehicle engine.

    2> Press the POWER key to start the refrigeration

    unit. The type of controller will be displayed shortly.

    3> Current cargo temperature will be displayed.

    4> If the cargo temperature is higher than set

    temperature, refrigeration unit running in Cooling

    mode. Cooling indicator will be on.

    5> To stop the controller, press POWER key again.

    2-1 How to change the set point(temperature)

    1> Press the MODE/SET key once to change the

    set temperature value.

    2> Current value of the set point will be displayed.

    3> To change the set value, push the UP or

    DOWN key

    4> Push the MODE/SET key again to memorize

    the new set temperature.

    ! Cooling indicators can be light on whenever

    temperature is higher than set temperature and will be off when it reaches at set point. Condenser and

    evaporator fans will be stopped at the same time of cooling off.

    2-2 How to start a manual defrost

    1> Push DEF key and a manual defrost will be

    started.

    2> Defrost indicator will be light on.

    3> Push DEF key to stop the defrost.

    4> Defrost will be automatically stopped if you DEF key is not pressed.

    Caution If cargo temperature is over 15, defrost will be automatically stopped and DEF key will not be operated.

    Defrost time(duration) can be set between 0~30minutes and only manual defrost is operated with 0 minute.

    2-3 How to change the defrost time

    Determine the defrost duration.

    1> Push MODE/SET key more than 3seconds until

    t10 is displayed.

    2> To change the defrost time, push UP or DOWN

    key.

    3> To memorized the new Defrost time, push the

    MODE/SET key again.

    ! Defrost time(duration) can be set between

    0~30minutes. Eg) t05(4min.), t10(10min.)

    ! : Factory setting : t10(10minutes)

  • - 17 -

    2-4 How to change the defrost period

    Determine the time interval between the beginning

    of two defrost cycles.

    1> d00 will be displayed after new defrost time is

    set Or Press the MODE/SET key more than

    3seconds until t10is displayed.

    2> Press once more and D0.0will be displayed.

    3> To change the defrost value, push UP or

    DOWN key.

    4> Push the MODE/SET key again to memorize the new defrost period.

    5> Defrost period can be set from 0.0 to 3.0hours,every 30mintues.

    Display 0.0 0.3 1.0 1.3 2.0 2.3 3.0

    Value 0 30min. 1hour 1hr & 30min. 2hours 2hrs & 30min 3hours

    ! Factory setting : d0.0, User has to enter the value.

    2-5 How to change the temperature calibration

    Allows to adjust possible offset of the thermostat

    probe.

    1> Press the MODE/SET key more than 6seconds

    until C0.0 is displayed.

    2> To change the value, push UP or DOWN key.

    3> Press MODE/SET key to memorize the new

    value.

    4> Temperature calibration range : 9.9 ! Factory setting : 0.0

    2-6 Differential

    Interval differential for set point. Compressor Cut In is set point plus Differential and Compressor Cut

    Out is when the temperature reaches at set point.

    ! Factory setting : 2 and impossible to change the value.

  • - 18 -

    3. How to start Air conditioning(optional feature)

    1> Press the POWER key to start the controller for

    refrigeration unit..

    1> Press the A/C key to start air conditioning. A/C indicator

    will be light on.

    2> Press the A/C key again to stop air conditioning.

    Although Air conditioning is off, refrigeration unit is still

    running.

    ! If Air conditioning is only necessary to operate, turn off the Power Switch. Then refrigeration unit will be

    stopped and only the air conditioning will be operated.

    4. Electric Standby power input.(900ES Only)

    1> When you stop operating by vehicle engine, and wish to operate the unit by standby motor, connect

    the plug to outside electricity .

    2> Push the POWER Switch to start the electric standby. Plug indicator will be light on

    3> Cooling and Defrost indicators will be light on together for pressure equalization at the beginning of

    start for about 8seconds.

    4> After equalization, defrost indicator will be off and if cooling will be started.

    5> To stop the electric standby, press the power switch off and disconnect the plug.

  • - 19 -

    Cab control system Model SH900, 900K (Kia Motor New Frontier 1ton)

    1. Front Panel commands

    Power switch :Power on/off switch for refrigeration unit. A/C :To start air conditioning(optional feature) Mode/Set :To display target set point, in programming mode it selects a parameter or

    confirm an operation.

    Def :To start a manual defrost Up :To see the max. stored temperature, in programming mode it browses the

    parameter code, or increase the displayed value.

    Down :To see the min. stored temperature, in programming mode it browses the parameter code, or decrease the displayed value.

    1-2. Description of indicators in the displays

    Indicators Mode Function

    On Showing Temperature A(single compartment)

    On Showing Temperature B for second compartment(option)

    On Showing Temperature setting

    On Cooling is started

    On Defrost enabled

    On Air conditioning mode(Option)

    On Electric power engaged(Option)

  • - 20 -

    2. How to start and stop the cab controller

    1> Start the vehicle engine.

    2> Press the POWER key, then the type of

    controller will be displayed in very short time.

    3> Current cargo temperature will be displayed.

    4> If the cargo temperature is higher than set

    temperature, refrigeration unit running in Cooling

    mode. Cooling indicator will be on.

    5> To stop the controller, press POWER key again.

    2-1 How to change the set point(temperature)

    1> Press the MODE/SET key once to change the

    set temperature value.

    2> Current value of the set point will be displayed.

    3> To change the set value, push the UP or

    DOWN key

    4> Push the MODE/SET key again to memorize

    the new set temperature.

    ! Cooling indicators can be light on whenever

    temperature is higher than set temperature and will be off when it reaches at set point. Condenser and

    evaporator fans will be stopped at the same time of cooling off.

    2-2 How to start a manual defrost

    1> Push DEF key and a manual defrost will be

    started.

    2> Defrost indicator will be light on.

    3> Push DEF key to stop the defrost.

    4> Defrost will be automatically stopped if you DEF key is not pressed.

    Caution If cargo temperature is over 15, defrost will be automatically stopped and DEF key will not be operated.

    Defrost time(duration) can be set between 0~30minutes and only manual defrost is operated with 0 minute.

    2-3 How to change the defrost time

    Determine the defrost duration.

    1> Push MODE/SET key more than 3seconds

    until t10 is displayed.

    2> To change the defrost time, push UP or DOWN

    key.3> To memorized the new Defrost time, push

    the MODE/SET key again.

    ! Defrost time(duration) can be set between

    0~30minutes. Eg) t05(4min.), t10(10min.)

    ! : Factory setting : t10(10minutes)

  • - 21 -

    2-4 How to change the defrost period

    Determine the time interval between the beginning

    of two defrost cycles.

    1> d00 will be displayed after new defrost time is

    set Or Press the MODE/SET key more than

    3seconds until t10is displayed.

    2> Press once more and D0.0will be displayed.

    3> To change the defrost value, push UP or

    DOWN key.

    4> Push the MODE/SET key again to memorize the new defrost period.

    5> Defrost period can be set from 0.0 to 3.0hours,every 30mintues.

    Display 0.0 0.3 1.0 1.3 2.0 2.3 3.0

    Value 0 30min. 1hour 1hr & 30min. 2hours 2hrs & 30min 3hours

    ! Factory setting : d0.0, User has to enter the value.

    2-5 How to change the temperature calibration

    Allows to adjust possible offset of the thermostat

    probe.

    1> Press the MODE/SET key more than 6seconds

    until C0.0 is displayed.

    2> To change the value, push UP or DOWN key.

    3> Press MODE/SET key to memorize the new

    value.

    4> Temperature calibration range : 9.9 ! Factory setting : 0.0

    2-6 Differential

    Interval differential for set point. Compressor Cut In is set point plus Differential and Compressor Cut

    Out is when the temperature reaches at set point.

    ! Factory setting : 2 and impossible to change the value.

    3. How to start Air conditioning(optional feature)

    1> Press the POWER key to start the controller for

    refrigeration unit.

    2> Press the A/C key to start air conditioning. A/C indicator

    will be light on.

    3> Press the A/C key again to stop air conditioning.

    Although Air conditioning is off, refrigeration unit is still running.

    ! If Air conditioning is only necessary to operate, turn off the Power Switch. Then refrigeration unit will be stopped and only the air conditioning will be operated.

  • - 22 -

    Cab control system Model SH-800H (Hyundai Motor New Porter II 1ton)

    1. Front Panel commands

    Power S/W :Power on/off switch for refrigeration unit. A/C :To start air conditioning(optional feature) Set :To display target set point, in programming mode it selects a parameter or

    confirm an operation.

    Def :To start a manual defrost Up :To see the max. stored temperature, in programming mode it browses the

    parameter code, or increase the displayed value.

    Down :To see the min. stored temperature, in programming mode it browses the parameter code, or decrease the displayed value.

    1.1 Description of indicators in the displays

    Indicators Mode Function

    On Cooling is started

    On Defrost enabled

    On Air conditioning mode(Option)

    On Showing Temperature setting

    On Electric power engaged(Option)

    2. How to start and stop the cab controller

    1> Start the vehicle engine.

    2> Press the POWER key, then the type of

    controller will be displayed in very short time.

    2> Current cargo temperature will be displayed.

    3> If the cargo temperature is higher than set

    temperature, refrigeration unit running in Cooling

    mode. Cooling indicator will be on.

    4> To stop the controller, press the POWER key

    again.

  • - 23 -

    2-1 How to change the set point(temperature)

    1> Press the SET key once to change the set

    temperature value.

    2> Current value of the set point will be displayed

    and SET indicator will be light on.

    3> To change the set value, push the UP or

    DOWN key

    4> Push the SET key again to memorize the new

    set temperature.

    ! Cooling indicators can be light on whenever

    temperature is higher than set temperature and will be off when it reaches at set point. Condenser and

    evaporator fans will be stopped at the same time of cooling off.

    2-2 How to start a manual defrost

    1> Push DEF key and a manual defrost will be

    started.

    2> Defrost indicator will be light on.

    3> Push DEF key to stop the defrost.

    4> Defrost will be automatically stopped if you

    DEF key is not pressed.

    Caution If cargo temperature is over 15, defrost will be automatically stopped and DEF key will not be operated.

    Defrost time(duration) can be set between 0~30minutes and only manual defrost is operated with 0 minute.

    2-3 How to change the defrost time

    Determine the defrost duration.

    1> Push SET key more than 3seconds until t10

    is displayed.

    2>To change the defrost time, push UP or DOWN

    key.

    3> To memorized the new Defrost time, push the

    MODE/SET key again.

    ! Defrost time(duration) can be set between

    0~30minutes. Eg) t05(4min.), t10(10min.)

    ! : Factory setting : t10(10minutes)

  • - 24 -

    2-4 How to change the defrost period

    Determine the time interval between the beginning

    of two defrost cycles.

    1> d00 will be displayed after new defrost time is

    set Or Press the SET key more than 3seconds

    until t10is displayed.

    2> Press once more and D0.0will be displayed.

    3> To change the defrost value, push UP or

    DOWN key.

    4> Push the SET key again to memorize the new

    defrost period.

    5> Defrost period can be set from 0.0 to 3.0hours,every 30mintues.

    Display 0.0 0.3 1.0 1.3 2.0 2.3 3.0

    Value 0 30min. 1hour 1hr & 30min. 2hours 2hrs & 30min 3hours

    ! Factory setting : d0.0, User has to enter the value.

    2-5 How to change the temperature calibration

    Allows to adjust possible offset of the thermostat

    probe.

    1> Press the SET key more than 6seconds until

    C0.0 is displayed.

    2> To change the value, push UP or DOWN key.

    3> Press SET key to memorize the new value.

    4> Temperature calibration range : 9.9 ! Factory setting : 0.0

    2-6 Differential

    Interval differential for set point. Compressor Cut In is set point plus Differential and Compressor Cut

    Out is when the temperature reaches at set point.

    ! Factory setting : 2 and impossible to change the value.

    3. How to start Air conditioning(optional feature)

    1> Press the POWER key to start the controller for

    refrigeration unit.

    2> Press the A/C key to start air conditioning. A/C indicator

    will be light on.

    3> Press the A/C key again to stop air conditioning.

    Although Air conditioning is off, refrigeration unit is still

    running.

    ! If Air conditioning is only necessary to operate, turn off the Power Switch. Then refrigeration unit will be stopped and only the air conditioning will be operated.

  • - 25 -

    ERROR CODE AND TROUBLE SHOOTING

    1. Error code

    < Shortage >

    SH-700ES SH-900/900ES SH-900K SH-800H

    < Open >

    SH-700ES SH-900/900ES SH-900K SH-800H

    < Compressor problematic >

    If compressor does not operated or has some problem, SH700ES and SH900/900ES models

    showing SH-900K and SH-800H displayed CEr code.

    SH-700ES SH-900/900ES SH-900K SH-800H

  • - 26 -

    2. Trouble shooting

    Symptoms Management Cause

    -Display Sh.t

    -Refrigerator can not be stopped.

    -Check the sensor wire-short.

    -Check the sensor and change it.

    -wire injured and short

    -Sensor defective

    -Display Op.n

    -Refrigerator can not be stopped.

    -Check the sensor connection.

    -Check the sensor wire cut.

    -Check the sensor and change it.

    -Sensor wire open

    -Sensor defective

    -Evaporator fan has trouble

    -Temperature can not be down

    -Check the fuse of a evaporator.

    -Check the relay output of a

    evaporator.

    -Check wire open

    -Check the motor of evaporator.

    -Motor overload

    -Wire injured or opened

    -Display CE.r

    -Compressor can not be

    operated

    -Check the fuse of compressor.

    -Check the relay output of

    compressor.

    -Check wire open

    -Check the condenser.

    -Compressor pressure over

    loaded

    -Wire opened

    -No display after power on -Check the connection. -Check the GND wire.

    -Check the fuse of the battery.

    -Wire opened

    -Relay and main Line

    disconnected.

    -Main power is trouble

  • - 27 -

    PRE-TRIP INSPECTION OF REFRIGERATION UNIT While pre-trip inspections are not intended to take the place of regular maintenance inspections, to

    following suggested functions should be performed prior of every trip involving refrigerated good.

    1. Battery

    It is necessary to check the battery periodically. The checking method is

    same as the car battery. Terminals must be clean, tight and free of

    corrosion.

    2.Temperature control system

    Temperature indication should be set carefully and correctly. Control box

    system is corresponded to all the electric system and it should be kept away

    from heavy shock and free of corrosion, cracks and moisture.

    3.Electrical

    Ensure all the electrical connections are secure. Wires and terminals should be free of corrosion, cracks

    or moisture

    4.Belt

    Belt must not be frayed or cracked and must be adjusted with correct tension.

    5.Structural

    Visually inspect the unit for leaks, loose or broken parts and any damages. Both condenser and

    evaporator coil should be free from debris.

    6.Compressor handling

    Do not strike, drop or turn the compressor upside down. Refrigerating

    compressor is connected with the car main engine pulley through v-belt, so

    tension of the belt should be checked regularly whether it is suitable or not.

    When the belt is loose, must be adjusted to the correct tension.

    Damaged belt should be replaced by new one. Also the pulley rotation of

    magnet clutch should by replaced if there is a friction because of melting the

    clutch pulley.

    7.Listening of unusual noise

    When you hear an unusual noise during the operating the unit, all over the

    refrigerating system should be checked. Listen to the sound of the

    compressor and check. If the clutch has a noise, it should be repaired and

    check the tension of the bolts that fixed to compressor on main engine and

    other fan of the blower. All of the bolts should be tied up and prompt repair is

    necessary.

  • - 28 -

    8.Refrigerant

    Refrigerant is charged normally when there is no vapor in the refrigerant flow in the sight glass and the

    checking method is as below.

    Quantity of Refrigerant Status of refrigerant flow Remarks

    O

    Refrigerant flow is laminar is a normal

    operation. The quantity is proper.

    X

    The quantity of refrigerant is not enough

    and the bubbles appear.

    The operating state is unstable.

    x

    Small bubbles is too much and the

    refrigerant is not laminar.

    9.Checking the joining parts

    When there is an oil in the pipe joint parts, check it with the soap water. If

    the bubbles founded, this is indication of a refrigerant leakage. If leaks are

    in flare fittings, tighten the firings and leaks are in the pipe, welding repair

    should be done.

    10. Pre-Cooling the system before loading

    It is very important and necessary to be pre-cooling the refrigerated truck body before loading. Products

    may get damaged without pre-cooling the unit. Please refer below table for the pre-cooling temperature.

    Loading product Product required temperature Pre-Cooling temperature

    Cooling products

    Chilled products

    Frozen products

    Ice cream

    +5 ~ +15 5 ~ +5 10 ~ 15

    25

    +10 0 7 20

    SAFETY DEVICE 1.High pressure switch

    It is located at the receiver tank in the condenser. If the pressure is higher than normal operating

    pressure, the circuit will be shut and protect the system.

    2.Low pressure switch

    It is located in condenser or evaporator. If the pressure is lower than normal operating pressure, the

    circuit will be shut down not to operate in a vacuum state and thus to protect the system.

    3.Fuse

    It is a15ampere fuse, located in the relay box and protects the unit from over ampere input.

  • - 29 -

    ADJUST BELT TENSION Adjusting method of tension the belt pulley will be followed as below two instruction. However the

    method would be different depend on the type of vehicle and engines.

    1.Method of adjusting by the compressor body for 0.5ton refrigerated vehicle

    Available model : HT-050II

    Release the tension adjust-bar fixing bolt by turning one or two rotations. Release the bracket fixing bolt by turning half rotation and strain the belt through pushing the compressor body outwards.

    When the tension is suitable, fasten the adjust-bar fixing bolt and bracket fixing bolt. Check the deflection is about 6mm when you push the belt by hand.

    2.Method of adjusting by idle pulley for the 1ton~5ton refrigerated vehicle

    Available model : HT-070II, HT-100II, HT-250II, HT-500II

    Release the nut of the idle pulley shaft by turning one or two rotations. Adjust the tension with idle adjustment bolt. (Fasten the bolt when the belt is loosened and release the bolt when belt is too much tightened)

    Fix the nut of idle pulley shaft. Check the deflection is about 6mm when you push down the belt by hand.

  • - 30 -

    SAFETY COUNTERMEASURE 1.Do not operate the unit with the outlet valve of the compressor closed.

    2.Do not touch the blower and the belt when under the units operating.(same as when open or close the service of the compressor)

    3.Check if the hose is located in a suitable place and keep the hose off the belt of other parts.

    4.Keep wear safety glasses for protection. Refrigeration liquid or the batterys acidity may be critically harmful to the eyes.

    5.Check if all the joint bolts are tightly fastened and its size is suitable.

    6.Be careful when charging the refrigerant of refrigerating system in a closed space where the air can

    not be well circulated.

    HANDLING REFRIGERATED VEHICLE 1. Checking the truck body

    Inspect the outside of the truck for damage or loose or improperly

    fitting doors or seals. Repair any damages to the walls or insulation.

    It may affect the refrigeration units performance. Inspect the inside of the cargo area and check for blocked drain

    hoses.

    2. Loading procedure

    Ensure sufficient spacing in front of the evaporator for air

    circulation when loading the products.

    Ensure goods are at the correct temperature before loading

    Caution : Do not load anything if the refrigeration unit makes

    unusual noise or doesnt operated well or temperature doesnt drops.

    If the unit causes any problem, all the loaded products should be

    removed to safety place as soon as possible and the refrigeration unit should be get serviced.

    3. Cleaning the inside cargo area

    The inside cargo area must be kept clean always for the sanitary of

    goods. The remains may cause to generate the bacteria and gas

    and that will adhere to the pin of evaporator plate by circulating air.

    The capacity if the refrigeration unit can be decreased by such oily

    components.

    Water should be removed after cleaning the cargo.

    4. Parking

    Avoid direct sunlight and recommend to be parked the vehicle in the shady and windy area. The sunlight

    will be increased the heat inside of the cargo and thus refrigeration capacity can be affected.

    5. Cleaning the condenser coil

    Keep the condenser coil clean from the dust. Refrigeration unit should be stopped when cleaning.

  • - 31 -

    MAINTENANCE INSPECTION SCHEDULE

    Inspect/Service these items After

    Installation

    Every

    month

    Every

    3 months

    Check the engine condition Check the compressor oil Check the compressor clutch Check condition of pulleys bearing Check the joining parts of each components Check the tighten of bolts and nuts Inspect compressor belt condition and proper tension Check the pipe and pipe clamp Listen for unusual noises, vibrations, etc Check the gas leakage Inspect the refrigerant through sight glass Inspect wire harness for damage wires or connections Inspect terminal of the electric cable Inspect the digital thermometer Check defrost initiation and termination Inspect refrigerators components (Sightglass, expansion valve and solenoid valve etc.)