Name of the program attended Name of the program attended Seminar on “ Understanding IEC 61850 Seminar on “ Understanding IEC 61850 Technology ”Technology ”

Followed by practical demoFollowed by practical demo

Program conducted by (Agency)Program conducted by (Agency)M/s Schweitzer Engineering Laboratories M/s Schweitzer Engineering Laboratories ( SEL )( SEL )

E Mail : E Mail : [email protected]

Web Site: www.selinc.comWeb Site: www.selinc.com

Duration of the programDuration of the program

VENUEVENUE

One Day on 17One Day on 17thth September’08 September’08

Hotel Le Meridian , New DelhiHotel Le Meridian , New Delhi

Faculty/Eminent SpeakersFaculty/Eminent Speakers Mr. Timothy P. TibbalsMr. Timothy P. Tibbals

Senior Product EngineerSenior Product Engineer

Page 3: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Program ObjectivesProgram Objectives To understandTo understand

1. Protocol & its Objective1. Protocol & its Objective

2. Overview of Network Protocol & 2. Overview of Network Protocol &

Communication w.r.t SCADA compatibility andCommunication w.r.t SCADA compatibility and

Control & Protection.Control & Protection.

3. Benefits of IEC 61850 3. Benefits of IEC 61850

4. Multi-Vender Interoperability4. Multi-Vender Interoperability

5. Ethernet Switch Networks & Security5. Ethernet Switch Networks & Security

6. Protocols & Services within IEC 618506. Protocols & Services within IEC 61850

7. Solutions provided by M/s SEL to meet the7. Solutions provided by M/s SEL to meet the

requirement of Sub-station & Distributionrequirement of Sub-station & Distribution

automationautomation

Page 4: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Key Learning

o Electric utilities were among the first entities to embrace data telemetry.

o Data telemetry was introduced for monitoring , Control and Protection.

o Development in communication, Computer, introduction of Intelligent

o Electronic Devices (IED) made information collection easier.

o Different manufacturers introduced different rules for communicating and exchanging information among their intelligent devices.

o This introduced barriers in communicating with other device manufactured by others.

Page 5: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Communication Protocol used inside sub- station

PB

SB

IEC 61850-8-1, IEEE 1379,IEEE P1525, Profibus,IEC 60870-5-101, -104,Modbus, LON, UCA.2

CT 1A/5AVT 100V

IEC 61850-9-1IEC 60044-8

IEC 60870-5-103

IEC 61850-9-2IEC 61850-8-1

ComU

SU

C/PPU

SG

SU - Station UnitPU - Protection UnitCU - Control Unit

CU

SB - Station BusPB - Process BusSG - Switchgear

C/P - Control/Protection UnitCT/VT - Instrument TransformerComU - Communication Unit

CTVT

CTVT

CTVT

IEC 61850, IEEE-SA TR 1550 (UCA.2), IEEE P1525

HMI

Fil

ter

C/P

SG

Page 6: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Page 7: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Key Learning

What is Protocol ? When Intelligent Devices communicate with each other, there needs to be a common set of rules

and instructions that each device follows.

A specific set of communication rules is called a protocol.

Protocols used in Electrical utilities are as follows:

1) Modbus -- Developed by MODICON , USA during 1976

o An application Layer Protocol ( 7th Layer of OSI )

o Extensively used in Industrial environment

o Used in process bus of sub-station bay ( Relays )

o It operates on master-slave type mode. Lave mode will not typically transmit data without a request from master.

2) DNP 3.0 ( Distributed Network Protocol ) -- Developed by Harris, USA

( Based on earlier work of IEC TC57)

DNP 3.0 is an open protocol that was developed to establish interoperability between RTUs, IEDs (Intelligent Electronic Devices) and master stations

Page 8: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

3) IEC 60870 series -- IEC 60870 Tele-control equipment and systems

It is bit serial communication standards. The standard is optimised for efficient and reliable transfer of process data and commands to and from geographically widespread systems over low-speed (up to 64 kbps) fixed and dial-up connections.

IEC 60870-5-101 Standard for Basic Tele-control Transmission ProtocolIEC 60870-5-103 Standard for informative Interface of Protection EquipmentIEC 60870-5-104 Standard for Network access for IEC 60870-5-101IEC 60870-6 Protocol for Inter-control center communication for Tele-Equipment & System

This is a protocol which provides High integrity , Efficient data transmission and protection against undetected transmission errors.

SCADA is supported by IEC 60870

4) UCA ( Utility Communication Architecture ) – IEC 61850 series – IEC 61850 ( Communication networks and systems in substations)

This standard unifies UCA with European standard. It aims to design a communication system that provides interoperability between the functions to be performed in a substation.

Page 9: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Basic Features – IEC 61850

o High Speed Data Exchange: Ethernet links operating at 100 Mbit/s exchange polled data and commands between devices at a far faster rate than traditional serial/ field bus protocols. Clients (master stations) can perform supervisory control with negligible delay. Client-Server replaces Master-Slave communications and allows simultaneous access of several clients to the same server.

o Peer-to-Peer Communication: Since all Intelligent Electronic Devices (IEDs) within the substation can communicate with each other using reliable high-speed peer-to-peer communications, extensive hardwiring in equipment bays is eliminated and the cost of implementing advanced distributed protection and control schemes is significantly reduced. Generic Substation Event (GSE) messages can be used for interlocking, disturbance recording , cross-triggering, breaker failure protection tripping, directional comparison bus protection and many other advanced applications.

o Process Bus Interface: Analog interface units (or Merging Units) located in the substation yard interface with conventional or non-conventional instrument transformers and send the sampled current and voltage values over fiber, thus significantly reducing (actually eliminating) the copper wires between the substation primary equipment and the protection, control and measuring devices.

o Standard Bay Schemes: Standard protection and control bay schemes can be engineered and customized to suit the application in software, using GSE logic , thus achieving economical solution.

o True Interoperability : The self-descriptive nature of IEC 61850-compatible IEDs means that system integration and commissioning is easier.

Page 10: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Benefits

o Cost effective solution due to reduced inter-wiring o Flexible programming allowing relays and new protection functions to be added without affecting

physical wiring o No external protocol converters are required

Various venders viz. SEL , AREVA ,SIEMENS have provided solutions that allow the migration from conventional or different legacy substation automation systems to IEC 61850 based SAS. Relays which have already been delivered with UCA2 on Ethernet can be easily upgraded to IEC 61850, while relays that support other communication protocols can be integrated using "proxy" servers.

Protocols used for protection IED by various vendors

Vender Protcol ABB SPA / LONGE MODBUS / DNP 3.0AREVA IEC 103RETROLLE IEC 103SCHNEIDER MODBUS

Page 11: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

GOOSE & GSSE

Peer - to - Peer messaging is accomplished with two compliant messages ( GOOSE & GSSE ) that differ slightly , are collectively referred to as GSE .The standardization of GSE messages ensures interoperability directly between IED’s for protection , interlocking & automation.

 GOOSE : Generic Object Oriented Sub-station EventsGSSE : Generic Sub-station Status Events 

GOOSE is for high speed control messages.Sends messages continuously.Each GOOSE message is dealt separately and at different rate depending upon what is happening , hence transmission time may differ.

 SCL Files : Sub-station Configuration Language Files , based on XML based configuration Language.SSD Files : System Specification description Files , contains details of SLD , Logical Nodes & their type .ICD Files – These files contains IED description , map IED’s with Logical devices.

Page 12: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

OSI 7 Layer Model

Functionality of different layerso Application Layer: This provides the interface and services that support user application. Ex. E-mail,

WWW, SMTP.

o Presentation Layer: This layer responsible for data encryption, data compression .Ex JPG, MPEG etc

o Sessions Layer: Responsible for setting up the communication link and manages the sessions. It could provide connection oriented and connectionless services.

o Transportation Layer: Responsible for flow control, Packet size, error free delivery with proper sequence.

o Network layer: Route determination takes place in this layer. Translation of IP address to physical address ( NIC) also takes place here.

o Data link layer : Responsible for data movement across the actual physical link.

o Physical Layer: It defines the physical aspect of how the cabling is hooked.

Page 13: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

Basic Abbreviations Used

IP – Internet ProtocolTCP – Transmission Control ProtocolUDP – Users Datagram protocolDNP – Distribution Network ProtocolLAN – Local Area NetworkWAN – Wide Area NetworkHMI – Human Machine InterfaceGUI – Graphical Users InterfaceOSI - Open System Interconnection , a reference model for computer to

computer data communication. UCA – Utility communication ArchitectureMMS – Manufacturing Message SpecificationsACSI – Abstract Communication Service InterfaceSCSM – Specific Communication Service MappingGOOSE - Generic Object Oriented Sub-station EventsGSSE - Generic Sub-station Status EventsBCU – Bay Control UnitBMU – Bay Monitoring UnitBPU – Bay Protection UnitSCU – Station Control Unit

Page 14: NDPL Shiksha Document Contribruted by R.N.KUMAR Subhadip Ray Choudhury.

4

ApplicationApplication of Learning in Participant’s Area of Responsibility

Today is the demand of utility users & manufacturers to merge the communication capabilities of all IED’s in a sub-station or even across the entire power network through Wide Area Network (WAN). Most of the utilities have already installed IED’s which provides centralized sub-station control & monitoring . A big amount of information collected in these IED’s remains unused because of traditional integration technique designed exclusively to support SCADA. Protocol IEC 61850 has been created as an international standard for communication & integration for the systems built up from multi vender IED’s networked together to perform Protection, Monitoring , Automation , Metering & Control.

This standard has been developed for communication & integration of Power system Control equipment and Systems viz. Supervisory Control and Data acquisition ( SCADA ), Energy Management System (EMS), Distribution Management System ( DMS ) , Distribution Automation ( DA ), Tele-protection & associated communication for a sub station.

It has built-in capability for high speed control and data sharing over the communication network, eliminating a lot of dedicated hard wiring & communication channels with security which is essential in substations today. The protection relays integrate with the PACiS substation control systems over the IEC 61850 8-1 Substation Bus and at the same time can interface with vendors Merging Units over the IEC 61850 9-2 Process Bus.

Possible application areas in NDPL other than Participant’s Area

All the Fifty four 66 / 33 / 11 kV NDPL Grid sub-stations , power distribution system , CENNET w.r.t Protection , communication , SCADA , DMS , DA , EMS through WAN & LAN , Fibre optics by integration of this latest technology protocol IEC 61850 with existing IED’s with different protocols as supplied by various venders.