Top Banner
0CVT0-01A R410A 50/60Hz
123
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Multi V Water PDB(08.04.10_)final .pdf

0CVT0-01A

R410A 50/60Hz

Page 2: Multi V Water PDB(08.04.10_)final .pdf

LG Airconditioners Product Data

Introduction

• General Information

• Outdoor Units

• Installation of Outdoor Units

(R410A)

Page 3: Multi V Water PDB(08.04.10_)final .pdf

Introduction

Introduction44

1. Preface

R410A Model

is the most favored choice when there is a need for precise air conditioning of relatively big pro-jects extending from Multi-Room structure to big commercial places. We have a big line up, that offers widerflexibility of model selection.

Equipped with inverter technology and long piping installation, the product matches well if one talk about opti-mum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existingcapacity at any time.

With the growing concern about environment preservation, comes with R410A refrigerant which isenvironment friendly and thus our system is a high technology and environment friendly product.

Unique refrigerant flow and electronic circuit control gives this system an unique capability to work inextreme/abnormal working conditions making our customer feel great about their decision of selectingLG as their first choice.

This publication provides a detailed and in depth information about the design and installation of .

We hope that with this information you would become an expert of your system.

Air-Conditioning Division

Page 4: Multi V Water PDB(08.04.10_)final .pdf

Introduction 55

2. Step by Step System Selection Process

(1) Calculate or obtain the maximum heat load for the area(s) to be air conditioned

Decide the indoor unit specifications

Decide the outdoor unit specifications

Capacity coefficient factor

Decide the air velocity and temperature distributions

(2)

(3)

(4)Selection of the control system

Control wiring method

Description of devices

Selection of refrigerant pipe joints and headers

(5) Electrical wiring

Electric characteristics

Field wiring

• Air conditioners should not be installed in areas where corrosive gases such as acid gasor alkaline gas is produced.

Page 5: Multi V Water PDB(08.04.10_)final .pdf

General information

General Information

1. Model Names

2. External Appearance

3. Combination of Outdoor Units

4. Nomenclature

5. Outdoor Units information

Page 6: Multi V Water PDB(08.04.10_)final .pdf

1. Model Names

General information 11

Power Supply 10HP 20HP 30HP 40HP

3Ø, 380~415V, 50HzARWN100LA2 ARWN200LA2 ARWN300LA2 ARWN400LA2

3Ø, 380V, 60Hz

Page 7: Multi V Water PDB(08.04.10_)final .pdf

General information22

2. External Appearance

10 HPARWN100LA2

20 HPARWN200LA2

30 HPARWN300LA2

40 HPARWN400LA2

Page 8: Multi V Water PDB(08.04.10_)final .pdf

3. Combination of Outdoor Units

General information 33

SystemCapacity

(HP)

10 1 1

20 1 1

30 2 1 1

40 2 2

Number of UnitsModule(HP)

10 20

Page 9: Multi V Water PDB(08.04.10_)final .pdf

General information44

4. Nomenclature

Serial Number

A: Basic Function

Electrical Ratings

L: 3Ø, 380 ~ 415V, 50Hz / 3Ø, 380V, 60Hz

Total Cooling Capacity in Horse Power(HP) unit EX) 10HP'100'

Indicates that this is System Outdoor Unit using the R410A

Combination of Inverter Type and Cooling Only or Heat PumpN: Inverter and H/P

ARW N L100 A 2

Page 10: Multi V Water PDB(08.04.10_)final .pdf

General information 55

5. Outdoor Units Information

CAUTION: A ratio of the connectable Indoor Units with the Outdoor: Within 50 ~ 130% A ratio of the running Indoor Units with the Outdoor: Within 10 ~ 100% A combinated operation over 100% causes to reduce the total capacity.

Power Supply: Outdoor Unit (3Ø, 380 ~ 415V, 50Hz / 3Ø, 380V, 60Hz)

System Capacity HPModel NameProduct Refrigerant Charge kgCF(Correction Factor) kgMaximum Connectable No. of Indoor Units

Net Weightkglb

Dimensions(WxHxD)mminch

Refrigerant Liquid mm(inch)Connecting Pipes Gas mm(inch)

WaterInlet

Connecting PipesOutletDrain Outlet

10 20ARWN100LA2 ARWN200LA2

7.3 8.8- -

16 32(170) x 1 (238)x1

(374.8) x 1 (524.7)x1(772 x 1,120 x 547) x 1 (772 x 1,120 x 547) x 1(30.4 x 44.1 x 21.5) x 1 (30.4 x 44.1 x 21.5) x 1

9.52(3/8) 12.7(1/2)22.2(7/8) 28.58(1 1/8)PT 32A PT 40APT 32A PT 40APT 20A PT 20A

System Capacity HPModel NameProduct Refrigerant Charge kgCF(Correction Factor) kgMaximum Connectable No. of Indoor Units

Net Weightkglb

Dimensions(WxHxD)mminch

Refrigerant Liquid mm(inch)Connecting Pipes Gas mm(inch)

WaterInlet

Connecting PipesOutletDrain Outlet

30 40ARWN300LA2 ARWN400LA2

7.3+8.8 8.8+8.8- -

49 64(170) x 1, (238) x 1 (238) x 1, (238) x1

(374.8) x 1, (524.7) x 1 (524.7) x 1, (524.7) x1(772 x 1,120 x 547) x 2 (772 x 1,120 x 547) x 2(30.4 x 44.1 x 21.5) x 2 (30.4 x 44.1 x 21.5) x 2

15.88(5/8) 19.05(3/4)34.9(1 3/8) 41.3(1 5/8)

PT32A, PT40A (PT40A)x2PT32A, PT40A (PT40A)x2

PT 20A PT 20A

Page 11: Multi V Water PDB(08.04.10_)final .pdf

General information66

Page 12: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units

1. Specifications

2. Dimensions

3. Piping Diagrams

4. Wiring Diagrams

5. Field Wiring

6. Electric Characteristics

7. Capacity Tables

8. Operation Limits

9. Sound Levels

10. Accessories

Outdoor Units

Page 13: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units11

1. Specifications

Notes:1. Capacities are based on the following conditions

Cooling : Indoor temp. 27°C [80.6°F]DB/19°C[66.2°F]WBWater inlet temp. 30°C[86°F]

Heating : Indoor temp. 20°C[68°F]DBWater Inlet temp. 20°C[68°F]

* Interconnecting Piping Length 7.5m* Level Difference of Zero

2. Capacities are net capacities3. Due to our policy of innovation some specifications may be changed without notification4. Recommend operation temp: Outdoor 0~40 °C

System Capacity HPModel Name

kWCooling kcal/h

CapacityBtu/hkW

Heating kcal/hBtu/h

Input Cooling kWHeating kW

Casing ColorTypeCombinationPiston Displacement cm3/rev

Compressor Number of revolution rev/minMotor Output kWStarting MethodOil TypeOil Charge Amount ccType

Heat Exchanger Maximum Pressure Loss kgf/cm2

Rated Water Flow L/min

RefrigerantLiquid mm(inch)

Connecting PipesGas mm(inch)High/Low Pressure Common mm(inch)

WaterInlet

Connecting PipesOutletDrain Outlet

Dimensions(WxHxD)mminch

Net Weightkglb

Transmission Cable(CVV-SB) mm2

NameRefrigerant Charge Amount kg

Control Device

Power Supply Ø/V/Hz

10 20ARWN100LA2 ARWN200LA2

29.0 5824,940 48,20098,950 197,90432.6 65

28,030 54,100111,240 211,798

5.8 11.66.0 12.0

Warm Gray Warm GrayHermetic Motor Scroll Hermetic Motor Scroll

(Inverter)x1 (Inverter)x1, (Constant)x152.0 52.0, 81.0

3,600 at 60Hz 3,600 at 60Hz, 2,891(5.4)x1 (5.4)x1 , (6.7)x1

Direct On Line Direct On LineFVC68D(PVE) FVC68D(PVE)(2,325±10)x1 (2,325±10)x1, (2,325±70)x1

Stainless Steel Plate Stainless Steel Plate43 4396 192

9.52(3/8) 12.7(1/2)22.2(7/8) 28.85(1 1/8)

- -PT 32A PT 40APT 32A PT 40APT 20A PT 20A

(772x1,120x547)x1 (772x1,120x547)x1(30.4x44.1x21.5)x1 (30.4x44.1x21.5)x1

(170)x1 (238)x1(374.8)x1 (524.7)x1(1.25)x2 (1.25)x2R410A R410A

7.3 8.8EEV(Electronic Expansion Valve) EEV(Electronic Expansion Valve)

3/380~415/50 3/380~415/503/380/60 3/380/60

Heat Pump(50Hz/60Hz)

Page 14: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 22

Notes:1. Capacities are based on the following conditions

Cooling : Indoor temp. 27°C [80.6°F]DB/19°C[66.2°F]WBWater inlet temp. 30°C[86°F]

Heating : Indoor temp. 20°C[68°F]DBWater Inlet temp. 20°C[68°F]

* Interconnecting Piping Length 7.5m* Level Difference of Zero

2. Capacities are net capacities3. Due to our policy of innovation some specifications may be changed without notification4. Recommend operation temp: Outdoor 0~40 °C

System Capacity HPModel Name

kWCooling kcal/h

CapacityBtu/hkW

Heating kcal/hBtu/h

Input Cooling kWHeating kW

Casing ColorTypeCombinationPiston Displacement cm3/rev

Compressor Number of revolution rev/minMotor Output kWStarting MethodOil TypeOil Charge Amount ccType

Heat Exchanger Maximum Pressure Loss kgf/cm2

Rated Water Flow L/min

RefrigerantLiquid mm(inch)

Connecting PipesGas mm(inch)High/Low Pressure Common mm(inch)

WaterInlet

Connecting PipesOutletDrain Outlet

Dimensions(WxHxD)mminch

Net Weightkglb

Transmission Cable(CVV-SB) mm2

NameRefrigerant Charge Amount kg

Control Device

Power Supply Ø/V/Hz

30 40ARWN300LA2 ARWN400LA2

87.0 11674,800 99,700296,860 395,808

97.9 13084,180 118,000334,050 443,578

17.4 23.2 18.1 24.0

Warm Gray Warm GrayHermetic Motor Scroll Hermetic Motor Scroll

(Inverter)x2, (Constant)x1 (Inverter)x2, (Constant)x252.0, 81.0 52.0, 81.0

3,600 at 60Hz, 2,891 3,600 at 60Hz, 2,891(5.4)x2 , (6.7)x1 (5.4)x2 , (6.7)x2Direct On Line Direct On LineFVC68D(PVE) FVC68D(PVE)

(2,325±10)x2, (2,325±70)x1 (2,325±10)x2, (2,325±70)x2Stainless Steel Plate Stainless Steel Plate

43 4396+192 192+192

15.88(5/8) 19.05(3/4)34.9(1 3/8) 41.3(1 5/8)19.05(3/4) 19.05(3/4)

PT32A+PT40A PT40A+PT40APT32A+PT40A PT40A+PT40A

PT 20A PT 20A(772x1,120x547)x2 (772x1,120x547)x2(30.4x44.1x21.5)x2 (30.4x44.1x21.5)x2

(170)x1, (238)x1 (238)x2(374.8)x1, (524.7)x1 (524.7)x2

(1.25)x2 (1.25)x2R410A R410A

7.3 8.8EEV(Electronic Expansion Valve) EEV(Electronic Expansion Valve)

3/380~415/50 3/380~415/503/380/60 3/380/60

Heat Pump(50Hz/60Hz)

Page 15: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units33

2. Dimensions

ARWN100LA2ARWN200LA2

Page 16: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 44

3. Piping Diagrams

ARWN100LA2

Hot Gas Bypass

LiquidInjection

Receiver

HIgh

Low

WaterOutletPipe

WaterInletPipe

LiquidPipe

GasPipe

High/LowPressureCommon

Pipe(Ø19.05mm)

(For Only 30 HP)

PlateHeat

Exchanger

OutdoorAir

s

s

Accum

INVComp

O/S

SC HEX

Oil return

s

S

Pressure sensor

Pressure switch

Check valve

EEV

Thermistor

Solenoid valve

Service valve

Strainer

INV : InverterComp. : CompressorEEV : Electronic Expansion ValveO/S : Oil SeparatorAccum. : AccumulatorSC HEX: Subcooling Circuit

Heat Exchanger

Page 17: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units55

ARWN200LA2

WaterInletPipe

Hot Gas Bypass

LiquidInjection

Receiver

HIgh

Low

WaterOutletPipe

LiquidPipe

GasPipe

High/LowPressureCommon

Pipe(Ø19.05mm)

(For Only 30 / 40 HP)

PlateHeat

Exchanger

OutdoorAir

s s

s

Accum

INVComp

O/S

SC HEX

Oil return

s

NormalComp

O/S

S

Pressure sensor

Pressure switch

Check valve

EEV

Thermistor

Solenoid valve

Service valve

Strainer

INV : InverterComp. : CompressorEEV : Electronic Expansion ValveO/S : Oil SeparatorAccum. : AccumulatorSC HEX: Subcooling Circuit

Heat Exchanger

Page 18: Multi V Water PDB(08.04.10_)final .pdf

4. Wiring Diagrams

Outdoor Units 66

ARWN100LA2

Page 19: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units77

ARWN200LA2

Page 20: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 88

5. Field Wiring

3 phase 4 wires power supply

50Hz 380~415V

Power supply1 phase 50Hz

220V

Power supply switch(switch fuse)

3 phase 4 wires power line(R, S, T, N)

Transmission line (3 line): wired remote control

Single phase of power supply line(L, N)

Transmission line (2 shield line): between indoor unit and outdoor unit

3 4 3 4 3 4

The GND terminal is a '–' terminal for the central controller, not ground line

Outdoor unitSODU

B A B A

IDU INTERNET DRY1 DRY2 GND 12V

Example Connection of Transmission Cable

WARNING• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,

transmission disorder by noise effect and motor current leakage (without connection to pipe).• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the

power supply.

Page 21: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units99

6. Electric Characteristics

1. Use a separate power supply for the Outdoor Unit and Indoor Unit.2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the

line voltage drops. Make sure the power-supply voltage does not drop more than 10%.3. Specific wiring requirements should adhere to the wiring regulations of the region.4. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.5. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.

WARNING• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regu-

lations and guidance of each electric power company.• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If con-

nections are not fixed firmly, it may cause heating or fire.• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include

some amount of direct current.

CAUTION• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause

an electric shock.• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large

capacity may cause a malfunction of unit or fire.

Wiring of Main Power Supply and Equipment Capacity

Model Hz Volts Voltage-range MCA MOP Compressor

MSC RLAMin.:342Max.:456Min.:342Max.:456Min.:342Max.:456Min.:342Max.:456

ARWN100LA2 50 380~415 15.1 26.4 - 20.2

ARWN200LA2 50 380~415 30.1 53.4 -/61 20.2/11.6

ARWN300LA2 50 380~415 43.4 77.3 -/-/61 20.2/20.2/11.6

ARWN400LA2 50 380~415 59.3 105.9 -/61/-/61 20.2/11.6/20.2/11.6

Model Hz Volts Voltage-range MCA MOP Compressor

MSC RLAMin.:342Max.:418Min.:342Max.:418Min.:342Max.:418Min.:342Max.:418

ARWN100LA2 60 380 15.1 26.4 - 20.2

ARWN200LA2 60 380 30.1 53.4 -/61 20.2/11.6

ARWN300LA2 60 380 43.4 77.3 -/-/61 20.2/20.2/11.6

ARWN400LA2 60 380 59.3 105.9 -/61/-/61 20.2/11.6/20.2/11.6

50Hz

60Hz

Page 22: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 1010

Notes:1. Voltage range

Voltage supplied to the unit terminals should be within the min-imum and maximum range

2. Maximum allowable voltage unbalance between phase is 2 %

3. MCA / MOPMCA = (1.25 x Load1) + Load2 MOP = (2.25 x Load1) + Load2 - Load1 : Rated running current of largest motor

(Compressor or other motor) - Load2 : any other load rated 1.0A or more

4. Select wire spec. based on the MCA5. Select proper circuit breaker as given below

MCA < Selected circuit breaker ≤ MOP6. Recommended circuit breaker is ELCB (Earth Leakage Circuit

Breaker)7. MSC & RLA are measured as the compressor only test condi-

tion. 8. MSC values

-/61 : MSC of (INV. Comp) / (Const. Comp.1)

9. RLA is measured during each individual compressor test con-dition.20.2/11.6 : RLA of (INV. Comp) / (Const. Comp.1)

(Example)Selection of proper circuit breaker

➀ 10HP- Rated running current : 11.3 A ➁ MCA = (1.25 x Load1) + Load2

= (1.25 x 11.3) + 1 = 15.1 A➂ MOP = (2.25 x Load1) + Load2

= (2.25 x 11.3) + 1 = 26.4 A Finally select circuit breaker 20A

MCA : Minimum Circuit Amperes (A)

MOP : Maximum rating Over current Protective device

MSC : Maximum Starting Current

RLA : Rated Load Amperes (A)

Page 23: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units1111

7. Capacity Tables

7.1 Cooling capacity

ARWN100LA2

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

50 26.5 2.71 22.8 28.7 3.18 23.5 31.3 3.70 24.3 34.0 4.17 25.1 35.0 4.27 25.4 36.4 4.38 25.896 26.5 2.49 19.1 28.7 2.97 19.4 31.3 3.46 19.8 34.0 3.90 20.2 35.0 4.00 20.4 36.4 4.10 20.6

120 26.5 2.42 18.3 28.7 2.91 18.5 31.3 3.39 18.9 34.0 3.82 19.2 35.0 3.92 19.3 36.4 4.02 19.550 26.1 3.29 27.9 28.3 3.85 28.5 30.8 4.49 29.3 33.5 5.05 30.1 34.5 5.17 30.4 35.8 5.30 30.896 26.1 3.02 24.1 28.3 3.60 24.4 30.8 4.20 24.8 33.5 4.73 25.3 34.5 4.84 25.4 35.8 4.97 25.6

120 26.1 2.94 23.3 28.3 3.53 23.6 30.8 4.11 23.9 33.5 4.63 24.2 34.5 4.75 24.3 35.8 4.87 24.550 26.1 4.05 33.0 28.3 4.75 33.7 30.8 5.54 29.3 33.5 6.23 35.3 34.5 6.38 35.6 35.8 6.54 36.096 26.1 3.73 29.2 28.3 4.44 29.5 30.8 5.18 29.9 33.5 5.83 30.4 34.5 5.97 30.5 35.8 6.13 30.7

120 26.1 3.62 28.3 28.3 4.35 28.6 30.8 5.07 28.9 33.5 5.71 29.3 34.5 5.86 29.4 35.8 6.01 29.650 26.1 4.86 38.3 28.3 5.70 38.9 30.8 6.64 39.7 33.5 7.48 40.6 34.5 7.66 40.9 35.8 7.85 41.396 26.1 4.47 34.3 28.3 5.33 34.7 30.8 6.21 35.1 33.5 6.99 35.5 34.5 7.17 35.7 35.8 7.36 35.9

120 26.1 4.35 33.4 28.3 5.22 33.7 30.8 6.08 34.1 33.5 6.86 34.4 34.5 7.03 34.5 35.8 7.21 34.750 23.5 4.92 42.6 25.5 5.77 43.3 27.7 6.72 44.0 30.2 7.56 44.8 31.1 7.75 45.1 32.3 7.94 45.596 23.5 4.52 39.0 25.5 5.39 39.3 27.7 6.28 39.7 30.2 7.07 40.1 31.1 7.25 40.3 32.3 7.44 40.5

120 23.5 4.40 38.2 25.5 5.28 38.4 27.7 6.15 38.8 30.2 6.93 39.1 31.1 7.11 39.2 32.3 7.30 39.450 20.9 5.19 47.0 22.6 6.08 47.6 24.7 7.09 48.3 26.8 7.98 49.0 27.6 8.17 49.3 28.7 8.37 49.696 20.9 4.77 43.7 22.6 5.69 44.0 24.7 6.63 44.3 26.8 7.46 44.7 27.6 7.65 44.8 28.7 7.85 45.0

120 20.9 4.64 42.9 22.6 5.57 43.2 24.7 6.49 43.5 26.8 7.31 43.8 27.6 7.50 43.9 28.7 7.70 44.050 25.2 2.59 22.5 27.3 3.04 23.1 29.7 3.54 23.8 32.3 3.99 24.6 33.3 4.08 24.9 34.6 4.18 25.296 25.2 2.38 18.9 27.3 2.84 19.2 29.7 3.31 19.6 32.3 3.73 20.0 33.3 3.82 20.1 34.6 3.92 20.3

120 25.2 2.32 18.1 27.3 2.78 18.4 29.7 3.24 18.7 32.3 3.66 19.0 33.3 3.75 19.1 34.6 3.85 19.350 25.0 3.16 27.5 27.0 3.71 28.2 29.4 4.32 28.9 32.0 4.86 29.7 33.0 4.98 29.9 34.2 5.10 30.396 25.0 2.91 23.9 27.0 3.46 24.2 29.4 4.04 24.6 32.0 4.54 25.0 33.0 4.66 25.2 34.2 4.78 25.4

120 25.0 2.83 23.1 27.0 3.39 23.4 29.4 3.95 23.7 32.0 4.46 24.0 33.0 4.57 24.1 34.2 4.69 24.350 25.0 3.88 32.7 27.0 4.55 33.3 29.4 5.30 28.9 32.0 5.97 34.8 33.0 6.12 35.1 34.2 6.27 35.596 25.0 3.57 29.0 27.0 4.26 29.3 29.4 4.96 29.7 32.0 5.59 30.1 33.0 5.72 30.3 34.2 5.87 30.5

120 25.0 3.47 28.2 27.0 4.17 28.5 29.4 4.86 28.8 32.0 5.48 29.1 33.0 5.62 29.2 34.2 5.76 29.450 25.0 4.69 37.9 27.0 5.51 38.5 29.4 6.41 39.3 32.0 7.22 40.1 33.0 7.40 40.4 34.2 7.58 40.896 25.0 4.32 34.1 27.0 5.15 34.4 29.4 6.00 34.8 32.0 6.75 35.3 33.0 6.92 35.4 34.2 7.10 35.6

120 25.0 4.20 33.3 27.0 5.04 33.6 29.4 5.87 33.9 32.0 6.62 34.2 33.0 6.79 34.3 34.2 6.96 34.550 22.8 4.81 42.4 24.7 5.64 43.0 26.9 6.57 43.7 29.3 7.40 44.5 30.2 7.58 44.8 31.3 7.77 45.296 22.8 4.43 38.9 24.7 5.28 39.2 26.9 6.15 39.6 29.3 6.92 40.0 30.2 7.09 40.1 31.3 7.28 40.3

120 22.8 4.30 38.1 24.7 5.16 38.3 26.9 6.02 38.6 29.3 6.79 39.0 30.2 6.96 39.1 31.3 7.14 39.250 20.7 5.18 47.0 22.4 6.07 47.5 24.4 7.08 48.2 26.6 7.97 48.9 27.4 8.16 49.2 28.4 8.36 49.696 20.7 4.76 43.6 22.4 5.68 43.9 24.4 6.62 44.3 26.6 7.45 44.7 27.4 7.63 44.8 28.4 7.83 45.0

120 20.7 4.63 42.9 22.4 5.56 43.1 24.4 6.48 43.4 26.6 7.30 43.7 27.4 7.49 43.8 28.4 7.68 44.0

37.4 4.45 26.137.4 4.18 20.837.4 4.09 19.636.9 5.40 31.136.9 5.07 25.836.9 4.96 24.636.9 6.66 36.336.9 6.26 30.936.9 6.11 29.736.9 7.99 41.636.9 7.51 36.136.9 7.34 34.933.2 8.08 45.833.2 7.59 40.633.2 7.42 39.529.5 8.52 49.929.5 8.01 45.229.5 7.83 44.135.6 4.26 25.535.6 4.00 20.535.6 3.90 19.435.2 5.19 30.635.2 4.87 25.535.2 4.76 24.435.2 6.38 35.835.2 5.99 30.635.2 5.85 29.535.2 7.71 41.135.2 7.24 35.835.2 7.07 34.632.2 7.91 45.532.2 7.42 40.432.2 7.24 39.429.2 8.51 49.829.2 7.98 45.129.2 7.79 44.1

120

130

Page 24: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 1212

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp. (°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

50 23.9 2.47 22.1 25.9 2.90 22.7 28.2 3.38 23.3 30.7 3.81 24.1 31.6 3.90 24.3 32.8 3.99 24.796 23.9 2.28 18.7 25.9 2.71 19.0 28.2 3.16 19.3 30.7 3.56 19.7 31.6 3.65 19.9 32.8 3.74 20.1120 23.9 2.21 17.9 25.9 2.66 18.2 28.2 3.10 18.5 30.7 3.49 18.8 31.6 3.58 18.9 32.8 3.67 19.050 23.8 3.03 27.2 25.8 3.56 27.8 28.1 4.14 28.5 30.5 4.67 29.2 31.4 4.78 29.5 32.6 4.89 29.896 23.8 2.79 23.7 25.8 3.33 24.0 28.1 3.87 24.4 30.5 4.36 24.8 31.4 4.47 24.9 32.6 4.58 25.1120 23.8 2.71 23.0 25.8 3.25 23.2 28.1 3.79 23.5 30.5 4.28 23.8 31.4 4.39 23.9 32.6 4.50 24.150 23.8 3.71 32.3 25.8 4.36 32.9 28.1 5.07 28.5 30.5 5.71 34.4 31.4 5.85 34.7 32.6 5.99 35.096 23.8 3.42 28.8 25.8 4.07 29.1 28.1 4.74 29.5 30.5 5.34 29.9 31.4 5.47 30.0 32.6 5.61 30.2120 23.8 3.32 28.0 25.8 3.99 28.3 28.1 4.65 28.6 30.5 5.24 28.9 31.4 5.37 29.0 32.6 5.51 29.250 23.8 4.53 37.5 25.8 5.31 38.1 28.1 6.19 38.9 30.5 6.97 39.6 31.4 7.13 39.9 32.6 7.31 40.396 23.8 4.16 33.9 25.8 4.97 34.2 28.1 5.78 34.6 30.5 6.51 35.0 31.4 6.67 35.2 32.6 6.84 35.4120 23.8 4.05 33.1 25.8 4.86 33.4 28.1 5.66 33.7 30.5 6.39 34.0 31.4 6.55 34.1 32.6 6.71 34.350 22.2 4.71 42.2 24.0 5.52 42.8 26.1 6.43 43.5 28.4 7.24 44.2 29.3 7.41 44.5 30.4 7.60 44.996 22.2 4.33 38.7 24.0 5.16 39.1 26.1 6.01 39.4 28.4 6.77 39.8 29.3 6.94 39.9 30.4 7.12 40.1120 22.2 4.21 38.0 24.0 5.05 38.2 26.1 5.89 38.5 28.4 6.64 38.8 29.3 6.81 39.0 30.4 6.98 39.150 20.5 5.17 46.9 22.2 6.07 47.5 24.2 7.06 48.1 26.3 7.96 48.9 27.1 8.15 49.1 28.2 8.35 49.596 20.5 4.76 43.6 22.2 5.67 43.9 24.2 6.61 44.2 26.3 7.44 44.6 27.1 7.62 44.7 28.2 7.82 44.9120 20.5 4.62 42.9 22.2 5.55 43.1 24.2 6.47 43.4 26.3 7.29 43.7 27.1 7.48 43.8 28.2 7.67 43.950 22.6 2.36 21.7 24.5 2.76 22.2 26.7 3.22 22.9 29.0 3.63 23.6 29.9 3.71 23.8 31.0 3.80 24.296 22.6 2.17 18.5 24.5 2.58 18.8 26.7 3.01 19.1 29.0 3.39 19.5 29.9 3.47 19.6 31.0 3.56 19.8120 22.6 2.11 17.8 24.5 2.53 18.0 26.7 2.95 18.3 29.0 3.32 18.6 29.9 3.41 18.7 31.0 3.49 18.850 22.6 2.91 26.8 24.5 3.41 27.4 26.7 3.97 28.0 29.0 4.47 28.7 29.9 4.58 29.0 31.0 4.69 29.496 22.6 2.67 23.6 24.5 3.19 23.8 26.7 3.71 24.2 29.0 4.18 24.6 29.9 4.28 24.7 31.0 4.39 24.9120 22.6 2.60 22.8 24.5 3.12 23.1 26.7 3.64 23.4 29.0 4.10 23.6 29.9 4.20 23.8 31.0 4.31 23.950 22.6 3.54 32.0 24.5 4.16 32.5 26.7 4.84 28.0 29.0 5.45 33.9 29.9 5.58 34.2 31.0 5.72 34.596 22.6 3.26 28.6 24.5 3.89 28.9 26.7 4.53 29.3 29.0 5.10 29.6 29.9 5.22 29.8 31.0 5.35 30.0120 22.6 3.17 27.9 24.5 3.80 28.1 26.7 4.44 28.4 29.0 5.00 28.7 29.9 5.12 28.8 31.0 5.25 29.050 22.6 4.36 37.1 24.5 5.11 37.7 26.7 5.96 38.4 29.0 6.71 39.2 29.9 6.87 39.4 31.0 7.04 39.896 22.6 4.01 33.7 24.5 4.78 34.0 26.7 5.57 34.4 29.0 6.27 34.8 29.9 6.42 34.9 31.0 6.59 35.1120 22.6 3.90 33.0 24.5 4.68 33.2 26.7 5.46 33.5 29.0 6.15 33.8 29.9 6.30 33.9 31.0 6.46 34.150 21.5 4.60 42.0 23.3 5.40 42.6 25.3 6.29 43.2 27.6 7.08 43.9 28.4 7.25 44.2 29.5 7.43 44.696 21.5 4.23 38.6 23.3 5.05 38.9 25.3 5.88 39.3 27.6 6.62 39.7 28.4 6.78 39.8 29.5 6.95 40.0120 21.5 4.12 37.9 23.3 4.94 38.1 25.3 5.76 38.4 27.6 6.49 38.7 28.4 6.65 38.8 29.5 6.82 39.050 20.4 5.16 46.8 22.0 6.06 47.4 24.0 7.05 48.1 26.1 7.94 48.8 26.9 8.13 49.0 27.9 8.33 49.496 20.4 4.75 43.6 22.0 5.66 43.9 24.0 6.60 44.2 26.1 7.43 44.6 26.9 7.60 44.7 27.9 7.80 44.9120 20.4 4.62 42.9 22.0 5.54 43.1 24.0 6.46 43.4 26.1 7.28 43.7 26.9 7.46 43.8 27.9 7.65 43.9

33.7 4.07 25.033.7 3.81 20.233.7 3.72 19.233.6 4.98 30.133.6 4.67 25.333.6 4.55 24.233.6 6.10 35.333.6 5.72 30.433.6 5.58 29.333.6 7.44 40.633.6 6.97 35.533.6 6.80 34.431.3 7.73 45.131.3 7.25 40.331.3 7.07 39.229.0 8.50 49.729.0 7.96 45.129.0 7.76 44.131.9 3.87 24.431.9 3.62 19.931.9 3.53 18.931.9 4.78 29.631.9 4.47 25.031.9 4.35 24.031.9 5.82 34.831.9 5.45 30.131.9 5.31 29.131.9 7.16 40.131.9 6.70 35.231.9 6.53 34.230.3 7.56 44.830.3 7.08 40.130.3 6.89 39.128.7 8.48 49.628.7 7.94 45.028.7 7.73 44.0

110

100

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 25: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units1313

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Cooling Capacity

50 20.4 2.03 21.0 22.0 2.38 21.5 24.0 2.77 22.1 26.1 3.12 22.7 26.9 3.20 23.0 27.9 3.27 23.396 20.4 1.87 18.1 22.0 2.22 18.4 24.0 2.59 18.7 26.1 2.92 19.0 26.9 2.99 19.1 27.9 3.06 19.3

120 20.4 1.81 17.5 22.0 2.18 17.7 24.0 2.54 18.0 26.1 2.86 18.2 26.9 2.93 18.3 27.9 3.01 18.450 20.4 2.50 26.1 22.0 2.93 26.6 24.0 3.42 27.2 26.1 3.85 27.9 26.9 3.94 28.1 27.9 4.04 28.496 20.4 2.30 23.2 22.0 2.74 23.5 24.0 3.20 23.8 26.1 3.60 24.1 26.9 3.69 24.2 27.9 3.78 24.4

120 20.4 2.24 22.6 22.0 2.69 22.8 24.0 3.13 23.0 26.1 3.53 23.3 26.9 3.62 23.4 27.9 3.71 23.550 20.4 3.05 31.3 22.0 3.58 31.8 24.0 4.17 29.8 26.1 4.69 33.0 26.9 4.81 33.3 27.9 4.92 33.696 20.4 2.81 28.3 22.0 3.35 28.5 24.0 3.90 28.8 26.1 4.39 29.2 26.9 4.49 29.3 27.9 4.61 29.5

120 20.4 2.73 27.6 22.0 3.27 27.8 24.0 3.82 28.1 26.1 4.30 28.3 26.9 4.41 28.4 27.9 4.52 28.650 20.4 3.75 36.4 22.0 4.40 37.0 24.0 5.13 37.6 26.1 5.77 38.2 26.9 5.91 38.5 27.9 6.06 38.896 20.4 3.45 33.4 22.0 4.12 33.6 24.0 4.79 34.0 26.1 5.40 34.3 26.9 5.53 34.4 27.9 5.67 34.6

120 20.4 3.36 32.7 22.0 4.03 32.9 24.0 4.70 33.2 26.1 5.29 33.4 26.9 5.42 33.5 27.9 5.56 33.750 19.8 4.05 41.4 21.4 4.75 42.0 23.3 5.53 42.6 25.4 6.23 43.2 26.1 6.38 43.5 27.2 6.53 43.896 19.8 3.72 38.3 21.4 4.44 38.6 23.3 5.17 38.9 25.4 5.82 39.3 26.1 5.96 39.4 27.2 6.12 39.6

120 19.8 3.62 37.7 21.4 4.35 37.9 23.3 5.07 38.2 25.4 5.71 38.4 26.1 5.85 38.5 27.2 6.00 38.750 19.2 4.65 46.5 20.8 5.46 47.0 22.7 6.36 47.6 24.7 7.16 48.3 25.4 7.33 48.5 26.4 7.51 48.996 19.2 4.28 43.4 20.8 5.10 43.6 22.7 5.94 44.0 24.7 6.69 44.3 25.4 6.85 44.4 26.4 7.03 44.6

120 19.2 4.16 42.7 20.8 4.99 42.9 22.7 5.82 43.2 24.7 6.56 43.5 25.4 6.72 43.6 26.4 6.90 43.750 18.1 1.70 20.4 19.6 1.99 20.8 21.3 2.32 21.3 23.2 2.62 21.9 23.9 2.68 22.1 24.8 2.74 22.396 18.1 1.56 17.8 19.6 1.86 18.0 21.3 2.17 18.3 23.2 2.45 18.6 23.9 2.50 18.7 24.8 2.57 18.8

120 18.1 1.52 17.2 19.6 1.83 17.4 21.3 2.13 17.6 23.2 2.40 17.9 23.9 2.46 17.9 24.8 2.52 18.150 18.1 2.10 25.5 19.6 2.46 25.9 21.3 2.87 26.4 23.2 3.23 27.0 23.9 3.30 27.2 24.8 3.39 27.596 18.1 1.93 22.8 19.6 2.30 23.1 21.3 2.68 23.4 23.2 3.02 23.6 23.9 3.09 23.8 24.8 3.17 23.9

120 18.1 1.88 22.3 19.6 2.25 22.5 21.3 2.62 22.7 23.2 2.96 22.9 23.9 3.03 23.0 24.8 3.11 23.150 18.1 2.56 30.6 19.6 3.00 31.0 21.3 3.49 31.6 23.2 3.94 32.1 23.9 4.03 32.3 24.8 4.13 32.696 18.1 2.35 27.9 19.6 2.81 28.1 21.3 3.27 28.4 23.2 3.68 28.7 23.9 3.77 28.8 24.8 3.86 29.0

120 18.1 2.29 27.3 19.6 2.75 27.5 21.3 3.20 27.7 23.2 3.61 28.0 23.9 3.70 28.1 24.8 3.79 28.250 18.1 3.15 35.7 19.6 3.69 36.2 21.3 4.30 36.7 23.2 4.84 37.3 23.9 4.96 37.6 24.8 5.08 37.896 18.1 2.89 33.0 19.6 3.45 33.2 21.3 4.02 33.5 23.2 4.53 33.8 23.9 4.63 33.9 24.8 4.75 34.1

120 18.1 2.81 32.4 19.6 3.38 32.6 21.3 3.94 32.8 23.2 4.44 33.1 23.9 4.55 33.1 24.8 4.66 33.350 18.1 3.50 40.9 19.6 4.10 41.4 21.3 4.78 41.9 23.2 5.38 42.5 23.9 5.51 42.8 24.8 5.64 43.196 18.1 3.21 38.1 19.6 3.83 38.3 21.3 4.47 38.6 23.2 5.03 38.9 23.9 5.15 39.0 24.8 5.28 39.2

120 18.1 3.13 37.4 19.6 3.75 37.7 21.3 4.37 37.9 23.2 4.93 38.1 23.9 5.05 38.2 24.8 5.18 38.450 18.1 4.14 46.1 19.6 4.86 46.6 21.3 5.66 47.2 23.2 6.37 47.8 23.9 6.52 48.0 24.8 6.68 48.396 18.1 3.81 43.2 19.6 4.54 43.4 21.3 5.29 43.7 23.2 5.95 44.1 23.9 6.10 44.2 24.8 6.25 44.3

120 18.1 3.70 42.5 19.6 4.44 42.7 21.3 5.18 43.0 23.2 5.84 43.2 23.9 5.98 43.3 24.8 6.14 43.5

28.7 3.33 23.528.7 3.12 19.428.7 3.04 18.528.7 4.11 28.728.7 3.85 24.528.7 3.75 23.628.7 5.01 33.828.7 4.69 29.628.7 4.57 28.728.7 6.17 39.128.7 5.77 34.728.7 5.62 33.827.9 6.65 44.127.9 6.23 39.727.9 6.06 38.827.1 7.64 49.127.1 7.15 44.727.1 6.96 43.825.5 2.79 22.625.5 2.62 18.925.5 2.55 18.125.5 3.45 27.725.5 3.23 24.025.5 3.14 23.225.5 4.20 32.825.5 3.93 29.125.5 3.83 28.325.5 5.17 38.125.5 4.84 34.225.5 4.71 33.425.5 5.74 43.325.5 5.38 39.325.5 5.23 38.525.5 6.80 48.625.5 6.37 44.525.5 6.20 43.6

90

80

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 26: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 1414

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

50 15.8 1.41 19.7 17.1 1.66 20.1 18.7 1.93 20.5 20.3 2.18 21.0 20.9 2.23 21.2 21.7 2.28 21.496 15.8 1.30 17.4 17.1 1.55 17.6 18.7 1.81 17.9 20.3 2.03 18.1 20.9 2.08 18.2 21.7 2.14 18.3

120 15.8 1.26 17.0 17.1 1.52 17.1 18.7 1.77 17.3 20.3 1.99 17.5 20.9 2.04 17.6 21.7 2.10 17.750 15.8 1.74 24.8 17.1 2.05 25.2 18.7 2.38 25.6 20.3 2.68 26.1 20.9 2.75 26.3 21.7 2.81 26.696 15.8 1.60 22.5 17.1 1.91 22.7 18.7 2.23 22.9 20.3 2.51 23.2 20.9 2.57 23.3 21.7 2.63 23.4

120 15.8 1.56 22.0 17.1 1.87 22.2 18.7 2.18 22.3 20.3 2.46 22.6 20.9 2.52 22.6 21.7 2.58 22.750 15.8 2.13 29.9 17.1 2.49 30.3 18.7 2.91 30.7 20.3 3.27 31.2 20.9 3.35 31.4 21.7 3.43 31.796 15.8 1.96 27.5 17.1 2.33 27.7 18.7 2.72 28.0 20.3 3.06 28.2 20.9 3.13 28.3 21.7 3.21 28.5

120 15.8 1.90 27.0 17.1 2.28 27.2 18.7 2.66 27.4 20.3 3.00 27.6 20.9 3.07 27.7 21.7 3.15 27.850 15.8 2.62 35.0 17.1 3.07 35.4 18.7 3.57 35.9 20.3 4.02 36.4 20.9 4.12 36.6 21.7 4.22 36.996 15.8 2.41 32.6 17.1 2.87 32.8 18.7 3.34 33.1 20.3 3.76 33.3 20.9 3.85 33.4 21.7 3.95 33.6

120 15.8 2.34 32.1 17.1 2.81 32.3 18.7 3.27 32.5 20.3 3.69 32.7 20.9 3.78 32.8 21.7 3.88 32.950 15.8 2.91 40.1 17.1 3.41 40.6 18.7 3.97 41.1 20.3 4.47 41.6 20.9 4.58 41.8 21.7 4.69 42.196 15.8 2.67 37.7 17.1 3.19 37.9 18.7 3.71 38.2 20.3 4.18 38.4 20.9 4.28 38.5 21.7 4.39 38.7

120 15.8 2.60 37.1 17.1 3.12 37.3 18.7 3.64 37.5 20.3 4.10 37.7 20.9 4.20 37.8 21.7 4.31 37.950 15.8 3.44 45.3 17.1 4.04 45.8 18.7 4.70 46.3 20.3 5.30 46.8 20.9 5.42 47.0 21.7 5.55 47.396 15.8 3.17 42.8 17.1 3.77 43.0 18.7 4.40 43.3 20.3 4.95 43.6 20.9 5.07 43.7 21.7 5.20 43.8

120 15.8 3.08 42.2 17.1 3.69 42.4 18.7 4.31 42.6 20.3 4.85 42.8 20.9 4.97 42.9 21.7 5.10 43.050 13.6 1.13 19.0 14.7 1.32 19.3 16.0 1.54 19.7 17.4 1.73 20.1 17.9 1.78 20.3 18.6 1.82 20.596 13.6 1.04 17.1 14.7 1.24 17.3 16.0 1.44 17.5 17.4 1.62 17.7 17.9 1.66 17.8 18.6 1.70 17.9

120 13.6 1.01 16.7 14.7 1.21 16.8 16.0 1.41 17.0 17.4 1.59 17.1 17.9 1.63 17.2 18.6 1.67 17.350 13.6 1.39 24.1 14.7 1.63 24.4 16.0 1.90 24.8 17.4 2.14 25.2 17.9 2.19 25.4 18.6 2.24 25.696 13.6 1.28 22.1 14.7 1.52 22.3 16.0 1.78 22.5 17.4 2.00 22.7 17.9 2.05 22.8 18.6 2.10 22.9

120 13.6 1.24 21.7 14.7 1.49 21.8 16.0 1.74 22.0 17.4 1.96 22.2 17.9 2.01 22.3 18.6 2.06 22.350 13.6 1.70 29.2 14.7 1.99 29.5 16.0 2.32 29.9 17.4 2.61 30.3 17.9 2.67 30.5 18.6 2.74 30.796 13.6 1.56 27.2 14.7 1.86 27.4 16.0 2.17 27.6 17.4 2.44 27.8 17.9 2.50 27.9 18.6 2.56 28.0

120 13.6 1.52 26.7 14.7 1.82 26.9 16.0 2.12 27.1 17.4 2.39 27.2 17.9 2.45 27.3 18.6 2.51 27.450 13.6 2.09 34.3 14.7 2.45 34.6 16.0 2.85 35.1 17.4 3.21 35.5 17.9 3.28 35.7 18.6 3.37 35.996 13.6 1.92 32.2 14.7 2.29 32.4 16.0 2.66 32.6 17.4 3.00 32.9 17.9 3.07 32.9 18.6 3.15 33.1

120 13.6 1.86 31.8 14.7 2.24 31.9 16.0 2.61 32.1 17.4 2.94 32.3 17.9 3.01 32.4 18.6 3.09 32.550 13.6 2.32 39.4 14.7 2.72 39.8 16.0 3.17 40.2 17.4 3.56 40.6 17.9 3.65 40.8 18.6 3.74 41.096 13.6 2.13 37.3 14.7 2.54 37.5 16.0 2.96 37.7 17.4 3.33 37.9 17.9 3.41 38.0 18.6 3.50 38.1

120 13.6 2.07 36.8 14.7 2.49 37.0 16.0 2.90 37.2 17.4 3.27 37.4 17.9 3.35 37.4 18.6 3.43 37.550 13.6 2.74 44.6 14.7 3.22 44.9 16.0 3.75 45.4 17.4 4.22 45.8 17.9 4.32 46.0 18.6 4.43 46.396 13.6 2.52 42.4 14.7 3.01 42.6 16.0 3.50 42.8 17.4 3.95 43.0 17.9 4.04 43.1 18.6 4.14 43.3

120 13.6 2.45 41.9 14.7 2.94 42.1 16.0 3.43 42.2 17.4 3.87 42.4 17.9 3.97 42.5 18.6 4.07 42.6

22.3 2.32 21.622.3 2.17 18.422.3 2.12 17.822.3 2.87 26.722.3 2.68 23.522.3 2.61 22.822.3 3.49 31.922.3 3.27 28.622.3 3.18 27.922.3 4.30 37.122.3 4.02 33.722.3 3.92 32.922.3 4.78 42.222.3 4.47 38.822.3 4.35 38.022.3 5.65 47.522.3 5.29 43.922.3 5.15 43.119.1 1.85 20.719.1 1.73 17.919.1 1.69 17.419.1 2.28 25.819.1 2.14 23.019.1 2.08 22.419.1 2.79 30.919.1 2.61 28.119.1 2.54 27.519.1 3.43 36.019.1 3.21 33.119.1 3.12 32.519.1 3.81 41.219.1 3.56 38.219.1 3.47 37.619.1 4.51 46.419.1 4.22 43.419.1 4.11 42.7

70

60

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 27: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units1515

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

50 11.3 0.84 18.3 12.2 0.99 18.6 13.3 1.15 18.9 14.5 1.29 19.3 14.9 1.32 19.4 15.5 1.36 19.696 11.3 0.77 16.7 12.2 0.92 16.9 13.3 1.07 17.1 14.5 1.21 17.2 14.9 1.24 17.3 15.5 1.27 17.4

120 11.3 0.75 16.4 12.2 0.90 16.5 13.3 1.05 16.6 14.5 1.19 16.8 14.9 1.21 16.8 15.5 1.25 16.950 11.3 1.04 23.4 12.2 1.22 23.7 13.3 1.42 24.0 14.5 1.59 24.4 14.9 1.63 24.5 15.5 1.67 24.796 11.3 0.95 21.8 12.2 1.14 21.9 13.3 1.32 22.1 14.5 1.49 22.3 14.9 1.53 22.3 15.5 1.57 22.4

120 11.3 0.93 21.4 12.2 1.11 21.5 13.3 1.30 21.7 14.5 1.46 21.8 14.9 1.50 21.9 15.5 1.54 21.950 11.3 1.26 28.5 12.2 1.48 28.8 13.3 1.73 29.1 14.5 1.94 29.5 14.9 1.99 29.6 15.5 2.04 29.896 11.3 1.16 26.8 12.2 1.39 27.0 13.3 1.61 27.1 14.5 1.82 27.3 14.9 1.86 27.4 15.5 1.91 27.5

120 11.3 1.13 26.4 12.2 1.36 26.6 13.3 1.58 26.7 14.5 1.78 26.9 14.9 1.83 26.9 15.5 1.87 27.050 11.3 1.55 33.6 12.2 1.82 33.9 13.3 2.12 34.2 14.5 2.39 34.6 14.9 2.45 34.7 15.5 2.51 34.996 11.3 1.43 31.9 12.2 1.71 32.0 13.3 1.99 32.2 14.5 2.24 32.4 14.9 2.29 32.5 15.5 2.35 32.6

120 11.3 1.39 31.5 12.2 1.67 31.6 13.3 1.95 31.8 14.5 2.19 31.9 14.9 2.25 32.0 15.5 2.30 32.050 11.3 1.73 38.7 12.2 2.03 39.0 13.3 2.36 39.3 14.5 2.66 39.7 14.9 2.72 39.8 15.5 2.79 40.096 11.3 1.59 36.9 12.2 1.89 37.1 13.3 2.21 37.3 14.5 2.49 37.5 14.9 2.54 37.5 15.5 2.61 37.6

120 11.3 1.54 36.5 12.2 1.85 36.7 13.3 2.16 36.8 14.5 2.44 37.0 14.9 2.50 37.0 15.5 2.56 37.150 11.3 2.05 43.8 12.2 2.40 44.1 13.3 2.79 44.5 14.5 3.15 44.9 14.9 3.22 45.0 15.5 3.30 45.296 11.3 1.88 42.0 12.2 2.24 42.1 13.3 2.61 42.3 14.5 2.94 42.5 14.9 3.01 42.6 15.5 3.09 42.7

120 11.3 1.83 41.6 12.2 2.20 41.7 13.3 2.56 41.9 14.5 2.89 42.0 14.9 2.96 42.1 15.5 3.03 42.2

16.0 1.38 19.716.0 1.29 17.516.0 1.26 17.016.0 1.70 24.816.0 1.59 22.516.0 1.55 22.016.0 2.08 29.916.0 1.94 27.616.0 1.89 27.016.0 2.55 35.016.0 2.39 32.616.0 2.33 32.116.0 2.84 40.216.0 2.66 37.716.0 2.59 37.216.0 3.36 45.416.0 3.15 42.816.0 3.06 42.2

50

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 28: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 1616

ARWN200LA2 Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

100 53.0 5.24 22.8 57.4 6.11 23.5 62.6 7.12 24.3 68.0 8.02 25.1 70.0 8.21 25.4 72.8 8.41 25.8192 53.0 4.82 19.1 57.4 5.72 19.4 62.6 6.66 19.8 68.0 7.50 20.2 70.0 7.69 20.4 72.8 7.89 20.6240 53.0 4.69 18.3 57.4 5.60 18.5 62.6 6.52 18.9 68.0 7.35 19.2 70.0 7.54 19.3 72.8 7.74 19.5100 52.3 6.35 27.9 56.6 7.41 28.5 61.6 8.63 29.3 67.0 9.72 30.1 69.0 9.95 30.4 71.7 10.2 30.8192 52.3 5.84 24.1 56.6 6.93 24.4 61.6 8.07 24.8 67.0 9.09 25.3 69.0 9.31 25.4 71.7 9.56 25.6240 52.3 5.68 23.3 56.6 6.78 23.6 61.6 7.91 23.9 67.0 8.91 24.2 69.0 9.14 24.3 71.7 9.37 24.5100 52.3 7.84 33.0 56.6 9.14 33.7 61.6 10.6 29.3 67.0 12.0 35.3 69.0 12.3 35.6 71.7 12.6 36.0192 52.3 7.21 29.2 56.6 8.55 29.5 61.6 9.95 29.9 67.0 11.2 30.4 69.0 11.5 30.5 71.7 11.8 30.7240 52.3 7.01 28.3 56.6 8.36 28.6 61.6 9.75 28.9 67.0 11.0 29.3 69.0 11.3 29.4 71.7 11.6 29.6100 52.3 9.40 38.3 56.6 11.0 38.9 61.6 12.8 39.7 67.0 14.4 40.6 69.0 14.7 40.9 71.7 15.1 41.3192 52.3 8.65 34.3 56.6 10.3 34.7 61.6 11.9 35.1 67.0 13.5 35.5 69.0 13.8 35.7 71.7 14.2 35.9240 52.3 8.41 33.4 56.6 10.0 33.7 61.6 11.7 34.1 67.0 13.2 34.4 69.0 13.5 34.5 71.7 13.9 34.7100 47.0 9.51 42.6 50.9 11.1 43.3 55.5 12.9 44.0 60.3 14.5 44.8 62.1 14.9 45.1 64.5 15.3 45.5192 47.0 8.74 39.0 50.9 10.4 39.3 55.5 12.1 39.7 60.3 13.6 40.1 62.1 13.9 40.3 64.5 14.3 40.5240 47.0 8.50 38.2 50.9 10.1 38.4 55.5 11.8 38.8 60.3 13.3 39.1 62.1 13.7 39.2 64.5 14.0 39.4100 41.8 10.0 47.0 45.3 11.7 47.6 49.3 13.6 48.3 53.6 15.3 49.0 55.2 15.7 49.3 57.4 16.1 49.6192 41.8 9.22 43.7 45.3 10.9 44.0 49.3 12.7 44.3 53.6 14.3 44.7 55.2 14.7 44.8 57.4 15.1 45.0240 41.8 8.97 42.9 45.3 10.7 43.2 49.3 12.5 43.5 53.6 14.1 43.8 55.2 14.4 43.9 57.4 14.8 44.0100 50.4 5.01 22.5 54.6 5.85 23.1 59.5 6.81 23.8 64.7 7.67 24.6 66.6 7.85 24.9 69.2 8.05 25.2192 50.4 4.61 18.9 54.6 5.47 19.2 59.5 6.37 19.6 64.7 7.17 20.0 66.6 7.35 20.1 69.2 7.54 20.3240 50.4 4.48 18.1 54.6 5.35 18.4 59.5 6.24 18.7 64.7 7.03 19.0 66.6 7.21 19.1 69.2 7.40 19.3100 49.9 6.11 27.5 54.1 7.13 28.2 58.9 8.30 28.9 64.0 9.35 29.7 65.9 9.57 29.9 68.5 9.81 30.3192 49.9 5.62 23.9 54.1 6.66 24.2 58.9 7.76 24.6 64.0 8.74 25.0 65.9 8.95 25.2 68.5 9.19 25.4240 49.9 5.46 23.1 54.1 6.52 23.4 58.9 7.60 23.7 64.0 8.57 24.0 65.9 8.79 24.1 68.5 9.01 24.3100 49.9 7.51 32.7 54.1 8.76 33.3 58.9 10.2 28.9 64.0 11.5 34.8 65.9 11.8 35.1 68.5 12.1 35.5192 49.9 6.91 29.0 54.1 8.19 29.3 58.9 9.54 29.7 64.0 10.7 30.1 65.9 11.0 30.3 68.5 11.3 30.5240 49.9 6.71 28.2 54.1 8.01 28.5 58.9 9.34 28.8 64.0 10.5 29.1 65.9 10.8 29.2 68.5 11.1 29.4100 49.9 9.08 37.9 54.1 10.6 38.5 58.9 12.3 39.3 64.0 13.9 40.1 65.9 14.2 40.4 68.5 14.6 40.8192 49.9 8.35 34.1 54.1 9.90 34.4 58.9 11.5 34.8 64.0 13.0 35.3 65.9 13.3 35.4 68.5 13.7 35.6240 49.9 8.12 33.3 54.1 9.69 33.6 58.9 11.3 33.9 64.0 12.7 34.2 65.9 13.1 34.3 68.5 13.4 34.5100 45.7 9.31 42.4 49.5 10.9 43.0 53.9 12.6 43.7 58.6 14.2 44.5 60.3 14.6 44.8 62.7 14.9 45.2192 45.7 8.56 38.9 49.5 10.1 39.2 53.9 11.8 39.6 58.6 13.3 40.0 60.3 13.6 40.1 62.7 14.0 40.3240 45.7 8.32 38.1 49.5 9.93 38.3 53.9 11.6 38.6 58.6 13.1 39.0 60.3 13.4 39.1 62.7 13.7 39.2100 41.4 10.0 47.0 44.9 11.7 47.5 48.9 13.6 48.2 53.1 15.3 48.9 54.7 15.7 49.2 56.9 16.1 49.6192 41.4 9.21 43.6 44.9 10.9 43.9 48.9 12.7 44.3 53.1 14.3 44.7 54.7 14.7 44.8 56.9 15.1 45.0240 41.4 8.96 42.9 44.9 10.7 43.1 48.9 12.5 43.4 53.1 14.0 43.7 54.7 14.4 43.8 56.9 14.8 44.0

74.8 8.57 26.174.8 8.05 20.874.8 7.87 19.673.7 10.4 31.173.7 9.75 25.873.7 9.53 24.673.7 12.8 36.373.7 12.0 30.973.7 11.8 29.773.7 15.4 41.673.7 14.4 36.173.7 14.1 34.966.3 15.5 45.866.3 14.6 40.666.3 14.3 39.559.0 16.4 49.959.0 15.4 45.259.0 15.1 44.171.1 8.19 25.571.1 7.69 20.571.1 7.51 19.470.4 9.98 30.670.4 9.37 25.570.4 9.15 24.470.4 12.3 35.870.4 11.5 30.670.4 11.2 29.570.4 14.8 41.170.4 13.9 35.870.4 13.6 34.664.4 15.2 45.564.4 14.3 40.464.4 13.9 39.458.5 16.4 49.858.5 15.4 45.158.5 15.0 44.1

120

130

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 29: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units1717

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

100 47.8 4.79 22.1 51.8 5.58 22.7 56.4 6.50 23.3 61.3 7.32 24.1 63.2 7.50 24.3 65.6 7.68 24.7192 47.8 4.40 18.7 51.8 5.22 19.0 56.4 6.08 19.3 61.3 6.85 19.7 63.2 7.01 19.9 65.6 7.19 20.1240 47.8 4.28 17.9 51.8 5.11 18.2 56.4 5.95 18.5 61.3 6.71 18.8 63.2 6.88 18.9 65.6 7.06 19.0100 47.6 5.87 27.2 51.5 6.84 27.8 56.1 7.97 28.5 61.0 8.97 29.2 62.8 9.19 29.5 65.3 9.41 29.8192 47.6 5.39 23.7 51.5 6.40 24.0 56.1 7.45 24.4 61.0 8.39 24.8 62.8 8.59 24.9 65.3 8.82 25.1240 47.6 5.25 23.0 51.5 6.26 23.2 56.1 7.30 23.5 61.0 8.23 23.8 62.8 8.43 23.9 65.3 8.65 24.1100 47.6 7.18 32.3 51.5 8.38 32.9 56.1 9.76 28.5 61.0 11.0 34.4 62.8 11.3 34.7 65.3 11.5 35.0192 47.6 6.60 28.8 51.5 7.83 29.1 56.1 9.12 29.5 61.0 10.3 29.9 62.8 10.5 30.0 65.3 10.8 30.2240 47.6 6.42 28.0 51.5 7.67 28.3 56.1 8.94 28.6 61.0 10.1 28.9 62.8 10.3 29.0 65.3 10.6 29.2100 47.6 8.76 37.5 51.5 10.2 38.1 56.1 11.9 38.9 61.0 13.4 39.6 62.8 13.7 39.9 65.3 14.1 40.3192 47.6 8.05 33.9 51.5 9.55 34.2 56.1 11.1 34.6 61.0 12.5 35.0 62.8 12.8 35.2 65.3 13.2 35.4240 47.6 7.83 33.1 51.5 9.34 33.4 56.1 10.9 33.7 61.0 12.3 34.0 62.8 12.6 34.1 65.3 12.9 34.3100 44.3 9.10 42.2 48.0 10.6 42.8 52.3 12.4 43.5 56.8 13.9 44.2 58.5 14.3 44.5 60.8 14.6 44.9192 44.3 8.37 38.7 48.0 9.93 39.1 52.3 11.6 39.4 56.8 13.0 39.8 58.5 13.3 39.9 60.8 13.7 40.1240 44.3 8.14 38.0 48.0 9.72 38.2 52.3 11.3 38.5 56.8 12.8 38.8 58.5 13.1 39.0 60.8 13.4 39.1100 41.1 10.0 46.9 44.5 11.7 47.5 48.5 13.6 48.1 52.7 15.3 48.9 54.2 15.7 49.1 56.4 16.0 49.5192 41.1 9.20 43.6 44.5 10.9 43.9 48.5 12.7 44.2 52.7 14.3 44.6 54.2 14.7 44.7 56.4 15.0 44.9240 41.1 8.94 42.9 44.5 10.7 43.1 48.5 12.4 43.4 52.7 14.0 43.7 54.2 14.4 43.8 56.4 14.7 43.9100 45.2 4.56 21.7 49.0 5.32 22.2 53.4 6.19 22.9 58.0 6.97 23.6 59.7 7.14 23.8 62.1 7.32 24.2192 45.2 4.19 18.5 49.0 4.97 18.8 53.4 5.79 19.1 58.0 6.52 19.5 59.7 6.68 19.6 62.1 6.85 19.8240 45.2 4.08 17.8 49.0 4.86 18.0 53.4 5.67 18.3 58.0 6.39 18.6 59.7 6.55 18.7 62.1 6.72 18.8100 45.2 5.62 26.8 49.0 6.56 27.4 53.4 7.64 28.0 58.0 8.60 28.7 59.7 8.81 29.0 62.1 9.02 29.4192 45.2 5.17 23.6 49.0 6.13 23.8 53.4 7.14 24.2 58.0 8.04 24.6 59.7 8.23 24.7 62.1 8.44 24.9240 45.2 5.03 22.8 49.0 6.00 23.1 53.4 6.99 23.4 58.0 7.88 23.6 59.7 8.08 23.8 62.1 8.29 23.9100 45.2 6.85 32.0 49.0 8.00 32.5 53.4 9.31 28.0 58.0 10.5 33.9 59.7 10.7 34.2 62.1 11.0 34.5192 45.2 6.30 28.6 49.0 7.48 28.9 53.4 8.71 29.3 58.0 9.81 29.6 59.7 10.0 29.8 62.1 10.3 30.0240 45.2 6.13 27.9 49.0 7.32 28.1 53.4 8.53 28.4 58.0 9.61 28.7 59.7 9.85 28.8 62.1 10.1 29.0100 45.2 8.43 37.1 49.0 9.84 37.7 53.4 11.5 38.4 58.0 12.9 39.2 59.7 13.2 39.4 62.1 13.5 39.8192 45.2 7.75 33.7 49.0 9.20 34.0 53.4 10.7 34.4 58.0 12.1 34.8 59.7 12.3 34.9 62.1 12.7 35.1240 45.2 7.54 33.0 49.0 9.00 33.2 53.4 10.5 33.5 58.0 11.8 33.8 59.7 12.1 33.9 62.1 12.4 34.1100 43.0 8.90 42.0 46.5 10.4 42.6 50.7 12.1 43.2 55.1 13.6 43.9 56.8 13.9 44.2 59.0 14.3 44.6192 43.0 8.19 38.6 46.5 9.71 38.9 50.7 11.3 39.3 55.1 12.7 39.7 56.8 13.0 39.8 59.0 13.4 40.0240 43.0 7.96 37.9 46.5 9.50 38.1 50.7 11.1 38.4 55.1 12.5 38.7 56.8 12.8 38.8 59.0 13.1 39.0100 40.7 9.98 46.8 44.1 11.6 47.4 48.0 13.6 48.1 52.2 15.3 48.8 53.8 15.6 49.0 55.9 16.0 49.4192 40.7 9.18 43.6 44.1 10.9 43.9 48.0 12.7 44.2 52.2 14.3 44.6 53.8 14.6 44.7 55.9 15.0 44.9240 40.7 8.93 42.9 44.1 10.7 43.1 48.0 12.4 43.4 52.2 14.0 43.7 53.8 14.4 43.8 55.9 14.7 43.9

67.5 7.82 25.067.5 7.33 20.267.5 7.15 19.267.1 9.58 30.167.1 8.98 25.367.1 8.76 24.267.1 11.7 35.367.1 11.0 30.467.1 10.7 29.367.1 14.3 40.667.1 13.4 35.567.1 13.1 34.462.5 14.9 45.162.5 13.9 40.362.5 13.6 39.257.9 16.3 49.757.9 15.3 45.157.9 14.9 44.163.8 7.45 24.463.8 6.97 19.963.8 6.79 18.963.8 9.18 29.663.8 8.60 25.063.8 8.37 24.063.8 11.2 34.863.8 10.5 30.163.8 10.2 29.163.8 13.8 40.163.8 12.9 35.263.8 12.6 34.260.6 14.5 44.860.6 13.6 40.160.6 13.3 39.157.4 16.3 49.657.4 15.3 45.057.4 14.9 44.0

110

100

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 30: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 1818

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Cooling Capacity

100 40.7 3.92 21.0 44.1 4.58 21.5 48.0 5.33 22.1 52.2 6.00 22.7 53.8 6.15 23.0 55.9 6.30 23.3192 40.7 3.61 18.1 44.1 4.28 18.4 48.0 4.98 18.7 52.2 5.61 19.0 53.8 5.75 19.1 55.9 5.89 19.3240 40.7 3.51 17.5 44.1 4.19 17.7 48.0 4.88 18.0 52.2 5.50 18.2 53.8 5.64 18.3 55.9 5.78 18.4100 40.7 4.84 26.1 44.1 5.64 26.6 48.0 6.57 27.2 52.2 7.40 27.9 53.8 7.58 28.1 55.9 7.77 28.4192 40.7 4.45 23.2 44.1 5.28 23.5 48.0 6.15 23.8 52.2 6.92 24.1 53.8 7.09 24.2 55.9 7.27 24.4240 40.7 4.33 22.6 44.1 5.16 22.8 48.0 6.02 23.0 52.2 6.79 23.3 53.8 6.96 23.4 55.9 7.13 23.5100 40.7 5.90 31.3 44.1 6.88 31.8 48.0 8.02 29.8 52.2 9.03 33.0 53.8 9.24 33.3 55.9 9.47 33.6192 40.7 5.43 28.3 44.1 6.44 28.5 48.0 7.50 28.8 52.2 8.44 29.2 53.8 8.64 29.3 55.9 8.86 29.5240 40.7 5.28 27.6 44.1 6.30 27.8 48.0 7.34 28.1 52.2 8.28 28.3 53.8 8.48 28.4 55.9 8.70 28.6100 40.7 7.26 36.4 44.1 8.47 37.0 48.0 9.86 37.6 52.2 11.1 38.2 53.8 11.4 38.5 55.9 11.6 38.8192 40.7 6.67 33.4 44.1 7.92 33.6 48.0 9.22 34.0 52.2 10.4 34.3 53.8 10.6 34.4 55.9 10.9 34.6240 40.7 6.49 32.7 44.1 7.75 32.9 48.0 9.03 33.2 52.2 10.2 33.4 53.8 10.4 33.5 55.9 10.7 33.7100 39.6 7.83 41.4 42.9 9.13 42.0 46.7 10.6 42.6 50.8 12.0 43.2 52.3 12.3 43.5 54.3 12.6 43.8192 39.6 7.20 38.3 42.9 8.54 38.6 46.7 9.95 38.9 50.8 11.2 39.3 52.3 11.5 39.4 54.3 11.8 39.6240 39.6 7.00 37.7 42.9 8.36 37.9 46.7 9.74 38.2 50.8 11.0 38.4 52.3 11.3 38.5 54.3 11.5 38.7100 38.5 8.99 46.5 41.6 10.5 47.0 45.4 12.2 47.6 49.3 13.8 48.3 50.8 14.1 48.5 52.8 14.4 48.9192 38.5 8.27 43.4 41.6 9.81 43.6 45.4 11.4 44.0 49.3 12.9 44.3 50.8 13.2 44.4 52.8 13.5 44.6240 38.5 8.04 42.7 41.6 9.60 42.9 45.4 11.2 43.2 49.3 12.6 43.5 50.8 12.9 43.6 52.8 13.3 43.7100 36.2 3.29 20.4 39.2 3.84 20.8 42.7 4.47 21.3 46.4 5.03 21.9 47.8 5.15 22.1 49.6 5.28 22.3192 36.2 3.02 17.8 39.2 3.59 18.0 42.7 4.18 18.3 46.4 4.70 18.6 47.8 4.82 18.7 49.6 4.94 18.8240 36.2 2.94 17.2 39.2 3.51 17.4 42.7 4.09 17.6 46.4 4.61 17.9 47.8 4.73 17.9 49.6 4.85 18.1100 36.2 4.06 25.5 39.2 4.73 25.9 42.7 5.51 26.4 46.4 6.21 27.0 47.8 6.35 27.2 49.6 6.51 27.5192 36.2 3.73 22.8 39.2 4.42 23.1 42.7 5.15 23.4 46.4 5.80 23.6 47.8 5.94 23.8 49.6 6.09 23.9240 36.2 3.63 22.3 39.2 4.33 22.5 42.7 5.05 22.7 46.4 5.69 22.9 47.8 5.83 23.0 49.6 5.98 23.1100 36.2 4.95 30.6 39.2 5.77 31.0 42.7 6.72 31.6 46.4 7.57 32.1 47.8 7.75 32.3 49.6 7.94 32.6192 36.2 4.55 27.9 39.2 5.39 28.1 42.7 6.28 28.4 46.4 7.08 28.7 47.8 7.24 28.8 49.6 7.43 29.0240 36.2 4.42 27.3 39.2 5.28 27.5 42.7 6.15 27.7 46.4 6.94 28.0 47.8 7.11 28.1 49.6 7.29 28.2100 36.2 6.08 35.7 39.2 7.10 36.2 42.7 8.27 36.7 46.4 9.31 37.3 47.8 9.53 37.6 49.6 9.77 37.8192 36.2 5.60 33.0 39.2 6.64 33.2 42.7 7.73 33.5 46.4 8.70 33.8 47.8 8.91 33.9 49.6 9.14 34.1240 36.2 5.44 32.4 39.2 6.49 32.6 42.7 7.57 32.8 46.4 8.53 33.1 47.8 8.75 33.1 49.6 8.97 33.3100 36.2 6.76 40.9 39.2 7.89 41.4 42.7 9.18 41.9 46.4 10.3 42.5 47.8 10.6 42.8 49.6 10.9 43.1192 36.2 6.22 38.1 39.2 7.37 38.3 42.7 8.59 38.6 46.4 9.67 38.9 47.8 9.90 39.0 49.6 10.2 39.2240 36.2 6.05 37.4 39.2 7.22 37.7 42.7 8.41 37.9 46.4 9.48 38.1 47.8 9.72 38.2 49.6 9.97 38.4100 36.2 8.01 46.1 39.2 9.34 46.6 42.7 10.9 47.2 46.4 12.2 47.8 47.8 12.5 48.0 49.6 12.8 48.3192 36.2 7.36 43.2 39.2 8.73 43.4 42.7 10.2 43.7 46.4 11.5 44.1 47.8 11.7 44.2 49.6 12.0 44.3240 36.2 7.16 42.5 39.2 8.54 42.7 42.7 9.96 43.0 46.4 11.2 43.2 47.8 11.5 43.3 49.6 11.8 43.5

57.4 6.41 23.557.4 6.00 19.457.4 5.84 18.557.4 7.91 28.757.4 7.40 24.557.4 7.20 23.657.4 9.64 33.857.4 9.02 29.657.4 8.79 28.757.4 11.9 39.157.4 11.1 34.757.4 10.8 33.855.8 12.8 44.155.8 12.0 39.755.8 11.7 38.854.2 14.7 49.154.2 13.8 44.754.2 13.4 43.851.0 5.37 22.651.0 5.03 18.951.0 4.90 18.151.0 6.63 27.751.0 6.20 24.051.0 6.04 23.251.0 8.08 32.851.0 7.56 29.151.0 7.37 28.351.0 9.94 38.151.0 9.30 34.251.0 9.06 33.451.0 11.0 43.351.0 10.3 39.351.0 10.1 38.551.0 13.1 48.651.0 12.2 44.551.0 11.9 43.6

90

80

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 31: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units1919

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

100 31.7 2.73 19.7 34.3 3.19 20.1 37.4 3.71 20.5 40.6 4.18 21.0 41.8 4.28 21.2 43.4 4.39 21.4192 31.7 2.51 17.4 34.3 2.98 17.6 37.4 3.47 17.9 40.6 3.91 18.1 41.8 4.00 18.2 43.4 4.11 18.3240 31.7 2.45 17.0 34.3 2.92 17.1 37.4 3.40 17.3 40.6 3.83 17.5 41.8 3.93 17.6 43.4 4.03 17.7100 31.7 3.37 24.8 34.3 3.93 25.2 37.4 4.58 25.6 40.6 5.16 26.1 41.8 5.28 26.3 43.4 5.41 26.6192 31.7 3.10 22.5 34.3 3.68 22.7 37.4 4.28 22.9 40.6 4.82 23.2 41.8 4.94 23.3 43.4 5.07 23.4240 31.7 3.02 22.0 34.3 3.60 22.2 37.4 4.20 22.3 40.6 4.73 22.6 41.8 4.85 22.6 43.4 4.97 22.7100 31.7 4.11 29.9 34.3 4.80 30.3 37.4 5.59 30.7 40.6 6.29 31.2 41.8 6.44 31.4 43.4 6.60 31.7192 31.7 3.78 27.5 34.3 4.49 27.7 37.4 5.22 28.0 40.6 5.88 28.2 41.8 6.02 28.3 43.4 6.18 28.5240 31.7 3.68 27.0 34.3 4.39 27.2 37.4 5.12 27.4 40.6 5.77 27.6 41.8 5.91 27.7 43.4 6.06 27.8100 31.7 5.06 35.0 34.3 5.90 35.4 37.4 6.87 35.9 40.6 7.74 36.4 41.8 7.92 36.6 43.4 8.12 36.9192 31.7 4.65 32.6 34.3 5.52 32.8 37.4 6.43 33.1 40.6 7.24 33.3 41.8 7.41 33.4 43.4 7.60 33.6240 31.7 4.52 32.1 34.3 5.40 32.3 37.4 6.29 32.5 40.6 7.09 32.7 41.8 7.27 32.8 43.4 7.46 32.9100 31.7 5.62 40.1 34.3 6.56 40.6 37.4 7.64 41.1 40.6 8.60 41.6 41.8 8.80 41.8 43.4 9.02 42.1192 31.7 5.17 37.7 34.3 6.13 37.9 37.4 7.14 38.2 40.6 8.04 38.4 41.8 8.23 38.5 43.4 8.44 38.7240 31.7 5.03 37.1 34.3 6.00 37.3 37.4 6.99 37.5 40.6 7.88 37.7 41.8 8.08 37.8 43.4 8.29 37.9100 31.7 6.66 45.3 34.3 7.76 45.8 37.4 9.04 46.3 40.6 10.2 46.8 41.8 10.4 47.0 43.4 10.7 47.3192 31.7 6.12 42.8 34.3 7.26 43.0 37.4 8.46 43.3 40.6 9.52 43.6 41.8 9.75 43.7 43.4 10.0 43.8240 31.7 5.95 42.2 34.3 7.10 42.4 37.4 8.28 42.6 40.6 9.33 42.8 41.8 9.57 42.9 43.4 9.81 43.0100 27.1 2.18 19.0 29.4 2.54 19.3 32.0 2.96 19.7 34.8 3.33 20.1 35.8 3.41 20.3 37.2 3.50 20.5192 27.1 2.00 17.1 29.4 2.38 17.3 32.0 2.77 17.5 34.8 3.12 17.7 35.8 3.19 17.8 37.2 3.27 17.9240 27.1 1.95 16.7 29.4 2.33 16.8 32.0 2.71 17.0 34.8 3.06 17.1 35.8 3.13 17.2 37.2 3.21 17.3100 27.1 2.69 24.1 29.4 3.14 24.4 32.0 3.65 24.8 34.8 4.11 25.2 35.8 4.21 25.4 37.2 4.31 25.6192 27.1 2.47 22.1 29.4 2.93 22.3 32.0 3.42 22.5 34.8 3.85 22.7 35.8 3.94 22.8 37.2 4.04 22.9240 27.1 2.40 21.7 29.4 2.87 21.8 32.0 3.34 22.0 34.8 3.77 22.2 35.8 3.86 22.3 37.2 3.96 22.3100 27.1 3.28 29.2 29.4 3.82 29.5 32.0 4.45 29.9 34.8 5.02 30.3 35.8 5.14 30.5 37.2 5.26 30.7192 27.1 3.02 27.2 29.4 3.58 27.4 32.0 4.16 27.6 34.8 4.69 27.8 35.8 4.80 27.9 37.2 4.92 28.0240 27.1 2.93 26.7 29.4 3.50 26.9 32.0 4.08 27.1 34.8 4.60 27.2 35.8 4.71 27.3 37.2 4.83 27.4100 27.1 4.03 34.3 29.4 4.70 34.6 32.0 5.48 35.1 34.8 6.17 35.5 35.8 6.32 35.7 37.2 6.47 35.9192 27.1 3.71 32.2 29.4 4.40 32.4 32.0 5.12 32.6 34.8 5.77 32.9 35.8 5.91 32.9 37.2 6.06 33.1240 27.1 3.61 31.8 29.4 4.30 31.9 32.0 5.02 32.1 34.8 5.66 32.3 35.8 5.80 32.4 37.2 5.94 32.5100 27.1 4.48 39.4 29.4 5.23 39.8 32.0 6.09 40.2 34.8 6.86 40.6 35.8 7.02 40.8 37.2 7.19 41.0192 27.1 4.12 37.3 29.4 4.89 37.5 32.0 5.69 37.7 34.8 6.41 37.9 35.8 6.56 38.0 37.2 6.73 38.1240 27.1 4.01 36.8 29.4 4.78 37.0 32.0 5.57 37.2 34.8 6.28 37.4 35.8 6.44 37.4 37.2 6.60 37.5100 27.1 5.31 44.6 29.4 6.19 44.9 32.0 7.21 45.4 34.8 8.12 45.8 35.8 8.31 46.0 37.2 8.52 46.3192 27.1 4.88 42.4 29.4 5.79 42.6 32.0 6.74 42.8 34.8 7.59 43.0 35.8 7.77 43.1 37.2 7.97 43.3240 27.1 4.74 41.9 29.4 5.66 42.1 32.0 6.60 42.2 34.8 7.44 42.4 35.8 7.63 42.5 37.2 7.82 42.6

44.7 4.47 21.644.7 4.18 18.444.7 4.07 17.844.7 5.51 26.744.7 5.16 23.544.7 5.02 22.844.7 6.72 31.944.7 6.29 28.644.7 6.12 27.944.7 8.27 37.144.7 7.74 33.744.7 7.53 32.944.7 9.18 42.244.7 8.59 38.844.7 8.37 38.044.7 10.9 47.544.7 10.2 43.944.7 9.91 43.138.3 3.56 20.738.3 3.33 17.938.3 3.25 17.438.3 4.39 25.838.3 4.11 23.038.3 4.00 22.438.3 5.36 30.938.3 5.01 28.138.3 4.88 27.538.3 6.59 36.038.3 6.17 33.138.3 6.00 32.538.3 7.32 41.238.3 6.85 38.238.3 6.67 37.638.3 8.67 46.438.3 8.11 43.438.3 7.90 42.7

70

60

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 32: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 2020

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

100 22.6 1.63 18.3 24.5 1.90 18.6 26.7 2.21 18.9 29.0 2.49 19.3 29.9 2.55 19.4 31.0 2.61 19.6192 22.6 1.49 16.7 24.5 1.77 16.9 26.7 2.06 17.1 29.0 2.32 17.2 29.9 2.38 17.3 31.0 2.44 17.4240 22.6 1.45 16.4 24.5 1.73 16.5 26.7 2.02 16.6 29.0 2.28 16.8 29.9 2.34 16.8 31.0 2.40 16.9100 22.6 2.00 23.4 24.5 2.34 23.7 26.7 2.72 24.0 29.0 3.07 24.4 29.9 3.14 24.5 31.0 3.22 24.7192 22.6 1.84 21.8 24.5 2.19 21.9 26.7 2.55 22.1 29.0 2.87 22.3 29.9 2.94 22.3 31.0 3.01 22.4240 22.6 1.79 21.4 24.5 2.14 21.5 26.7 2.49 21.7 29.0 2.81 21.8 29.9 2.88 21.9 31.0 2.95 21.9100 22.6 2.44 28.5 24.5 2.85 28.8 26.7 3.32 29.1 29.0 3.74 29.5 29.9 3.83 29.6 31.0 3.92 29.8192 22.6 2.25 26.8 24.5 2.67 27.0 26.7 3.11 27.1 29.0 3.50 27.3 29.9 3.58 27.4 31.0 3.67 27.5240 22.6 2.19 26.4 24.5 2.61 26.6 26.7 3.04 26.7 29.0 3.43 26.9 29.9 3.51 26.9 31.0 3.60 27.0100 22.6 3.01 33.6 24.5 3.51 33.9 26.7 4.09 34.2 29.0 4.60 34.6 29.9 4.71 34.7 31.0 4.83 34.9192 22.6 2.77 31.9 24.5 3.28 32.0 26.7 3.82 32.2 29.0 4.30 32.4 29.9 4.40 32.5 31.0 4.52 32.6240 22.6 2.69 31.5 24.5 3.21 31.6 26.7 3.74 31.8 29.0 4.22 31.9 29.9 4.32 32.0 31.0 4.43 32.0100 22.6 3.34 38.7 24.5 3.90 39.0 26.7 4.54 39.3 29.0 5.11 39.7 29.9 5.23 39.8 31.0 5.36 40.0192 22.6 3.07 36.9 24.5 3.64 37.1 26.7 4.24 37.3 29.0 4.78 37.5 29.9 4.89 37.5 31.0 5.02 37.6240 22.6 2.99 36.5 24.5 3.57 36.7 26.7 4.16 36.8 29.0 4.69 37.0 29.9 4.80 37.0 31.0 4.92 37.1100 22.6 3.96 43.8 24.5 4.61 44.1 26.7 5.38 44.5 29.0 6.05 44.9 29.9 6.20 45.0 31.0 6.35 45.2192 22.6 3.64 42.0 24.5 4.31 42.1 26.7 5.03 42.3 29.0 5.66 42.5 29.9 5.79 42.6 31.0 5.94 42.7240 22.6 3.54 41.6 24.5 4.22 41.7 26.7 4.92 41.9 29.0 5.55 42.0 29.9 5.69 42.1 31.0 5.83 42.2

31.9 2.66 19.731.9 2.49 17.531.9 2.42 17.031.9 3.28 24.831.9 3.07 22.531.9 2.98 22.031.9 3.99 29.931.9 3.74 27.631.9 3.64 27.031.9 4.91 35.031.9 4.60 32.631.9 4.48 32.131.9 5.46 40.231.9 5.11 37.731.9 4.97 37.231.9 6.46 45.431.9 6.05 42.831.9 5.89 42.2

50

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 33: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units2121

ARWN300LA2Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

150 79.6 7.95 22.8 86.1 9.29 23.5 93.8 10.8 24.3 102.0 12.2 25.1 105.0 12.5 25.4 109.1 12.8 25.8288 79.6 7.31 19.1 86.1 8.69 19.4 93.8 10.1 19.8 102.0 11.4 20.2 105.0 11.7 20.4 109.1 12.0 20.6360 79.6 7.11 18.3 86.1 8.50 18.5 93.8 9.91 18.9 102.0 11.2 19.2 105.0 11.5 19.3 109.1 11.8 19.5150 78.4 9.64 27.9 84.9 11.3 28.5 92.5 13.1 29.3 100.5 14.8 30.1 103.5 15.1 30.4 107.5 15.5 30.8288 78.4 8.86 24.1 84.9 10.5 24.4 92.5 12.3 24.8 100.5 13.8 25.3 103.5 14.2 25.4 107.5 14.5 25.6360 78.4 8.62 23.3 84.9 10.3 23.6 92.5 12.0 23.9 100.5 13.5 24.2 103.5 13.9 24.3 107.5 14.2 24.5150 78.4 11.9 33.0 84.9 13.9 33.7 92.5 16.2 29.3 100.5 18.2 35.3 103.5 18.7 35.6 107.5 19.1 36.0288 78.4 10.9 29.2 84.9 13.0 29.5 92.5 15.1 29.9 100.5 17.0 30.4 103.5 17.5 30.5 107.5 17.9 30.7360 78.4 10.6 28.3 84.9 12.7 28.6 92.5 14.8 28.9 100.5 16.7 29.3 103.5 17.1 29.4 107.5 17.6 29.6150 78.4 14.3 38.3 84.9 16.7 38.9 92.5 19.4 39.7 100.5 21.9 40.6 103.5 22.4 40.9 107.5 22.9 41.3288 78.4 13.1 34.3 84.9 15.6 34.7 92.5 18.2 35.1 100.5 20.4 35.5 103.5 21.0 35.7 107.5 21.5 35.9360 78.4 12.8 33.4 84.9 15.3 33.7 92.5 17.8 34.1 100.5 20.0 34.4 103.5 20.6 34.5 107.5 21.1 34.7150 70.6 14.4 42.6 76.4 16.9 43.3 83.2 19.6 44.0 90.5 22.1 44.8 93.2 22.6 45.1 96.8 23.2 45.5288 70.6 13.3 39.0 76.4 15.8 39.3 83.2 18.4 39.7 90.5 20.7 40.1 93.2 21.2 40.3 96.8 21.8 40.5360 70.6 12.9 38.2 76.4 15.4 38.4 83.2 18.0 38.8 90.5 20.3 39.1 93.2 20.8 39.2 96.8 21.3 39.4150 62.7 15.2 47.0 67.9 17.8 47.6 74.0 20.7 48.3 80.4 23.3 49.0 82.8 23.9 49.3 86.0 24.5 49.6288 62.7 14.0 43.7 67.9 16.6 44.0 74.0 19.4 44.3 80.4 21.8 44.7 82.8 22.4 44.8 86.0 22.9 45.0360 62.7 13.6 42.9 67.9 16.3 43.2 74.0 19.0 43.5 80.4 21.4 43.8 82.8 21.9 43.9 86.0 22.5 44.0150 75.7 7.61 22.5 81.9 8.89 23.1 89.2 10.4 23.8 97.0 11.7 24.6 99.9 11.9 24.9 103.8 12.2 25.2288 75.7 7.00 18.9 81.9 8.31 19.2 89.2 9.68 19.6 97.0 10.9 20.0 99.9 11.2 20.1 103.8 11.5 20.3360 75.7 6.80 18.1 81.9 8.13 18.4 89.2 9.48 18.7 97.0 10.7 19.0 99.9 11.0 19.1 103.8 11.2 19.3150 74.9 9.27 27.5 81.1 10.8 28.2 88.3 12.6 28.9 96.0 14.2 29.7 98.9 14.5 29.9 102.7 14.9 30.3288 74.9 8.52 23.9 81.1 10.1 24.2 88.3 11.8 24.6 96.0 13.3 25.0 98.9 13.6 25.2 102.7 14.0 25.4360 74.9 8.29 23.1 81.1 9.91 23.4 88.3 11.6 23.7 96.0 13.0 24.0 98.9 13.4 24.1 102.7 13.7 24.3150 74.9 11.4 32.7 81.1 13.3 33.3 88.3 15.5 28.9 96.0 17.5 34.8 98.9 17.9 35.1 102.7 18.3 35.5288 74.9 10.5 29.0 81.1 12.4 29.3 88.3 14.5 29.7 96.0 16.3 30.1 98.9 16.7 30.3 102.7 17.2 30.5360 74.9 10.2 28.2 81.1 12.2 28.5 88.3 14.2 28.8 96.0 16.0 29.1 98.9 16.4 29.2 102.7 16.8 29.4150 74.9 13.8 37.9 81.1 16.1 38.5 88.3 18.7 39.3 96.0 21.1 40.1 98.9 21.6 40.4 102.7 22.1 40.8288 74.9 12.7 34.1 81.1 15.1 34.4 88.3 17.5 34.8 96.0 19.7 35.3 98.9 20.2 35.4 102.7 20.8 35.6360 74.9 12.3 33.3 81.1 14.7 33.6 88.3 17.2 33.9 96.0 19.4 34.2 98.9 19.8 34.3 102.7 20.4 34.5150 68.5 14.1 42.4 74.2 16.5 43.0 80.8 19.2 43.7 87.9 21.6 44.5 90.5 22.2 44.8 94.0 22.7 45.2288 68.5 13.0 38.9 74.2 15.4 39.2 80.8 18.0 39.6 87.9 20.2 40.0 90.5 20.7 40.1 94.0 21.3 40.3360 68.5 12.6 38.1 74.2 15.1 38.3 80.8 17.6 38.6 87.9 19.8 39.0 90.5 20.3 39.1 94.0 20.9 39.2150 62.2 15.2 47.0 67.3 17.8 47.5 73.3 20.7 48.2 79.7 23.3 48.9 82.1 23.8 49.2 85.3 24.4 49.6288 62.2 14.0 43.6 67.3 16.6 43.9 73.3 19.3 44.3 79.7 21.8 44.7 82.1 22.3 44.8 85.3 22.9 45.0360 62.2 13.6 42.9 67.3 16.2 43.1 73.3 18.9 43.4 79.7 21.3 43.7 82.1 21.9 43.8 85.3 22.5 44.0

112.2 13.0 26.1112.2 12.2 20.8112.2 12.0 19.6110.6 15.8 31.1110.6 14.8 25.8110.6 14.5 24.6110.6 19.5 36.3110.6 18.3 30.9110.6 17.9 29.7110.6 23.4 41.6110.6 21.9 36.1110.6 21.4 34.999.5 23.6 45.899.5 22.2 40.699.5 21.7 39.588.4 24.9 49.988.4 23.4 45.288.4 22.9 44.1

106.7 12.5 25.5106.7 11.7 20.5106.7 11.4 19.4105.6 15.2 30.6105.6 14.2 25.5105.6 13.9 24.4105.6 18.6 35.8105.6 17.5 30.6105.6 17.1 29.5105.6 22.5 41.1105.6 21.2 35.8105.6 20.7 34.696.6 23.1 45.596.6 21.7 40.496.6 21.2 39.487.7 24.9 49.887.7 23.3 45.187.7 22.8 44.1

120

130

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 34: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 2222

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

150 71.8 7.26 22.1 77.7 8.49 22.7 84.6 9.88 23.3 92.0 11.1 24.1 94.8 11.4 24.3 98.4 11.7 24.7288 71.8 6.68 18.7 77.7 7.93 19.0 84.6 9.24 19.3 92.0 10.4 19.7 94.8 10.7 19.9 98.4 10.9 20.1360 71.8 6.49 17.9 77.7 7.76 18.2 84.6 9.05 18.5 92.0 10.2 18.8 94.8 10.5 18.9 98.4 10.7 19.0150 71.4 8.90 27.2 77.3 10.4 27.8 84.2 12.1 28.5 91.5 13.6 29.2 94.2 14.0 29.5 97.9 14.3 29.8288 71.4 8.18 23.7 77.3 9.72 24.0 84.2 11.3 24.4 91.5 12.8 24.8 94.2 13.1 24.9 97.9 13.4 25.1360 71.4 7.96 23.0 77.3 9.51 23.2 84.2 11.1 23.5 91.5 12.5 23.8 94.2 12.8 23.9 97.9 13.1 24.1150 71.4 10.9 32.3 77.3 12.7 32.9 84.2 14.8 28.5 91.5 16.7 34.4 94.2 17.1 34.7 97.9 17.5 35.0288 71.4 10.0 28.8 77.3 11.9 29.1 84.2 13.9 29.5 91.5 15.6 29.9 94.2 16.0 30.0 97.9 16.4 30.2360 71.4 9.74 28.0 77.3 11.7 28.3 84.2 13.6 28.6 91.5 15.3 28.9 94.2 15.7 29.0 97.9 16.1 29.2150 71.4 13.3 37.5 77.3 15.5 38.1 84.2 18.1 38.9 91.5 20.4 39.6 94.2 20.8 39.9 97.9 21.4 40.3288 71.4 12.2 33.9 77.3 14.5 34.2 84.2 16.9 34.6 91.5 19.0 35.0 94.2 19.5 35.2 97.9 20.0 35.4360 71.4 11.9 33.1 77.3 14.2 33.4 84.2 16.6 33.7 91.5 18.7 34.0 94.2 19.1 34.1 97.9 19.6 34.3150 66.5 13.8 42.2 72.0 16.1 42.8 78.4 18.8 43.5 85.3 21.2 44.2 87.8 21.7 44.5 91.2 22.2 44.9288 66.5 12.7 38.7 72.0 15.1 39.1 78.4 17.6 39.4 85.3 19.8 39.8 87.8 20.3 39.9 91.2 20.8 40.1360 66.5 12.4 38.0 72.0 14.8 38.2 78.4 17.2 38.5 85.3 19.4 38.8 87.8 19.9 39.0 91.2 20.4 39.1150 61.6 15.2 46.9 66.7 17.7 47.5 72.7 20.7 48.1 79.0 23.3 48.9 81.4 23.8 49.1 84.5 24.4 49.5288 61.6 14.0 43.6 66.7 16.6 43.9 72.7 19.3 44.2 79.0 21.7 44.6 81.4 22.3 44.7 84.5 22.8 44.9360 61.6 13.6 42.9 66.7 16.2 43.1 72.7 18.9 43.4 79.0 21.3 43.7 81.4 21.9 43.8 84.5 22.4 43.9150 67.9 6.91 21.7 73.5 8.08 22.2 80.0 9.41 22.9 87.0 10.6 23.6 89.6 10.9 23.8 93.1 11.1 24.2288 67.9 6.36 18.5 73.5 7.56 18.8 80.0 8.80 19.1 87.0 9.91 19.5 89.6 10.1 19.6 93.1 10.4 19.8360 67.9 6.18 17.8 73.5 7.39 18.0 80.0 8.62 18.3 87.0 9.72 18.6 89.6 9.96 18.7 93.1 10.2 18.8150 67.9 8.53 26.8 73.5 9.97 27.4 80.0 11.6 28.0 87.0 13.1 28.7 89.6 13.4 29.0 93.1 13.7 29.4288 67.9 7.84 23.6 73.5 9.32 23.8 80.0 10.9 24.2 87.0 12.2 24.6 89.6 12.5 24.7 93.1 12.8 24.9360 67.9 7.63 22.8 73.5 9.12 23.1 80.0 10.6 23.4 87.0 12.0 23.6 89.6 12.3 23.8 93.1 12.6 23.9150 67.9 10.4 32.0 73.5 12.2 32.5 80.0 14.2 28.0 87.0 15.9 33.9 89.6 16.3 34.2 93.1 16.7 34.5288 67.9 9.56 28.6 73.5 11.4 28.9 80.0 13.2 29.3 87.0 14.9 29.6 89.6 15.3 29.8 93.1 15.7 30.0360 67.9 9.30 27.9 73.5 11.1 28.1 80.0 13.0 28.4 87.0 14.6 28.7 89.6 15.0 28.8 93.1 15.4 29.0150 67.9 12.8 37.1 73.5 14.9 37.7 80.0 17.4 38.4 87.0 19.6 39.2 89.6 20.1 39.4 93.1 20.6 39.8288 67.9 11.8 33.7 73.5 14.0 34.0 80.0 16.3 34.4 87.0 18.3 34.8 89.6 18.8 34.9 93.1 19.3 35.1360 67.9 11.4 33.0 73.5 13.7 33.2 80.0 15.9 33.5 87.0 18.0 33.8 89.6 18.4 33.9 93.1 18.9 34.1150 64.5 13.5 42.0 69.8 15.8 42.6 76.0 18.4 43.2 82.7 20.7 43.9 85.1 21.2 44.2 88.4 21.7 44.6288 64.5 12.4 38.6 69.8 14.8 38.9 76.0 17.2 39.3 82.7 19.4 39.7 85.1 19.8 39.8 88.4 20.3 40.0360 64.5 12.1 37.9 69.8 14.4 38.1 76.0 16.8 38.4 82.7 19.0 38.7 85.1 19.4 38.8 88.4 19.9 39.0150 61.1 15.1 46.8 66.1 17.7 47.4 72.0 20.6 48.1 78.3 23.2 48.8 80.6 23.8 49.0 83.8 24.4 49.4288 61.1 13.9 43.6 66.1 16.6 43.9 72.0 19.3 44.2 78.3 21.7 44.6 80.6 22.2 44.7 83.8 22.8 44.9360 61.1 13.5 42.9 66.1 16.2 43.1 72.0 18.9 43.4 78.3 21.3 43.7 80.6 21.8 43.8 83.8 22.4 43.9

101.2 11.9 25.0101.2 11.1 20.2101.2 10.9 19.2100.7 14.6 30.1100.7 13.7 25.3100.7 13.3 24.2100.7 17.8 35.3100.7 16.7 30.4100.7 16.3 29.3100.7 21.7 40.6100.7 20.4 35.5100.7 19.9 34.493.8 22.6 45.193.8 21.2 40.393.8 20.7 39.286.9 24.8 49.786.9 23.3 45.186.9 22.7 44.195.7 11.3 24.495.7 10.6 19.995.7 10.3 18.995.7 14.0 29.695.7 13.1 25.095.7 12.7 24.095.7 17.0 34.895.7 15.9 30.195.7 15.5 29.195.7 20.9 40.195.7 19.6 35.295.7 19.1 34.290.9 22.1 44.890.9 20.7 40.190.9 20.1 39.186.1 24.8 49.686.1 23.2 45.086.1 22.6 44.0

110

100

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 35: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units2323

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Cooling Capacity

150 61.1 5.95 21.0 66.1 6.96 21.5 72.0 8.10 22.1 78.3 9.12 22.7 80.6 9.34 23.0 83.8 9.57 23.3288 61.1 5.47 18.1 66.1 6.50 18.4 72.0 7.58 18.7 78.3 8.53 19.0 80.6 8.73 19.1 83.8 8.96 19.3360 61.1 5.32 17.5 66.1 6.36 17.7 72.0 7.42 18.0 78.3 8.36 18.2 80.6 8.57 18.3 83.8 8.79 18.4150 61.1 7.34 26.1 66.1 8.58 26.6 72.0 10.0 27.2 78.3 11.3 27.9 80.6 11.5 28.1 83.8 11.8 28.4288 61.1 6.75 23.2 66.1 8.02 23.5 72.0 9.34 23.8 78.3 10.5 24.1 80.6 10.8 24.2 83.8 11.0 24.4360 61.1 6.56 22.6 66.1 7.85 22.8 72.0 9.15 23.0 78.3 10.3 23.3 80.6 10.6 23.4 83.8 10.8 23.5150 61.1 8.95 31.3 66.1 10.5 31.8 72.0 12.2 29.8 78.3 13.7 33.0 80.6 14.1 33.3 83.8 14.4 33.6288 61.1 8.23 28.3 66.1 9.78 28.5 72.0 11.4 28.8 78.3 12.8 29.2 80.6 13.1 29.3 83.8 13.5 29.5360 61.1 8.01 27.6 66.1 9.57 27.8 72.0 11.2 28.1 78.3 12.6 28.3 80.6 12.9 28.4 83.8 13.2 28.6150 61.1 11.0 36.4 66.1 12.9 37.0 72.0 15.0 37.6 78.3 16.9 38.2 80.6 17.3 38.5 83.8 17.7 38.8288 61.1 10.1 33.4 66.1 12.0 33.6 72.0 14.0 34.0 78.3 15.8 34.3 80.6 16.2 34.4 83.8 16.6 34.6360 61.1 9.85 32.7 66.1 11.8 32.9 72.0 13.7 33.2 78.3 15.5 33.4 80.6 15.9 33.5 83.8 16.3 33.7150 59.4 11.9 41.4 64.3 13.9 42.0 70.0 16.2 42.6 76.1 18.2 43.2 78.4 18.6 43.5 81.5 19.1 43.8288 59.4 10.9 38.3 64.3 13.0 38.6 70.0 15.1 38.9 76.1 17.0 39.3 78.4 17.4 39.4 81.5 17.9 39.6360 59.4 10.6 37.7 64.3 12.7 37.9 70.0 14.8 38.2 76.1 16.7 38.4 78.4 17.1 38.5 81.5 17.5 38.7150 57.7 13.6 46.5 62.5 15.9 47.0 68.0 18.6 47.6 74.0 20.9 48.3 76.2 21.4 48.5 79.1 21.9 48.9288 57.7 12.6 43.4 62.5 14.9 43.6 68.0 17.4 44.0 74.0 19.6 44.3 76.2 20.0 44.4 79.1 20.5 44.6360 57.7 12.2 42.7 62.5 14.6 42.9 68.0 17.0 43.2 74.0 19.2 43.5 76.2 19.7 43.6 79.1 20.2 43.7150 54.3 4.99 20.4 58.8 5.83 20.8 64.0 6.79 21.3 69.6 7.65 21.9 71.7 7.83 22.1 74.5 8.02 22.3288 54.3 4.59 17.8 58.8 5.45 18.0 64.0 6.35 18.3 69.6 7.15 18.6 71.7 7.32 18.7 74.5 7.51 18.8360 54.3 4.46 17.2 58.8 5.34 17.4 64.0 6.22 17.6 69.6 7.01 17.9 71.7 7.19 17.9 74.5 7.37 18.1150 54.3 6.15 25.5 58.8 7.19 25.9 64.0 8.38 26.4 69.6 9.43 27.0 71.7 9.66 27.2 74.5 9.90 27.5288 54.3 5.66 22.8 58.8 6.72 23.1 64.0 7.83 23.4 69.6 8.82 23.6 71.7 9.03 23.8 74.5 9.26 23.9360 54.3 5.50 22.3 58.8 6.58 22.5 64.0 7.67 22.7 69.6 8.65 22.9 71.7 8.86 23.0 74.5 9.09 23.1150 54.3 7.50 30.6 58.8 8.77 31.0 64.0 10.2 31.6 69.6 11.5 32.1 71.7 11.8 32.3 74.5 12.1 32.6288 54.3 6.90 27.9 58.8 8.20 28.1 64.0 9.55 28.4 69.6 10.8 28.7 71.7 11.0 28.8 74.5 11.3 29.0360 54.3 6.71 27.3 58.8 8.02 27.5 64.0 9.35 27.7 69.6 10.5 28.0 71.7 10.8 28.1 74.5 11.1 28.2150 54.3 9.23 35.7 58.8 10.8 36.2 64.0 12.6 36.7 69.6 14.1 37.3 71.7 14.5 37.6 74.5 14.8 37.8288 54.3 8.49 33.0 58.8 10.1 33.2 64.0 11.7 33.5 69.6 13.2 33.8 71.7 13.5 33.9 74.5 13.9 34.1360 54.3 8.25 32.4 58.8 9.87 32.6 64.0 11.5 32.8 69.6 13.0 33.1 71.7 13.3 33.1 74.5 13.6 33.3150 54.3 10.3 40.9 58.8 12.0 41.4 64.0 14.0 41.9 69.6 15.7 42.5 71.7 16.1 42.8 74.5 16.5 43.1288 54.3 9.43 38.1 58.8 11.2 38.3 64.0 13.1 38.6 69.6 14.7 38.9 71.7 15.0 39.0 74.5 15.4 39.2360 54.3 9.17 37.4 58.8 11.0 37.7 64.0 12.8 37.9 69.6 14.4 38.1 71.7 14.8 38.2 74.5 15.1 38.4150 54.3 12.1 46.1 58.8 14.2 46.6 64.0 16.5 47.2 69.6 18.6 47.8 71.7 19.1 48.0 74.5 19.5 48.3288 54.3 11.2 43.2 58.8 13.3 43.4 64.0 15.5 43.7 69.6 17.4 44.1 71.7 17.8 44.2 74.5 18.3 44.3360 54.3 10.9 42.5 58.8 13.0 42.7 64.0 15.1 43.0 69.6 17.1 43.2 71.7 17.5 43.3 74.5 17.9 43.5

86.1 9.74 23.586.1 9.12 19.486.1 8.88 18.586.1 12.0 28.786.1 11.2 24.586.1 11.0 23.686.1 14.7 33.886.1 13.7 29.686.1 13.4 28.786.1 18.0 39.186.1 16.9 34.786.1 16.4 33.883.7 19.4 44.183.7 18.2 39.783.7 17.7 38.881.3 22.3 49.181.3 20.9 44.781.3 20.4 43.876.6 8.17 22.676.6 7.64 18.976.6 7.44 18.176.6 10.1 27.776.6 9.43 24.076.6 9.18 23.276.6 12.3 32.876.6 11.5 29.176.6 11.2 28.376.6 15.1 38.176.6 14.1 34.276.6 13.8 33.476.6 16.8 43.376.6 15.7 39.376.6 15.3 38.576.6 19.9 48.676.6 18.6 44.576.6 18.1 43.6

90

80

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 36: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 2424

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

150 47.5 4.15 19.7 51.4 4.85 20.1 56.0 5.65 20.5 60.9 6.36 21.0 62.7 6.51 21.2 65.2 6.67 21.4288 47.5 3.81 17.4 51.4 4.53 17.6 56.0 5.28 17.9 60.9 5.95 18.1 62.7 6.09 18.2 65.2 6.24 18.3360 47.5 3.71 17.0 51.4 4.44 17.1 56.0 5.17 17.3 60.9 5.83 17.5 62.7 5.97 17.6 65.2 6.13 17.7150 47.5 5.12 24.8 51.4 5.98 25.2 56.0 6.96 25.6 60.9 7.84 26.1 62.7 8.03 26.3 65.2 8.23 26.6288 47.5 4.70 22.5 51.4 5.59 22.7 56.0 6.51 22.9 60.9 7.33 23.2 62.7 7.51 23.3 65.2 7.70 23.4360 47.5 4.58 22.0 51.4 5.47 22.2 56.0 6.38 22.3 60.9 7.19 22.6 62.7 7.37 22.6 65.2 7.56 22.7150 47.5 6.24 29.9 51.4 7.29 30.3 56.0 8.49 30.7 60.9 9.56 31.2 62.7 9.79 31.4 65.2 10.0 31.7288 47.5 5.74 27.5 51.4 6.82 27.7 56.0 7.94 28.0 60.9 8.94 28.2 62.7 9.16 28.3 65.2 9.39 28.5360 47.5 5.58 27.0 51.4 6.67 27.2 56.0 7.78 27.4 60.9 8.77 27.6 62.7 8.98 27.7 65.2 9.21 27.8150 47.5 7.67 35.0 51.4 8.97 35.4 56.0 10.4 35.9 60.9 11.8 36.4 62.7 12.0 36.6 65.2 12.3 36.9288 47.5 7.06 32.6 51.4 8.39 32.8 56.0 9.77 33.1 60.9 11.0 33.3 62.7 11.3 33.4 65.2 11.5 33.6360 47.5 6.86 32.1 51.4 8.21 32.3 56.0 9.57 32.5 60.9 10.8 32.7 62.7 11.1 32.8 65.2 11.3 32.9150 47.5 8.53 40.1 51.4 9.96 40.6 56.0 11.6 41.1 60.9 13.1 41.6 62.7 13.4 41.8 65.2 13.7 42.1288 47.5 7.84 37.7 51.4 9.32 37.9 56.0 10.9 38.2 60.9 12.2 38.4 62.7 12.5 38.5 65.2 12.8 38.7360 47.5 7.63 37.1 51.4 9.12 37.3 56.0 10.6 37.5 60.9 12.0 37.7 62.7 12.3 37.8 65.2 12.6 37.9150 47.5 10.1 45.3 51.4 11.8 45.8 56.0 13.7 46.3 60.9 15.5 46.8 62.7 15.8 47.0 65.2 16.2 47.3288 47.5 9.29 42.8 51.4 11.0 43.0 56.0 12.9 43.3 60.9 14.5 43.6 62.7 14.8 43.7 65.2 15.2 43.8360 47.5 9.03 42.2 51.4 10.8 42.4 56.0 12.6 42.6 60.9 14.2 42.8 62.7 14.5 42.9 65.2 14.9 43.0150 40.7 3.31 19.0 44.1 3.86 19.3 48.0 4.50 19.7 52.2 5.07 20.1 53.8 5.19 20.3 55.9 5.32 20.5288 40.7 3.04 17.1 44.1 3.61 17.3 48.0 4.21 17.5 52.2 4.74 17.7 53.8 4.85 17.8 55.9 4.98 17.9360 40.7 2.96 16.7 44.1 3.54 16.8 48.0 4.12 17.0 52.2 4.65 17.1 53.8 4.76 17.2 55.9 4.88 17.3150 40.7 4.08 24.1 44.1 4.77 24.4 48.0 5.55 24.8 52.2 6.25 25.2 53.8 6.40 25.4 55.9 6.56 25.6288 40.7 3.75 22.1 44.1 4.46 22.3 48.0 5.19 22.5 52.2 5.85 22.7 53.8 5.98 22.8 55.9 6.14 22.9360 40.7 3.65 21.7 44.1 4.36 21.8 48.0 5.08 22.0 52.2 5.73 22.2 53.8 5.87 22.3 55.9 6.02 22.3150 40.7 4.97 29.2 44.1 5.81 29.5 48.0 6.77 29.9 52.2 7.62 30.3 53.8 7.81 30.5 55.9 8.00 30.7288 40.7 4.57 27.2 44.1 5.43 27.4 48.0 6.33 27.6 52.2 7.13 27.8 53.8 7.30 27.9 55.9 7.49 28.0360 40.7 4.45 26.7 44.1 5.32 26.9 48.0 6.20 27.1 52.2 6.99 27.2 53.8 7.16 27.3 55.9 7.35 27.4150 40.7 6.12 34.3 44.1 7.15 34.6 48.0 8.33 35.1 52.2 9.38 35.5 53.8 9.60 35.7 55.9 9.84 35.9288 40.7 5.63 32.2 44.1 6.68 32.4 48.0 7.79 32.6 52.2 8.77 32.9 53.8 8.98 32.9 55.9 9.21 33.1360 40.7 5.47 31.8 44.1 6.54 31.9 48.0 7.63 32.1 52.2 8.60 32.3 53.8 8.81 32.4 55.9 9.04 32.5150 40.7 6.80 39.4 44.1 7.94 39.8 48.0 9.25 40.2 52.2 10.4 40.6 53.8 10.7 40.8 55.9 10.9 41.0288 40.7 6.25 37.3 44.1 7.43 37.5 48.0 8.65 37.7 52.2 9.74 37.9 53.8 9.97 38.0 55.9 10.2 38.1360 40.7 6.08 36.8 44.1 7.27 37.0 48.0 8.47 37.2 52.2 9.55 37.4 53.8 9.79 37.4 55.9 10.0 37.5150 40.7 8.05 44.6 44.1 9.41 44.9 48.0 11.0 45.4 52.2 12.3 45.8 53.8 12.6 46.0 55.9 12.9 46.3288 40.7 7.40 42.4 44.1 8.80 42.6 48.0 10.2 42.8 52.2 11.5 43.0 53.8 11.8 43.1 55.9 12.1 43.3360 40.7 7.20 41.9 44.1 8.61 42.1 48.0 10.0 42.2 52.2 11.3 42.4 53.8 11.6 42.5 55.9 11.9 42.6

67.0 6.79 21.667.0 6.36 18.467.0 6.19 17.867.0 8.38 26.767.0 7.84 23.567.0 7.63 22.867.0 10.2 31.967.0 9.56 28.667.0 9.31 27.967.0 12.6 37.167.0 11.8 33.767.0 11.4 32.967.0 14.0 42.267.0 13.1 38.867.0 12.7 38.067.0 16.5 47.567.0 15.5 43.967.0 15.1 43.157.4 5.41 20.757.4 5.07 17.957.4 4.93 17.457.4 6.68 25.857.4 6.25 23.057.4 6.08 22.457.4 8.14 30.957.4 7.62 28.157.4 7.42 27.557.4 10.0 36.057.4 9.37 33.157.4 9.13 32.557.4 11.1 41.257.4 10.4 38.257.4 10.1 37.657.4 13.2 46.457.4 12.3 43.457.4 12.0 42.7

70

60

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 37: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units2525

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

150 33.9 2.47 18.3 36.7 2.88 18.6 40.0 3.36 18.9 43.5 3.78 19.3 44.8 3.87 19.4 46.5 3.96 19.6288 33.9 2.27 16.7 36.7 2.69 16.9 40.0 3.14 17.1 43.5 3.53 17.2 44.8 3.62 17.3 46.5 3.71 17.4360 33.9 2.21 16.4 36.7 2.64 16.5 40.0 3.07 16.6 43.5 3.46 16.8 44.8 3.55 16.8 46.5 3.64 16.9150 33.9 3.04 23.4 36.7 3.55 23.7 40.0 4.14 24.0 43.5 4.66 24.4 44.8 4.77 24.5 46.5 4.89 24.7288 33.9 2.80 21.8 36.7 3.32 21.9 40.0 3.87 22.1 43.5 4.36 22.3 44.8 4.46 22.3 46.5 4.58 22.4360 33.9 2.72 21.4 36.7 3.25 21.5 40.0 3.79 21.7 43.5 4.27 21.8 44.8 4.38 21.9 46.5 4.49 21.9150 33.9 3.71 28.5 36.7 4.33 28.8 40.0 5.05 29.1 43.5 5.68 29.5 44.8 5.82 29.6 46.5 5.96 29.8288 33.9 3.41 26.8 36.7 4.05 27.0 40.0 4.72 27.1 43.5 5.32 27.3 44.8 5.44 27.4 46.5 5.58 27.5360 33.9 3.32 26.4 36.7 3.97 26.6 40.0 4.62 26.7 43.5 5.21 26.9 44.8 5.34 26.9 46.5 5.48 27.0150 33.9 4.56 33.6 36.7 5.33 33.9 40.0 6.21 34.2 43.5 6.99 34.6 44.8 7.16 34.7 46.5 7.34 34.9288 33.9 4.19 31.9 36.7 4.98 32.0 40.0 5.81 32.2 43.5 6.54 32.4 44.8 6.69 32.5 46.5 6.86 32.6360 33.9 4.08 31.5 36.7 4.88 31.6 40.0 5.69 31.8 43.5 6.41 31.9 44.8 6.57 32.0 46.5 6.74 32.0150 33.9 5.07 38.7 36.7 5.92 39.0 40.0 6.90 39.3 43.5 7.77 39.7 44.8 7.95 39.8 46.5 8.15 40.0288 33.9 4.66 36.9 36.7 5.54 37.1 40.0 6.45 37.3 43.5 7.26 37.5 44.8 7.44 37.5 46.5 7.63 37.6360 33.9 4.53 36.5 36.7 5.42 36.7 40.0 6.32 36.8 43.5 7.12 37.0 44.8 7.30 37.0 46.5 7.49 37.1150 33.9 6.00 43.8 36.7 7.01 44.1 40.0 8.17 44.5 43.5 9.20 44.9 44.8 9.42 45.0 46.5 9.65 45.2288 33.9 5.52 42.0 36.7 6.56 42.1 40.0 7.64 42.3 43.5 8.60 42.5 44.8 8.81 42.6 46.5 9.03 42.7360 33.9 5.37 41.6 36.7 6.42 41.7 40.0 7.48 41.9 43.5 8.43 42.0 44.8 8.64 42.1 46.5 8.86 42.2

47.9 4.04 19.747.9 3.78 17.547.9 3.68 17.047.9 4.98 24.847.9 4.66 22.547.9 4.54 22.047.9 6.07 29.947.9 5.68 27.647.9 5.53 27.047.9 7.47 35.047.9 6.99 32.647.9 6.81 32.147.9 8.30 40.247.9 7.77 37.747.9 7.56 37.247.9 9.83 45.447.9 9.20 42.847.9 8.95 42.2

50

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 38: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 2626

ARWN400LA2Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

200 106.1 10.5 22.8 114.9 12.2 23.5 125.1 14.2 24.3 136.0 16.0 25.1 140.1 16.4 25.4 145.5 16.8 25.8384 106.1 9.64 19.1 114.9 11.4 19.4 125.1 13.3 19.8 136.0 15.0 20.2 140.1 15.4 20.4 145.5 15.8 20.6480 106.1 9.38 18.3 114.9 11.2 18.5 125.1 13.0 18.9 136.0 14.7 19.2 140.1 15.1 19.3 145.5 15.5 19.5200 104.5 12.7 27.9 113.2 14.8 28.5 123.3 17.3 29.3 134.0 19.4 30.1 138.0 19.9 30.4 143.4 20.4 30.8384 104.5 11.7 24.1 113.2 13.9 24.4 123.3 16.1 24.8 134.0 18.2 25.3 138.0 18.6 25.4 143.4 19.1 25.6480 104.5 11.4 23.3 113.2 13.6 23.6 123.3 15.8 23.9 134.0 17.8 24.2 138.0 18.3 24.3 143.4 18.7 24.5200 104.5 15.7 33.0 113.2 18.3 33.7 123.3 21.3 29.3 134.0 24.0 35.3 138.0 24.5 35.6 143.4 25.2 36.0384 104.5 14.4 29.2 113.2 17.1 29.5 123.3 19.9 29.9 134.0 22.4 30.4 138.0 23.0 30.5 143.4 23.6 30.7480 104.5 14.0 28.3 113.2 16.7 28.6 123.3 19.5 28.9 134.0 22.0 29.3 138.0 22.5 29.4 143.4 23.1 29.6200 104.5 18.8 38.3 113.2 21.9 38.9 123.3 25.6 39.7 134.0 28.8 40.6 138.0 29.5 40.9 143.4 30.2 41.3384 104.5 17.3 34.3 113.2 20.5 34.7 123.3 23.9 35.1 134.0 26.9 35.5 138.0 27.6 35.7 143.4 28.3 35.9480 104.5 16.8 33.4 113.2 20.1 33.7 123.3 23.4 34.1 134.0 26.4 34.4 138.0 27.1 34.5 143.4 27.7 34.7200 94.1 19.0 42.6 101.9 22.2 43.3 111.0 25.8 44.0 120.6 29.1 44.8 124.2 29.8 45.1 129.1 30.5 45.5384 94.1 17.5 39.0 101.9 20.7 39.3 111.0 24.2 39.7 120.6 27.2 40.1 124.2 27.9 40.3 129.1 28.6 40.5480 94.1 17.0 38.2 101.9 20.3 38.4 111.0 23.7 38.8 120.6 26.7 39.1 124.2 27.4 39.2 129.1 28.1 39.4200 83.6 20.1 47.0 90.6 23.4 47.6 98.6 27.3 48.3 107.2 30.7 49.0 110.4 31.4 49.3 114.7 32.2 49.6384 83.6 18.4 43.7 90.6 21.9 44.0 98.6 25.5 44.3 107.2 28.7 44.7 110.4 29.4 44.8 114.7 30.2 45.0480 83.6 17.9 42.9 90.6 21.4 43.2 98.6 25.0 43.5 107.2 28.1 43.8 110.4 28.9 43.9 114.7 29.6 44.0200 100.9 10.0 22.5 109.2 11.7 23.1 119.0 13.6 23.8 129.3 15.3 24.6 133.2 15.7 24.9 138.4 16.1 25.2384 100.9 9.22 18.9 109.2 10.9 19.2 119.0 12.7 19.6 129.3 14.3 20.0 133.2 14.7 20.1 138.4 15.1 20.3480 100.9 8.97 18.1 109.2 10.7 18.4 119.0 12.5 18.7 129.3 14.1 19.0 133.2 14.4 19.1 138.4 14.8 19.3200 99.8 12.2 27.5 108.1 14.3 28.2 117.8 16.6 28.9 128.0 18.7 29.7 131.9 19.1 29.9 137.0 19.6 30.3384 99.8 11.2 23.9 108.1 13.3 24.2 117.8 15.5 24.6 128.0 17.5 25.0 131.9 17.9 25.2 137.0 18.4 25.4480 99.8 10.9 23.1 108.1 13.0 23.4 117.8 15.2 23.7 128.0 17.1 24.0 131.9 17.6 24.1 137.0 18.0 24.3200 99.8 15.0 32.7 108.1 17.5 33.3 117.8 20.4 28.9 128.0 23.0 34.8 131.9 23.5 35.1 137.0 24.1 35.5384 99.8 13.8 29.0 108.1 16.4 29.3 117.8 19.1 29.7 128.0 21.5 30.1 131.9 22.0 30.3 137.0 22.6 30.5480 99.8 13.4 28.2 108.1 16.0 28.5 117.8 18.7 28.8 128.0 21.1 29.1 131.9 21.6 29.2 137.0 22.2 29.4200 99.8 18.2 37.9 108.1 21.2 38.5 117.8 24.7 39.3 128.0 27.8 40.1 131.9 28.4 40.4 137.0 29.1 40.8384 99.8 16.7 34.1 108.1 19.8 34.4 117.8 23.1 34.8 128.0 26.0 35.3 131.9 26.6 35.4 137.0 27.3 35.6480 99.8 16.2 33.3 108.1 19.4 33.6 117.8 22.6 33.9 128.0 25.5 34.2 131.9 26.1 34.3 137.0 26.8 34.5200 91.4 18.6 42.4 99.0 21.7 43.0 107.8 25.3 43.7 117.1 28.5 44.5 120.7 29.2 44.8 125.3 29.9 45.2384 91.4 17.1 38.9 99.0 20.3 39.2 107.8 23.6 39.6 117.1 26.6 40.0 120.7 27.3 40.1 125.3 28.0 40.3480 91.4 16.6 38.1 99.0 19.9 38.3 107.8 23.2 38.6 117.1 26.1 39.0 120.7 26.8 39.1 125.3 27.5 39.2200 82.9 20.0 47.0 89.8 23.4 47.5 97.8 27.2 48.2 106.3 30.6 48.9 109.5 31.4 49.2 113.7 32.1 49.6384 82.9 18.4 43.6 89.8 21.8 43.9 97.8 25.4 44.3 106.3 28.7 44.7 109.5 29.4 44.8 113.7 30.1 45.0480 82.9 17.9 42.9 89.8 21.4 43.1 97.8 24.9 43.4 106.3 28.1 43.7 109.5 28.8 43.8 113.7 29.5 44.0

149.6 17.1 26.1149.6 16.1 20.8149.6 15.7 19.6147.4 20.8 31.1147.4 19.5 25.8147.4 19.1 24.6147.4 25.6 36.3147.4 24.1 30.9147.4 23.5 29.7147.4 30.7 41.6147.4 28.9 36.1147.4 28.2 34.9132.7 31.1 45.8132.7 29.2 40.6132.7 28.5 39.5117.9 32.8 49.9117.9 30.8 45.2117.9 30.1 44.1142.3 16.4 25.5142.3 15.4 20.5142.3 15.0 19.4140.8 20.0 30.6140.8 18.7 25.5140.8 18.3 24.4140.8 24.5 35.8140.8 23.0 30.6140.8 22.5 29.5140.8 29.7 41.1140.8 27.8 35.8140.8 27.2 34.6128.9 30.4 45.5128.9 28.5 40.4128.9 27.9 39.4116.9 32.7 49.8116.9 30.7 45.1116.9 30.0 44.1

120

130

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 39: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units2727

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

200 95.7 9.57 22.1 103.6 11.2 22.7 112.8 13.0 23.3 122.7 14.6 24.1 126.3 15.0 24.3 131.2 15.4 24.7384 95.7 8.80 18.7 103.6 10.4 19.0 112.8 12.2 19.3 122.7 13.7 19.7 126.3 14.0 19.9 131.2 14.4 20.1480 95.7 8.56 17.9 103.6 10.2 18.2 112.8 11.9 18.5 122.7 13.4 18.8 126.3 13.8 18.9 131.2 14.1 19.0200 95.2 11.7 27.2 103.1 13.7 27.8 112.2 15.9 28.5 122.0 17.9 29.2 125.7 18.4 29.5 130.5 18.8 29.8384 95.2 10.8 23.7 103.1 12.8 24.0 112.2 14.9 24.4 122.0 16.8 24.8 125.7 17.2 24.9 130.5 17.6 25.1480 95.2 10.5 23.0 103.1 12.5 23.2 112.2 14.6 23.5 122.0 16.5 23.8 125.7 16.9 23.9 130.5 17.3 24.1200 95.2 14.4 32.3 103.1 16.8 32.9 112.2 19.5 28.5 122.0 22.0 34.4 125.7 22.5 34.7 130.5 23.1 35.0384 95.2 13.2 28.8 103.1 15.7 29.1 112.2 18.2 29.5 122.0 20.5 29.9 125.7 21.0 30.0 130.5 21.6 30.2480 95.2 12.8 28.0 103.1 15.3 28.3 112.2 17.9 28.6 122.0 20.1 28.9 125.7 20.7 29.0 130.5 21.2 29.2200 95.2 17.5 37.5 103.1 20.4 38.1 112.2 23.8 38.9 122.0 26.8 39.6 125.7 27.4 39.9 130.5 28.1 40.3384 95.2 16.1 33.9 103.1 19.1 34.2 112.2 22.2 34.6 122.0 25.1 35.0 125.7 25.7 35.2 130.5 26.3 35.4480 95.2 15.7 33.1 103.1 18.7 33.4 112.2 21.8 33.7 122.0 24.6 34.0 125.7 25.2 34.1 130.5 25.8 34.3200 88.7 18.2 42.2 96.0 21.2 42.8 104.6 24.7 43.5 113.7 27.9 44.2 117.1 28.5 44.5 121.6 29.2 44.9384 88.7 16.7 38.7 96.0 19.9 39.1 104.6 23.1 39.4 113.7 26.0 39.8 117.1 26.7 39.9 121.6 27.4 40.1480 88.7 16.3 38.0 96.0 19.4 38.2 104.6 22.7 38.5 113.7 25.5 38.8 117.1 26.2 39.0 121.6 26.8 39.1200 82.2 20.0 46.9 89.0 23.3 47.5 96.9 27.2 48.1 105.3 30.6 48.9 108.5 31.3 49.1 112.7 32.1 49.5384 82.2 18.4 43.6 89.0 21.8 43.9 96.9 25.4 44.2 105.3 28.6 44.6 108.5 29.3 44.7 112.7 30.1 44.9480 82.2 17.9 42.9 89.0 21.3 43.1 96.9 24.9 43.4 105.3 28.0 43.7 108.5 28.8 43.8 112.7 29.5 43.9200 90.5 9.12 21.7 98.0 10.6 22.2 106.7 12.4 22.9 116.0 13.9 23.6 119.5 14.3 23.8 124.1 14.6 24.2384 90.5 8.38 18.5 98.0 9.94 18.8 106.7 11.6 19.1 116.0 13.0 19.5 119.5 13.4 19.6 124.1 13.7 19.8480 90.5 8.15 17.8 98.0 9.73 18.0 106.7 11.3 18.3 116.0 12.8 18.6 119.5 13.1 18.7 124.1 13.4 18.8200 90.5 11.2 26.8 98.0 13.1 27.4 106.7 15.3 28.0 116.0 17.2 28.7 119.5 17.6 29.0 124.1 18.0 29.4384 90.5 10.3 23.6 98.0 12.3 23.8 106.7 14.3 24.2 116.0 16.1 24.6 119.5 16.5 24.7 124.1 16.9 24.9480 90.5 10.1 22.8 98.0 12.0 23.1 106.7 14.0 23.4 116.0 15.8 23.6 119.5 16.2 23.8 124.1 16.6 23.9200 90.5 13.7 32.0 98.0 16.0 32.5 106.7 18.6 28.0 116.0 21.0 33.9 119.5 21.5 34.2 124.1 22.0 34.5384 90.5 12.6 28.6 98.0 15.0 28.9 106.7 17.4 29.3 116.0 19.6 29.6 119.5 20.1 29.8 124.1 20.6 30.0480 90.5 12.3 27.9 98.0 14.6 28.1 106.7 17.1 28.4 116.0 19.2 28.7 119.5 19.7 28.8 124.1 20.2 29.0200 90.5 16.9 37.1 98.0 19.7 37.7 106.7 22.9 38.4 116.0 25.8 39.2 119.5 26.4 39.4 124.1 27.1 39.8384 90.5 15.5 33.7 98.0 18.4 34.0 106.7 21.4 34.4 116.0 24.1 34.8 119.5 24.7 34.9 124.1 25.3 35.1480 90.5 15.1 33.0 98.0 18.0 33.2 106.7 21.0 33.5 116.0 23.7 33.8 119.5 24.2 33.9 124.1 24.9 34.1200 86.0 17.8 42.0 93.1 20.8 42.6 101.4 24.2 43.2 110.2 27.2 43.9 113.5 27.9 44.2 117.9 28.6 44.6384 86.0 16.4 38.6 93.1 19.4 38.9 101.4 22.6 39.3 110.2 25.5 39.7 113.5 26.1 39.8 117.9 26.7 40.0480 86.0 15.9 37.9 93.1 19.0 38.1 101.4 22.1 38.4 110.2 25.0 38.7 113.5 25.6 38.8 117.9 26.2 39.0200 81.4 20.0 46.8 88.2 23.3 47.4 96.0 27.1 48.1 104.4 30.6 48.8 107.5 31.3 49.0 111.7 32.1 49.4384 81.4 18.4 43.6 88.2 21.8 43.9 96.0 25.4 44.2 104.4 28.6 44.6 107.5 29.2 44.7 111.7 30.0 44.9480 81.4 17.9 42.9 88.2 21.3 43.1 96.0 24.8 43.4 104.4 28.0 43.7 107.5 28.7 43.8 111.7 29.4 43.9

134.9 15.6 25.0134.9 14.7 20.2134.9 14.3 19.2134.2 19.2 30.1134.2 18.0 25.3134.2 17.5 24.2134.2 23.5 35.3134.2 22.0 30.4134.2 21.4 29.3134.2 28.6 40.6134.2 26.8 35.5134.2 26.1 34.4125.0 29.7 45.1125.0 27.9 40.3125.0 27.2 39.2115.9 32.7 49.7115.9 30.6 45.1115.9 29.9 44.1127.6 14.9 24.4127.6 13.9 19.9127.6 13.6 18.9127.6 18.4 29.6127.6 17.2 25.0127.6 16.7 24.0127.6 22.4 34.8127.6 21.0 30.1127.6 20.4 29.1127.6 27.6 40.1127.6 25.8 35.2127.6 25.1 34.2121.2 29.1 44.8121.2 27.2 40.1121.2 26.5 39.1114.8 32.6 49.6114.8 30.5 45.0114.8 29.7 44.0

110

100

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 40: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 2828

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Cooling Capacity

200 81.4 7.85 21.0 88.2 9.15 21.5 96.0 10.7 22.1 104.4 12.0 22.7 107.5 12.3 23.0 111.7 12.6 23.3384 81.4 7.22 18.1 88.2 8.56 18.4 96.0 9.97 18.7 104.4 11.2 19.0 107.5 11.5 19.1 111.7 11.8 19.3480 81.4 7.02 17.5 88.2 8.37 17.7 96.0 9.76 18.0 104.4 11.0 18.2 107.5 11.3 18.3 111.7 11.6 18.4200 81.4 9.68 26.1 88.2 11.3 26.6 96.0 13.1 27.2 104.4 14.8 27.9 107.5 15.2 28.1 111.7 15.5 28.4384 81.4 8.90 23.2 88.2 10.6 23.5 96.0 12.3 23.8 104.4 13.8 24.1 107.5 14.2 24.2 111.7 14.5 24.4480 81.4 8.65 22.6 88.2 10.3 22.8 96.0 12.0 23.0 104.4 13.6 23.3 107.5 13.9 23.4 111.7 14.3 23.5200 81.4 11.8 31.3 88.2 13.8 31.8 96.0 16.0 29.8 104.4 18.1 33.0 107.5 18.5 33.3 111.7 18.9 33.6384 81.4 10.9 28.3 88.2 12.9 28.5 96.0 15.0 28.8 104.4 16.9 29.2 107.5 17.3 29.3 111.7 17.7 29.5480 81.4 10.6 27.6 88.2 12.6 27.8 96.0 14.7 28.1 104.4 16.6 28.3 107.5 17.0 28.4 111.7 17.4 28.6200 81.4 14.5 36.4 88.2 16.9 37.0 96.0 19.7 37.6 104.4 22.2 38.2 107.5 22.7 38.5 111.7 23.3 38.8384 81.4 13.3 33.4 88.2 15.8 33.6 96.0 18.4 34.0 104.4 20.8 34.3 107.5 21.3 34.4 111.7 21.8 34.6480 81.4 13.0 32.7 88.2 15.5 32.9 96.0 18.1 33.2 104.4 20.4 33.4 107.5 20.9 33.5 111.7 21.4 33.7200 79.2 15.7 41.4 85.7 18.3 42.0 93.4 21.3 42.6 101.5 24.0 43.2 104.5 24.5 43.5 108.6 25.1 43.8384 79.2 14.4 38.3 85.7 17.1 38.6 93.4 19.9 38.9 101.5 22.4 39.3 104.5 22.9 39.4 108.6 23.5 39.6480 79.2 14.0 37.7 85.7 16.7 37.9 93.4 19.5 38.2 101.5 22.0 38.4 104.5 22.5 38.5 108.6 23.1 38.7200 76.9 18.0 46.5 83.3 21.0 47.0 90.7 24.4 47.6 98.6 27.5 48.3 101.6 28.2 48.5 105.5 28.9 48.9384 76.9 16.5 43.4 83.3 19.6 43.6 90.7 22.9 44.0 98.6 25.7 44.3 101.6 26.4 44.4 105.5 27.0 44.6480 76.9 16.1 42.7 83.3 19.2 42.9 90.7 22.4 43.2 98.6 25.2 43.5 101.6 25.9 43.6 105.5 26.5 43.7200 72.4 6.58 20.4 78.4 7.67 20.8 85.4 8.94 21.3 92.8 10.1 21.9 95.6 10.3 22.1 99.3 10.6 22.3384 72.4 6.05 17.8 78.4 7.17 18.0 85.4 8.36 18.3 92.8 9.41 18.6 95.6 9.63 18.7 99.3 9.88 18.8480 72.4 5.88 17.2 78.4 7.02 17.4 85.4 8.18 17.6 92.8 9.22 17.9 95.6 9.45 17.9 99.3 9.70 18.1200 72.4 8.11 25.5 78.4 9.46 25.9 85.4 11.0 26.4 92.8 12.4 27.0 95.6 12.7 27.2 99.3 13.0 27.5384 72.4 7.46 22.8 78.4 8.85 23.1 85.4 10.3 23.4 92.8 11.6 23.6 95.6 11.9 23.8 99.3 12.2 23.9480 72.4 7.25 22.3 78.4 8.66 22.5 85.4 10.1 22.7 92.8 11.4 22.9 95.6 11.7 23.0 99.3 12.0 23.1200 72.4 9.89 30.6 78.4 11.5 31.0 85.4 13.4 31.6 92.8 15.1 32.1 95.6 15.5 32.3 99.3 15.9 32.6384 72.4 9.10 27.9 78.4 10.8 28.1 85.4 12.6 28.4 92.8 14.2 28.7 95.6 14.5 28.8 99.3 14.9 29.0480 72.4 8.85 27.3 78.4 10.6 27.5 85.4 12.3 27.7 92.8 13.9 28.0 95.6 14.2 28.1 99.3 14.6 28.2200 72.4 12.2 35.7 78.4 14.2 36.2 85.4 16.5 36.7 92.8 18.6 37.3 95.6 19.1 37.6 99.3 19.5 37.8384 72.4 11.2 33.0 78.4 13.3 33.2 85.4 15.5 33.5 92.8 17.4 33.8 95.6 17.8 33.9 99.3 18.3 34.1480 72.4 10.9 32.4 78.4 13.0 32.6 85.4 15.1 32.8 92.8 17.1 33.1 95.6 17.5 33.1 99.3 17.9 33.3200 72.4 13.5 40.9 78.4 15.8 41.4 85.4 18.4 41.9 92.8 20.7 42.5 95.6 21.2 42.8 99.3 21.7 43.1384 72.4 12.4 38.1 78.4 14.7 38.3 85.4 17.2 38.6 92.8 19.3 38.9 95.6 19.8 39.0 99.3 20.3 39.2480 72.4 12.1 37.4 78.4 14.4 37.7 85.4 16.8 37.9 92.8 19.0 38.1 95.6 19.4 38.2 99.3 19.9 38.4200 72.4 16.0 46.1 78.4 18.7 46.6 85.4 21.8 47.2 92.8 24.5 47.8 95.6 25.1 48.0 99.3 25.7 48.3384 72.4 14.7 43.2 78.4 17.5 43.4 85.4 20.3 43.7 92.8 22.9 44.1 95.6 23.5 44.2 99.3 24.1 44.3480 72.4 14.3 42.5 78.4 17.1 42.7 85.4 19.9 43.0 92.8 22.5 43.2 95.6 23.0 43.3 99.3 23.6 43.5

114.8 12.8 23.5114.8 12.0 19.4114.8 11.7 18.5114.8 15.8 28.7114.8 14.8 24.5114.8 14.4 23.6114.8 19.3 33.8114.8 18.0 29.6114.8 17.6 28.7114.8 23.7 39.1114.8 22.2 34.7114.8 21.6 33.8111.7 25.6 44.1111.7 23.9 39.7111.7 23.3 38.8108.5 29.4 49.1108.5 27.5 44.7108.5 26.8 43.8102.1 10.7 22.6102.1 10.1 18.9102.1 9.79 18.1102.1 13.3 27.7102.1 12.4 24.0102.1 12.1 23.2102.1 16.2 32.8102.1 15.1 29.1102.1 14.7 28.3102.1 19.9 38.1102.1 18.6 34.2102.1 18.1 33.4102.1 22.1 43.3102.1 20.7 39.3102.1 20.1 38.5102.1 26.2 48.6102.1 24.5 44.5102.1 23.8 43.6

90

80

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 41: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units2929

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

200 63.3 5.47 19.7 68.6 6.38 20.1 74.7 7.43 20.5 81.2 8.37 21.0 83.6 8.57 21.2 86.9 8.78 21.4384 63.3 5.03 17.4 68.6 5.96 17.6 74.7 6.95 17.9 81.2 7.82 18.1 83.6 8.01 18.2 86.9 8.21 18.3480 63.3 4.89 17.0 68.6 5.84 17.1 74.7 6.80 17.3 81.2 7.67 17.5 83.6 7.86 17.6 86.9 8.06 17.7200 63.3 6.74 24.8 68.6 7.87 25.2 74.7 9.16 25.6 81.2 10.3 26.1 83.6 10.6 26.3 86.9 10.8 26.6384 63.3 6.20 22.5 68.6 7.36 22.7 74.7 8.57 22.9 81.2 9.65 23.2 83.6 9.88 23.3 86.9 10.1 23.4480 63.3 6.03 22.0 68.6 7.20 22.2 74.7 8.39 22.3 81.2 9.46 22.6 83.6 9.69 22.6 86.9 9.94 22.7200 63.3 8.22 29.9 68.6 9.59 30.3 74.7 11.2 30.7 81.2 12.6 31.2 83.6 12.9 31.4 86.9 13.2 31.7384 63.3 7.56 27.5 68.6 8.97 27.7 74.7 10.4 28.0 81.2 11.8 28.2 83.6 12.0 28.3 86.9 12.4 28.5480 63.3 7.36 27.0 68.6 8.78 27.2 74.7 10.2 27.4 81.2 11.5 27.6 83.6 11.8 27.7 86.9 12.1 27.8200 63.3 10.1 35.0 68.6 11.8 35.4 74.7 13.7 35.9 81.2 15.5 36.4 83.6 15.8 36.6 86.9 16.2 36.9384 63.3 9.30 32.6 68.6 11.0 32.8 74.7 12.9 33.1 81.2 14.5 33.3 83.6 14.8 33.4 86.9 15.2 33.6480 63.3 9.05 32.1 68.6 10.8 32.3 74.7 12.6 32.5 81.2 14.2 32.7 83.6 14.5 32.8 86.9 14.9 32.9200 63.3 11.2 40.1 68.6 13.1 40.6 74.7 15.3 41.1 81.2 17.2 41.6 83.6 17.6 41.8 86.9 18.0 42.1384 63.3 10.3 37.7 68.6 12.3 37.9 74.7 14.3 38.2 81.2 16.1 38.4 83.6 16.5 38.5 86.9 16.9 38.7480 63.3 10.1 37.1 68.6 12.0 37.3 74.7 14.0 37.5 81.2 15.8 37.7 83.6 16.2 37.8 86.9 16.6 37.9200 63.3 13.3 45.3 68.6 15.5 45.8 74.7 18.1 46.3 81.2 20.4 46.8 83.6 20.9 47.0 86.9 21.4 47.3384 63.3 12.2 42.8 68.6 14.5 43.0 74.7 16.9 43.3 81.2 19.0 43.6 83.6 19.5 43.7 86.9 20.0 43.8480 63.3 11.9 42.2 68.6 14.2 42.4 74.7 16.6 42.6 81.2 18.7 42.8 83.6 19.1 42.9 86.9 19.6 43.0200 54.3 4.36 19.0 58.8 5.08 19.3 64.0 5.92 19.7 69.6 6.67 20.1 71.7 6.83 20.3 74.5 7.00 20.5384 54.3 4.01 17.1 58.8 4.75 17.3 64.0 5.54 17.5 69.6 6.24 17.7 71.7 6.39 17.8 74.5 6.55 17.9480 54.3 3.90 16.7 58.8 4.65 16.8 64.0 5.42 17.0 69.6 6.11 17.1 71.7 6.27 17.2 74.5 6.43 17.3200 54.3 5.38 24.1 58.8 6.27 24.4 64.0 7.31 24.8 69.6 8.23 25.2 71.7 8.42 25.4 74.5 8.63 25.6384 54.3 4.94 22.1 58.8 5.86 22.3 64.0 6.83 22.5 69.6 7.69 22.7 71.7 7.88 22.8 74.5 8.08 22.9480 54.3 4.81 21.7 58.8 5.74 21.8 64.0 6.69 22.0 69.6 7.54 22.2 71.7 7.73 22.3 74.5 7.93 22.3200 54.3 6.56 29.2 58.8 7.65 29.5 64.0 8.91 29.9 69.6 10.0 30.3 71.7 10.3 30.5 74.5 10.5 30.7384 54.3 6.03 27.2 58.8 7.15 27.4 64.0 8.33 27.6 69.6 9.38 27.8 71.7 9.60 27.9 74.5 9.85 28.0480 54.3 5.86 26.7 58.8 7.00 26.9 64.0 8.16 27.1 69.6 9.20 27.2 71.7 9.42 27.3 74.5 9.67 27.4200 54.3 8.06 34.3 58.8 9.41 34.6 64.0 11.0 35.1 69.6 12.3 35.5 71.7 12.6 35.7 74.5 12.9 35.9384 54.3 7.42 32.2 58.8 8.80 32.4 64.0 10.2 32.6 69.6 11.5 32.9 71.7 11.8 32.9 74.5 12.1 33.1480 54.3 7.21 31.8 58.8 8.61 31.9 64.0 10.0 32.1 69.6 11.3 32.3 71.7 11.6 32.4 74.5 11.9 32.5200 54.3 8.96 39.4 58.8 10.5 39.8 64.0 12.2 40.2 69.6 13.7 40.6 71.7 14.0 40.8 74.5 14.4 41.0384 54.3 8.24 37.3 58.8 9.77 37.5 64.0 11.4 37.7 69.6 12.8 37.9 71.7 13.1 38.0 74.5 13.5 38.1480 54.3 8.01 36.8 58.8 9.56 37.0 64.0 11.1 37.2 69.6 12.6 37.4 71.7 12.9 37.4 74.5 13.2 37.5200 54.3 10.6 44.6 58.8 12.4 44.9 64.0 14.4 45.4 69.6 16.2 45.8 71.7 16.6 46.0 74.5 17.0 46.3384 54.3 9.76 42.4 58.8 11.6 42.6 64.0 13.5 42.8 69.6 15.2 43.0 71.7 15.5 43.1 74.5 15.9 43.3480 54.3 9.49 41.9 58.8 11.3 42.1 64.0 13.2 42.2 69.6 14.9 42.4 71.7 15.3 42.5 74.5 15.6 42.6

89.3 8.94 21.689.3 8.36 18.489.3 8.14 17.889.3 11.0 26.789.3 10.3 23.589.3 10.0 22.889.3 13.4 31.989.3 12.6 28.689.3 12.2 27.989.3 16.5 37.189.3 15.5 33.789.3 15.1 32.989.3 18.4 42.289.3 17.2 38.889.3 16.7 38.089.3 21.8 47.589.3 20.4 43.989.3 19.8 43.176.6 7.12 20.776.6 6.67 17.976.6 6.49 17.476.6 8.79 25.876.6 8.22 23.076.6 8.01 22.476.6 10.7 30.976.6 10.0 28.176.6 9.76 27.576.6 13.2 36.076.6 12.3 33.176.6 12.0 32.576.6 14.6 41.276.6 13.7 38.276.6 13.3 37.676.6 17.3 46.476.6 16.2 43.476.6 15.8 42.7

70

60

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 42: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 3030

Cooling Capacity

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CWB)

14 16 18 19 20 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

200 45.2 3.25 18.3 49.0 3.79 18.6 53.4 4.42 18.9 58.0 4.97 19.3 59.7 5.09 19.4 62.1 5.22 19.6384 45.2 2.99 16.7 49.0 3.54 16.9 53.4 4.13 17.1 58.0 4.65 17.2 59.7 4.76 17.3 62.1 4.88 17.4480 45.2 2.91 16.4 49.0 3.47 16.5 53.4 4.04 16.6 58.0 4.56 16.8 59.7 4.67 16.8 62.1 4.79 16.9200 45.2 4.01 23.4 49.0 4.68 23.7 53.4 5.45 24.0 58.0 6.13 24.4 59.7 6.28 24.5 62.1 6.43 24.7384 45.2 3.69 21.8 49.0 4.37 21.9 53.4 5.09 22.1 58.0 5.73 22.3 59.7 5.87 22.3 62.1 6.02 22.4480 45.2 3.59 21.4 49.0 4.28 21.5 53.4 4.99 21.7 58.0 5.62 21.8 59.7 5.76 21.9 62.1 5.91 21.9200 45.2 4.89 28.5 49.0 5.70 28.8 53.4 6.64 29.1 58.0 7.48 29.5 59.7 7.66 29.6 62.1 7.85 29.8384 45.2 4.50 26.8 49.0 5.33 27.0 53.4 6.21 27.1 58.0 6.99 27.3 59.7 7.16 27.4 62.1 7.34 27.5480 45.2 4.37 26.4 49.0 5.22 26.6 53.4 6.08 26.7 58.0 6.86 26.9 59.7 7.03 26.9 62.1 7.21 27.0200 45.2 6.01 33.6 49.0 7.01 33.9 53.4 8.17 34.2 58.0 9.20 34.6 59.7 9.42 34.7 62.1 9.65 34.9384 45.2 5.53 31.9 49.0 6.56 32.0 53.4 7.64 32.2 58.0 8.60 32.4 59.7 8.81 32.5 62.1 9.03 32.6480 45.2 5.38 31.5 49.0 6.42 31.6 53.4 7.48 31.8 58.0 8.43 31.9 59.7 8.64 32.0 62.1 8.86 32.0200 45.2 6.68 38.7 49.0 7.79 39.0 53.4 9.08 39.3 58.0 10.2 39.7 59.7 10.5 39.8 62.1 10.7 40.0384 45.2 6.14 36.9 49.0 7.29 37.1 53.4 8.49 37.3 58.0 9.56 37.5 59.7 9.79 37.5 62.1 10.0 37.6480 45.2 5.98 36.5 49.0 7.13 36.7 53.4 8.31 36.8 58.0 9.37 37.0 59.7 9.60 37.0 62.1 9.85 37.1200 45.2 7.91 43.8 49.0 9.23 44.1 53.4 10.8 44.5 58.0 12.1 44.9 59.7 12.4 45.0 62.1 12.7 45.2384 45.2 7.28 42.0 49.0 8.63 42.1 53.4 10.1 42.3 58.0 11.3 42.5 59.7 11.6 42.6 62.1 11.9 42.7480 45.2 7.08 41.6 49.0 8.44 41.7 53.4 9.85 41.9 58.0 11.1 42.0 59.7 11.4 42.1 62.1 11.7 42.2

63.8 5.31 19.763.8 4.97 17.563.8 4.84 17.063.8 6.55 24.863.8 6.13 22.563.8 5.97 22.063.8 7.99 29.963.8 7.48 27.663.8 7.28 27.063.8 9.83 35.063.8 9.20 32.663.8 8.95 32.163.8 10.9 40.263.8 10.2 37.763.8 9.95 37.263.8 12.9 45.463.8 12.1 42.863.8 11.8 42.2

50

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

Page 43: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units3131

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

7.2 Heating capacity

ARWN100LA2 Heating Capacity

50 38.5 6.76 5.92 38.4 6.99 5.95 38.3 7.26 5.98 37.3 7.17 6.21 36.3 6.86 6.44 34.3 6.22 6.9296 39.8 6.77 9.85 39.6 6.99 9.87 39.5 7.26 9.89 38.5 6.95 10.0 37.4 6.65 10.2 35.4 6.04 10.4

120 40.0 6.80 10.9 40.0 7.07 10.9 40.0 7.30 10.9 38.9 6.99 11.0 37.9 6.68 11.1 35.8 6.67 11.350 40.0 6.17 10.3 39.9 6.32 10.4 39.8 6.48 10.4 38.7 6.46 10.7 37.6 6.45 10.9 35.4 6.34 11.596 41.3 6.26 14.7 41.2 6.44 14.7 41.0 6.61 14.7 39.9 6.56 14.9 38.9 6.56 15.0 36.7 6.47 15.3

120 41.5 6.26 15.7 41.5 6.46 15.7 41.5 6.66 15.7 40.3 6.59 15.8 39.2 6.57 15.9 37.0 6.47 16.150 43.6 6.44 14.1 42.5 6.46 14.4 41.5 6.48 14.6 40.7 6.35 14.8 39.8 6.22 15.0 37.5 5.87 15.696 43.6 6.29 19.2 42.5 6.34 19.3 41.5 6.37 19.5 40.7 6.24 19.6 39.8 6.12 19.7 37.5 5.77 20.0

120 43.6 6.20 20.3 42.5 6.24 20.4 41.5 6.28 20.5 40.7 6.16 20.6 39.8 6.04 20.7 37.5 5.69 21.050 43.6 6.18 18.7 42.5 6.20 19.0 41.5 6.22 19.3 40.7 6.06 19.5 39.8 5.91 19.7 37.5 5.51 20.396 43.6 6.01 24.0 42.5 6.05 24.1 41.5 6.08 24.3 40.7 5.93 24.4 39.8 5.78 24.5 37.5 5.39 24.8

120 43.6 5.93 25.2 42.5 5.96 25.3 41.5 6.00 25.4 40.7 5.86 25.5 39.8 5.71 25.6 37.5 5.32 25.850 43.6 5.96 23.5 42.5 5.98 23.8 41.5 6.00 24.0 40.7 5.79 24.3 39.8 5.59 24.5 37.5 5.12 25.196 43.6 5.75 28.8 42.5 5.78 29.0 41.5 5.82 29.1 40.7 5.62 29.2 39.8 5.42 29.3 37.5 4.96 29.7

120 43.6 5.67 30.0 42.5 5.71 30.2 41.5 5.75 30.3 40.7 5.55 30.4 39.8 5.36 30.5 37.5 4.90 30.750 43.6 5.76 28.2 42.5 5.78 28.5 41.5 5.80 28.8 40.7 5.57 29.0 39.8 5.35 29.2 37.5 4.85 29.996 43.6 5.51 33.7 42.5 5.54 33.8 41.5 5.58 34.0 40.7 5.36 34.1 39.8 5.15 34.2 37.5 4.67 34.6

120 43.6 5.44 34.9 42.5 5.48 35.1 41.5 5.52 35.2 40.7 5.30 35.3 39.8 5.09 35.4 37.5 4.62 35.650 36.6 6.79 6.38 36.5 7.01 6.40 36.4 7.28 6.42 35.5 7.14 6.64 34.4 6.81 6.91 32.5 6.21 7.3496 37.5 6.75 10.1 37.4 6.99 10.2 37.2 7.26 10.2 36.3 6.96 10.3 35.1 6.61 10.5 33.2 6.04 10.7

120 37.7 6.76 11.1 37.7 7.03 11.1 37.5 7.26 11.1 36.6 6.96 11.2 35.4 6.61 11.3 33.5 6.43 11.550 37.7 6.00 10.8 37.6 6.20 10.9 37.4 6.39 11.0 36.4 6.31 11.2 35.2 6.20 11.5 33.3 6.00 12.096 38.7 6.07 15.0 38.5 6.26 15.1 38.2 6.46 15.1 37.3 6.35 15.2 36.1 6.23 15.4 34.1 6.02 15.6

120 38.9 6.06 15.9 38.8 6.26 16.0 38.5 6.47 16.0 37.5 6.34 16.1 36.3 6.21 16.2 34.3 6.00 16.450 41.0 6.12 14.8 39.8 6.10 15.0 38.5 6.05 15.4 37.7 5.90 15.6 36.7 5.72 15.8 34.7 5.36 16.396 41.1 6.02 19.5 39.8 5.99 19.7 38.5 5.95 19.9 37.7 5.81 20.0 36.7 5.63 20.1 34.7 5.28 20.4

120 41.2 5.95 20.6 39.8 5.91 20.7 38.5 5.87 20.8 37.7 5.73 20.9 36.7 5.56 21.0 34.7 5.21 21.350 41.2 5.81 19.4 39.8 5.72 19.7 38.5 5.63 20.0 37.7 5.48 20.2 36.7 5.29 20.5 34.7 4.93 21.096 41.2 5.66 24.3 39.8 5.58 24.5 38.5 5.51 24.7 37.7 5.36 24.8 36.7 5.18 24.9 34.7 4.82 25.2

120 41.2 5.59 25.4 39.8 5.51 25.6 38.5 5.44 25.7 37.7 5.29 25.8 36.7 5.12 25.9 34.7 4.77 26.150 41.2 5.53 24.1 39.8 5.41 24.5 38.5 5.31 24.8 37.7 5.13 25.0 36.7 4.92 25.3 34.7 4.52 25.896 41.2 5.34 29.1 39.8 5.24 29.3 38.5 5.15 29.5 37.7 4.97 29.6 36.7 4.77 29.8 34.7 4.38 30.1

120 41.2 5.27 30.3 39.8 5.18 30.5 38.5 5.09 30.6 37.7 4.92 30.7 36.7 4.72 30.8 34.7 4.34 31.150 41.2 5.30 28.9 39.8 5.19 29.2 38.5 5.04 29.6 37.7 4.85 29.8 36.7 4.64 30.1 34.7 4.23 30.696 41.2 5.05 34.0 39.8 4.98 34.2 38.5 4.84 34.4 37.7 4.66 34.5 36.7 4.46 34.7 34.7 4.07 35.0

120 41.2 5.00 35.2 39.8 4.92 35.4 38.5 4.79 35.5 37.7 4.61 35.6 36.7 4.42 35.7 34.7 4.03 36.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

130

120

Page 44: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 3232

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

50 34.6 6.81 6.84 34.6 7.03 6.85 34.5 7.31 6.87 33.7 7.10 7.06 32.4 6.76 7.37 30.8 6.20 7.7596 35.2 6.73 10.4 35.1 6.98 10.5 34.9 7.26 10.5 34.1 6.97 10.6 32.8 6.58 10.8 31.1 6.03 11.0

120 35.4 6.73 11.3 35.3 7.00 11.3 35.1 7.22 11.4 34.2 6.93 11.5 32.9 6.55 11.6 31.3 6.20 11.850 35.3 5.84 11.3 35.2 6.07 11.5 35.0 6.30 11.6 34.1 6.16 11.8 32.8 5.95 12.1 31.1 5.66 12.596 36.1 5.87 15.3 35.7 6.08 15.4 35.4 6.31 15.4 34.6 6.14 15.6 33.2 5.90 15.7 31.6 5.57 15.9

120 36.3 5.86 16.2 36.0 6.07 16.2 35.6 6.27 16.3 34.7 6.09 16.4 33.4 5.85 16.5 31.7 5.53 16.750 38.3 5.80 15.4 37.1 5.74 15.7 35.6 5.62 16.1 34.8 5.45 16.3 33.6 5.21 16.6 31.8 4.86 17.096 38.6 5.74 19.9 37.1 5.65 20.1 35.6 5.53 20.3 34.8 5.37 20.4 33.6 5.13 20.5 31.8 4.78 20.8

120 38.8 5.69 20.8 37.1 5.57 21.0 35.6 5.46 21.2 34.8 5.30 21.3 33.6 5.07 21.4 31.8 4.73 21.650 38.8 5.44 20.0 37.1 5.24 20.4 35.6 5.05 20.8 34.8 4.90 21.0 33.6 4.67 21.3 31.8 4.34 21.896 38.8 5.31 24.7 37.1 5.12 24.9 35.6 4.94 25.1 34.8 4.79 25.2 33.6 4.57 25.4 31.8 4.25 25.6

120 38.8 5.25 25.7 37.1 5.06 25.9 35.6 4.88 26.0 34.8 4.73 26.1 33.6 4.53 26.3 31.8 4.21 26.550 38.8 5.09 24.7 37.1 4.85 25.2 35.6 4.62 25.6 34.8 4.46 25.8 33.6 4.25 26.1 31.8 3.92 26.696 38.8 4.93 29.5 37.1 4.70 29.7 35.6 4.48 29.9 34.8 4.33 30.1 33.6 4.12 30.2 31.8 3.80 30.5

120 38.8 4.87 30.6 37.1 4.64 30.8 35.6 4.43 31.0 34.8 4.28 31.0 33.6 4.08 31.2 31.8 3.77 31.450 38.8 4.83 29.5 37.1 4.61 30.0 35.6 4.27 30.4 34.8 4.12 30.6 33.6 3.92 30.9 31.8 3.60 31.496 38.8 4.60 34.4 37.1 4.41 34.6 35.6 4.11 34.8 34.8 3.97 34.9 33.6 3.77 35.1 31.8 3.47 35.4

120 38.8 4.55 35.5 37.1 4.36 35.7 35.6 4.07 35.9 34.8 3.93 36.0 33.6 3.74 36.1 31.8 3.44 36.350 32.7 6.84 7.30 32.7 7.05 7.30 32.6 7.33 7.32 31.9 7.07 7.49 30.4 6.71 7.83 29.0 6.18 8.1796 32.9 6.72 10.7 32.8 6.98 10.8 32.6 7.25 10.8 31.9 6.98 10.9 30.4 6.54 11.1 29.0 6.03 11.2

120 33.2 6.70 11.6 33.0 6.96 11.6 32.6 7.18 11.6 31.9 6.91 11.7 30.4 6.48 11.8 29.0 5.97 12.050 33.0 5.67 11.8 32.9 5.95 12.1 32.6 6.22 12.1 31.9 6.02 12.3 30.4 5.70 12.7 29.0 5.33 13.096 33.5 5.67 15.6 33.0 5.91 15.7 32.6 6.17 15.8 31.9 5.93 15.9 30.4 5.56 16.1 29.0 5.13 16.3

120 33.7 5.66 16.4 33.3 5.88 16.5 32.6 6.07 16.6 31.9 5.85 16.7 30.4 5.49 16.8 29.0 5.07 17.050 35.7 5.48 16.1 34.4 5.39 16.4 32.6 5.20 16.9 31.9 5.01 17.0 30.4 4.71 17.4 29.0 4.35 17.896 36.2 5.46 20.2 34.4 5.30 20.4 32.6 5.11 20.7 31.9 4.93 20.8 30.4 4.63 20.9 29.0 4.28 21.1

120 36.4 5.43 21.1 34.4 5.23 21.3 32.6 5.04 21.5 31.9 4.87 21.6 30.4 4.59 21.7 29.0 4.25 21.950 36.4 5.07 20.6 34.4 4.76 21.1 32.6 4.46 21.6 31.9 4.31 21.8 30.4 4.06 22.1 29.0 3.76 22.596 36.4 4.96 25.0 34.4 4.66 25.3 32.6 4.37 25.5 31.9 4.22 25.6 30.4 3.97 25.8 29.0 3.67 26.0

120 36.4 4.91 25.9 34.4 4.60 26.2 32.6 4.31 26.4 31.9 4.17 26.5 30.4 3.94 26.6 29.0 3.65 26.850 36.4 4.66 25.4 34.4 4.28 25.9 32.6 3.93 26.4 31.9 3.80 26.6 30.4 3.58 27.0 29.0 3.32 27.396 36.4 4.52 29.8 34.4 4.15 30.1 32.6 3.81 30.4 31.9 3.68 30.5 30.4 3.47 30.7 29.0 3.22 30.9

120 36.4 4.47 30.9 34.4 4.11 31.1 32.6 3.77 31.3 31.9 3.65 31.4 30.4 3.45 31.5 29.0 3.20 31.750 36.4 4.36 30.2 34.4 4.02 30.7 32.6 3.51 31.2 31.9 3.40 31.4 30.4 3.21 31.8 29.0 2.98 32.296 36.4 4.15 34.7 34.4 3.84 35.0 32.6 3.38 35.3 31.9 3.27 35.4 30.4 3.08 35.6 29.0 2.87 35.8

120 36.4 4.11 35.8 34.4 3.80 36.0 32.6 3.34 36.2 31.9 3.24 36.3 30.4 3.06 36.5 29.0 2.86 36.6

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

110

100

Page 45: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units3333

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

50 30.9 6.26 7.72 30.1 6.22 7.91 29.3 6.25 8.09 28.7 6.03 8.24 27.4 5.72 8.55 26.1 5.29 8.8596 31.0 6.11 11.0 30.2 6.12 11.1 29.3 6.16 11.2 28.7 5.93 11.3 27.4 5.57 11.5 26.1 5.15 11.6120 31.2 6.08 11.8 30.3 6.09 11.9 29.3 6.10 12.0 28.7 5.87 12.0 27.4 5.52 12.2 26.1 5.10 12.350 31.1 5.22 12.4 30.2 5.28 12.7 29.3 5.34 12.9 28.7 5.17 13.1 27.4 4.89 13.4 26.1 4.58 13.796 31.3 5.17 15.9 30.3 5.21 16.1 29.3 5.27 16.2 28.7 5.08 16.3 27.4 4.78 16.5 26.1 4.42 16.6120 31.4 5.14 16.7 30.4 5.17 16.8 29.3 5.20 16.9 28.7 5.01 17.0 27.4 4.72 17.1 26.1 4.37 17.350 32.4 4.86 16.9 31.0 4.71 17.3 29.3 4.52 17.7 28.7 4.36 17.8 27.4 4.11 18.2 26.1 3.82 18.596 32.7 4.80 20.7 31.0 4.62 20.9 29.3 4.43 21.1 28.7 4.28 21.2 27.4 4.03 21.4 26.1 3.75 21.5120 32.8 4.77 21.5 31.0 4.57 21.7 29.3 4.38 21.8 28.7 4.24 21.9 27.4 4.00 22.0 26.1 3.72 22.250 32.8 4.45 21.5 31.0 4.18 22.0 29.3 3.92 22.4 28.7 3.79 22.6 27.4 3.58 22.9 26.1 3.33 23.396 32.8 4.34 25.5 31.0 4.08 25.7 29.3 3.83 26.0 28.7 3.70 26.1 27.4 3.49 26.2 26.1 3.25 26.4120 32.8 4.30 26.3 31.0 4.03 26.6 29.3 3.78 26.7 28.7 3.67 26.8 27.4 3.47 27.0 26.1 3.23 27.150 32.8 4.07 26.3 31.0 3.76 26.8 29.3 3.47 27.2 28.7 3.36 27.4 27.4 3.18 27.8 26.1 2.96 28.196 32.8 3.95 30.3 31.0 3.65 30.6 29.3 3.37 30.8 28.7 3.26 30.9 27.4 3.08 31.1 26.1 2.87 31.3120 32.8 3.92 31.3 31.0 3.61 31.5 29.3 3.33 31.7 28.7 3.23 31.7 27.4 3.06 31.9 26.1 2.86 32.050 32.8 3.80 31.1 31.0 3.52 31.6 29.3 3.12 32.1 28.7 3.03 32.3 27.4 2.86 32.6 26.1 2.67 33.096 32.8 3.63 35.2 31.0 3.37 35.5 29.3 3.00 35.7 28.7 2.91 35.8 27.4 2.75 36.0 26.1 2.57 36.2120 32.8 3.60 36.2 31.0 3.34 36.4 29.3 2.98 36.6 28.7 2.89 36.7 27.4 2.74 36.8 26.1 2.57 37.050 29.2 5.68 8.13 27.5 5.40 8.52 26.1 5.18 8.86 25.5 4.99 8.99 24.4 4.72 9.26 23.2 4.39 9.5496 29.2 5.50 11.2 27.5 5.27 11.4 26.1 5.06 11.6 25.5 4.88 11.7 24.4 4.60 11.8 23.2 4.27 12.0120 29.2 5.45 12.0 27.5 5.22 12.2 26.1 5.02 12.3 25.5 4.84 12.4 24.4 4.56 12.5 23.2 4.23 12.650 29.2 4.77 13.0 27.5 4.61 13.4 26.1 4.47 13.7 25.5 4.32 13.8 24.4 4.09 14.1 23.2 3.84 14.496 29.2 4.66 16.2 27.5 4.51 16.5 26.1 4.37 16.6 25.5 4.23 16.7 24.4 3.99 16.9 23.2 3.71 17.0120 29.2 4.62 17.0 27.5 4.46 17.1 26.1 4.32 17.3 25.5 4.18 17.3 24.4 3.95 17.5 23.2 3.68 17.650 29.2 4.24 17.7 27.5 4.03 18.1 26.1 3.84 18.5 25.5 3.72 18.6 24.4 3.51 18.9 23.2 3.28 19.296 29.2 4.14 21.1 27.5 3.94 21.3 26.1 3.75 21.5 25.5 3.63 21.6 24.4 3.44 21.8 23.2 3.21 21.9120 29.2 4.10 21.9 27.5 3.90 22.0 26.1 3.71 22.2 25.5 3.60 22.3 24.4 3.41 22.4 23.2 3.19 22.550 29.2 3.83 22.5 27.5 3.59 22.9 26.1 3.37 23.3 25.5 3.27 23.4 24.4 3.09 23.7 23.2 2.90 24.096 29.2 3.73 26.0 27.5 3.50 26.2 26.1 3.28 26.4 25.5 3.19 26.5 24.4 3.02 26.6 23.2 2.83 26.8120 29.2 3.70 26.8 27.5 3.47 26.9 26.1 3.25 27.1 25.5 3.16 27.2 24.4 3.00 27.3 23.2 2.81 27.450 29.2 3.49 27.3 27.5 3.24 27.7 26.1 3.01 28.1 25.5 2.93 28.3 24.4 2.77 28.6 23.2 2.60 28.996 29.2 3.39 30.9 27.5 3.15 31.1 26.1 2.92 31.3 25.5 2.84 31.4 24.4 2.69 31.5 23.2 2.52 31.7120 29.2 3.36 31.7 27.5 3.12 31.9 26.1 2.89 32.0 25.5 2.82 32.1 24.4 2.68 32.2 23.2 2.52 32.450 29.2 3.24 32.1 27.5 3.01 32.6 26.1 2.72 33.0 25.5 2.65 33.1 24.4 2.51 33.4 23.2 2.36 33.796 29.2 3.11 35.8 27.5 2.90 36.0 26.1 2.63 36.2 25.5 2.56 36.3 24.4 2.43 36.5 23.2 2.28 36.6120 29.2 3.08 36.6 27.5 2.88 36.8 26.1 2.61 37.0 25.5 2.54 37.0 24.4 2.42 37.2 23.2 2.28 37.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

90

80

Page 46: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 3434

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

50 25.5 4.86 8.99 24.1 4.59 9.33 22.8 4.37 9.62 22.3 4.21 9.74 21.3 3.98 9.98 20.3 3.71 10.296 25.5 4.70 11.7 24.1 4.46 11.9 22.8 4.26 12.0 22.3 4.11 12.1 21.3 3.88 12.2 20.3 3.61 12.4

120 25.5 4.66 12.4 24.1 4.42 12.5 22.8 4.22 12.6 22.3 4.08 12.7 21.3 3.84 12.8 20.3 3.57 12.950 25.5 4.11 13.8 24.1 3.93 14.2 22.8 3.78 14.5 22.3 3.66 14.6 21.3 3.47 14.9 20.3 3.26 15.196 25.5 4.01 16.7 24.1 3.84 16.9 22.8 3.69 17.1 22.3 3.57 17.1 21.3 3.38 17.3 20.3 3.15 17.4

120 25.5 3.97 17.3 24.1 3.80 17.5 22.8 3.66 17.6 22.3 3.54 17.7 21.3 3.35 17.8 20.3 3.13 17.950 25.5 3.65 18.6 24.1 3.46 19.0 22.8 3.28 19.3 22.3 3.18 19.4 21.3 3.00 19.7 20.3 2.82 19.996 25.5 3.56 21.6 24.1 3.37 21.8 22.8 3.20 22.0 22.3 3.10 22.0 21.3 2.94 22.2 20.3 2.75 22.3

120 25.5 3.53 22.3 24.1 3.34 22.4 22.8 3.17 22.5 22.3 3.07 22.6 21.3 2.92 22.7 20.3 2.73 22.850 25.5 3.29 23.4 24.1 3.08 23.8 22.8 2.90 24.1 22.3 2.81 24.2 21.3 2.67 24.5 20.3 2.51 24.896 25.5 3.20 26.5 24.1 3.00 26.7 22.8 2.82 26.9 22.3 2.74 26.9 21.3 2.60 27.1 20.3 2.44 27.2

120 25.5 3.17 27.2 24.1 2.97 27.3 22.8 2.79 27.5 22.3 2.72 27.5 21.3 2.58 27.6 20.3 2.43 27.750 25.5 2.99 28.3 24.1 2.79 28.6 22.8 2.60 29.0 22.3 2.53 29.1 21.3 2.40 29.4 20.3 2.26 29.696 25.5 2.90 31.4 24.1 2.70 31.6 22.8 2.52 31.8 22.3 2.45 31.8 21.3 2.33 32.0 20.3 2.19 32.1

120 25.5 2.88 32.1 24.1 2.68 32.3 22.8 2.50 32.4 22.3 2.44 32.5 21.3 2.32 32.6 20.3 2.19 32.750 25.5 2.77 33.1 24.1 2.58 33.5 22.8 2.36 33.8 22.3 2.30 34.0 21.3 2.19 34.2 20.3 2.06 34.596 25.5 2.66 36.3 24.1 2.49 36.5 22.8 2.28 36.7 22.3 2.22 36.8 21.3 2.11 36.9 20.3 1.99 37.1

120 25.5 2.64 37.0 24.1 2.47 37.2 22.8 2.26 37.4 22.3 2.21 37.4 21.3 2.10 37.5 20.3 1.99 37.650 21.9 4.04 9.85 20.6 3.78 10.1 19.6 3.57 10.4 19.1 3.44 10.5 18.3 3.24 10.7 17.4 3.02 10.996 21.9 3.90 12.2 20.6 3.66 12.3 19.6 3.46 12.5 19.1 3.34 12.5 18.3 3.16 12.6 17.4 2.95 12.7

120 21.9 3.86 12.7 20.6 3.63 12.9 19.6 3.43 13.0 19.1 3.31 13.0 18.3 3.13 13.1 17.4 2.92 13.250 21.9 3.45 14.7 20.6 3.26 15.0 19.6 3.10 15.3 19.1 3.00 15.4 18.3 2.84 15.6 17.4 2.67 15.896 21.9 3.35 17.2 20.6 3.17 17.3 19.6 3.01 17.5 19.1 2.92 17.5 18.3 2.77 17.7 17.4 2.59 17.8

120 21.9 3.32 17.7 20.6 3.14 17.9 19.6 2.99 18.0 19.1 2.90 18.0 18.3 2.74 18.1 17.4 2.57 18.250 21.9 3.06 19.5 20.6 2.88 19.8 19.6 2.72 20.1 19.1 2.64 20.2 18.3 2.50 20.4 17.4 2.35 20.796 21.9 2.97 22.1 20.6 2.80 22.3 19.6 2.64 22.4 19.1 2.57 22.5 18.3 2.44 22.6 17.4 2.29 22.7

120 21.9 2.95 22.6 20.6 2.77 22.8 19.6 2.62 22.9 19.1 2.55 22.9 18.3 2.42 23.0 17.4 2.28 23.150 21.9 2.75 24.3 20.6 2.57 24.7 19.6 2.42 24.9 19.1 2.35 25.1 18.3 2.24 25.3 17.4 2.11 25.596 21.9 2.67 27.0 20.6 2.50 27.2 19.6 2.35 27.3 19.1 2.29 27.4 18.3 2.18 27.5 17.4 2.05 27.6

120 21.9 2.65 27.6 20.6 2.48 27.7 19.6 2.33 27.8 19.1 2.27 27.9 18.3 2.17 28.0 17.4 2.05 28.150 21.9 2.50 29.2 20.6 2.33 29.5 19.6 2.18 29.8 19.1 2.13 29.9 18.3 2.03 30.2 17.4 1.92 30.496 21.9 2.42 31.9 20.6 2.26 32.1 19.6 2.12 32.2 19.1 2.07 32.3 18.3 1.97 32.4 17.4 1.86 32.5

120 21.9 2.40 32.5 20.6 2.25 32.7 19.6 2.10 32.8 19.1 2.05 32.8 18.3 1.96 32.9 17.4 1.86 33.050 21.9 2.29 34.1 20.6 2.15 34.4 19.6 1.99 34.7 19.1 1.94 34.8 18.3 1.86 35.1 17.4 1.76 35.396 21.9 2.22 36.8 20.6 2.08 37.0 19.6 1.93 37.2 19.1 1.88 37.2 18.3 1.80 37.3 17.4 1.70 37.5

120 21.9 2.20 37.5 20.6 2.07 37.6 19.6 1.92 37.7 19.1 1.87 37.8 18.3 1.79 37.9 17.4 1.70 38.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

70

60

Page 47: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units3535

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

Heating Capacity

50 18.2 3.21 10.7 17.2 2.97 10.9 16.3 2.76 11.2 15.9 2.66 11.2 15.2 2.50 11.4 14.5 2.34 11.696 18.2 3.09 12.6 17.2 2.86 12.8 16.3 2.65 12.9 15.9 2.57 12.9 15.2 2.44 13.0 14.5 2.28 13.1

120 18.2 3.07 13.1 17.2 2.84 13.2 16.3 2.63 13.3 15.9 2.55 13.3 15.2 2.41 13.4 14.5 2.26 13.550 18.2 2.79 15.6 17.2 2.59 15.8 16.3 2.42 16.1 15.9 2.34 16.2 15.2 2.22 16.3 14.5 2.09 16.596 18.2 2.69 17.7 17.2 2.50 17.8 16.3 2.34 17.9 15.9 2.27 17.9 15.2 2.16 18.0 14.5 2.03 18.1

120 18.2 2.67 18.1 17.2 2.48 18.2 16.3 2.32 18.3 15.9 2.25 18.3 15.2 2.14 18.4 14.5 2.02 18.550 18.2 2.46 20.4 17.2 2.30 20.7 16.3 2.16 20.9 15.9 2.10 21.0 15.2 1.99 21.2 14.5 1.89 21.496 18.2 2.38 22.6 17.2 2.22 22.7 16.3 2.09 22.8 15.9 2.03 22.9 15.2 1.94 23.0 14.5 1.83 23.1

120 18.2 2.37 23.0 17.2 2.21 23.1 16.3 2.07 23.2 15.9 2.02 23.3 15.2 1.93 23.4 14.5 1.82 23.450 18.2 2.21 25.3 17.2 2.07 25.6 16.3 1.94 25.8 15.9 1.90 25.9 15.2 1.81 26.1 14.5 1.72 26.396 18.2 2.14 27.5 17.2 2.00 27.6 16.3 1.88 27.8 15.9 1.84 27.8 15.2 1.76 27.9 14.5 1.67 28.0

120 18.2 2.12 28.0 17.2 1.99 28.1 16.3 1.87 28.2 15.9 1.83 28.2 15.2 1.75 28.3 14.5 1.66 28.450 18.2 2.00 30.2 17.2 1.88 30.5 16.3 1.77 30.7 15.9 1.73 30.8 15.2 1.66 31.0 14.5 1.58 31.296 18.2 1.94 32.4 17.2 1.82 32.6 16.3 1.72 32.7 15.9 1.68 32.7 15.2 1.61 32.8 14.5 1.53 32.9

120 18.2 1.93 32.9 17.2 1.81 33.0 16.3 1.71 33.1 15.9 1.67 33.2 15.2 1.60 33.3 14.5 1.53 33.450 18.2 1.82 35.1 17.2 1.72 35.4 16.3 1.62 35.6 15.9 1.59 35.7 15.2 1.53 35.9 14.5 1.46 36.196 18.2 1.77 37.4 17.2 1.67 37.5 16.3 1.58 37.6 15.9 1.55 37.7 15.2 1.48 37.8 14.5 1.42 37.9

120 18.2 1.76 37.9 17.2 1.66 38.0 16.3 1.57 38.1 15.9 1.54 38.1 15.2 1.48 38.2 14.5 1.42 38.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

50

Page 48: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 3636

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

ARWN200LA2

Heating Capacity

100 77.1 12.1 5.92 76.9 12.4 5.95 76.6 12.9 5.98 74.6 12.7 6.21 72.6 12.2 6.44 68.6 11.1 6.92192 79.6 12.1 9.85 79.3 12.4 9.87 79.0 12.9 9.89 76.9 12.4 10.0 74.9 11.8 10.2 70.7 10.7 10.4240 79.9 12.1 10.9 79.9 12.6 10.9 79.9 13.0 10.9 77.9 12.4 11.0 75.8 11.9 11.1 71.6 11.8 11.3100 80.0 11.0 10.3 79.8 11.2 10.4 79.5 11.5 10.4 77.3 11.5 10.7 75.3 11.5 10.9 70.8 11.3 11.5192 82.6 11.2 14.7 82.3 11.4 14.7 82.0 11.7 14.7 79.9 11.6 14.9 77.7 11.7 15.0 73.4 11.5 15.3240 83.0 11.2 15.7 83.0 11.5 15.7 83.0 11.8 15.7 80.7 11.7 15.8 78.4 11.7 15.9 74.0 11.5 16.1100 87.1 11.5 14.1 85.1 11.5 14.4 83.0 11.5 14.6 81.3 11.3 14.8 79.7 11.1 15.0 75.0 10.4 15.6192 87.1 11.2 19.2 85.1 11.3 19.3 83.0 11.3 19.5 81.3 11.1 19.6 79.7 10.9 19.7 75.0 10.3 20.0240 87.1 11.1 20.3 85.1 11.1 20.4 83.0 11.2 20.5 81.3 10.9 20.6 79.7 10.7 20.7 75.0 10.1 21.0100 87.1 11.0 18.7 85.1 11.0 19.0 83.0 11.0 19.3 81.3 10.8 19.5 79.7 10.5 19.7 75.0 9.79 20.3192 87.1 10.7 24.0 85.1 10.7 24.1 83.0 10.8 24.3 81.3 10.5 24.4 79.7 10.3 24.5 75.0 9.58 24.8240 87.1 10.6 25.2 85.1 10.6 25.3 83.0 10.7 25.4 81.3 10.4 25.5 79.7 10.1 25.6 75.0 9.45 25.8100 87.1 10.7 23.5 85.1 10.6 23.8 83.0 10.7 24.0 81.3 10.3 24.3 79.7 9.93 24.5 75.0 9.09 25.1192 87.1 10.3 28.8 85.1 10.3 29.0 83.0 10.3 29.1 81.3 9.98 29.2 79.7 9.63 29.3 75.0 8.81 29.7240 87.1 10.1 30.0 85.1 10.1 30.2 83.0 10.2 30.3 81.3 9.86 30.4 79.7 9.52 30.5 75.0 8.71 30.7100 87.1 10.3 28.2 85.1 10.3 28.5 83.0 10.3 28.8 81.3 9.89 29.0 79.7 9.50 29.2 75.0 8.62 29.9192 87.1 9.84 33.7 85.1 9.85 33.8 83.0 9.90 34.0 81.3 9.52 34.1 79.7 9.14 34.2 75.0 8.29 34.6240 87.1 9.72 34.9 85.1 9.73 35.1 83.0 9.80 35.2 81.3 9.41 35.3 79.7 9.04 35.4 75.0 8.20 35.6100 73.2 12.1 6.38 73.0 12.5 6.40 72.8 12.9 6.42 71.0 12.7 6.64 68.7 12.1 6.91 65.1 11.0 7.34192 75.0 12.1 10.1 74.7 12.4 10.2 74.4 12.9 10.2 72.5 12.4 10.3 70.2 11.7 10.5 66.5 10.7 10.7240 75.4 12.1 11.1 75.3 12.5 11.1 75.0 12.9 11.1 73.2 12.4 11.2 70.8 11.7 11.3 67.0 11.4 11.5100 75.3 10.7 10.8 75.1 11.0 10.9 74.8 11.4 11.0 72.8 11.2 11.2 70.5 11.0 11.5 66.5 10.7 12.0192 77.4 10.8 15.0 76.9 11.1 15.1 76.4 11.5 15.1 74.5 11.3 15.2 72.1 11.1 15.4 68.3 10.7 15.6240 77.8 10.8 15.9 77.5 11.1 16.0 77.1 11.5 16.0 75.0 11.3 16.1 72.6 11.0 16.2 68.7 10.7 16.4100 81.9 10.9 14.8 79.6 10.8 15.0 77.1 10.7 15.4 75.5 10.5 15.6 73.4 10.2 15.8 69.3 9.52 16.3192 82.2 10.7 19.5 79.6 10.6 19.7 77.1 10.6 19.9 75.5 10.3 20.0 73.4 10.0 20.1 69.3 9.37 20.4240 82.4 10.6 20.6 79.6 10.5 20.7 77.1 10.4 20.8 75.5 10.2 20.9 73.4 9.87 21.0 69.3 9.26 21.3100 82.4 10.4 19.4 79.6 10.2 19.7 77.1 10.0 20.0 75.5 9.73 20.2 73.4 9.40 20.5 69.3 8.75 21.0192 82.4 10.1 24.3 79.6 9.92 24.5 77.1 9.79 24.7 75.5 9.52 24.8 73.4 9.20 24.9 69.3 8.56 25.2240 82.4 9.98 25.4 79.6 9.79 25.6 77.1 9.66 25.7 75.5 9.40 25.8 73.4 9.09 25.9 69.3 8.46 26.1100 82.4 9.87 24.1 79.6 9.62 24.5 77.1 9.43 24.8 75.5 9.11 25.0 73.4 8.74 25.3 69.3 8.02 25.8192 82.4 9.53 29.1 79.6 9.31 29.3 77.1 9.15 29.5 75.5 8.83 29.6 73.4 8.48 29.8 69.3 7.78 30.1240 82.4 9.42 30.3 79.6 9.19 30.5 77.1 9.04 30.6 75.5 8.73 30.7 73.4 8.39 30.8 69.3 7.70 31.1100 82.4 9.46 28.9 79.6 9.23 29.2 77.1 8.94 29.6 75.5 8.61 29.8 73.4 8.23 30.1 69.3 7.51 30.6192 82.4 9.03 34.0 79.6 8.84 34.2 77.1 8.60 34.4 75.5 8.28 34.5 73.4 7.92 34.7 69.3 7.22 35.0240 82.4 8.93 35.2 79.6 8.74 35.4 77.1 8.51 35.5 75.5 8.19 35.6 73.4 7.84 35.7 69.3 7.16 36.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

130

120

Page 49: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units3737

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 69.3 12.2 6.84 69.2 12.5 6.85 69.0 13.0 6.87 67.4 12.6 7.06 64.8 12.0 7.37 61.5 11.0 7.75192 70.4 12.0 10.4 70.2 12.4 10.5 69.8 12.9 10.5 68.2 12.4 10.6 65.5 11.7 10.8 62.2 10.7 11.0240 70.9 12.0 11.3 70.7 12.4 11.3 70.1 12.8 11.4 68.5 12.3 11.5 65.8 11.6 11.6 62.5 11.0 11.8100 70.7 10.4 11.3 70.5 10.8 11.5 70.0 11.2 11.6 68.3 10.9 11.8 65.7 10.6 12.1 62.3 10.1 12.5192 72.2 10.5 15.3 71.5 10.8 15.4 70.8 11.2 15.4 69.1 10.9 15.6 66.5 10.5 15.7 63.1 9.90 15.9240 72.6 10.5 16.2 72.0 10.8 16.2 71.1 11.1 16.3 69.4 10.8 16.4 66.7 10.4 16.5 63.3 9.83 16.7100 76.7 10.4 15.4 74.2 10.2 15.7 71.1 9.99 16.1 69.6 9.69 16.3 67.1 9.26 16.6 63.7 8.63 17.0192 77.3 10.2 19.9 74.2 10.0 20.1 71.1 9.83 20.3 69.6 9.53 20.4 67.1 9.11 20.5 63.7 8.49 20.8240 77.6 10.2 20.8 74.2 9.89 21.0 71.1 9.69 21.2 69.6 9.41 21.3 67.1 9.01 21.4 63.7 8.40 21.6100 77.6 9.72 20.0 74.2 9.31 20.4 71.1 8.97 20.8 69.6 8.70 21.0 67.1 8.30 21.3 63.7 7.71 21.8192 77.6 9.48 24.7 74.2 9.10 24.9 71.1 8.77 25.1 69.6 8.50 25.2 67.1 8.12 25.4 63.7 7.54 25.6240 77.6 9.37 25.7 74.2 8.98 25.9 71.1 8.66 26.0 69.6 8.41 26.1 67.1 8.04 26.3 63.7 7.48 26.5100 77.6 9.09 24.7 74.2 8.61 25.2 71.1 8.20 25.6 69.6 7.93 25.8 67.1 7.55 26.1 63.7 6.96 26.6192 77.6 8.80 29.5 74.2 8.34 29.7 71.1 7.96 29.9 69.6 7.69 30.1 67.1 7.32 30.2 63.7 6.75 30.5240 77.6 8.70 30.6 74.2 8.25 30.8 71.1 7.86 31.0 69.6 7.61 31.0 67.1 7.25 31.2 63.7 6.70 31.4100 77.6 8.63 29.5 74.2 8.19 30.0 71.1 7.59 30.4 69.6 7.32 30.6 67.1 6.96 30.9 63.7 6.40 31.4192 77.6 8.22 34.4 74.2 7.83 34.6 71.1 7.30 34.8 69.6 7.05 34.9 67.1 6.70 35.1 63.7 6.16 35.4240 77.6 8.13 35.5 74.2 7.75 35.7 71.1 7.22 35.9 69.6 6.98 36.0 67.1 6.64 36.1 63.7 6.11 36.3100 65.4 12.2 7.30 65.4 12.5 7.30 65.2 13.0 7.32 63.8 12.6 7.49 60.9 11.9 7.83 58.0 11.0 8.17192 65.9 12.0 10.7 65.6 12.4 10.8 65.2 12.9 10.8 63.8 12.4 10.9 60.9 11.6 11.1 58.0 10.7 11.2240 66.3 12.0 11.6 66.1 12.4 11.6 65.2 12.8 11.6 63.8 12.3 11.7 60.9 11.5 11.8 58.0 10.6 12.0100 66.0 10.1 11.8 65.9 10.6 12.1 65.2 11.0 12.1 63.8 10.7 12.3 60.9 10.1 12.7 58.0 9.46 13.0192 67.0 10.1 15.6 66.1 10.5 15.7 65.2 11.0 15.8 63.8 10.5 15.9 60.9 9.88 16.1 58.0 9.10 16.3240 67.5 10.1 16.4 66.6 10.4 16.5 65.2 10.8 16.6 63.8 10.4 16.7 60.9 9.75 16.8 58.0 9.00 17.0100 71.4 9.78 16.1 68.8 9.57 16.4 65.2 9.23 16.9 63.8 8.90 17.0 60.9 8.36 17.4 58.0 7.73 17.8192 72.4 9.75 20.2 68.8 9.41 20.4 65.2 9.08 20.7 63.8 8.75 20.8 60.9 8.23 20.9 58.0 7.61 21.1240 72.9 9.71 21.1 68.8 9.29 21.3 65.2 8.96 21.5 63.8 8.65 21.6 60.9 8.15 21.7 58.0 7.55 21.9100 72.9 9.06 20.6 68.8 8.46 21.1 65.2 7.93 21.6 63.8 7.66 21.8 60.9 7.21 22.1 58.0 6.67 22.5192 72.9 8.86 25.0 68.8 8.27 25.3 65.2 7.76 25.5 63.8 7.49 25.6 60.9 7.05 25.8 58.0 6.53 26.0240 72.9 8.76 25.9 68.8 8.18 26.2 65.2 7.66 26.4 63.8 7.41 26.5 60.9 6.99 26.6 58.0 6.49 26.8100 72.9 8.32 25.4 68.8 7.61 25.9 65.2 6.98 26.4 63.8 6.75 26.6 60.9 6.35 27.0 58.0 5.90 27.3192 72.9 8.07 29.8 68.8 7.38 30.1 65.2 6.77 30.4 63.8 6.54 30.5 60.9 6.16 30.7 58.0 5.72 30.9240 72.9 7.99 30.9 68.8 7.30 31.1 65.2 6.69 31.3 63.8 6.48 31.4 60.9 6.12 31.5 58.0 5.69 31.7100 72.9 7.80 30.2 68.8 7.15 30.7 65.2 6.24 31.2 63.8 6.04 31.4 60.9 5.69 31.8 58.0 5.29 32.2192 72.9 7.41 34.7 68.8 6.83 35.0 65.2 6.00 35.3 63.8 5.81 35.4 60.9 5.48 35.6 58.0 5.09 35.8240 72.9 7.34 35.8 68.8 6.76 36.0 65.2 5.94 36.2 63.8 5.76 36.3 60.9 5.44 36.5 58.0 5.07 36.6

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

110

100

Page 50: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 3838

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 61.8 11.2 7.72 60.2 11.1 7.91 58.7 11.1 8.09 57.4 10.7 8.24 54.8 10.2 8.55 52.2 9.39 8.85192 62.1 10.9 11.0 60.3 10.9 11.1 58.7 10.9 11.2 57.4 10.5 11.3 54.8 9.90 11.5 52.2 9.15 11.6240 62.3 10.9 11.8 60.5 10.8 11.9 58.7 10.8 12.0 57.4 10.4 12.0 54.8 9.80 12.2 52.2 9.06 12.3100 62.2 9.33 12.4 60.4 9.38 12.7 58.7 9.49 12.9 57.4 9.18 13.1 54.8 8.69 13.4 52.2 8.14 13.7192 62.6 9.23 15.9 60.6 9.25 16.1 58.7 9.36 16.2 57.4 9.02 16.3 54.8 8.48 16.5 52.2 7.85 16.6240 62.9 9.18 16.7 60.8 9.18 16.8 58.7 9.24 16.9 57.4 8.91 17.0 54.8 8.38 17.1 52.2 7.77 17.3100 64.9 8.68 16.9 61.9 8.37 17.3 58.7 8.03 17.7 57.4 7.75 17.8 54.8 7.30 18.2 52.2 6.78 18.5192 65.3 8.58 20.7 61.9 8.20 20.9 58.7 7.87 21.1 57.4 7.60 21.2 54.8 7.16 21.4 52.2 6.65 21.5240 65.6 8.52 21.5 61.9 8.11 21.7 58.7 7.77 21.8 57.4 7.52 21.9 54.8 7.11 22.0 52.2 6.61 22.2100 65.6 7.95 21.5 61.9 7.42 22.0 58.7 6.96 22.4 57.4 6.73 22.6 54.8 6.35 22.9 52.2 5.91 23.3192 65.6 7.76 25.5 61.9 7.24 25.7 58.7 6.79 26.0 57.4 6.57 26.1 54.8 6.20 26.2 52.2 5.77 26.4240 65.6 7.68 26.3 61.9 7.17 26.6 58.7 6.72 26.7 57.4 6.51 26.8 54.8 6.16 27.0 52.2 5.74 27.1100 65.6 7.28 26.3 61.9 6.68 26.8 58.7 6.16 27.2 57.4 5.97 27.4 54.8 5.64 27.8 52.2 5.26 28.1192 65.6 7.06 30.3 61.9 6.48 30.6 58.7 5.98 30.8 57.4 5.79 30.9 54.8 5.47 31.1 52.2 5.10 31.3240 65.6 7.00 31.3 61.9 6.42 31.5 58.7 5.91 31.7 57.4 5.74 31.7 54.8 5.44 31.9 52.2 5.08 32.0100 65.6 6.79 31.1 61.9 6.25 31.6 58.7 5.54 32.1 57.4 5.37 32.3 54.8 5.08 32.6 52.2 4.75 33.0192 65.6 6.48 35.2 61.9 5.99 35.5 58.7 5.34 35.7 57.4 5.18 35.8 54.8 4.89 36.0 52.2 4.57 36.2240 65.6 6.42 36.2 61.9 5.93 36.4 58.7 5.29 36.6 57.4 5.14 36.7 54.8 4.87 36.8 52.2 4.56 37.0100 58.3 10.1 8.13 55.0 9.59 8.52 52.2 9.20 8.86 51.0 8.87 8.99 48.7 8.39 9.26 46.4 7.79 9.54192 58.3 9.83 11.2 55.0 9.35 11.4 52.2 8.99 11.6 51.0 8.68 11.7 48.7 8.18 11.8 46.4 7.59 12.0240 58.3 9.74 12.0 55.0 9.27 12.2 52.2 8.91 12.3 51.0 8.60 12.4 48.7 8.10 12.5 46.4 7.52 12.6100 58.3 8.53 13.0 55.0 8.18 13.4 52.2 7.93 13.7 51.0 7.68 13.8 48.7 7.27 14.1 46.4 6.82 14.4192 58.3 8.33 16.2 55.0 8.00 16.5 52.2 7.77 16.6 51.0 7.51 16.7 48.7 7.08 16.9 46.4 6.60 17.0240 58.3 8.26 17.0 55.0 7.93 17.1 52.2 7.68 17.3 51.0 7.43 17.3 48.7 7.01 17.5 46.4 6.53 17.6100 58.3 7.58 17.7 55.0 7.16 18.1 52.2 6.82 18.5 51.0 6.60 18.6 48.7 6.24 18.9 46.4 5.83 19.2192 58.3 7.40 21.1 55.0 6.99 21.3 52.2 6.66 21.5 51.0 6.45 21.6 48.7 6.10 21.8 46.4 5.70 21.9240 58.3 7.33 21.9 55.0 6.93 22.0 52.2 6.59 22.2 51.0 6.39 22.3 48.7 6.06 22.4 46.4 5.66 22.5100 58.3 6.84 22.5 55.0 6.38 22.9 52.2 5.99 23.3 51.0 5.81 23.4 48.7 5.50 23.7 46.4 5.15 24.0192 58.3 6.66 26.0 55.0 6.21 26.2 52.2 5.83 26.4 51.0 5.66 26.5 48.7 5.36 26.6 46.4 5.02 26.8240 58.3 6.60 26.8 55.0 6.16 26.9 52.2 5.78 27.1 51.0 5.61 27.2 48.7 5.33 27.3 46.4 5.00 27.4100 58.3 6.24 27.3 55.0 5.76 27.7 52.2 5.35 28.1 51.0 5.20 28.3 48.7 4.93 28.6 46.4 4.62 28.9192 58.3 6.05 30.9 55.0 5.59 31.1 52.2 5.19 31.3 51.0 5.04 31.4 48.7 4.78 31.5 46.4 4.48 31.7240 58.3 6.00 31.7 55.0 5.54 31.9 52.2 5.14 32.0 51.0 5.00 32.1 48.7 4.75 32.2 46.4 4.47 32.4100 58.3 5.78 32.1 55.0 5.35 32.6 52.2 4.84 33.0 51.0 4.71 33.1 48.7 4.47 33.4 46.4 4.20 33.7192 58.3 5.55 35.8 55.0 5.15 36.0 52.2 4.67 36.2 51.0 4.54 36.3 48.7 4.31 36.5 46.4 4.05 36.6240 58.3 5.51 36.6 55.0 5.11 36.8 52.2 4.63 37.0 51.0 4.51 37.0 48.7 4.29 37.2 46.4 4.04 37.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

90

80

Page 51: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units3939

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 51.0 8.67 8.99 48.2 8.15 9.33 45.6 7.77 9.62 44.6 7.49 9.74 42.6 7.07 9.98 40.6 6.58 10.2192 51.0 8.39 11.7 48.2 7.93 11.9 45.6 7.56 12.0 44.6 7.31 12.1 42.6 6.89 12.2 40.6 6.41 12.4240 51.0 8.32 12.4 48.2 7.86 12.5 45.6 7.50 12.6 44.6 7.24 12.7 42.6 6.83 12.8 40.6 6.35 12.9100 51.0 7.34 13.8 48.2 6.99 14.2 45.6 6.72 14.5 44.6 6.51 14.6 42.6 6.16 14.9 40.6 5.78 15.1192 51.0 7.15 16.7 48.2 6.82 16.9 45.6 6.56 17.1 44.6 6.35 17.1 42.6 6.00 17.3 40.6 5.60 17.4240 51.0 7.10 17.3 48.2 6.75 17.5 45.6 6.49 17.6 44.6 6.29 17.7 42.6 5.94 17.8 40.6 5.55 17.9100 51.0 6.52 18.6 48.2 6.14 19.0 45.6 5.83 19.3 44.6 5.64 19.4 42.6 5.34 19.7 40.6 5.00 19.9192 51.0 6.35 21.6 48.2 5.98 21.8 45.6 5.68 22.0 44.6 5.51 22.0 42.6 5.21 22.2 40.6 4.89 22.3240 51.0 6.30 22.3 48.2 5.93 22.4 45.6 5.62 22.5 44.6 5.46 22.6 42.6 5.18 22.7 40.6 4.86 22.8100 51.0 5.87 23.4 48.2 5.48 23.8 45.6 5.14 24.1 44.6 5.00 24.2 42.6 4.74 24.5 40.6 4.45 24.8192 51.0 5.71 26.5 48.2 5.33 26.7 45.6 5.00 26.9 44.6 4.86 26.9 42.6 4.61 27.1 40.6 4.33 27.2240 51.0 5.67 27.2 48.2 5.28 27.3 45.6 4.96 27.5 44.6 4.83 27.5 42.6 4.59 27.6 40.6 4.32 27.7100 51.0 5.35 28.3 48.2 4.95 28.6 45.6 4.61 29.0 44.6 4.49 29.1 42.6 4.26 29.4 40.6 4.02 29.6192 51.0 5.19 31.4 48.2 4.80 31.6 45.6 4.48 31.8 44.6 4.35 31.8 42.6 4.14 32.0 40.6 3.90 32.1240 51.0 5.15 32.1 48.2 4.76 32.3 45.6 4.44 32.4 44.6 4.33 32.5 42.6 4.12 32.6 40.6 3.89 32.7100 51.0 4.94 33.1 48.2 4.58 33.5 45.6 4.19 33.8 44.6 4.08 34.0 42.6 3.88 34.2 40.6 3.66 34.5192 51.0 4.75 36.3 48.2 4.42 36.5 45.6 4.05 36.7 44.6 3.94 36.8 42.6 3.75 36.9 40.6 3.54 37.1240 51.0 4.72 37.0 48.2 4.39 37.2 45.6 4.02 37.4 44.6 3.92 37.4 42.6 3.74 37.5 40.6 3.53 37.6100 43.7 7.21 9.85 41.3 6.71 10.1 39.1 6.33 10.4 38.3 6.10 10.5 36.5 5.76 10.7 34.8 5.37 10.9192 43.7 6.96 12.2 41.3 6.50 12.3 39.1 6.14 12.5 38.3 5.94 12.5 36.5 5.61 12.6 34.8 5.23 12.7240 43.7 6.90 12.7 41.3 6.45 12.9 39.1 6.09 13.0 38.3 5.89 13.0 36.5 5.56 13.1 34.8 5.18 13.2100 43.7 6.16 14.7 41.3 5.80 15.0 39.1 5.51 15.3 38.3 5.33 15.4 36.5 5.05 15.6 34.8 4.75 15.8192 43.7 5.98 17.2 41.3 5.63 17.3 39.1 5.35 17.5 38.3 5.19 17.5 36.5 4.92 17.7 34.8 4.61 17.8240 43.7 5.94 17.7 41.3 5.58 17.9 39.1 5.31 18.0 38.3 5.15 18.0 36.5 4.87 18.1 34.8 4.57 18.2100 43.7 5.46 19.5 41.3 5.11 19.8 39.1 4.83 20.1 38.3 4.68 20.2 36.5 4.44 20.4 34.8 4.18 20.7192 43.7 5.30 22.1 41.3 4.97 22.3 39.1 4.69 22.4 38.3 4.56 22.5 36.5 4.33 22.6 34.8 4.07 22.7240 43.7 5.26 22.6 41.3 4.93 22.8 39.1 4.65 22.9 38.3 4.52 22.9 36.5 4.30 23.0 34.8 4.05 23.1100 43.7 4.90 24.3 41.3 4.57 24.7 39.1 4.30 24.9 38.3 4.18 25.1 36.5 3.97 25.3 34.8 3.75 25.5192 43.7 4.76 27.0 41.3 4.44 27.2 39.1 4.17 27.3 38.3 4.06 27.4 36.5 3.87 27.5 34.8 3.65 27.6240 43.7 4.73 27.6 41.3 4.41 27.7 39.1 4.14 27.8 38.3 4.04 27.9 36.5 3.85 28.0 34.8 3.64 28.1100 43.7 4.46 29.2 41.3 4.14 29.5 39.1 3.88 29.8 38.3 3.78 29.9 36.5 3.60 30.2 34.8 3.41 30.4192 43.7 4.32 31.9 41.3 4.02 32.1 39.1 3.76 32.2 38.3 3.67 32.3 36.5 3.49 32.4 34.8 3.31 32.5240 43.7 4.30 32.5 41.3 3.99 32.7 39.1 3.74 32.8 38.3 3.65 32.8 36.5 3.48 32.9 34.8 3.30 33.0100 43.7 4.10 34.1 41.3 3.82 34.4 39.1 3.54 34.7 38.3 3.45 34.8 36.5 3.30 35.1 34.8 3.13 35.3192 43.7 3.96 36.8 41.3 3.69 37.0 39.1 3.43 37.2 38.3 3.34 37.2 36.5 3.19 37.3 34.8 3.03 37.5240 43.7 3.93 37.5 41.3 3.67 37.6 39.1 3.40 37.7 38.3 3.33 37.8 36.5 3.18 37.9 34.8 3.02 38.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

70

60

Page 52: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 4040

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

Heating Capacity

100 36.4 5.74 10.7 34.4 5.28 10.9 32.6 4.90 11.2 31.9 4.72 11.2 30.4 4.44 11.4 29.0 4.16 11.6192 36.4 5.53 12.6 34.4 5.08 12.8 32.6 4.71 12.9 31.9 4.57 12.9 30.4 4.33 13.0 29.0 4.05 13.1240 36.4 5.48 13.1 34.4 5.04 13.2 32.6 4.68 13.3 31.9 4.53 13.3 30.4 4.28 13.4 29.0 4.01 13.5100 36.4 4.98 15.6 34.4 4.61 15.8 32.6 4.30 16.1 31.9 4.16 16.2 30.4 3.94 16.3 29.0 3.71 16.5192 36.4 4.81 17.7 34.4 4.44 17.8 32.6 4.15 17.9 31.9 4.03 17.9 30.4 3.83 18.0 29.0 3.61 18.1240 36.4 4.77 18.1 34.4 4.41 18.2 32.6 4.12 18.3 31.9 4.00 18.3 30.4 3.80 18.4 29.0 3.59 18.5100 36.4 4.40 20.4 34.4 4.08 20.7 32.6 3.83 20.9 31.9 3.72 21.0 30.4 3.54 21.2 29.0 3.35 21.4192 36.4 4.25 22.6 34.4 3.95 22.7 32.6 3.70 22.8 31.9 3.61 22.9 30.4 3.44 23.0 29.0 3.26 23.1240 36.4 4.23 23.0 34.4 3.93 23.1 32.6 3.68 23.2 31.9 3.59 23.3 30.4 3.42 23.4 29.0 3.24 23.4100 36.4 3.94 25.3 34.4 3.67 25.6 32.6 3.45 25.8 31.9 3.37 25.9 30.4 3.21 26.1 29.0 3.05 26.3192 36.4 3.81 27.5 34.4 3.55 27.6 32.6 3.35 27.8 31.9 3.27 27.8 30.4 3.12 27.9 29.0 2.96 28.0240 36.4 3.79 28.0 34.4 3.53 28.1 32.6 3.33 28.2 31.9 3.25 28.2 30.4 3.11 28.3 29.0 2.96 28.4100 36.4 3.57 30.2 34.4 3.33 30.5 32.6 3.14 30.7 31.9 3.07 30.8 30.4 2.94 31.0 29.0 2.80 31.2192 36.4 3.46 32.4 34.4 3.23 32.6 32.6 3.05 32.7 31.9 2.98 32.7 30.4 2.85 32.8 29.0 2.72 32.9240 36.4 3.44 32.9 34.4 3.22 33.0 32.6 3.04 33.1 31.9 2.97 33.2 30.4 2.85 33.3 29.0 2.72 33.4100 36.4 3.26 35.1 34.4 3.05 35.4 32.6 2.89 35.6 31.9 2.83 35.7 30.4 2.71 35.9 29.0 2.59 36.1192 36.4 3.16 37.4 34.4 2.96 37.5 32.6 2.80 37.6 31.9 2.74 37.7 30.4 2.63 37.8 29.0 2.51 37.9240 36.4 3.15 37.9 34.4 2.95 38.0 32.6 2.79 38.1 31.9 2.74 38.1 30.4 2.63 38.2 29.0 2.52 38.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

50

Page 53: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units4141

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

ARWN300LA2 Heating Capacity

100 115.6 18.8 5.92 115.3 19.4 5.95 114.9 20.2 5.98 112.0 19.9 6.21 109.0 19.0 6.44 102.9 17.3 6.92192 119.4 18.9 9.85 118.9 19.4 9.87 118.5 20.2 9.89 115.4 19.3 10.0 112.3 18.4 10.2 106.1 16.8 10.4240 119.9 18.9 10.9 119.9 19.6 10.9 119.9 20.3 10.9 116.8 19.4 11.0 113.7 18.5 11.1 107.3 18.5 11.3100 120.0 17.2 10.3 119.7 17.5 10.4 119.3 18.0 10.4 116.0 17.9 10.7 112.9 17.9 10.9 106.2 17.6 11.5192 123.9 17.5 14.7 123.5 17.9 14.7 123.0 18.4 14.7 119.8 18.2 14.9 116.6 18.2 15.0 110.1 18.0 15.3240 124.5 17.4 15.7 124.5 17.9 15.7 124.5 18.5 15.7 121.0 18.3 15.8 117.6 18.3 15.9 111.0 18.0 16.1100 130.7 17.9 14.1 127.6 17.9 14.4 124.5 18.0 14.6 122.0 17.6 14.8 119.5 17.3 15.0 112.5 16.3 15.6192 130.7 17.5 19.2 127.6 17.6 19.3 124.5 17.7 19.5 122.0 17.3 19.6 119.5 17.0 19.7 112.5 16.0 20.0240 130.7 17.3 20.3 127.6 17.3 20.4 124.5 17.4 20.5 122.0 17.1 20.6 119.5 16.8 20.7 112.5 15.8 21.0100 130.7 17.2 18.7 127.6 17.2 19.0 124.5 17.3 19.3 122.0 16.8 19.5 119.5 16.4 19.7 112.5 15.3 20.3192 130.7 16.7 24.0 127.6 16.8 24.1 124.5 16.9 24.3 122.0 16.5 24.4 119.5 16.1 24.5 112.5 15.0 24.8240 130.7 16.5 25.2 127.6 16.6 25.3 124.5 16.7 25.4 122.0 16.3 25.5 119.5 15.8 25.6 112.5 14.8 25.8100 130.7 16.6 23.5 127.6 16.6 23.8 124.5 16.7 24.0 122.0 16.1 24.3 119.5 15.5 24.5 112.5 14.2 25.1192 130.7 16.0 28.8 127.6 16.1 29.0 124.5 16.2 29.1 122.0 15.6 29.2 119.5 15.1 29.3 112.5 13.8 29.7240 130.7 15.8 30.0 127.6 15.9 30.2 124.5 16.0 30.3 122.0 15.4 30.4 119.5 14.9 30.5 112.5 13.6 30.7100 130.7 16.1 28.2 127.6 16.0 28.5 124.5 16.1 28.8 122.0 15.5 29.0 119.5 14.9 29.2 112.5 13.5 29.9192 130.7 15.3 33.7 127.6 15.4 33.8 124.5 15.5 34.0 122.0 14.9 34.1 119.5 14.3 34.2 112.5 13.0 34.6240 130.7 15.2 34.9 127.6 15.2 35.1 124.5 15.3 35.2 122.0 14.7 35.3 119.5 14.1 35.4 112.5 12.8 35.6100 109.8 18.9 6.38 109.6 19.5 6.40 109.2 20.2 6.42 106.5 19.8 6.64 103.1 18.9 6.91 97.6 17.2 7.34192 112.5 18.8 10.1 112.1 19.4 10.2 111.6 20.2 10.2 108.8 19.3 10.3 105.3 18.4 10.5 99.7 16.8 10.7240 113.1 18.8 11.1 113.0 19.5 11.1 112.5 20.2 11.1 109.7 19.3 11.2 106.2 18.4 11.3 100.6 17.9 11.5100 113.0 16.7 10.8 112.7 17.2 10.9 112.1 17.7 11.0 109.2 17.5 11.2 105.7 17.2 11.5 99.8 16.7 12.0192 116.1 16.9 15.0 115.4 17.4 15.1 114.6 17.9 15.1 111.8 17.6 15.2 108.2 17.3 15.4 102.4 16.7 15.6240 116.7 16.9 15.9 116.3 17.4 16.0 115.6 18.0 16.0 112.5 17.6 16.1 108.9 17.2 16.2 103.0 16.7 16.4100 122.9 17.0 14.8 119.5 16.9 15.0 115.6 16.8 15.4 113.2 16.4 15.6 110.1 15.9 15.8 104.0 14.9 16.3192 123.3 16.8 19.5 119.5 16.6 19.7 115.6 16.5 19.9 113.2 16.1 20.0 110.1 15.6 20.1 104.0 14.6 20.4240 123.6 16.6 20.6 119.5 16.4 20.7 115.6 16.3 20.8 113.2 15.9 20.9 110.1 15.4 21.0 104.0 14.5 21.3100 123.6 16.2 19.4 119.5 15.9 19.7 115.6 15.6 20.0 113.2 15.2 20.2 110.1 14.7 20.5 104.0 13.7 21.0192 123.6 15.8 24.3 119.5 15.5 24.5 115.6 15.3 24.7 113.2 14.9 24.8 110.1 14.4 24.9 104.0 13.4 25.2240 123.6 15.6 25.4 119.5 15.3 25.6 115.6 15.1 25.7 113.2 14.7 25.8 110.1 14.2 25.9 104.0 13.2 26.1100 123.6 15.4 24.1 119.5 15.0 24.5 115.6 14.7 24.8 113.2 14.2 25.0 110.1 13.7 25.3 104.0 12.5 25.8192 123.6 14.9 29.1 119.5 14.5 29.3 115.6 14.3 29.5 113.2 13.8 29.6 110.1 13.2 29.8 104.0 12.2 30.1240 123.6 14.7 30.3 119.5 14.4 30.5 115.6 14.1 30.6 113.2 13.6 30.7 110.1 13.1 30.8 104.0 12.0 31.1100 123.6 14.8 28.9 119.5 14.4 29.2 115.6 14.0 29.6 113.2 13.5 29.8 110.1 12.9 30.1 104.0 11.7 30.6192 123.6 14.1 34.0 119.5 13.8 34.2 115.6 13.4 34.4 113.2 12.9 34.5 110.1 12.4 34.7 104.0 11.3 35.0240 123.6 13.9 35.2 119.5 13.7 35.4 115.6 13.3 35.5 113.2 12.8 35.6 110.1 12.3 35.7 104.0 11.2 36.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

130

120

Page 54: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 4242

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 103.9 19.0 6.84 103.8 19.5 6.85 103.5 20.3 6.87 101.1 19.7 7.06 97.2 18.8 7.37 92.3 17.2 7.75192 105.6 18.8 10.4 105.2 19.4 10.5 104.7 20.1 10.5 102.2 19.3 10.6 98.3 18.3 10.8 93.3 16.8 11.0240 106.3 18.7 11.3 106.0 19.4 11.3 105.2 20.0 11.4 102.7 19.2 11.5 98.8 18.2 11.6 93.8 17.2 11.8100 106.0 16.3 11.3 105.7 16.9 11.5 105.0 17.5 11.6 102.4 17.1 11.8 98.5 16.5 12.1 93.4 15.7 12.5192 108.3 16.4 15.3 107.2 16.9 15.4 106.2 17.5 15.4 103.7 17.0 15.6 99.7 16.4 15.7 94.7 15.5 15.9240 109.0 16.3 16.2 108.1 16.9 16.2 106.7 17.4 16.3 104.1 16.9 16.4 100.1 16.2 16.5 95.0 15.4 16.7100 115.0 16.2 15.4 111.3 15.9 15.7 106.7 15.6 16.1 104.4 15.1 16.3 100.7 14.5 16.6 95.5 13.5 17.0192 115.9 16.0 19.9 111.3 15.7 20.1 106.7 15.4 20.3 104.4 14.9 20.4 100.7 14.2 20.5 95.5 13.3 20.8240 116.4 15.9 20.8 111.3 15.5 21.0 106.7 15.1 21.2 104.4 14.7 21.3 100.7 14.1 21.4 95.5 13.1 21.6100 116.4 15.2 20.0 111.3 14.6 20.4 106.7 14.0 20.8 104.4 13.6 21.0 100.7 13.0 21.3 95.5 12.1 21.8192 116.4 14.8 24.7 111.3 14.2 24.9 106.7 13.7 25.1 104.4 13.3 25.2 100.7 12.7 25.4 95.5 11.8 25.6240 116.4 14.6 25.7 111.3 14.0 25.9 106.7 13.5 26.0 104.4 13.1 26.1 100.7 12.6 26.3 95.5 11.7 26.5100 116.4 14.2 24.7 111.3 13.5 25.2 106.7 12.8 25.6 104.4 12.4 25.8 100.7 11.8 26.1 95.5 10.9 26.6192 116.4 13.7 29.5 111.3 13.0 29.7 106.7 12.4 29.9 104.4 12.0 30.1 100.7 11.4 30.2 95.5 10.6 30.5240 116.4 13.6 30.6 111.3 12.9 30.8 106.7 12.3 31.0 104.4 11.9 31.0 100.7 11.3 31.2 95.5 10.5 31.4100 116.4 13.5 29.5 111.3 12.8 30.0 106.7 11.9 30.4 104.4 11.4 30.6 100.7 10.9 30.9 95.5 10.0 31.4192 116.4 12.8 34.4 111.3 12.2 34.6 106.7 11.4 34.8 104.4 11.0 34.9 100.7 10.5 35.1 95.5 9.62 35.4240 116.4 12.7 35.5 111.3 12.1 35.7 106.7 11.3 35.9 104.4 10.9 36.0 100.7 10.4 36.1 95.5 9.56 36.3100 98.1 19.1 7.30 98.1 19.6 7.30 97.8 20.3 7.32 95.6 19.6 7.49 91.3 18.6 7.83 87.0 17.2 8.17192 98.8 18.7 10.7 98.4 19.4 10.8 97.8 20.1 10.8 95.6 19.4 10.9 91.3 18.2 11.1 87.0 16.7 11.2240 99.5 18.7 11.6 99.1 19.3 11.6 97.8 19.9 11.6 95.6 19.2 11.7 91.3 18.0 11.8 87.0 16.6 12.0100 99.0 15.8 11.8 98.8 16.5 12.1 97.8 17.3 12.1 95.6 16.7 12.3 91.3 15.8 12.7 87.0 14.8 13.0192 100.5 15.8 15.6 99.1 16.4 15.7 97.8 17.1 15.8 95.6 16.5 15.9 91.3 15.4 16.1 87.0 14.2 16.3240 101.2 15.8 16.4 99.8 16.3 16.5 97.8 16.9 16.6 95.6 16.2 16.7 91.3 15.2 16.8 87.0 14.1 17.0100 107.1 15.3 16.1 103.2 15.0 16.4 97.8 14.4 16.9 95.6 13.9 17.0 91.3 13.1 17.4 87.0 12.1 17.8192 108.6 15.2 20.2 103.2 14.7 20.4 97.8 14.2 20.7 95.6 13.7 20.8 91.3 12.9 20.9 87.0 11.9 21.1240 109.3 15.1 21.1 103.2 14.5 21.3 97.8 14.0 21.5 95.6 13.5 21.6 91.3 12.7 21.7 87.0 11.8 21.9100 109.3 14.1 20.6 103.2 13.2 21.1 97.8 12.4 21.6 95.6 12.0 21.8 91.3 11.3 22.1 87.0 10.4 22.5192 109.3 13.8 25.0 103.2 12.9 25.3 97.8 12.1 25.5 95.6 11.7 25.6 91.3 11.0 25.8 87.0 10.2 26.0240 109.3 13.7 25.9 103.2 12.8 26.2 97.8 12.0 26.4 95.6 11.6 26.5 91.3 10.9 26.6 87.0 10.1 26.8100 109.3 13.0 25.4 103.2 11.9 25.9 97.8 10.9 26.4 95.6 10.5 26.6 91.3 9.93 27.0 87.0 9.21 27.3192 109.3 12.6 29.8 103.2 11.5 30.1 97.8 10.6 30.4 95.6 10.2 30.5 91.3 9.63 30.7 87.0 8.94 30.9240 109.3 12.5 30.9 103.2 11.4 31.1 97.8 10.5 31.3 95.6 10.1 31.4 91.3 9.57 31.5 87.0 8.89 31.7100 109.3 12.2 30.2 103.2 11.2 30.7 97.8 9.76 31.2 95.6 9.44 31.4 91.3 8.90 31.8 87.0 8.27 32.2192 109.3 11.6 34.7 103.2 10.7 35.0 97.8 9.38 35.3 95.6 9.08 35.4 91.3 8.56 35.6 87.0 7.96 35.8240 109.3 11.4 35.8 103.2 10.6 36.0 97.8 9.28 36.2 95.6 9.00 36.3 91.3 8.51 36.5 87.0 7.93 36.6

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

110

100

Page 55: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units4343

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 92.8 17.4 7.72 90.3 17.3 7.91 88.0 17.4 8.09 86.1 16.7 8.24 82.2 15.9 8.55 78.3 14.7 8.85192 93.1 17.0 11.0 90.5 17.0 11.1 88.0 17.1 11.2 86.1 16.5 11.3 82.2 15.5 11.5 78.3 14.3 11.6240 93.5 16.9 11.8 90.8 16.9 11.9 88.0 16.9 12.0 86.1 16.3 12.0 82.2 15.3 12.2 78.3 14.2 12.3100 93.2 14.5 12.4 90.7 14.7 12.7 88.0 14.8 12.9 86.1 14.4 13.1 82.2 13.6 13.4 78.3 12.7 13.7192 94.0 14.4 15.9 90.8 14.5 16.1 88.0 14.6 16.2 86.1 14.1 16.3 82.2 13.3 16.5 78.3 12.3 16.6240 94.3 14.3 16.7 91.2 14.4 16.8 88.0 14.4 16.9 86.1 13.9 17.0 82.2 13.1 17.1 78.3 12.1 17.3100 97.3 13.5 16.9 92.9 13.1 17.3 88.0 12.5 17.7 86.1 12.1 17.8 82.2 11.4 18.2 78.3 10.6 18.5192 98.0 13.4 20.7 92.9 12.8 20.9 88.0 12.3 21.1 86.1 11.9 21.2 82.2 11.2 21.4 78.3 10.4 21.5240 98.4 13.3 21.5 92.9 12.7 21.7 88.0 12.2 21.8 86.1 11.8 21.9 82.2 11.1 22.0 78.3 10.3 22.2100 98.4 12.4 21.5 92.9 11.6 22.0 88.0 10.9 22.4 86.1 10.5 22.6 82.2 9.93 22.9 78.3 9.24 23.3192 98.4 12.1 25.5 92.9 11.3 25.7 88.0 10.6 26.0 86.1 10.3 26.1 82.2 9.70 26.2 78.3 9.02 26.4240 98.4 12.0 26.3 92.9 11.2 26.6 88.0 10.5 26.7 86.1 10.2 26.8 82.2 9.63 27.0 78.3 8.97 27.1100 98.4 11.4 26.3 92.9 10.4 26.8 88.0 9.63 27.2 86.1 9.33 27.4 82.2 8.81 27.8 78.3 8.22 28.1192 98.4 11.0 30.3 92.9 10.1 30.6 88.0 9.34 30.8 86.1 9.05 30.9 82.2 8.55 31.1 78.3 7.97 31.3240 98.4 10.9 31.3 92.9 10.0 31.5 88.0 9.24 31.7 86.1 8.97 31.7 82.2 8.50 31.9 78.3 7.94 32.0100 98.4 10.6 31.1 92.9 9.77 31.6 88.0 8.66 32.1 86.1 8.40 32.3 82.2 7.94 32.6 78.3 7.42 33.0192 98.4 10.1 35.2 92.9 9.36 35.5 88.0 8.34 35.7 86.1 8.09 35.8 82.2 7.65 36.0 78.3 7.15 36.2240 98.4 10.0 36.2 92.9 9.27 36.4 88.0 8.26 36.6 86.1 8.03 36.7 82.2 7.61 36.8 78.3 7.12 37.0100 87.5 15.8 8.13 82.5 15.0 8.52 78.2 14.4 8.86 76.5 13.9 8.99 73.1 13.1 9.26 69.6 12.2 9.54192 87.5 15.3 11.2 82.5 14.6 11.4 78.2 14.1 11.6 76.5 13.6 11.7 73.1 12.8 11.8 69.6 11.9 12.0240 87.5 15.2 12.0 82.5 14.5 12.2 78.2 13.9 12.3 76.5 13.4 12.4 73.1 12.7 12.5 69.6 11.7 12.6100 87.5 13.3 13.0 82.5 12.8 13.4 78.2 12.4 13.7 76.5 12.0 13.8 73.1 11.4 14.1 69.6 10.7 14.4192 87.5 13.0 16.2 82.5 12.5 16.5 78.2 12.1 16.6 76.5 11.7 16.7 73.1 11.1 16.9 69.6 10.3 17.0240 87.5 12.9 17.0 82.5 12.4 17.1 78.2 12.0 17.3 76.5 11.6 17.3 73.1 11.0 17.5 69.6 10.2 17.6100 87.5 11.8 17.7 82.5 11.2 18.1 78.2 10.7 18.5 76.5 10.3 18.6 73.1 9.75 18.9 69.6 9.11 19.2192 87.5 11.5 21.1 82.5 10.9 21.3 78.2 10.4 21.5 76.5 10.1 21.6 73.1 9.54 21.8 69.6 8.91 21.9240 87.5 11.4 21.9 82.5 10.8 22.0 78.2 10.3 22.2 76.5 10.0 22.3 73.1 9.47 22.4 69.6 8.85 22.5100 87.5 10.7 22.5 82.5 9.97 22.9 78.2 9.36 23.3 76.5 9.08 23.4 73.1 8.59 23.7 69.6 8.05 24.0192 87.5 10.4 26.0 82.5 9.71 26.2 78.2 9.12 26.4 76.5 8.85 26.5 73.1 8.38 26.6 69.6 7.84 26.8240 87.5 10.3 26.8 82.5 9.62 26.9 78.2 9.03 27.1 76.5 8.77 27.2 73.1 8.33 27.3 69.6 7.81 27.4100 87.5 9.73 27.3 82.5 9.00 27.7 78.2 8.36 28.1 76.5 8.12 28.3 73.1 7.70 28.6 69.6 7.22 28.9192 87.5 9.44 30.9 82.5 8.73 31.1 78.2 8.11 31.3 76.5 7.88 31.4 73.1 7.47 31.5 69.6 7.01 31.7240 87.5 9.37 31.7 82.5 8.66 31.9 78.2 8.04 32.0 76.5 7.82 32.1 73.1 7.43 32.2 69.6 6.98 32.4100 87.5 9.02 32.1 82.5 8.36 32.6 78.2 7.56 33.0 76.5 7.35 33.1 73.1 6.98 33.4 69.6 6.56 33.7192 87.5 8.65 35.8 82.5 8.05 36.0 78.2 7.30 36.2 76.5 7.10 36.3 73.1 6.74 36.5 69.6 6.34 36.6240 87.5 8.59 36.6 82.5 7.98 36.8 78.2 7.24 37.0 76.5 7.05 37.0 73.1 6.71 37.2 69.6 6.32 37.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

90

80

Page 56: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 4444

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

100 76.5 13.5 8.99 72.2 12.7 9.33 68.5 12.1 9.62 66.9 11.7 9.74 63.9 11.1 9.98 60.9 10.3 10.2192 76.5 13.1 11.7 72.2 12.4 11.9 68.5 11.8 12.0 66.9 11.4 12.1 63.9 10.8 12.2 60.9 10.0 12.4240 76.5 13.0 12.4 72.2 12.3 12.5 68.5 11.7 12.6 66.9 11.3 12.7 63.9 10.7 12.8 60.9 9.92 12.9100 76.5 11.5 13.8 72.2 10.9 14.2 68.5 10.5 14.5 66.9 10.2 14.6 63.9 9.62 14.9 60.9 9.04 15.1192 76.5 11.2 16.7 72.2 10.7 16.9 68.5 10.3 17.1 66.9 9.92 17.1 63.9 9.38 17.3 60.9 8.75 17.4240 76.5 11.1 17.3 72.2 10.6 17.5 68.5 10.1 17.6 66.9 9.83 17.7 63.9 9.29 17.8 60.9 8.68 17.9100 76.5 10.2 18.6 72.2 9.59 19.0 68.5 9.11 19.3 66.9 8.82 19.4 63.9 8.34 19.7 60.9 7.82 19.9192 76.5 9.91 21.6 72.2 9.35 21.8 68.5 8.87 22.0 66.9 8.61 22.0 63.9 8.15 22.2 60.9 7.64 22.3240 76.5 9.82 22.3 72.2 9.26 22.4 68.5 8.79 22.5 66.9 8.53 22.6 63.9 8.09 22.7 60.9 7.59 22.8100 76.5 9.16 23.4 72.2 8.56 23.8 68.5 8.04 24.1 66.9 7.81 24.2 63.9 7.40 24.5 60.9 6.96 24.8192 76.5 8.91 26.5 72.2 8.32 26.7 68.5 7.82 26.9 66.9 7.60 26.9 63.9 7.21 27.1 60.9 6.77 27.2240 76.5 8.84 27.2 72.2 8.26 27.3 68.5 7.75 27.5 66.9 7.54 27.5 63.9 7.17 27.6 60.9 6.75 27.7100 76.5 8.34 28.3 72.2 7.74 28.6 68.5 7.21 29.0 66.9 7.02 29.1 63.9 6.66 29.4 60.9 6.28 29.6192 76.5 8.09 31.4 72.2 7.50 31.6 68.5 6.99 31.8 66.9 6.81 31.8 63.9 6.46 32.0 60.9 6.09 32.1240 76.5 8.03 32.1 72.2 7.45 32.3 68.5 6.94 32.4 66.9 6.76 32.5 63.9 6.44 32.6 60.9 6.07 32.7100 76.5 7.71 33.1 72.2 7.16 33.5 68.5 6.54 33.8 66.9 6.38 34.0 63.9 6.07 34.2 60.9 5.73 34.5192 76.5 7.41 36.3 72.2 6.91 36.5 68.5 6.33 36.7 66.9 6.16 36.8 63.9 5.86 36.9 60.9 5.53 37.1240 76.5 7.36 37.0 72.2 6.86 37.2 68.5 6.28 37.4 66.9 6.13 37.4 63.9 5.84 37.5 60.9 5.52 37.6100 65.6 11.2 9.85 61.9 10.5 10.1 58.7 9.90 10.4 57.4 9.54 10.5 54.8 9.00 10.7 52.2 8.40 10.9192 65.6 10.9 12.2 61.9 10.2 12.3 58.7 9.60 12.5 57.4 9.28 12.5 54.8 8.77 12.6 52.2 8.18 12.7240 65.6 10.8 12.7 61.9 10.1 12.9 58.7 9.51 13.0 57.4 9.20 13.0 54.8 8.68 13.1 52.2 8.10 13.2100 65.6 9.61 14.7 61.9 9.06 15.0 58.7 8.61 15.3 57.4 8.34 15.4 54.8 7.89 15.6 52.2 7.42 15.8192 65.6 9.33 17.2 61.9 8.80 17.3 58.7 8.37 17.5 57.4 8.11 17.5 54.8 7.68 17.7 52.2 7.20 17.8240 65.6 9.26 17.7 61.9 8.73 17.9 58.7 8.29 18.0 57.4 8.04 18.0 54.8 7.62 18.1 52.2 7.14 18.2100 65.6 8.51 19.5 61.9 7.99 19.8 58.7 7.55 20.1 57.4 7.32 20.2 54.8 6.94 20.4 52.2 6.53 20.7192 65.6 8.27 22.1 61.9 7.76 22.3 58.7 7.33 22.4 57.4 7.12 22.5 54.8 6.76 22.6 52.2 6.36 22.7240 65.6 8.21 22.6 61.9 7.70 22.8 58.7 7.27 22.9 57.4 7.07 22.9 54.8 6.72 23.0 52.2 6.33 23.1100 65.6 7.65 24.3 61.9 7.15 24.7 58.7 6.72 24.9 57.4 6.54 25.1 54.8 6.21 25.3 52.2 5.86 25.5192 65.6 7.43 27.0 61.9 6.94 27.2 58.7 6.53 27.3 57.4 6.35 27.4 54.8 6.04 27.5 52.2 5.70 27.6240 65.6 7.38 27.6 61.9 6.89 27.7 58.7 6.48 27.8 57.4 6.31 27.9 54.8 6.01 28.0 52.2 5.68 28.1100 65.6 6.95 29.2 61.9 6.47 29.5 58.7 6.06 29.8 57.4 5.91 29.9 54.8 5.63 30.2 52.2 5.33 30.4192 65.6 6.74 31.9 61.9 6.28 32.1 58.7 5.88 32.2 57.4 5.73 32.3 54.8 5.46 32.4 52.2 5.17 32.5240 65.6 6.70 32.5 61.9 6.24 32.7 58.7 5.84 32.8 57.4 5.70 32.8 54.8 5.44 32.9 52.2 5.16 33.0100 65.6 6.39 34.1 61.9 5.97 34.4 58.7 5.53 34.7 57.4 5.40 34.8 54.8 5.15 35.1 52.2 4.89 35.3192 65.6 6.17 36.8 61.9 5.77 37.0 58.7 5.35 37.2 57.4 5.23 37.2 54.8 4.98 37.3 52.2 4.73 37.5240 65.6 6.14 37.5 61.9 5.73 37.6 58.7 5.32 37.7 57.4 5.20 37.8 54.8 4.97 37.9 52.2 4.73 38.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

70

60

Page 57: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units4545

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

Heating Capacity

100 54.7 8.96 10.7 51.6 8.25 10.9 48.9 7.66 11.2 47.8 7.37 11.2 45.7 6.94 11.4 43.5 6.50 11.6192 54.7 8.62 12.6 51.6 7.94 12.8 48.9 7.37 12.9 47.8 7.14 12.9 45.7 6.76 13.0 43.5 6.33 13.1240 54.7 8.55 13.1 51.6 7.88 13.2 48.9 7.31 13.3 47.8 7.08 13.3 45.7 6.70 13.4 43.5 6.27 13.5100 54.7 7.77 15.6 51.6 7.20 15.8 48.9 6.72 16.1 47.8 6.51 16.2 45.7 6.16 16.3 43.5 5.80 16.5192 54.7 7.50 17.7 51.6 6.95 17.8 48.9 6.48 17.9 47.8 6.30 17.9 45.7 5.99 18.0 43.5 5.64 18.1240 54.7 7.45 18.1 51.6 6.90 18.2 48.9 6.44 18.3 47.8 6.26 18.3 45.7 5.95 18.4 43.5 5.60 18.5100 54.7 6.86 20.4 51.6 6.38 20.7 48.9 5.99 20.9 47.8 5.82 21.0 45.7 5.53 21.2 43.5 5.24 21.4192 54.7 6.64 22.6 51.6 6.17 22.7 48.9 5.79 22.8 47.8 5.64 22.9 45.7 5.37 23.0 43.5 5.09 23.1240 54.7 6.59 23.0 51.6 6.14 23.1 48.9 5.75 23.2 47.8 5.61 23.3 45.7 5.35 23.4 43.5 5.07 23.4100 54.7 6.14 25.3 51.6 5.74 25.6 48.9 5.40 25.8 47.8 5.26 25.9 45.7 5.02 26.1 43.5 4.77 26.3192 54.7 5.95 27.5 51.6 5.56 27.6 48.9 5.23 27.8 47.8 5.10 27.8 45.7 4.87 27.9 43.5 4.63 28.0240 54.7 5.92 28.0 51.6 5.53 28.1 48.9 5.20 28.2 47.8 5.08 28.2 45.7 4.86 28.3 43.5 4.62 28.4100 54.7 5.56 30.2 51.6 5.21 30.5 48.9 4.92 30.7 47.8 4.81 30.8 45.7 4.60 31.0 43.5 4.38 31.2192 54.7 5.39 32.4 51.6 5.05 32.6 48.9 4.77 32.7 47.8 4.66 32.7 45.7 4.46 32.8 43.5 4.25 32.9240 54.7 5.37 32.9 51.6 5.03 33.0 48.9 4.74 33.1 47.8 4.64 33.2 45.7 4.45 33.3 43.5 4.25 33.4100 54.7 5.08 35.1 51.6 4.77 35.4 48.9 4.51 35.6 47.8 4.42 35.7 45.7 4.24 35.9 43.5 4.05 36.1192 54.7 4.93 37.4 51.6 4.63 37.5 48.9 4.38 37.6 47.8 4.29 37.7 45.7 4.11 37.8 43.5 3.93 37.9240 54.7 4.91 37.9 51.6 4.61 38.0 48.9 4.36 38.1 47.8 4.28 38.1 45.7 4.11 38.2 43.5 3.93 38.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

50

Page 58: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 4646

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

ARWN400LA2Heating Capacity

200 154.1 24.1 5.92 153.7 24.8 5.95 153.3 25.8 5.98 149.3 25.5 6.21 145.3 24.4 6.44 137.2 22.1 6.92384 159.1 24.2 9.85 158.6 24.8 9.87 158.0 25.8 9.89 153.9 24.7 10.0 149.8 23.6 10.2 141.4 21.5 10.4480 159.9 24.3 10.9 159.9 25.1 10.9 159.9 25.9 10.9 155.7 24.8 11.0 151.6 23.7 11.1 143.1 23.7 11.3200 160.0 22.0 10.3 159.6 22.5 10.4 159.1 23.0 10.4 154.6 22.9 10.7 150.5 22.9 10.9 141.6 22.5 11.5384 165.2 22.4 14.7 164.6 22.9 14.7 164.0 23.5 14.7 159.8 23.3 14.9 155.5 23.3 15.0 146.8 23.0 15.3480 166.0 22.4 15.7 166.0 22.9 15.7 166.0 23.7 15.7 161.3 23.4 15.8 156.9 23.4 15.9 148.0 23.0 16.1200 174.3 23.0 14.1 170.1 22.9 14.4 166.0 23.0 14.6 162.7 22.5 14.8 159.3 22.1 15.0 150.1 20.8 15.6384 174.3 22.5 19.2 170.1 22.5 19.3 166.0 22.6 19.5 162.7 22.2 19.6 159.3 21.8 19.7 150.1 20.5 20.0480 174.3 22.2 20.3 170.1 22.2 20.4 166.0 22.3 20.5 162.7 21.9 20.6 159.3 21.5 20.7 150.1 20.2 21.0200 174.3 22.1 18.7 170.1 22.0 19.0 166.0 22.1 19.3 162.7 21.5 19.5 159.3 21.0 19.7 150.1 19.6 20.3384 174.3 21.5 24.0 170.1 21.5 24.1 166.0 21.6 24.3 162.7 21.1 24.4 159.3 20.5 24.5 150.1 19.2 24.8480 174.3 21.2 25.2 170.1 21.2 25.3 166.0 21.3 25.4 162.7 20.8 25.5 159.3 20.3 25.6 150.1 18.9 25.8200 174.3 21.3 23.5 170.1 21.2 23.8 166.0 21.3 24.0 162.7 20.6 24.3 159.3 19.9 24.5 150.1 18.2 25.1384 174.3 20.5 28.8 170.1 20.5 29.0 166.0 20.7 29.1 162.7 20.0 29.2 159.3 19.3 29.3 150.1 17.6 29.7480 174.3 20.3 30.0 170.1 20.3 30.2 166.0 20.4 30.3 162.7 19.7 30.4 159.3 19.0 30.5 150.1 17.4 30.7200 174.3 20.6 28.2 170.1 20.5 28.5 166.0 20.6 28.8 162.7 19.8 29.0 159.3 19.0 29.2 150.1 17.2 29.9384 174.3 19.7 33.7 170.1 19.7 33.8 166.0 19.8 34.0 162.7 19.0 34.1 159.3 18.3 34.2 150.1 16.6 34.6480 174.3 19.4 34.9 170.1 19.5 35.1 166.0 19.6 35.2 162.7 18.8 35.3 159.3 18.1 35.4 150.1 16.4 35.6200 146.4 24.2 6.38 146.1 24.9 6.40 145.6 25.9 6.42 142.0 25.4 6.64 137.4 24.2 6.91 130.1 22.1 7.34384 150.0 24.1 10.1 149.4 24.8 10.2 148.8 25.8 10.2 145.1 24.7 10.3 140.4 23.5 10.5 132.9 21.4 10.7480 150.8 24.2 11.1 150.6 25.0 11.1 150.1 25.8 11.1 146.3 24.7 11.2 141.6 23.5 11.3 134.1 22.9 11.5200 150.7 21.4 10.8 150.3 22.0 10.9 149.5 22.7 11.0 145.6 22.4 11.2 140.9 22.0 11.5 133.1 21.3 12.0384 154.8 21.7 15.0 153.8 22.2 15.1 152.8 23.0 15.1 149.0 22.6 15.2 144.2 22.1 15.4 136.5 21.4 15.6480 155.6 21.7 15.9 155.0 22.3 16.0 154.1 23.0 16.0 150.1 22.5 16.1 145.2 22.1 16.2 137.3 21.3 16.4200 163.8 21.9 14.8 159.3 21.7 15.0 154.1 21.5 15.4 150.9 21.0 15.6 146.8 20.3 15.8 138.7 19.0 16.3384 164.4 21.5 19.5 159.3 21.3 19.7 154.1 21.1 19.9 150.9 20.6 20.0 146.8 20.0 20.1 138.7 18.7 20.4480 164.8 21.2 20.6 159.3 21.0 20.7 154.1 20.9 20.8 150.9 20.4 20.9 146.8 19.7 21.0 138.7 18.5 21.3200 164.8 20.8 19.4 159.3 20.3 19.7 154.1 20.0 20.0 150.9 19.5 20.2 146.8 18.8 20.5 138.7 17.5 21.0384 164.8 20.2 24.3 159.3 19.8 24.5 154.1 19.6 24.7 150.9 19.0 24.8 146.8 18.4 24.9 138.7 17.1 25.2480 164.8 20.0 25.4 159.3 19.6 25.6 154.1 19.3 25.7 150.9 18.8 25.8 146.8 18.2 25.9 138.7 16.9 26.1200 164.8 19.7 24.1 159.3 19.2 24.5 154.1 18.9 24.8 150.9 18.2 25.0 146.8 17.5 25.3 138.7 16.0 25.8384 164.8 19.1 29.1 159.3 18.6 29.3 154.1 18.3 29.5 150.9 17.7 29.6 146.8 17.0 29.8 138.7 15.6 30.1480 164.8 18.8 30.3 159.3 18.4 30.5 154.1 18.1 30.6 150.9 17.5 30.7 146.8 16.8 30.8 138.7 15.4 31.1200 164.8 18.9 28.9 159.3 18.5 29.2 154.1 17.9 29.6 150.9 17.2 29.8 146.8 16.5 30.1 138.7 15.0 30.6384 164.8 18.1 34.0 159.3 17.7 34.2 154.1 17.2 34.4 150.9 16.6 34.5 146.8 15.8 34.7 138.7 14.4 35.0480 164.8 17.9 35.2 159.3 17.5 35.4 154.1 17.0 35.5 150.9 16.4 35.6 146.8 15.7 35.7 138.7 14.3 36.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

130

120

Page 59: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units4747

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

200 138.6 24.3 6.84 138.4 25.0 6.85 138.0 26.0 6.87 134.8 25.2 7.06 129.6 24.0 7.37 123.0 22.0 7.75384 140.8 24.1 10.4 140.3 24.8 10.5 139.6 25.8 10.5 136.3 24.8 10.6 131.1 23.4 10.8 124.5 21.4 11.0480 141.7 24.0 11.3 141.4 24.9 11.3 140.2 25.7 11.4 136.9 24.6 11.5 131.7 23.3 11.6 125.0 22.0 11.8200 141.3 20.8 11.3 141.0 21.6 11.5 140.0 22.4 11.6 136.6 21.9 11.8 131.3 21.1 12.1 124.5 20.1 12.5384 144.4 21.0 15.3 143.0 21.6 15.4 141.6 22.4 15.4 138.3 21.8 15.6 133.0 20.9 15.7 126.3 19.8 15.9480 145.3 20.9 16.2 144.1 21.6 16.2 142.3 22.3 16.3 138.8 21.7 16.4 133.5 20.8 16.5 126.7 19.7 16.7200 153.3 20.7 15.4 148.4 20.4 15.7 142.3 20.0 16.1 139.2 19.4 16.3 134.3 18.5 16.6 127.3 17.3 17.0384 154.6 20.5 19.9 148.4 20.1 20.1 142.3 19.7 20.3 139.2 19.1 20.4 134.3 18.2 20.5 127.3 17.0 20.8480 155.3 20.3 20.8 148.4 19.8 21.0 142.3 19.4 21.2 139.2 18.8 21.3 134.3 18.0 21.4 127.3 16.8 21.6200 155.3 19.4 20.0 148.4 18.6 20.4 142.3 17.9 20.8 139.2 17.4 21.0 134.3 16.6 21.3 127.3 15.4 21.8384 155.3 19.0 24.7 148.4 18.2 24.9 142.3 17.5 25.1 139.2 17.0 25.2 134.3 16.2 25.4 127.3 15.1 25.6480 155.3 18.7 25.7 148.4 18.0 25.9 142.3 17.3 26.0 139.2 16.8 26.1 134.3 16.1 26.3 127.3 15.0 26.5200 155.3 18.2 24.7 148.4 17.2 25.2 142.3 16.4 25.6 139.2 15.9 25.8 134.3 15.1 26.1 127.3 13.9 26.6384 155.3 17.6 29.5 148.4 16.7 29.7 142.3 15.9 29.9 139.2 15.4 30.1 134.3 14.6 30.2 127.3 13.5 30.5480 155.3 17.4 30.6 148.4 16.5 30.8 142.3 15.7 31.0 139.2 15.2 31.0 134.3 14.5 31.2 127.3 13.4 31.4200 155.3 17.3 29.5 148.4 16.4 30.0 142.3 15.2 30.4 139.2 14.6 30.6 134.3 13.9 30.9 127.3 12.8 31.4384 155.3 16.4 34.4 148.4 15.7 34.6 142.3 14.6 34.8 139.2 14.1 34.9 134.3 13.4 35.1 127.3 12.3 35.4480 155.3 16.3 35.5 148.4 15.5 35.7 142.3 14.4 35.9 139.2 14.0 36.0 134.3 13.3 36.1 127.3 12.2 36.3200 130.8 24.4 7.30 130.8 25.0 7.30 130.4 26.0 7.32 127.5 25.1 7.49 121.8 23.8 7.83 116.0 22.0 8.17384 131.7 24.0 10.7 131.2 24.8 10.8 130.4 25.8 10.8 127.5 24.8 10.9 121.8 23.2 11.1 116.0 21.4 11.2480 132.6 23.9 11.6 132.1 24.7 11.6 130.4 25.5 11.6 127.5 24.5 11.7 121.8 23.0 11.8 116.0 21.2 12.0200 132.0 20.2 11.8 131.7 21.1 12.1 130.4 22.1 12.1 127.5 21.4 12.3 121.8 20.2 12.7 116.0 18.9 13.0384 134.0 20.3 15.6 132.2 21.0 15.7 130.4 21.9 15.8 127.5 21.1 15.9 121.8 19.8 16.1 116.0 18.2 16.3480 134.9 20.2 16.4 133.1 20.9 16.5 130.4 21.6 16.6 127.5 20.8 16.7 121.8 19.5 16.8 116.0 18.0 17.0200 142.9 19.6 16.1 137.6 19.1 16.4 130.4 18.5 16.9 127.5 17.8 17.0 121.8 16.7 17.4 116.0 15.5 17.8384 144.7 19.5 20.2 137.6 18.8 20.4 130.4 18.2 20.7 127.5 17.5 20.8 121.8 16.5 20.9 116.0 15.2 21.1480 145.8 19.4 21.1 137.6 18.6 21.3 130.4 17.9 21.5 127.5 17.3 21.6 121.8 16.3 21.7 116.0 15.1 21.9200 145.8 18.1 20.6 137.6 16.9 21.1 130.4 15.9 21.6 127.5 15.3 21.8 121.8 14.4 22.1 116.0 13.3 22.5384 145.8 17.7 25.0 137.6 16.5 25.3 130.4 15.5 25.5 127.5 15.0 25.6 121.8 14.1 25.8 116.0 13.1 26.0480 145.8 17.5 25.9 137.6 16.4 26.2 130.4 15.3 26.4 127.5 14.8 26.5 121.8 14.0 26.6 116.0 13.0 26.8200 145.8 16.6 25.4 137.6 15.2 25.9 130.4 14.0 26.4 127.5 13.5 26.6 121.8 12.7 27.0 116.0 11.8 27.3384 145.8 16.1 29.8 137.6 14.8 30.1 130.4 13.5 30.4 127.5 13.1 30.5 121.8 12.3 30.7 116.0 11.4 30.9480 145.8 16.0 30.9 137.6 14.6 31.1 130.4 13.4 31.3 127.5 13.0 31.4 121.8 12.2 31.5 116.0 11.4 31.7200 145.8 15.6 30.2 137.6 14.3 30.7 130.4 12.5 31.2 127.5 12.1 31.4 121.8 11.4 31.8 116.0 10.6 32.2384 145.8 14.8 34.7 137.6 13.7 35.0 130.4 12.0 35.3 127.5 11.6 35.4 121.8 11.0 35.6 116.0 10.2 35.8480 145.8 14.7 35.8 137.6 13.5 36.0 130.4 11.9 36.2 127.5 11.5 36.3 121.8 10.9 36.5 116.0 10.1 36.6

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

110

100

Page 60: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 4848

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

200 123.7 22.4 7.72 120.4 22.1 7.91 117.4 22.2 8.09 114.8 21.4 8.24 109.6 20.3 8.55 104.4 18.8 8.85384 124.2 21.8 11.0 120.6 21.7 11.1 117.4 21.9 11.2 114.8 21.1 11.3 109.6 19.8 11.5 104.4 18.3 11.6480 124.6 21.7 11.8 121.1 21.6 11.9 117.4 21.7 12.0 114.8 20.9 12.0 109.6 19.6 12.2 104.4 18.1 12.3200 124.3 18.7 12.4 120.9 18.8 12.7 117.4 19.0 12.9 114.8 18.4 13.1 109.6 17.4 13.4 104.4 16.3 13.7384 125.3 18.5 15.9 121.1 18.5 16.1 117.4 18.7 16.2 114.8 18.0 16.3 109.6 17.0 16.5 104.4 15.7 16.6480 125.8 18.4 16.7 121.6 18.4 16.8 117.4 18.5 16.9 114.8 17.8 17.0 109.6 16.8 17.1 104.4 15.5 17.3200 129.7 17.4 16.9 123.8 16.7 17.3 117.4 16.1 17.7 114.8 15.5 17.8 109.6 14.6 18.2 104.4 13.6 18.5384 130.7 17.2 20.7 123.8 16.4 20.9 117.4 15.7 21.1 114.8 15.2 21.2 109.6 14.3 21.4 104.4 13.3 21.5480 131.2 17.0 21.5 123.8 16.2 21.7 117.4 15.5 21.8 114.8 15.0 21.9 109.6 14.2 22.0 104.4 13.2 22.2200 131.2 15.9 21.5 123.8 14.8 22.0 117.4 13.9 22.4 114.8 13.5 22.6 109.6 12.7 22.9 104.4 11.8 23.3384 131.2 15.5 25.5 123.8 14.5 25.7 117.4 13.6 26.0 114.8 13.1 26.1 109.6 12.4 26.2 104.4 11.5 26.4480 131.2 15.4 26.3 123.8 14.3 26.6 117.4 13.4 26.7 114.8 13.0 26.8 109.6 12.3 27.0 104.4 11.5 27.1200 131.2 14.6 26.3 123.8 13.4 26.8 117.4 12.3 27.2 114.8 11.9 27.4 109.6 11.3 27.8 104.4 10.5 28.1384 131.2 14.1 30.3 123.8 13.0 30.6 117.4 12.0 30.8 114.8 11.6 30.9 109.6 10.9 31.1 104.4 10.2 31.3480 131.2 14.0 31.3 123.8 12.8 31.5 117.4 11.8 31.7 114.8 11.5 31.7 109.6 10.9 31.9 104.4 10.2 32.0200 131.2 13.6 31.1 123.8 12.5 31.6 117.4 11.1 32.1 114.8 10.7 32.3 109.6 10.2 32.6 104.4 9.49 33.0384 131.2 13.0 35.2 123.8 12.0 35.5 117.4 10.7 35.7 114.8 10.4 35.8 109.6 9.79 36.0 104.4 9.14 36.2480 131.2 12.8 36.2 123.8 11.9 36.4 117.4 10.6 36.6 114.8 10.3 36.7 109.6 9.74 36.8 104.4 9.12 37.0200 116.6 20.3 8.13 110.1 19.2 8.52 104.3 18.4 8.86 102.0 17.7 8.99 97.4 16.8 9.26 92.8 15.6 9.54384 116.6 19.7 11.2 110.1 18.7 11.4 104.3 18.0 11.6 102.0 17.4 11.7 97.4 16.4 11.8 92.8 15.2 12.0480 116.6 19.5 12.0 110.1 18.5 12.2 104.3 17.8 12.3 102.0 17.2 12.4 97.4 16.2 12.5 92.8 15.0 12.6200 116.6 17.1 13.0 110.1 16.4 13.4 104.3 15.9 13.7 102.0 15.4 13.8 97.4 14.5 14.1 92.8 13.6 14.4384 116.6 16.7 16.2 110.1 16.0 16.5 104.3 15.5 16.6 102.0 15.0 16.7 97.4 14.2 16.9 92.8 13.2 17.0480 116.6 16.5 17.0 110.1 15.9 17.1 104.3 15.4 17.3 102.0 14.9 17.3 97.4 14.0 17.5 92.8 13.1 17.6200 116.6 15.2 17.7 110.1 14.3 18.1 104.3 13.6 18.5 102.0 13.2 18.6 97.4 12.5 18.9 92.8 11.7 19.2384 116.6 14.8 21.1 110.1 14.0 21.3 104.3 13.3 21.5 102.0 12.9 21.6 97.4 12.2 21.8 92.8 11.4 21.9480 116.6 14.7 21.9 110.1 13.9 22.0 104.3 13.2 22.2 102.0 12.8 22.3 97.4 12.1 22.4 92.8 11.3 22.5200 116.6 13.7 22.5 110.1 12.8 22.9 104.3 12.0 23.3 102.0 11.6 23.4 97.4 11.0 23.7 92.8 10.3 24.0384 116.6 13.3 26.0 110.1 12.4 26.2 104.3 11.7 26.4 102.0 11.3 26.5 97.4 10.7 26.6 92.8 10.0 26.8480 116.6 13.2 26.8 110.1 12.3 26.9 104.3 11.6 27.1 102.0 11.2 27.2 97.4 10.7 27.3 92.8 10.0 27.4200 116.6 12.5 27.3 110.1 11.5 27.7 104.3 10.7 28.1 102.0 10.4 28.3 97.4 9.85 28.6 92.8 9.24 28.9384 116.6 12.1 30.9 110.1 11.2 31.1 104.3 10.4 31.3 102.0 10.1 31.4 97.4 9.55 31.5 92.8 8.97 31.7480 116.6 12.0 31.7 110.1 11.1 31.9 104.3 10.3 32.0 102.0 10.0 32.1 97.4 9.51 32.2 92.8 8.94 32.4200 116.6 11.6 32.1 110.1 10.7 32.6 104.3 9.67 33.0 102.0 9.41 33.1 97.4 8.93 33.4 92.8 8.40 33.7384 116.6 11.1 35.8 110.1 10.3 36.0 104.3 9.34 36.2 102.0 9.08 36.3 97.4 8.62 36.5 92.8 8.11 36.6480 116.6 11.0 36.6 110.1 10.2 36.8 104.3 9.26 37.0 102.0 9.02 37.0 97.4 8.59 37.2 92.8 8.09 37.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

90

80

Page 61: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units4949

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

15

20

25

30

35

40

Heating Capacity

200 102.0 17.3 8.99 96.3 16.3 9.33 91.3 15.5 9.62 89.3 15.0 9.74 85.2 14.1 9.98 81.2 13.2 10.2384 102.0 16.8 11.7 96.3 15.9 11.9 91.3 15.1 12.0 89.3 14.6 12.1 85.2 13.8 12.2 81.2 12.8 12.4480 102.0 16.6 12.4 96.3 15.7 12.5 91.3 15.0 12.6 89.3 14.5 12.7 85.2 13.7 12.8 81.2 12.7 12.9200 102.0 14.7 13.8 96.3 14.0 14.2 91.3 13.4 14.5 89.3 13.0 14.6 85.2 12.3 14.9 81.2 11.6 15.1384 102.0 14.3 16.7 96.3 13.6 16.9 91.3 13.1 17.1 89.3 12.7 17.1 85.2 12.0 17.3 81.2 11.2 17.4480 102.0 14.2 17.3 96.3 13.5 17.5 91.3 13.0 17.6 89.3 12.6 17.7 85.2 11.9 17.8 81.2 11.1 17.9200 102.0 13.0 18.6 96.3 12.3 19.0 91.3 11.7 19.3 89.3 11.3 19.4 85.2 10.7 19.7 81.2 10.0 19.9384 102.0 12.7 21.6 96.3 12.0 21.8 91.3 11.4 22.0 89.3 11.0 22.0 85.2 10.4 22.2 81.2 9.77 22.3480 102.0 12.6 22.3 96.3 11.9 22.4 91.3 11.2 22.5 89.3 10.9 22.6 85.2 10.4 22.7 81.2 9.71 22.8200 102.0 11.7 23.4 96.3 11.0 23.8 91.3 10.3 24.1 89.3 10.0 24.2 85.2 9.47 24.5 81.2 8.90 24.8384 102.0 11.4 26.5 96.3 10.7 26.7 91.3 10.0 26.9 89.3 9.72 26.9 85.2 9.22 27.1 81.2 8.67 27.2480 102.0 11.3 27.2 96.3 10.6 27.3 91.3 9.92 27.5 89.3 9.65 27.5 85.2 9.17 27.6 81.2 8.63 27.7200 102.0 10.7 28.3 96.3 9.90 28.6 91.3 9.23 29.0 89.3 8.98 29.1 85.2 8.53 29.4 81.2 8.03 29.6384 102.0 10.4 31.4 96.3 9.60 31.6 91.3 8.95 31.8 89.3 8.71 31.8 85.2 8.27 32.0 81.2 7.79 32.1480 102.0 10.3 32.1 96.3 9.53 32.3 91.3 8.88 32.4 89.3 8.65 32.5 85.2 8.24 32.6 81.2 7.77 32.7200 102.0 9.88 33.1 96.3 9.17 33.5 91.3 8.37 33.8 89.3 8.16 34.0 85.2 7.76 34.2 81.2 7.33 34.5384 102.0 9.50 36.3 96.3 8.84 36.5 91.3 8.10 36.7 89.3 7.89 36.8 85.2 7.50 36.9 81.2 7.08 37.1480 102.0 9.44 37.0 96.3 8.78 37.2 91.3 8.04 37.4 89.3 7.84 37.4 85.2 7.47 37.5 81.2 7.07 37.6200 87.5 14.4 9.85 82.6 13.4 10.1 78.2 12.7 10.4 76.5 12.2 10.5 73.1 11.5 10.7 69.6 10.7 10.9384 87.5 13.9 12.2 82.6 13.0 12.3 78.2 12.3 12.5 76.5 11.9 12.5 73.1 11.2 12.6 69.6 10.5 12.7480 87.5 13.8 12.7 82.6 12.9 12.9 78.2 12.2 13.0 76.5 11.8 13.0 73.1 11.1 13.1 69.6 10.4 13.2200 87.5 12.3 14.7 82.6 11.6 15.0 78.2 11.0 15.3 76.5 10.7 15.4 73.1 10.1 15.6 69.6 9.50 15.8384 87.5 12.0 17.2 82.6 11.3 17.3 78.2 10.7 17.5 76.5 10.4 17.5 73.1 9.83 17.7 69.6 9.21 17.8480 87.5 11.9 17.7 82.6 11.2 17.9 78.2 10.6 18.0 76.5 10.3 18.0 73.1 9.75 18.1 69.6 9.14 18.2200 87.5 10.9 19.5 82.6 10.2 19.8 78.2 9.66 20.1 76.5 9.37 20.2 73.1 8.88 20.4 69.6 8.35 20.7384 87.5 10.6 22.1 82.6 9.93 22.3 78.2 9.38 22.4 76.5 9.11 22.5 73.1 8.65 22.6 69.6 8.14 22.7480 87.5 10.5 22.6 82.5 9.85 22.8 78.2 9.30 22.9 76.5 9.05 22.9 73.1 8.60 23.0 69.6 8.10 23.1200 87.5 9.81 24.3 82.5 9.14 24.7 78.2 8.60 24.9 76.5 8.36 25.1 73.1 7.95 25.3 69.6 7.50 25.5384 87.5 9.53 27.0 82.5 8.88 27.2 78.2 8.35 27.3 76.5 8.13 27.4 73.1 7.73 27.5 69.6 7.30 27.6480 87.5 9.46 27.6 82.5 8.82 27.7 78.2 8.29 27.8 76.5 8.08 27.9 73.1 7.69 28.0 69.6 7.27 28.1200 87.5 8.91 29.2 82.5 8.28 29.5 78.2 7.76 29.8 76.5 7.56 29.9 73.1 7.20 30.2 69.6 6.82 30.4384 87.5 8.64 31.9 82.5 8.03 32.1 78.2 7.53 32.2 76.5 7.34 32.3 73.1 6.99 32.4 69.6 6.62 32.5480 87.5 8.59 32.5 82.5 7.98 32.7 78.2 7.47 32.8 76.5 7.30 32.8 73.1 6.97 32.9 69.6 6.60 33.0200 87.5 8.20 34.1 82.5 7.63 34.4 78.2 7.07 34.7 76.5 6.91 34.8 73.1 6.59 35.1 69.6 6.26 35.3384 87.5 7.91 36.8 82.5 7.38 37.0 78.2 6.85 37.2 76.5 6.69 37.2 73.1 6.38 37.3 69.6 6.05 37.5480 87.5 7.87 37.5 82.5 7.34 37.6 78.2 6.81 37.7 76.5 6.66 37.8 73.1 6.36 37.9 69.6 6.05 38.0

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

70

60

Page 62: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 5050

Combi.(%)

InletWaterTemp.(°C)

WaterFlowRate

(L/min)

Indoor Air Temp.(°CDB)

16 18 20 21 22 24

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

TC(kW)

PI(kW)

OutletWaterTemp.(°C)

15

20

25

30

35

40

Heating Capacity

200 72.9 11.5 10.7 68.8 10.6 10.9 65.2 9.80 11.2 63.8 9.44 11.2 60.9 8.88 11.4 58.0 8.32 11.6384 72.9 11.1 12.6 68.8 10.2 12.8 65.2 9.43 12.9 63.8 9.14 12.9 60.9 8.65 13.0 58.0 8.10 13.1480 72.9 11.0 13.1 68.8 10.1 13.2 65.2 9.35 13.3 63.8 9.06 13.3 60.9 8.57 13.4 58.0 8.02 13.5200 72.9 9.96 15.6 68.8 9.21 15.8 65.2 8.60 16.1 63.8 8.32 16.2 60.9 7.88 16.3 58.0 7.42 16.5384 72.9 9.61 17.7 68.8 8.89 17.8 65.2 8.30 17.9 63.8 8.07 17.9 60.9 7.66 18.0 58.0 7.22 18.1480 72.9 9.55 18.1 68.8 8.83 18.2 65.2 8.24 18.3 63.8 8.01 18.3 60.9 7.61 18.4 58.0 7.17 18.5200 72.9 8.80 20.4 68.8 8.17 20.7 65.2 7.66 20.9 63.8 7.45 21.0 60.9 7.08 21.2 58.0 6.70 21.4384 72.9 8.51 22.6 68.8 7.90 22.7 65.2 7.41 22.8 63.8 7.22 22.9 60.9 6.88 23.0 58.0 6.51 23.1480 72.9 8.46 23.0 68.8 7.85 23.1 65.2 7.36 23.2 63.8 7.18 23.3 60.9 6.84 23.4 58.0 6.48 23.4200 72.9 7.88 25.3 68.8 7.34 25.6 65.2 6.91 25.8 63.8 6.74 25.9 60.9 6.42 26.1 58.0 6.11 26.3384 72.9 7.63 27.5 68.8 7.11 27.6 65.2 6.69 27.8 63.8 6.53 27.8 60.9 6.24 27.9 58.0 5.93 28.0480 72.9 7.59 28.0 68.8 7.07 28.1 65.2 6.65 28.2 63.8 6.50 28.2 60.9 6.22 28.3 58.0 5.91 28.4200 72.9 7.13 30.2 68.8 6.66 30.5 65.2 6.29 30.7 63.8 6.15 30.8 60.9 5.88 31.0 58.0 5.61 31.2384 72.9 6.92 32.4 68.8 6.46 32.6 65.2 6.10 32.7 63.8 5.97 32.7 60.9 5.71 32.8 58.0 5.44 32.9480 72.9 6.88 32.9 68.8 6.43 33.0 65.2 6.07 33.1 63.8 5.94 33.2 60.9 5.69 33.3 58.0 5.44 33.4200 72.9 6.51 35.1 68.8 6.10 35.4 65.2 5.77 35.6 63.8 5.66 35.7 60.9 5.42 35.9 58.0 5.19 36.1384 72.9 6.32 37.4 68.8 5.92 37.5 65.2 5.61 37.6 63.8 5.49 37.7 60.9 5.26 37.8 58.0 5.03 37.9480 72.9 6.30 37.9 68.8 5.90 38.0 65.2 5.58 38.1 63.8 5.47 38.1 60.9 5.25 38.2 58.0 5.03 38.3

TC:Total Capacity(kW) Combi. : CombinationPI :Power Input(kW) Temp. : Temperature

50

Page 63: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units5151

7.3 Capacity Correction FactorARWN100LA2

Ex)

Rate of change in cooling capacity

Rate of change in heating capacity

1. SymbolsHU : Level difference between indoor and outdoor units where indoor unit in inferior position (m)HL : Level difference between indoor and outdoor units where indoor unit in superior position (m)L : Equivalent pipe length (m)α : Capacity correction factor

2. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard conditions. (Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.)

3. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.4. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease5. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outdoor units

= cooling / heating capacity of outdoor units obtained from capacity table X capacity correction factor due to piping length to the farthest indoor unit 6. Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1.0 m, calculation purposes.7. When overall equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes.

: ARWN100LA2 gas pipe Ø22.2 Ø25.4 liquid pipe Ø9.52 Ø12.7 8. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length.

: overall equivalent length = (equivalent length of main pipe) X correction factor + (equivalent length after first branching)

• (Cooling) Overall equivalent length =70 m x 0.5 + 40 m = 75 m The correction factor in cooling capacity when HU = 10 m is thus approximately0.887

• (Heatng) Overall equivalent length =70 m x 0.2 + 40 m = 54 mThe correction factor in heating capacity when HU = 10 m is thus approximately0.813

correction factor overall equivalent pipe length< 90 m ≥ 90 m

cooling 1.0 0.5heating 1.0 0.2

HU50 - - - - - 0.916 0.902 0.889 0.876 0.864 0.852 0.841 0.831 40 - - - - 0.933 0.918 0.903 0.890 0.877 0.865 0.853 0.842 0.832 30 - - - 0.951 0.934 0.919 0.905 0.891 0.878 0.866 0.854 0.843 0.833 20 - - 0.970 0.952 0.936 0.920 0.906 0.892 0.879 0.867 0.855 0.844 0.834 10 - 0.990 0.971 0.954 0.937 0.922 0.907 0.894 0.881 0.868 0.856 0.845 0.835 7.5 0.995 0.990 0.972 0.954 0.938 0.922 0.908 0.894 0.881 0.868 0.857 0.846 0.835 0 1.000 0.992 0.973 0.955 0.939 0.923 0.909 0.895 0.882 0.869 0.858 0.846 0.836 0 7.5 10 20 30 40 50 60 70 80 90 100 110 1200 1.000 0.992 0.973 0.955 0.939 0.923 0.909 0.895 0.882 0.869 0.858 0.846 0.836

7.5 1.000 0.993 0.974 0.957 0.940 0.924 0.910 0.896 0.883 0.870 0.858 0.847 0.836 10 - 0.994 0.975 0.957 0.940 0.925 0.910 0.896 0.883 0.870 0.859 0.847 0.837 20 - - 0.976 0.959 0.942 0.926 0.911 0.897 0.884 0.872 0.860 0.848 0.838 30 - - - 0.960 0.944 0.928 0.913 0.899 0.885 0.873 0.861 0.850 0.839 40 - - - - 0.945 0.929 0.914 0.900 0.887 0.874 0.862 0.851 0.840 HL

L

L

α

α

HU50 - - - - - 0.824 0.803 0.784 0.767 0.752 40 - - - - 0.850 0.824 0.803 0.784 0.767 0.75230 - - - 0.880 0.850 0.824 0.803 0.784 0.767 0.752 20 - - 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 10 - 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 7.5 1.000 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 0 1.000 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 0 7.5 10 20 30 40 50 60 70 80 900 1.000 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752

7.5 1.000 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 10 - 0.963 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 20 - - 0.916 0.880 0.850 0.824 0.803 0.784 0.767 0.752 30 - - - 0.880 0.850 0.824 0.803 0.784 0.767 0.752 40 - - - - 0.850 0.824 0.803 0.784 0.767 0.752HL

α

α

Equivalent pipelength 70 m

HU=10mEquivalent pipelength 40 m

Indoor unit

Outdoor

Indoor unit

Page 64: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 5252

ARWN200LA2

Rate of change in cooling capacity

Ex)

Rate of change in heating capacity

1. SymbolsHU : Level difference between indoor and outdoor units where indoor unit in inferior position (m)HL : Level difference between indoor and outdoor units where indoor unit in superior position (m)L : Equivalent pipe length (m)α : Capacity correction factor

2. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard conditions. (Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.)

3. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.4. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease5. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outdoor units

= cooling / heating capacity of outdoor units obtained from capacity table X capacity correction factor due to piping length to the farthest indoor unit 6. Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1.0 m, calculation purposes.7. When overall equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes.

: ARWN200LA2 gas pipe Ø28.58 Ø31.8 liquid pipe Ø12.7 Ø15.88

8. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length.: overall equivalent length = (equivalent length of main pipe) X correction factor + (equivalent length after first branching)

• (Cooling) Overall equivalent length =70 m x 0.5 + 40 m = 75 m The correction factor in cooling capacity when HU = 10 m is thus approximately0.886

• (Heatng) Overall equivalent length =70 m x 0.3 + 40 m = 61 mThe correction factor in heating capacity when HU = 10 m is thus approximately0.814

correction factor overall equivalent pipe length< 90 m ≥ 90 m

Cooling 1.0 0.5Heating 1.0 0.3

HU50 - - - - - 0.916 0.901 0.888 0.875 0.863 0.851 0.840 0.830 40 - - - - 0.932 0.917 0.903 0.889 0.876 0.864 0.852 0.841 0.831 30 - - - 0.950 0.934 0.918 0.904 0.890 0.877 0.865 0.853 0.842 0.832 20 - - 0.969 0.952 0.935 0.920 0.905 0.891 0.878 0.866 0.854 0.843 0.833 10 - 0.990 0.971 0.953 0.937 0.921 0.907 0.893 0.880 0.867 0.855 0.844 0.834 7.5 0.995 0.990 0.972 0.954 0.937 0.922 0.907 0.893 0.880 0.867 0.856 0.844 0.834 0 1.000 0.992 0.973 0.955 0.938 0.923 0.908 0.894 0.881 0.868 0.856 0.845 0.835 0 7.5 10 20 30 40 50 60 70 80 90 100 110 1200 1.000 0.992 0.973 0.955 0.938 0.923 0.908 0.894 0.881 0.868 0.856 0.845 0.835

7.5 1.000 0.993 0.974 0.956 0.940 0.924 0.909 0.895 0.882 0.869 0.857 0.846 0.835 10 - 0.994 0.975 0.957 0.940 0.924 0.909 0.895 0.882 0.869 0.858 0.846 0.836 20 - - 0.976 0.958 0.942 0.926 0.911 0.897 0.883 0.871 0.859 0.847 0.837 30 - - - 0.960 0.943 0.927 0.912 0.898 0.885 0.872 0.860 0.848 0.838 40 - - - - 0.945 0.929 0.913 0.899 0.886 0.873 0.861 0.849 0.839 HL

L

α

α

HU50 - - - - - 0.840 0.816 0.795 0.777 0.761 0.747 40 - - - - 0.867 0.840 0.816 0.795 0.777 0.761 0.747 30 - - - 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 20 - - 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 10 - 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 7.5 1.000 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 0 1.000 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 0 7.5 10 20 30 40 50 60 70 80 90 1000 1.000 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747

7.5 1.000 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 10 - 0.999 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 20 - - 0.944 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 30 - - - 0.901 0.867 0.840 0.816 0.795 0.777 0.761 0.747 40 - - - - 0.867 0.840 0.816 0.795 0.777 0.761 0.747 HL

L

α

α

Equivalent pipelength 70 m

HU=10mEquivalent pipelength 40 m

Indoor unit

Outdoor

Indoor unit

Page 65: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units5353

ARWN300LA2

Rate of change in cooling capacity

Ex)

Rate of change in heating capacity

1. SymbolsHU : Level difference between indoor and outdoor units where indoor unit in inferior position (m)HL : Level difference between indoor and outdoor units where indoor unit in superior position (m)L : Equivalent pipe length (m)α : Capacity correction factor

2. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard conditions. (Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.)

3. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.4. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease5. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outdoor units

= cooling / heating capacity of outdoor units obtained from capacity table X capacity correction factor due to piping length to the farthest indoor unit 6. Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1.0 m, calculation purposes.7. When overall equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes.

: ARWN300LA2 gas pipe Ø34.9 Ø38.1 liquid pipe Ø15.88 Ø19.05

8. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length.: overall equivalent length = (equivalent length of main pipe) X correction factor + (equivalent length after first branching)

• (Cooling) Overall equivalent length =70 m x 0.5 + 40 m = 75 m The correction factor in cooling capacity when HU = 10 m is thus approximately0.897

• (Heatng) Overall equivalent length =70 m x 0.4 + 40 m = 68 mThe correction factor in heating capacity when HU = 10 m is thus approximately0.834

correction factor overall equivalent pipe length< 90 m ≥ 90 m

Cooling 1.0 0.5Heating 1.0 0.4

Equivalent pipelength 70 m

HU=10mEquivalent pipelength 40 m

Indoor unit

Outdoor

Indoor unit

HU50 - - - - - 0.924 0.911 0.899 0.887 0.876 0.865 0.855 0.845 40 - - - - 0.939 0.925 0.912 0.900 0.888 0.877 0.866 0.856 0.846 30 - - - 0.954 0.940 0.926 0.913 0.901 0.889 0.878 0.867 0.857 0.847 20 - - 0.971 0.956 0.941 0.927 0.914 0.902 0.890 0.879 0.868 0.858 0.848 10 - 0.989 0.973 0.957 0.943 0.929 0.916 0.903 0.891 0.880 0.869 0.859 0.849 7.5 0.994 0.990 0.973 0.958 0.943 0.929 0.916 0.903 0.891 0.880 0.869 0.859 0.849 0 1.000 0.991 0.974 0.959 0.944 0.930 0.917 0.904 0.892 0.881 0.870 0.860 0.850 0 7.5 10 20 30 40 50 60 70 80 90 100 110 1200 1.000 0.991 0.974 0.959 0.944 0.930 0.917 0.904 0.892 0.881 0.870 0.860 0.850

7.5 1.000 0.992 0.975 0.960 0.945 0.931 0.918 0.905 0.893 0.882 0.871 0.860 0.850 10 - 0.992 0.976 0.960 0.945 0.931 0.918 0.905 0.893 0.882 0.871 0.861 0.851 20 - - 0.977 0.962 0.947 0.933 0.919 0.907 0.895 0.883 0.872 0.862 0.852 30 - - - 0.963 0.948 0.934 0.921 0.908 0.896 0.884 0.873 0.863 0.853 40 - - - - 0.950 0.935 0.922 0.909 0.897 0.885 0.874 0.864 0.853 HL

L

α

α

HU50 - - - - - 0.886 0.855 0.829 0.806 0.787 0.770 0.754 40 - - - - 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 30 - - - 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 20 - - 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 10 - 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.7547.5 1.000 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.7540 1.000 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.7540 7.5 10 20 30 40 50 60 70 80 90 100 1100 1.000 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754

7.5 1.000 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.75410 - 1.000 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 20 - - 1.000 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 30 - - - 0.973 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 40 - - - - 0.924 0.886 0.855 0.829 0.806 0.787 0.770 0.754 HL

L

α

α

Page 66: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 5454

ARWN400LA2

Ex)

Rate of change in heating capacity

1. SymbolsHU : Level difference between indoor and outdoor units where indoor unit in inferior position (m)HL : Level difference between indoor and outdoor units where indoor unit in superior position (m)L : Equivalent pipe length (m)α : Capacity correction factor

2. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard conditions. (Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.)

3. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.4. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease5. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outdoor units

= cooling / heating capacity of outdoor units obtained from capacity table X capacity correction factor due to piping length to the farthest indoor unit 6. Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1.0 m, calculation purposes.7. When overall equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes.

: ARWN400LA2 gas pipe Ø41.3 Ø41.3 liquid pipe Ø19.05 Ø22.2

8. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length.: overall equivalent length = (equivalent length of main pipe) X correction factor + (equivalent length after first branching)

• (Cooling) Overall equivalent length =70 m x 1.0 + 40 m = 110 m The correction factor in cooling capacity when HU = 10 m is thus approximately0.874

• (Heatng) Overall equivalent length =70 m x 0.4 + 40 m = 68 mThe correction factor in heating capacity when HU = 10 m is thus approximately1.000

correction factor overall equivalent pipe length< 90 m ≥ 90 m

Cooling 1.0 1.0Heating 1.0 0.4

Equivalent pipelength 70 m

HU=10mEquivalent pipelength 40 m

Indoor unit

Outdoor

Indoor unit

HU50 - - - - - 0.932 0.920 0.910 0.899 0.889 0.880 0.870 0.862 0.853 0.845 0.837 40 - - - - 0.945 0.933 0.922 0.911 0.900 0.890 0.881 0.871 0.862 0.854 0.846 0.838 30 - - - 0.959 0.946 0.934 0.923 0.912 0.901 0.891 0.881 0.872 0.863 0.855 0.846 0.838 20 - - 0.973 0.960 0.947 0.935 0.924 0.913 0.902 0.892 0.882 0.873 0.864 0.855 0.847 0.839 10 - 0.988 0.974 0.961 0.948 0.936 0.925 0.914 0.903 0.893 0.883 0.874 0.865 0.856 0.848 0.840 7.5 0.992 0.989 0.975 0.961 0.949 0.937 0.925 0.914 0.903 0.893 0.883 0.874 0.865 0.856 0.848 0.840 0 1.000 0.990 0.976 0.962 0.950 0.937 0.926 0.915 0.904 0.894 0.884 0.875 0.866 0.857 0.849 0.841 0 7.5 10 20 30 40 50 60 70 80 90 100 110 120 130 140 1500 1.000 0.990 0.976 0.962 0.950 0.937 0.926 0.915 0.904 0.894 0.884 0.875 0.866 0.857 0.849 0.841

7.5 1.000 0.991 0.977 0.963 0.950 0.938 0.927 0.916 0.905 0.895 0.885 0.875 0.866 0.858 0.849 0.841 10 - 0.991 0.977 0.964 0.951 0.939 0.927 0.916 0.905 0.895 0.885 0.876 0.867 0.858 0.849 0.841 20 - - 0.978 0.965 0.952 0.940 0.928 0.917 0.906 0.896 0.886 0.877 0.867 0.859 0.850 0.842 30 - - - 0.966 0.953 0.941 0.929 0.918 0.907 0.897 0.887 0.877 0.868 0.860 0.851 0.843 40 - - - - 0.954 0.942 0.930 0.919 0.908 0.898 0.888 0.878 0.869 0.860 0.852 0.844 HL

L

α

α

HU50 - - - - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 40 - - - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 30 - - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 20 - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 10 - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 7.5 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 0 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 0 7.5 10 20 30 40 50 60 70 80 90 100 1100 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000

7.5 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 10 - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 20 - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 30 - - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 40 - - - - 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 HL

L

α

α

0.829 0.818 0.830 0.8190.831 0.820 0.831 0.8200.832 0.821 0.832 0.821 0.833 0.822 160 1750.833 0.822 0.833 0.8220.834 0.822 0.834 0.8230.835 0.824 0.836 0.825

Page 67: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units5555

8. Operation Limits

Notes:These figures assume the following operating conditions:

Equivalent piping length:7.5m

Level difference:0m

Inle

t wat

er te

mpe

ratu

re (

°C)

Inle

t wat

er te

mpe

ratu

re (

°C)

Indoor temperature (°CWB) Indoor temperature (°CDB)

Range for continuous Range for operation

Range for pull down operation Range for warming up operation

Cooling Heating

10 15 20 25 30151010

15

20

25

30

35

45

40

10

15

20

25

30

35

45

40

20 25 30

Page 68: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units 5656

9. Sound Levels

Notes:• Data is valid at free field condition• Data is valid at nominal operating condition• Sound level will vary depending on a range of factors

such as the construction(acoustic absorption coefficient) of particular room inwhich the equipment is installed

• The operating conditions are assumed to bestandard(ISO conditions)

Unit:dB(A)

1m

1m

ARWN100LA2 ARWN200LA2 ARWN300LA2

ARWN400LA2

10

20

30

40

50

60

70

80

63 125 250 500 1000 2000 4000 8000Octave Band Center Frequency (Hz)

Oct

ave

Ban

d S

ound

Pre

ssur

e Le

vel (

dB re

20µ

Pa

)

Octave Band Center Frequency (Hz)

Oct

ave

Ban

d S

ound

Pre

ssur

e Le

vel (

dB re

20µ

Pa

)

Octave Band Center Frequency (Hz)

Oct

ave

Ban

d S

ound

Pre

ssur

e Le

vel (

dB re

20µ

Pa

)

Octave Band Center Frequency (Hz)

Oct

ave

Ban

d S

ound

Pre

ssur

e Le

vel (

dB re

20µ

Pa

)

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearing

Threshold10

20

30

40

50

60

70

80

63 125 250 500 1000 2000 4000 8000

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearing

Threshold

10

20

30

40

50

60

70

80

63 125 250 500 1000 2000 4000 8000

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearing

Threshold

10

20

30

40

50

60

70

80

63 125 250 500 1000 2000 4000 8000

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearing

Threshold

Model 50Hz

ARWN100LA2 51

ARWN200LA2 51

ARWN300LA2 53

ARWN400LA2 54

Page 69: Multi V Water PDB(08.04.10_)final .pdf

Outdoor Units5757

10. Accessories

No. Name Model

ARBLN01620

1 Y branch pipeARBLN03320

ARBLN07120

ARBLN14520

ARBL054

ARBL057

2 HeaderARBL104

ARBL107

ARBL1010

ARBL2010

Optional Accessories

Page 70: Multi V Water PDB(08.04.10_)final .pdf

Installation

Installation of Outdoor Units

1. Select the Installation Location

2. Installation Space

3. Water Control

4. Lifting Method

5. Installation

6. Refrigerant Piping System

7. Y Branch and Header Branch Pipe type

8. Leakage test and Vaccum

9. Electrical Wiring

10. Test Run

11. Site air conditioner/heater management sheet

12. Water cooling type cooling tower applied method

13. Caution For Refrigerant Leak

Page 71: Multi V Water PDB(08.04.10_)final .pdf

Installation11

1. Select Installation Location

1. Do not install Multi V water outdoor. Always install indoor like machine room.2. Inverter product may generate electric noise. Keep the body from computer, stereo etc. at

enough distance. Specially leave space from indoor remote controller to shoes electric devicesat the above 3m in weak electric wave area. Insert the power cable and other wire into separateconduit.

CAUTION

1.1 Precaution when selecting the installation location• Select space for installation outdoor unit, which will meet the following conditions.• With strength which bears weight of unit• With space for air passage and service work

Don't install the unit at the space where generation, inflow, stagnation, and leak of combustible gas is expected.• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.• Location with no leakage of combustible gas• Recommend the outdoor unit to be installed within 0~40°∆C.• Location with installation or service work space (Refer to required space)• Do not use the outdoor unit under any special environment where oil, steam and sulfuric gas exist. • Install in a separate machine room not exposed to external air

- Establish an anti-freeze plan for the water supply when the product is stopped during the winter.- Install the product so that the noise from the machine room is not transferred outdoors

• The floor of the machine room must be water proof.• Drainage must be installed in the machine room to process the water drainage. • Install a floor slope to make the drainage smooth. • Avoid installing the outdoor unit in the location with following conditions.• Location where corrosive gas such as acidic gas is generated. (It may cause the refrigerant leakage by corrosion of

the pipe.)• Location where electromagnetic waves happen. (It may cause the abnormal operation by control parts disorder.)• Location to be able to leak the combustible gas• Location with carbon fiber or combustible dust.• Location with the combustible material like thinner or gasoline. (It may cause a fire by leaking the gas near the prod-

uct.)

Page 72: Multi V Water PDB(08.04.10_)final .pdf

Installation 22

2. Installation space

2.1 Individual Installation

2.2 Collective / Continuous Installation

Required the minimum space as shown below for installation andcheck. If the space is not fit on this drawing, consult with LG.

Space required for collective installation and continuous installation as shown below considering passage for airand people.

: Service area

* In case of the water pipe passing side product, please make sufficient service place to avoid occurringbetween water pipe and product side.

1) In case of the water pipe passing overthe product

: Service area

300 300

350

772

Water pipeinstallation space

Service areaH-Beam Support

(unit : mm)

600

547

1120

100

100

20

Product(Outdoor unit)

<Top View> <Front View>

Service area(Front)

Product(Outdoor unit)

Product(Outdoor unit)

(Unit : mm)

<Top view>

20

350 350

772 100 772 100

600

547

20

Page 73: Multi V Water PDB(08.04.10_)final .pdf

Installation33

3. Water control

3.1 Water control• Keep the water temperature between 10~45°C. Other it may cause the breakdown.

- Standard water supply temperature is 30°C for air conditioning and 20°C for heating.• Properly control the water velocity. Otherwise it may cause the noise, pipe vibration or pipe contraction, expansion

according to the temperature. Use the same water pipe size connected with the product or more.• Refer to the water source pipe diameter and water velocity table below. As the water velocity is fast, air bubble will

increase.

• Be careful of the water purity control. Otherwise it may cause the breakdown due to water pipe corrosion. (Refer to 'Standard Table for Water Purity Control')

• In case the water temperature is above 40°C, it is good to prevent the corrosion by adding the antifreeze agent. • Install the pipe, valve and gauge sensor in the space where it is easy to maintain. Install the water valve in the low posi-

tion for drain, if required.• Be careful not to let air in. If so, the water velocity will be unstable in the circulation, pump efficiency will also decrease

and may cause the piping vibration. Therefore, install the air purge where it may generate the air.• Choose the following anti freezing methods. Otherwise, it will be dangerous for the pipe to break in the winter.

- Circulate the water with the pump before dropping the temperature. - Keep the normal temperature by boiler.- When the cooling tower is not operated for a long time, drain the water in the cooling tower.- Use an anti-freeze.- Refer to the additive amount about freezing temperature as in the table given below.

• In addition to anti freeze, it may cause the change of the pressure in the water system and the low performance of theproduct.

• Make sure to use the closed cooling type tower. When applying the open type cooling tower, use a middle heat exchanger to make the water supply system a closedtype system.

Diameter (mm) Velocity range (m/s)

>125 2.1~2.7

50~100 1.2~2.1

25 0.6~1.2

Minimum temperature for anti freezing

0 -5 -10 -15 -20 -25

Ethylene glycol (%) 0 12 20 30 - -

Propylene glycol (%) 0 17 25 33 - -

Methanol (%) 0 6 12 16 24 30

Anti freeze type

Page 74: Multi V Water PDB(08.04.10_)final .pdf

Installation 44

3.2 Standard table for water purity controlThe water may contain many foreign substances and hence may influence the performance and lifetime of the productdue to the corrosion of the condenser and water pipe. (Use water source that complies with the below standard table forwater purity control.)If you use water supply other than the tap water to supply the water for the cooling tower, you must do a water qualityinspection. • For closed type water cooling type water supply, the water quality must be controlled in accordance with the following

standard table. If you do not control the water quality in accordance with the following standard water quality table, it can cause perfor-mance deterioration to the air conditioner and severe problem to the product

[Reference](1) The O mark for corrosion and scale means that there is possibility of occurrence. (2) When the water temperature is 40°∆C or above or when uncoated iron is exposed to the water, it can result in corrosion.

Therefore adding anti-corrosion agent or removing the air can be very effective. (3) In the closed type circuit using the closed type cooling tower, the cooling water and supplementing water must satisfy the

water quality criteria of closed type system in the table. (4) Supplementing water and supplied water must be supplied with tap water, industrial water and underground water

excluding filtered water, neutral water, soft water etc. (5) 15 items in the table are general causes of corrosion and scale.

Items

pH(25°C)

Conductivity

Chlorine ion

Sulfuric acid ion

Acid demand

Total hardness

Ca hardness

Ion silica

Fe

Copper

Sulfuric acid ion

Ammonium ion

Residual chlorine

Free carbon dioxide

Stability index

7.0~8.0

Below 30

Below 50

Below 50

Below 50

Below 70

Below 50

Below 30

Below 1.0

Below 1.0

Must not be detected

Below 0.3

Below 0.25

Below 0.4

-

Below 0.3

Below 0.1

Must not be detected

Below 0.1

Below 0.3

Below 4.0

-

7.0~8.0

Below 30

Below 50

Below 50

Below 50

Below 70

Below 50

Below 30

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

Closed type Effect

Circulating water Supplemented water Corrosion Scale

Page 75: Multi V Water PDB(08.04.10_)final .pdf

Installation55

4. Lifting method• When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each

at the front and rear.

• Always lift the unit with ropes attached at fours points so that impact is not applied to the unit.

• Attach the ropes to the unit at an angle of 40°∆ or less

• Do not have only one person carry product if it is more than 20kg.

• PP bands are used to pack some products. Do not use them as a means for transportation because theyare dangerous.

• Tear the plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic pack-aging bag may suffocate children to death.

• When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point sup-port may make outdoor unit unstable, resulting in a fall of it.

• When carrying with the forklift, be careful not to drop the product.

40° or lessRope supporter

AB

Sub line

CAUTION

Page 76: Multi V Water PDB(08.04.10_)final .pdf

Installation 66

• Be sure to install unit in a place strong enough to withstand its weight.Any lack of strength may cause unit to fall down, resulting in a personal injury.

• Have installation work in order to protect against a strong wind and earthquake. Any installation defi-ciency may cause unit to fall down, resulting in a personal injury.

• Especially take care for support strength of the floor surface, water drain processing (processing ofwater flown out from the outdoor unit during operation) and paths of the pipe and wiring when makinga base support.

WARNING

5. Installation

5.1 Location of anchor bolt

The location of anchor bolt

5950

13

599

658

(Unit: mm)

Page 77: Multi V Water PDB(08.04.10_)final .pdf

Installation77

5.2 Preparation of Piping

1) Cut the pipes and the cable. Use the accessory piping kit or the pipes purchased

locally. Measure the distance between the indoor and the out-

door unit. Cut the pipes a little longer than measured distance. Cut the cable 1.5m longer than the pipe length.

2) Burrs removal Completely remove all burrs from the cut cross section

of pipe/tube. Put the end of the copper tube/pipe to downward direc-

tion as you remove burrs in order to avoid to let burrsdrop in the tubing.

3) Flaring work Carry out flaring work using flaring tool as shown below.

Firmly hold copper tube in a bar(or die) as indicateddimension in the table above.

4) Check Compare the flared work with figure below. If flare is noted to be defective, cut off the flared section

and do flaring work again.

Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.

Coppertube 90° Slanted Uneven Rough

Pipe

Reamer

Point down

Bar

Copper pipe

Clamp handleRed arrow mark

Cone

Yoke

Handle

Bar"A"

Inclined

Inside is shining without scratches.

Smooth all round

Even lengthall round

Surfacedamaged

Cracked Uneventhickness

= Improper flaring =

Pipe " A "Gas Liquid Gas Liquid

<5.6(19,100) Ø12.7 Ø6.35 1.6~1.8 1.1~1.3<16.0(54,600) Ø15.88 Ø9.52 1.6~1.8 1.5~1.7<22.4(76,400) Ø19.05 Ø9.52 1.9~2.1 1.5~1.7

Indoor unit[kW(Btu/h]

Page 78: Multi V Water PDB(08.04.10_)final .pdf

Installation 88

1. Follow the pipe path. Bend the pipe more than 3 times in 1 location and do not bend in the opposite direction. (This willstrengthen the pipe.)

2. After deforming the pipe, align the union fitting and center of the pipe, and tighten it with the wrench. 3. Connect the pipe to the service valve of the outdoor unit. 4. After finishing the piping work, check if there is any gas leakage 5. For the flare nut, always use the material that complies with KS B 0206 or better. 6. After completing the connection of the pipe, vacuum dry the indoor unit and the connecting pipe.

For the vacuum drying, you must use service ports of both the gas and liquid pipes.

CAUTIONWhen using two wrenches, tighten at regulated torque * For the pipe connection, use the method of connecting the end of the pipe to the branch pipe. The refrigerant pipe

coming out from the outdoor unit is branched out at the end and is individually connected to the indoor unit.

WARNING• Always be careful not to leak the refrigerant during the welding.• When the refrigerant is combusted, it generates a toxic poisonous gas.• Do not execute the welding work in a closed location.• Always do a leakage test after welding the pipes.

Pipe Size Tightening Torque(mm) (N·m) (kgf·cm)Ø6.35 18~25 180~250Ø9.52 34~42 340~420Ø12.7 55~66 550~660Ø15.88 63~82 630~820Ø19.05 99~121 990~1,210

After completing work, securely tighten both service ports and caps so that gas does not leak.

Open status when both the pipe and the valve are in a straight line.

Cut both the pipe and the valve with a cutter to suit the length (Don't cut the length of less than 70mm)

CLOSE OPEN

WARNING

4) Pipe connection

Page 79: Multi V Water PDB(08.04.10_)final .pdf

Installation99

CAUTIONAfter installing the pipe, block the pipe escape of front and side panel. (It can cause mouse or other animals to enter andcause damage to the wire.)

* High/low pressure side is the ball valve that is opened and closedby 1/4 rotation

Pipe joint (auxiliary parts): Securely perform brazing with a nitro-gen blow into the service valve port.(Releasing pressure : 0.02MPa or less)Flare nut: Loose or tighten flare nut by using the wrench withboth ends. Coat the flare connection part with oil for the com-pressor. Cap: Remove caps and operate valve, etc. After operation,always reattach caps (tightening torque of valve cap: 25Nm(250kg-cm) or more). (Don't remove the internal part of the port)Service port: Make the refrigerant pipe vacuum and charge itusing the service port. Always reattach caps after completingwork (tightening torque of service cap: 14Nm (140kg-cm) ormore).Liquid pipe Gas pipe Elbow joint (field supply) Elbow

Ball Valve(Gas Pipe)

Ball Valve(Liquid Pipe)

1. Use the heat insulation material for the refrigerantpiping which has an excellent heat-resistance (Over120°C)

2. When installing in a humid environment, use thickerheat insulation material. * Consult with LG on detailed technical specification. Indoor unit

Thermal insulator (accessory)

Fastening band (accessory)

Refrigerant piping

5) Heat Insulation

Page 80: Multi V Water PDB(08.04.10_)final .pdf

Installation 1010

* Note 1) General location: When the pipe passes through indoors in which the indoor unit is operated- Apartment, classroom, office, mall, hospital, office-tel etc.

Note 2) Special location1. When the location is air conditioned but has severe temperature/humidity difference due to high ceiling

- Church, auditorium, theater, lobby etc.2. When the location is air conditioned but the internal temperature/humidity of the ceiling finishing is high

- Bathroom/swimming pool locker room etc. (Building with roof ceiling of sandwich assembly type)Note 3) General location: When the pipe passes indoors where the indoor unit is not operated- Hall way etc. (Dormitory, school, office-tel)

Note 4) Negative condition: When below conditions 1 and 2 are met.1. When the pipe passes indoors where the indoor unit is not operated2. When the humidity is high, regionally, and there is no air flow in the pipe passing area

- When installing the outdoor unit within the outdoor pipe tray or at a location where it is ok to havefreezes, apply 13t.

- If you are not sure with the selection of heat insulation material, coordinate with the supervision or HQ.- The thickness of the above heat insulation material is based on the heat conductivity of 0.088W/m°C.

6) Standard refrigerant pipe EPDM heat insulation material thickness

Classification

Ø6.35Ø9.52

Above Ø12.7Ø9.52Ø12.7Ø15.88Ø19.05Ø22.22Ø25.4Ø28.58Ø31.75Ø34.9Ø38.1Ø44.45

Above 9t

Above 13t

Above 9t

Above 13t

Above 9t

Above 13t

Above 9t

Above 13t

Above 13t

Above 19t

Above 19t

Above 25t

Above 19t

Above 25t

Above 25t

Liquidpipe

Gaspipe

Air conditioned location Note1) General location Note1) Special location Note3) General location Note4) Negative condition

Non-air conditioned location

Page 81: Multi V Water PDB(08.04.10_)final .pdf

Installation1111

When installing the branch pipe vertically between the outdoor units, the refrigerant can be unevenbetween the outdoor units, leading to compressor burn and reduced capacity

CAUTION

SlaveOutdoor Unit

MasterOutdoor Unit

2 Outdoor Units

1. For the high/low pressure common pipe, connect both mas-ter outdoor unit and slave outdoor units to the pipe by usingelbows.

2. For cutting the pipe, connect the high/low pressure commonpipe after removing burrs, dusts and foreign material withinthe pipe. Otherwise, the product may not operate due tosludge within the pipe.

3. For the working part leakage test, apply the nitrogen gaspressure of 3.8MPa (38.7kgf/cm2).

4. The vacuum criteria is to maintain the vacuum level to lessthan 5 Torr 1 hour after reaching 5 Torr. (Execute the vacu-um work again when it is below the criteria.)

5. Open the valve with the hexagon wrench.

* Install the branch pipe between outdoor units sothat the outlet pipe is parallel to the surface.

7) Connection of high/low pressure common pipe

8) Connecting branch pipe between outdoor units

Connectingbranch pipeCombination specification Gas pipe Liquid pipe

Do not cut for 70mm or less

Execute the welding while pouring nitrogen

Outdoor pipe

Outdoor pipe

Main pipe Main pipe ARCNN20

Horizontal installationLocation when viewed from B

Horizontal surface

A. Outdoor unit sideB. Connecting outdoor unit side

Page 82: Multi V Water PDB(08.04.10_)final .pdf

Installation 1212

8) Installation of water pipe1. Water pipe system diagram

• The water pressure resistance of the water pipe system of this product is 1.98MPa

• When the water pipe passes indoors, make sure to execute heat insulation on the pipe so that water drops do not form on theouter side of the water pipe.

• The size of the drain pipe must be equal to or larger than the diameter of the connecting product. - Always install a trap so that the drained water does not back flush.

• Always install a strainer (50Mesh or above) at the entrance of the water pipe. (When sand, trash, rusted pieces get mixed intothe water supply, it can cause problems to the product due to corrosion.)- The ON/OFF valve blocks the water supply to the outdoor unit that is not operating to save the pump power. Select appro-

priate on whether to install this or not for the site.

• Install a pressure gauge at the inlet and outlet of the water pipe.

• Flexible joints must be installed not to cause any leakage from the vibration of pipes.

• Install a service port to clean the heat exchanger at the each end of the water inlet and outlet.

• For the components of the water pipe system, always use components above the designed water pressure.

2. Water pipe connection

• The water pipe should be the same size of the connection on the product or more.

• Be sure to install the insulation material in the water pipe inlet/outlet to prevent water drop, freeze and to save energy. (Use the above 20mm thickness Pe insulation material.)

• Tightly connect the socket to the water pipe refer to below table for recommended specification. (Too much torque may cause the damage of the facility.)

Water pipeoutlet Gate valve

Gate valve

Service port

Pressure gauge

Service port

Strainer

Drain line Condensedwater drain

Water pipeInlet

Do not directly connect the drain outlet to the water pipe outlet. (It can cause problems to the product.)

CAUTION

Page 83: Multi V Water PDB(08.04.10_)final .pdf

Installation1313

Water pipeconnection 3

Water pipe inlet

Water pipe outlet

mm inch (kN) (kgf) (kN) (kgf) (N.m) (kgf.m)(N.m) (kgf.m)

12.7 1/2 3.5 350 2.5 250 20 23 5 3.5

19.05 3/4 12 1200 2.5 250 20 2 115 11.5

25.4 1 11.2 1120 4 400 45 4.5 155 15.5

31.8 1 1/4 14.5 1450 6.5 650 87.5 8.75 265 26.5

38.1 1 1/2 16.5 1.7 9.5 0.95 155 16 350 35.5

50.8 2 21.5 2.2 13.5 1.4 255 26 600 61

Pipe thickness Shear stress Tensile stress Bending moment Torque

Page 84: Multi V Water PDB(08.04.10_)final .pdf

Installation 1414

6. Refrigerant piping system

Refrigerant pipe diameter frombranch to branch (B,C,D)

Total pipe length =A+B+C+D+a+b+c+d+e ≤ 300m

Outdoor unit A ~ 1st branch B: Main pipe diameter

L Below 150 m

Bel

ow H

50

m

Below 40 m

Below 15 m

Indoor unitdirection

• When the pipe diameter (B) connected after 1st branching is larger than the main pipe diameter (A), Install the pipewith the pipe diameter (B) after 1st branching that is the same as the main pipe diameter (A). Ex) When connecting with 120% of the indoor unit to 10 HP1) Outdoor unit main pipe diameter: 22.2 (Gas pipe) / 9.52(Liquid pipe)2) Pipe diameter after 1st branching by 120% indoor unit combination : 28.58 (Gas pipe) / 12.7 (Liquid pipe)Therefore set the pipe diameter (B) after 1st branching to 22.2 (Gas pipe) / 952 (Liquid pipe) of main pipe diameter (A).

• When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you mustchange the main pipe diameter according to the outdoor unit capacity in accordance with the following table. (Thisapplies to both the liquid and gas pipes.)

WARNING

Total capacity of indoor units con-nected to after branching (kW)

< 5.6 Ø6.35 Ø12.7< 16 Ø9.52 Ø15.88

< 22.4 Ø9.52 Ø19.05< 33 Ø9.52 Ø22.2< 47 Ø12.7 Ø28.58< 71 Ø15.88 Ø28.58< 104 Ø19.05 Ø34.9104 ≤ Ø19.05 Ø41.3

Liquid pipe (mm)

Gas pipe (mm)

6.1 Y branch method6.1.1 When installing 1 outdoor unit

independently

Ex) 5 indoor units connected: Outdoor unit: 1st branch (Y branch) : Indoor units: Indoor unit

For the first branch pipe (B), use the branch pipethat fits the main pipe diameter (A).

Longest pipe length (Top pipe length) A + B + C + D + e 150 m(175 m)Longest pipe length after 1st branching B + C + D + e 40 mHigh/Low difference (Outdoor unit ↔ Indoor unit)H 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit ↔ Indoor unit)h 15 m

L

H

h

Gas Pipe Liquid Pipe10 HP ...........................................Ø22.2 Ø25.4 10 HP...........................................Ø9.52 Ø12.720 HP ...........................................Ø28.58 Ø31.8 20 HP...........................................Ø12.7 Ø15.88

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 10 HP Ø9.52 Ø22.220 HP Ø12.7 Ø28.58

Page 85: Multi V Water PDB(08.04.10_)final .pdf

Installation1515

Below 2m

Master

Slave

L Below 150 m

Bel

ow H

50

m

Below 40 m

Below 15 m

Indoor unitdirection

Below 10m

Slave outdoor unit ~ Connectingbranch pipe (E): Pipe diameterbetween outdoor units (E)

Connecting branch pipe E ~ 1stbranch part B: Main pipe diameter (A)

Refrigerant pipe diameter from branchto branch (B, C, D)

Total refrigerant pipe length = A + B + C + D + a + b + c + d + e ≤ 300 m

Total capacity of indoorunits connected to after

branching (kW)< 5.6 Ø6.35 Ø12.7< 16 Ø9.52 Ø15.88

< 22.4 Ø9.52 Ø19.05< 33 Ø9.52 Ø22.2< 47 Ø12.7 Ø28.58< 71 Ø15.88 Ø28.58

< 104 Ø19.05 Ø34.9104 ≤ Ø19.05 Ø41.3

Liquid pipe (mm)

Gas pipe (mm)

6.1.2 When installing 1 outdoor units

Ex) 5 indoor units connected: Outdoor unit

: 1st branch

: Indoor units

: Indoor unit direction

: Connecting branch pipe between out-door units

Connecting branch pipe between outdoorunits: ARRCN20( )

For the first branch pipe (B), use the branch pipethat fits the main pipe diameter (A).

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 30 HP Ø15.88 Ø34.940 HP Ø19.05 Ø41.3

Longest pipe length (Top pipe length) A + B + C + D + e 150 m(175 m)Longest pipe length after 1st branching B + C + D + e 40 mHigh/Low difference (Outdoor unit ↔ Indoor unit)H 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit ↔ Indoor unit)h 15 mHigh/Low difference (Indoor unit ↔ Indoor unit)h 2 m

L

H

h

h1

• When the pipe diameter (B) connected after 1st branching is larger than the main pipe diameter (A), Install the pipe with the pipe diameter (B)after 1st branching that is the same as the main pipe diameter (A). Ex) When connecting with 120% of the indoor unit to 10 HP.1) Outdoor unit main pipe diameter: 22.2 (Gas pipe) / 9.52(Liquid pipe)2) Pipe diameter after 1st branching by 120% indoor unit combination : 28.58 (Gas pipe) / 12.7 (Liquid pipe)Therefore set the pipe diameter (B) after 1st branching to 22.2 (Gas pipe) / 9.52 (Liquid pipe) of main pipe diameter (A).

• When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you must change the main pipe diame-ter according to the outdoor unit capacity in accordance with the following table. (This applies to both the liquid and gas pipes.)

WARNING

Liquid pipe (mm) Gas pipe (mm) Low/high pressure

common pipe

Ø9.52/12.7 Ø22.2/28.58 Ø19.05

Gas Pipe Liquid Pipe30 HP ...........................................Ø37.9 Ø38.1 30 HP...........................................Ø15.88 Ø19.0640 HP ...........................................Ø41.3 40 HP...........................................Ø19.05 Ø22.2

Page 86: Multi V Water PDB(08.04.10_)final .pdf

Installation 1616

L Below 150 m

Bel

ow H

50

m

Below 40 m

Below 15 m

Total refrigerant pipe length = A +a +b +c +d +e +f ≤ 300 m

6.2 Header branch method6.2.1 When installing 1 outdoor unit inde-

pendently

Ex) 6 indoor units connectedOutdoor unit

Header branch

Indoor unit

Seal

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 10 HP Ø9.52 Ø22.220 HP Ø12.7 Ø28.58

Longest pipe length (Top pipe length) A +f ≤ 150 m(175 m)Longest pipe length after 1st branching f ≤ 40 mHigh/Low difference (Outdoor unit <-> Indoor unit)H ≤ 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit <-> Indoor unit)h ≤ 15 m

L

H

h

• For the pipe length after the header branch (a~f), it is recommended to install the unit so that the difference of the pipe dis-tance connected to the indoor unit is minimized.

• The large difference in pipe distance can cause performance difference between indoor units. • The indoor unit must be installed at a lower location than the header branch. • After the header branch, you cannot use the Y branch and header branch. • When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you must change the

main pipe diameter according to the outdoor unit capacity in accordance with the following table. (This applies to both the liquid and gas pipes.)

WARNING

Outdoor unit A ~ Header branchpart B: Main pipe diameter (A)

Page 87: Multi V Water PDB(08.04.10_)final .pdf

Installation1717

Master

Slave

L Below 150 m

Bel

ow H

50

m

Below 40 m

Below 15 m

Below 10m

Below 2m

Slave outdoor unit ~ Connectingbranch unit E: Pipe diameterbetween outdoor units

Connecting branch pipe E ~ Header branch part B: Main pipe diameter (A)

6.2.2 When installing 2 outdoor units

Ex) 6 indoor units connected: Outdoor unit

: Header branch

: Indoor unit

: Seal

: Connecting branch pipe between out-door units

Connecting branch pipe between outdoorunits: ARRCN20( )

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 30 HP Ø15.88 Ø34.940 HP Ø19.05 Ø41.3

• For the pipe length after the header branch (a~f), it is recommended to install the unit so that the difference of the pipe dis-tance connected to the indoor unit is minimized.

• The large difference in pipe distance can cause performance difference between indoor units. • The indoor unit must be installed at a lower location than the header branch. • After the header branch, you cannot use the Y branch and header branch. • When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you must change the

main pipe diameter according to the outdoor unit capacity in accordance with the following table. (This applies to both the liq-uid and gas pipes.)

WARNING

Liquid pipe (mm) Gas pipe (mm) Low/high pressure

common pipe

Ø9.52/12.7 Ø22.2/28.58 Ø19.05

Total refrigerant pipe length = A + B + C + D + a + b + c + d + e ≤ 300 m

Longest pipe length (Top pipe length) A +f ≤ 150 m(175 m)Longest pipe length after 1st branching f ≤ 40 mHigh/Low difference (Outdoor unit ↔ Indoor unit)H 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit ↔ Indoor unit)h 15 mHigh/Low difference (Indoor unit ↔ Indoor unit)h1 2 m

L

H

h

h1

Gas Pipe Liquid Pipe

30 HP ...........................................Ø37.9 Ø38.1 30 HP...........................................Ø15.88 Ø19.06

40 HP ...........................................Ø41.3 40 HP...........................................Ø19.05 Ø22.2

Page 88: Multi V Water PDB(08.04.10_)final .pdf

Installation 1818

* For the first branch pipe (B), use the branch pipethat fits the main pipe diameter (A)

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 10 HP Ø9.52 Ø22.220 HP Ø12.7 Ø28.58

Refrigerant pipe diameter frombranch to branch (B, C)

Total pipe length =A +B +C +a +b +c +d +e ≤ 300 m

Outdoor unit A ~ 1st Y branchpart B: Main pipe diameter (A)

L Below 150 m

Bel

ow H

50

m

Below 40 m

h B

elow

15

m• When the pipe diameter (B) connected after 1st branching is larger than the main pipe diameter (A), Install the pipe

with the pipe diameter (B) after 1st branching that is the same as the main pipe diameter (A). Ex) When connectingwith 120% of the indoor unit to 10 HP.1) Outdoor unit main pipe diameter: 22.2 (Gas pipe) / 9.52 (Liquid pipe)2) Pipe diameter after 1st branching by 120% indoor unit combination : 28.58 (Gas pipe) / 12.7 (Liquid pipe)Therefore set the pipe diameter (B) after 1st branching to 22.2 (Gas pipe) / 952 (Liquid pipe) of main pipe diameter (A).

• For the pipe length after the header branch (c~e), it is recommended to install the unit so that the difference of the pipedistance connected to the indoor unit is minimized.

• The large difference in pipe distance can cause performance difference between indoor units. • The indoor unit must be installed at a lower location than the header branch. • After the header branch, you cannot use the Y branch and header branch. • When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you must

change the main pipe diameter according to the outdoor unit capacity in accordance with the following table. (Thisapplies to both the liquid and gas pipes.)

WARNING

Total capacity of indoor units con-nected to after branching (kW)

< 5.6 Ø6.35 Ø12.7< 16 Ø9.52 Ø15.88

< 22.4 Ø9.52 Ø19.05< 33 Ø9.52 Ø22.2< 47 Ø12.7 Ø28.58< 71 Ø15.88 Ø28.58< 104 Ø19.05 Ø34.9104 ≤ Ø19.05 Ø41.3

Liquid pipe (mm)

Gas pipe (mm)

6.3 Y/Header branch method6.3.1 When installing 1 outdoor unit inde-

pendently

Ex) 5 indoor units connected: Outdoor unit: 1st Y branch: 2nd Y branch: Indoor unit: Header branch: Seal

Longest pipe length (Top pipe length) A +B +b,A +C +e ≤ 150 m(175 m)Longest pipe length after 1st branching B +b,C +e ≤ 40 mHigh/Low difference (Outdoor unit ↔ Indoor unit)H 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit ↔ Indoor unit)h 15 m

L

H

h

Gas Pipe Liquid Pipe10 HP ...........................................Ø22.2 Ø25.4 10 HP...........................................Ø9.52 Ø12.720 HP ...........................................Ø28.58 Ø31.8 20 HP...........................................Ø12.7 Ø15.88

Page 89: Multi V Water PDB(08.04.10_)final .pdf

Installation1919

Master

Slave

L Below 150 m

H B

elow

50

m

Below 40 m

h B

elow

15

m

Below 10m

Below 2m

Slave outdoor unit ~ Connectingbranch pipe G: Pipe diameterbetween outdoor units (E)

Connecting branch pipe G ~ 1st Ybranch part B: Main pipe diameter (A)

Refrigerant pipe diameter from branchto branch (B, C)

Total refrigerant pipe length = A + B + C + a + b + c + d + e ≤ 300 m

Total capacity of indoor units connected to after branching (kW)

< 5.6 Ø6.35 Ø12.7< 16 Ø9.52 Ø15.88

< 22.4 Ø9.52 Ø19.05< 33 Ø9.52 Ø22.2< 47 Ø12.7 Ø28.58< 71 Ø15.88 Ø28.58

< 104 Ø19.05 Ø34.9104 ≤ Ø19.05 Ø41.3

Liquid pipe (mm)

Gas pipe (mm)

6.3.2 When installing 2 outdoor unitsEx) 5 indoor units connected

: Outdoor unit: 1st Y branch: 2nd Y branch: Indoor unit: Header branch: Seal: Connecting branch pipe between outdoor units

Connecting branch pipe between outdoor units:ARRCN20( )

For the first branch pipe (B), use the branch pipethat fits the main pipe diameter (A).

Outdoor unit capacity Liquid pipe (mm) Gas pipe (mm) 30 HP Ø15.88 Ø34.940 HP Ø19.05 Ø41.3

Longest pipe length (Top pipe length) A +B +b,A +C +e ≤ 150 m(175 m)Longest pipe length after 1st branching B +b,C +e ≤ 40 mHigh/Low difference (Outdoor unit ↔ Indoor unit)H 50 m(40m: When the outdoor unit is low) High/Low difference (Indoor unit ↔ Indoor unit)h 15 mHigh/Low difference (Indoor unit ↔ Indoor unit)h 2 m

L

H

h

h1

• When the pipe diameter (B) connected after 1st branching is larger than the main pipe diameter (A), Install the pipewith the pipe diameter (B) after 1st branching that is the same as the main pipe diameter (A). Ex) When connecting with 120% of the indoor unit to 10 HP.1) Outdoor unit main pipe diameter: 22.2 (Gas pipe) / 9.52 (Liquid pipe)2) Pipe diameter after 1st branching by 120% indoor unit combination : 28.58 (Gas pipe) / 12.7 (Liquid pipe)Therefore set the pipe diameter (B) after 1st branching to 22.2 (Gas pipe) / 952 (Liquid pipe) of main pipe diameter (A).

• For the pipe length after the header branch (c~e), it is recommended to install the unit so that the difference of the pipedistance connected to the indoor unit is minimized.

• The large difference in pipe distance can cause performance difference between indoor units. • The indoor unit must be installed at a lower location than the header branch. • After the header branch, you cannot use the Y branch and header branch. • When the pipe distance corresponding to the farthest indoor unit from the outdoor unit is 90m or above, you must

change the main pipe diameter according to the outdoor unit capacity in accordance with the following table. (Thisapplies to both the liquid and gas pipes.)

WARNING

Liquid pipe (mm) Gas pipe (mm) Low/high pressure

common pipe

Ø9.52/12.7 Ø22.2/28.58 Ø19.05

Gas Pipe Liquid Pipe30 HP ...........................................Ø37.9 Ø38.1 30 HP...........................................Ø15.88 Ø19.0640 HP ...........................................Ø41.3 40 HP...........................................Ø19.05 Ø22.2

Page 90: Multi V Water PDB(08.04.10_)final .pdf

Installation 2020

6.4 Oil trap application method between outdoor units• Because of the possibility of oil being accumulated in the outdoor unit that has stopped, when there is a height difference between

outdoor unit pipes or if the pipe distance between the outdoor units is over 2m, you must always apply an oil trap. (But, the oil trapbetween outdoor units is limited to 1 time and is only applied to the gas pipe.)

• If the pipe distance between the outdoor units is 2m or below, and if the location of the main pipe is lower than that of the outdoorunit and if the location of the main pipe is lower than that of the outdoor unit, the oil trap does not have to be applied.

• If the location of the main pipe is higher than the location of the outdoor unit, be careful since the oil can be accumulated in thestopped outdoor unit.

• If there is high/low difference between the outdoor unit pipes, oil can be accumulated to the outdoor unit on the lower location untilthe unit stops.

High/Low difference between the outdoor units

Location ofmain pipe 2m or less

Location ofmain pipe 2m or less

Oil trapOver 200mm

Over 2m

Location ofmain pipe 2m or less

Oil trap

Location ofoutdoor unit

Location of main pipe

/Low difference etween outdoor

unit pipes

High/Low difference between outdoor

unit pipes

Oil trap

Location of main pipe

Location ofoutdoor unit

Oil is accumulated on theoutdoor unit because it can-not be poured out from thebottom of the pipe.

Because the oil flow to the right pipe, oil gets accumulated onthe outdoor unit on the lower side until the outdoor unit stops.

• When pipe distance between the outdoor unitsis 2m or less

• Example of incorrect installation

• When pipe distance between the outdoor unitsexceed 2m

• Example of correct installation

Page 91: Multi V Water PDB(08.04.10_)final .pdf

Installation2121

6.5 Indoor unit connectionEx) 5 indoor units connected

: Outdoor unit: 1st Y branch: 2nd Y branch: Indoor unit: Header branch: Seal

Refrigerant pipe diameter from branch to indoor unit (a, b, c, d, e)

L Below 150 m

H B

elow

50

m

Below 40 m

h B

elow

15

m

Outdoor unit capacity (kW) Liquid pipe (mm) Gas pipe (mm) ≤ 5.6 Ø6.35 Ø12.7< 16.0 Ø9.52 Ø15.88

Page 92: Multi V Water PDB(08.04.10_)final .pdf

Installation 2222

6.6 Calculation of amount of refrigerantThe calculation of the additional charge should take account of the diameter and length of the pipe.

Additional refrigerantcharge (kg)

Total length of liquid pipe (m):Ø15.88 mm+

+

x 0.173(kg/m)

Total length of liquid pipe (m):Ø22.2 mm= x 0.354(kg/m)

Total length of liquid pipe (m):Ø19.05 mm x 0.266(kg/m)

Total length of liquid pipe (m):Ø12.7 mm+ x 0.118(kg/m)

Total length of liquid pipe (m):Ø9.52 mm+ x 0.061(kg/m)

Total length of liquid pipe (m):Ø6.35 mm

+ x 0.022(kg/m)

Regulation for refrigerant leakage: the amount of refrigerant leakage should satisfy the following equation for human safety.

If the above equation cannot be satisfied, the following steps must be followed.- Selection of air conditioning system: Select one of the following

1. Installation of effective opening part: At the top and bottom of the door connecting the room to the outside, create an openingwith or without the door of with 0.15% of floor space or above.

2. Recheck of outdoor unit capacity and piping length3. Reduction of the amount of refrigerant4. Installation of 2 or more security devices (Alarm for gas leakage)

- Change indoor unit type: Installation position should be over 2m from the floor (Wall mounted type cassette type)

- Adoption of ventilation systemVentilation system prevents the refrigerant density from increasing when the refrigerant is leaked by the installation. Ventilation system comes in two types; external air inflow type or exhaust type. External air inflow type is recommended due tothe characteristics of the refrigerant. Always operate the ventilation system irrelevant from whether the air conditioner is used or not and whether the indoor or not.When it is impossible to operate this and in case of a refrigerant leakage by the sensor, the ventilation system is automaticallyoperated.

- Limitation in piping work: Prepare for earthquake and thermal stress

- Reduction of all refrigerant charge amount of the refrigerant facility (When calculated value exceeds 0.44kg/m3)1. Shorten the refrigerant pipe length.

Change the location of the outdoor unit and shorten the length of the refrigerant pipe to reduce all refrigerant charge amount. 2. Distribute the outdoor unit to several units to reduce the refrigerant charge amount per outdoor unit. (Ex. 20 HP 1 unit

10 HP 2 units)

WARNING

Total amount of refrigerant in the system

Volume of the room at which indoor unit of the least capacity is installed≤ 0.44 ( kg / m3)

Page 93: Multi V Water PDB(08.04.10_)final .pdf

Installation2323

To Outdoor Unit

Sealed Piping

A A

B

A

B

ARBLN01620 ARBLN03320 ARBL054 ARBL057 ARBL1010

ARBLN07120 ARBLN14520 ARBL104 ARBL107 ARBL2010

Y branchHeader

4 branch 7 branch 10 branch

0.99

22.2

1.1

31.8

1.21

34.9

1.35

38.1

1.43

41.3

0.99

28.58

0.99

25.4

0.99

19.05

0.99

15.88

0.8

12.7

0.8

9.52

0.8

6.35

Minimumthickness [mm]

Outer diameter [mm]

6.7 Refrigerant pipe fitting6.7.1 Caution1. Use the following materials for refrigerant piping.

• Material: Seamless phosphorous deoxidized copper pipe• Wall thickness : Comply with the relevant local and national regulations for the designed pressure

3.8MPa. We recommend the following table as the minimum wall thickness.

2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.

3. Use care to prevent dust, water or other contaminants from entering the piping during installation.

4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.

5. Always use the branch piping set shown below, which are sold separately.

6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut the connecting sec-tion and then use an adapter for connecting different diameters to connect the piping.

7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and piping diameter).Failure to do so can result in equipment failure or a decline in heating/cooling performance.

8. A second branch cannot be made after a header. (These are shown by .)

9. The system will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always properly chargethe unit. When servicing, always check the notes concerning both the piping length and the amount of additional refrigerant.

10. Never perform a pump down. This will not only damage the compressor but also deteriorate the performance.

11. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.

12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling performance, drip of con-densate and other such problems.

13. When connecting the refrigerant piping, make sure the service valves of the outdoor unit is completely closed (the factorysetting) and do not operate it until the refrigerant piping for the outdoor and indoor units has been connected, a refrigerantleakage test has been performed and the evacuation process has been completed.

14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film can cause clog-ging or damage to the compressors and flux can harm the copper piping or refrigerant oil.

Page 94: Multi V Water PDB(08.04.10_)final .pdf

Installation 2424

6.7.2 Y Branch and Header Fitting

Y branch

A B

To Outdoor Unit

To Branch Piping or Indoor Unit

A

B

Facingupwards

Facingdownwards

Within ± 3° Within ± 3°

Viewed from point Ain direction of arrow

Horizontalplane

Within +/- 10°

A

Insulator(included with kit)

Liquid and Gaspipe joints

Insulator forfield piping

Tape

(field supply)

A

B

Header To outdoor unit

To indoor unit

A

B

C

• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)

• There is no limitation on the joint mounting configuration.

• If the diameter of the refrigerant piping selected by the procedures described is different from the size of thejoint, the connecting section should be cut with a pipe cutter.

• Branch pipe should be insulated with the insulator in each kit.

• When the number of pipes to be connected issmaller than the number of header branches,install a cap to the unconnected branches.

• The indoor unit having larger capacity must beinstalled closer to than smaller one.

• If the diameter of the refrigerant piping selectedby the procedures described is different from thesize of the joint, the connecting section should becut with a pipe cutter.

Pipe cutter

Page 95: Multi V Water PDB(08.04.10_)final .pdf

Installation2525

• When the number of indoor units to be connected to the branch pipes is less than the number of branchpipes available for connection then cap pipes should be fitted to the surplus branches.

• Fit branch pipe lie in a horizontal plane.

• Header should be insulated with the insulator in each kit.

• Joints between branch and pipe should be sealed with the tape included in each kit.

• Any cap pipe should be insulated using the insulator provided with each kit and then taped as describedabove.

B

Piched pipe

Horizontal plane

View from point B in the direction of the arrow

Insulate the header usingthe insulationmaterial attached to thebranch pipe kitas shown in the figure.

Insulator

Insulator of field pipe

Tape

TapeCap pipe

Insulator for cap pipe

Page 96: Multi V Water PDB(08.04.10_)final .pdf

Installation 2626

6.7.3 Thermal insulation of refrigerant piping

Heatinsulationmaterial

Outercovering

Adhesive + Heat - resistant polyethylene foam +Adhesive tape

Indoor Vinyl tapeFloor exposed Water-proof hemp cloth + Bronze asphaltOutdoor Water-proof hemp cloth + Zinc plate + Oily paint

Note:When using polyethylene cover as covering material, asphalt roof-ing shall not be required.

• Do not insulate gas or low pressure pipe and liquid or highpressure pipe together.

• Be sure to fully insulate connecting portion.

Liquid pipe

Gas pipe

Power linesFinishing tapeInsulating material

Bad example

Good example

These parts are not insulated.

B A C

A

B

C

A

C

DE

A

B

C

D

E

Transmission linesF

Liquid pipe

Transmission lines

Transmission lines

SeparationGas pipe

Power linesInsulating material

A

B

C

D

E

A

A

BF

Heat insulation material

Pipe

Outer covering(Wind the connection part and cutting part of heat insulation material with a finishing tape.)

Power lines

E

DD

B A

C

Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately withenough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unitand insulating material, and insulating materials themselves. When insulation work is insufficient, there is apossibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.

1m1m

A B

D

F

G

B

G

D

B

H

IJ

A

EB

I

A B

DC

Inner wall (concealed)

Floor (fireproofing) Penetrating portion on fire

limit and boundary wallRoof pipe shaft

Outer wall Outer wall (exposed)

PenetrationsSleeveHeat insulating materialLaggingCaulking materialBandWaterproofing layerSleeve with edgeLagging materialMortar or other incombustible caulkingIncombustible heat insulation material

When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible materials for both insulation and covering.(Vinyl covering should not be used.)

Page 97: Multi V Water PDB(08.04.10_)final .pdf

7. Y branch pipe and header branch pipe type

Installation2727

Models Gas pipe Liquid pipe

ARBLN03320

ARBLN07120

ARBLN14520

[unit:mm]

ARBLN01620

7.1 Y branch pipe

Page 98: Multi V Water PDB(08.04.10_)final .pdf

Installation 2828

7.2 Header

Ø15.88

Ø12.7Ø15.88Ø12.7

Ø19.05

Ø15.88

Ø12.7

Ø15.88

Ø12.7

Ø19.05

[unit:mm]

4 branch

ARBL054

7 branch

ARBL057

4 branch

ARBL104

7 branch

ARBL107

10 branch

ARBL1010

10 branch

ARBL2010

Ø9.52 Ø9.52

Ø6.35Ø6.35

Ø12.7

Ø9.52Ø6.35

Ø9.52Ø6.35

Ø12.7

Ø15.88

Ø12.7

Ø28.58

Ø19.05

Ø15.88

Ø9.52Ø6.35

Ø9.52Ø12.7

Ø6.35

Ø15.88

Ø12.7

Ø28.58

Ø19.05

Ø15.88Ø9.52Ø6.35

Ø9.52Ø12.7

Ø6.35

Ø15.88

Ø12.7

Ø28.58

Ø19.05Ø15.88 Ø9.52Ø6.35

Ø9.52 Ø12.7

Ø6.35

Ø15.88Ø15.88

Ø19.05 Ø6.35

Ø9.52

Ø9.52 Ø6.35

Ø15.88

Ø19.05

Ø31.8

Ø38.1

Ø12.7

Models Gas pipe Liquid pipe

OD19.05 Ø15.88 Ø12.7 OD12.7 Ø9.52

OD19.05 Ø15.88 Ø12.7

OD12.7 Ø9.52

OD38.1 Ø34.9 Ø28.58 OD19.05 Ø15.88

OD28.58 Ø22.2 OD12.7 Ø9.52

OD28.58 Ø22.2

OD12.7 Ø9.52

OD28.58 Ø22.2 OD12.7 Ø9.52

Page 99: Multi V Water PDB(08.04.10_)final .pdf

Installation2929

8.1 Leak test

Indoor unit

Nitrogen gascylinder

Main outdoor unit

Close

CloseLi

quid

e pi

pe

Gas

pip

e

Liquid side

Gas side

Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7kgf/cm2). If the pressure does not drop for24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method,refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gaspipe and high/low pressure common pipe)The test result can be judged good if the pressure has not be reduced after leaving for about one day after com-pletion of nitrogen gas pressurization.

Note:

If the ambient temperature differs between the time when pressure is applied and when the pressure drop ischecked, apply the following correction factor

There is a pressure change of approximately 0.1 kg/cm2 (0.01 MPa) for each 1°C of temperature difference.

Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C

24 hour later: 3.73 MPa, 20°CIn this case the pressure drop of 0.07 is because of temperature dropAnd hence there is no leakage in pipe occurred.

Caution:To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must beat higher position than the bottom when you pressurize the system.

Usually the cylinder is used in a vertical standing position.

8. Leakage test and vacuum

Page 100: Multi V Water PDB(08.04.10_)final .pdf

Installation 3030

8.2 VacuumVacuum drying should be made from the service port provided on the outdoor unit’s service valve to the vac-uum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuumfrom liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.)* Never perform air purging using refrigerant.

• Vacuum drying: Use a vacuum pump that can evacuate to -100.7kPa (5 Torr, -755mmHg).

1. Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the sys-tem to -100.7kPa.After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The systemmay contain moisture or leak.

2. Following should be executed if there is a possibility of moisture remaining inside the pipe.(Rainwater may enter the pipe during work in the rainy season or over a long period of time)After evacuating the system for 2 hrs, give pressure to the system to 0.05MPa(vacuum break) with nitro-gen gas and then evacuate it again with the vacuum pump for 1hr to -100.7kPa(vacuum drying). If thesystem cannot be evacuated to -100.7kPa within 2 hrs, repeat the steps of vacuum break and its drying.Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.

ScaleUse a graviometer. (One that can measure down to 0.1kg). If you are unable to prepare such a high-precision gravimeter you may use a charge cylinder.

• Vacuum should be done for 3 hours or more after the pressure is under 0.5 torr.

Vacuum pump

Indoor unit

Main outdoor unit

Close

Close

Liqu

ide

pipe

Gas

pip

e

Liquid side

Gas side

Note : Always add an appropriate amount of refriger-ant. (For the refrigerant additional charge) Too much or too little refrigerant will causetrouble.

When installing and moving the air conditioner to another site, recharge after perfect evacuation.- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and

the unit may be damaged.

WARNING

Page 101: Multi V Water PDB(08.04.10_)final .pdf

Installation3131

9. Electrical Wiring

• Use the 2-core shield cables for transmission lines. Never use them together with power cables.• The conductive shielding layer of cable should be grounded to the metal part of both units.• Never use multi-core cable• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate

power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, neverinstall a phase leading capacitor.

• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of thesmoothing capacitor.

• Introducing with a missing N-phase or with a mistaken N-phase will break the equipment.

9.1 Areas of Caution

Remotecontrol

Remotecontrol

Remotecontrol

Remotecontrol

IndoorUnit

Outdoor Unit Outdoor Unit

Outdoor Unit

IndoorUnit

Remotecontrol

Remotecontrol

IndoorUnit

IndoorUnit

Remotecontrol

Remotecontrol

IndoorUnit

IndoorUnit

IndoorUnit

IndoorUnit

Be sure to correct the outdoor unit to earth. Do not connect earth line to any gas pipe, water pipe,lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.

Be sure to have authorized Electrical engineers do electric work using special circuits in accordancewith regulations and this installation manual. If power supply circuit has a lack of capacity or electricwork deficiency, it may cause an electric shock or fire.

1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,wiring regulations and guidance of each electric power company.

2. Install the outdoor unit transmission line away from the power source wiring so that it may not affected byelectric noise from the power source. (Do not run it through the same conduit.)

3. Be sure to provide designated grounding work to outdoor unit.

4. Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is some-times removed at the time of service work.

5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts willbe burnt out.

6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different systems are wired with the same multiplecore cable, the resultant poor transmission and receiving will causeerroneous operations. ( mark in the figure below)

7. Only the transmission line specified should be connected to the terminal block for outdoor unit transmission.

2-core shield cable Multi-core cable

WARNING

CAUTION

WARNING

Page 102: Multi V Water PDB(08.04.10_)final .pdf

Installation 3232

9.2 Control Box and Wiring Location- Unscrew all the screw, pull out the panel.- Connect the transmission wire between outdoor unit and indoor unit,

the connection between outdoor unit and central controller systempass through the sub PCB for central control.

- When connecting indoor unit with the shield cable, ground at thegrounding screw.When connecting central controller with the shield cable, ground atthe grounding screw.

- Refer to next page about the distance between main power cableand communication cable.- Refer to 106 page about Auto-Addressing and Test Run.

Front Panel

Page 103: Multi V Water PDB(08.04.10_)final .pdf

Installation3333

9.3 Transmission and Power Lines

1) Transmission cable• Types : shielding wire CVVS or CPEVS• Diameter : over 1.25mm2

• Insulation material : PVC • Maximum allowable temperature: 60°C• Maximum allowable line length: under 300m

2) Remote control cable• Types : 3-core cable

3) Simple central control cable• Types : 4-core cable (Shielding wire)• Diameter : over 1.25mm2

• Insulation material : PVC

4) Separation of transmission and power lines• If transmission and power lines are run alongside each other then here is a strong likelihood of operational

faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic cou-pling.

Note:

1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m thefigures will have to be recalculated in direct proportion to the additional length of line involved.

2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the tableshould be increased.

• If the lines are laid inside conduits then the following point must also be taken into account when groupingvarious lines together for introduction into the conduits.

• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the sameconduit.

• In the same way, when grouping the power lines and signal lines should not be bunched together.

Current capacity of power line Spacing

10A 300mm

50A 500mm

100A 1000mm

100A or more 1500mm

100V or more

If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of theapparatus must be carried out by a qualified person.

Use a power wire pipe for the power wiring.

CAUTION

Page 104: Multi V Water PDB(08.04.10_)final .pdf

Installation 3434

Example for mistake of wiring• Do not separately connect the power of the indoor unit.

Power supply3phase 4lines60Hz 380V

Single phase 60Hz 220V

Breaker

3phase 4lines power cable

Transmission cable(3lines): wired remote controller

Single phase 60Hz 220V

Transmission cable(2lines Shield cable) : Indoor~ Outdoor unit

Never install individual switch or individual outlet to cut the power connecting the indoor unit.CAUTION

Page 105: Multi V Water PDB(08.04.10_)final .pdf

Installation3535

9.4 Dip switch setting9.4.1 Location of setting switch

9.4.2 Dip switch setting1. Set the dip switch and turn on the power of the outdoor unit to check whether the set value is correctly entered

in the 7 segment. 2. This function is shown for only 2 seconds after the power is connected.

Check outdoor unit setting

• The number on the 7 segment is displayed in order after the power is connected.• This number represents the setting condition.

Mode code

If the applicable dip switch is not set correctly,the product may not operate properly.

CAUTION

SW01B SW02B

7 segment

SW01B

1 2 3 4 5 6 7

ON

SW02B

1 2 3 4 5 6 7

ON

Order Number Item

1 - Model code

2 - Total capacity in horsepower (Ex)

3 2 -

4 25 Normal mode display (If the dip switch is set incorrectly, it is not displayed.)

5 41 Refrigerant type (R410A)

Model Code Capacity Refrigerant

34 29

35 58R410A

36 87

37 116

Page 106: Multi V Water PDB(08.04.10_)final .pdf

Installation 3636

Master indoor Setting

SW01B Setting SW02B Setting Remark

Normal mode at shippingfactory

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

Slave outdoor Setting (1 unit: master outdoor)

SW01B Setting SW02B Setting Remark

Normal mode at shippingfactory

Slave1 outdoor setting (at the 2units)

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

Function SW01B Setting SW02B Setting Remark

Standard mode at shippingfactoryStandard

Short Pipe Length

Long Pipe Length

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

Page 107: Multi V Water PDB(08.04.10_)final .pdf

Installation3737

Function SW01B Setting SW02B Setting Remark

Standard mode at shippingfactory

After the system turn on,Dip Switch 7,12 are

completed is indicated on7-Segment

longest PipeLength

Test mode(Cooling)

Test mode(Heating)

Water temp checking

COP checkingmode

Indoor unit Forced Operation

(Cooling)

Indoor unitForced Operation

(Heating)

Forced Oil Return

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

Page 108: Multi V Water PDB(08.04.10_)final .pdf

Installation 3838

Function SW01B Setting SW02B Setting Remark

For water pipe SolenoidValve 220V power

Vacuum Mode

Water PipeSolenoid Valve220V Functions

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

1 2 3 4 5 6 7

ON

After operating the dip switch to set the additional function, you must reset the power of the main PCB toreflect the changed function. (After recovering the dip switch to cancel the additional function, you mustreset the power of the main PCB to reflect the change.)

If the dip switch is not set accurately, it can have excessive load on the product operation. Set the dip switch properly.

CAUTION

Page 109: Multi V Water PDB(08.04.10_)final .pdf

Installation3939

9.5 Indoor unit auto addressing• The address of the indoor units would be set by auto addressing.

1) Wait for 3 minutes after applying power supply (master and slave outdoor unit, indoor unit)

2) Press the switch of the outdoor unit (SW02V) for 5 seconds.

3) A "88" is indicated on 7-segment LED of the outdoor unit PCB.

4) For completing addressing, 2~7 minutes are required depending on numbers of indoor unit connection set.

5) Numbers of indoor unit connection set whose addressing is completed are indicated for 30 seconds on 7-segment LEDof the outdoor unit PCB.

6) After completing addressing, address of each indoor unit is indicated on the wired remote controller display window.(CH01, CH02, CH03, .... CH06 : Indicated as number of indoor unit connection set.)

• When replacing the indoor unit PCB, you must execute the auto addressing again. Always executethis with all the power of indoor units and outdoor units connected. If the power is not connected tothe indoor unit, it can generate an operation error.

• When power is connected to the Multi V Water II for the first time, it will standby for more than 3 min-utes to improve the indoor unit communication, and then the address must be set.

WARNING

Page 110: Multi V Water PDB(08.04.10_)final .pdf

Installation 4040

The Procedure of Automatic Addressing

• Auto addressing setting endNumbers of indoor unit connection set whose addressing is completed are indicated for 30seconds on 7-segment LED after completing setting

Indoor address number is displayed on wired remote control or indoor unit display window. It is not an error message, will disappeared when on/off button is pressed on remote control ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and auto addressing is completed normally.

Auto addressing start

Waiting 3 minutes

Power On

Press SW02V for 5 sec.

7-segment LED = 88

Don't Press SW02V

Waiting about 2~7 minutes

7-segment LED

OK

YES

NO Check the connectionsof transmission line= 88

Page 111: Multi V Water PDB(08.04.10_)final .pdf

Installation4141

9.6 Group Number Setting of Indoor Units

Timer Cancel

Program Week

Hour Min

Holiday

Set/Clr

RESET

ZONE 1 2 3 4Operation unit

HumidifyJETSLo

AUTO

AUTO SWING OPERATION FAN SPEED

Program set

SUB FUNCTIONSET TEMPRoom Temp

HIMEDLO

HeaterDefrostFilter

Preheat

Out doorTime

TimerOnSet no. Time

Off01 03 05 07 09 11 13 15 17 19 21 23

PLASMA

2ndF

2ndF

• Using the wired remote controller

1. Press Program button and Set/Clr button at the same time for 3 seconds.

2. The current group and the indoor unit numbers are indicated on the "88" of the wired remote control.

3. Set numbers by using the temperature adjust key.

4. Press Program button and Set/Clr button at the same time for3 seconds.

5. If transmit recognition data are received from the indoor unit,it returns to the general operation mode.

GroupNo.

Room(Indoor Unit)No.

EX) 3 A

Page 112: Multi V Water PDB(08.04.10_)final .pdf

10. Test Run

Installation 4242

10.1 Water supply system test run• Before executing the test run for the product, you must first test the cooling water system.

The test run for the product must be executed after checking the flux and temperature of the cooling watersupplied.

Design the system including cooling tower, boiler, pump etc. - Check the equipment capacity (Water flux, temperature control range).

Install the water supply pipe and piping system parts.- Connect the water supply pipe and install various valves and devices.

Connect the water supply pipe to the inlet/outlet of the product so that thewater can be supplied to the product.

Execute water supply system test run- The product does not operate but the pump and water supply equipment

will operate to flow the cooling water to the heat exchanger on the productside.

- Flow the water to all water piping system to clean any alien particles insidethe pipes and execute an air purge to remove an air within the pipes tomake the water supply smoother.

Execute the test of water supply system without operating the product.

- Check whether the unit outdoor unit inlet/outlet flux complies to the productspecification. Standard product flux is 96LPM based on 10HP and 193LPM based on20HP.

- Check the water supply temperature.

After checking the normal condition of the water supply, execute the test runof the product. To prevent the freezing of the heat exchanger when the refrigerant is dis-charged with the water supply blocked, discharge the refrigerant after sup-plying the water in the water supply line .

Equipment design

Water pipe system installation

Water supply system test run

Execute the product test run

Judging whether there is any problem with the water supply

Water supply pipe and productconnection

Page 113: Multi V Water PDB(08.04.10_)final .pdf

Installation4343

10.2 Precaution before test run

1

2

3

4

5

Check whether the air is completely removed and the water supply is flowing smoothly.

Check whether there is any refrigerant leakage of any disconnected or loose communication or power wire, or usethe electric wiring diagram to check the wiring connection condition. Check whether the power and communication wire are connected.

Check whether the power cable R, S, T and N are correctly connected. Check the insulation resistance with the DB mega tester device (DC 500V) between the power terminal block andgrounding, and check whether it is 2.0MΩ or above when measured.If the resistance is 2.0MΩ or less, do not operate the product. Precaution)- Never check the insulation resistance for the terminal control board.

(The control board can be damaged.)- If you leave the system turned off right after the installation or for a long period of time, the refrigerant gets accu-

mulated within the compressor and the insulation resistance reduces to less than 2 MΩ. When the insulationresistance is 2 MΩ or less, turn on the power and let the electricity be supplied to the crank case heater of thecompressor and let the refrigerant including the oil inside the compressor to evaporate. Then the insulation resistance value will increase to more than 2.0 MΩ.

Check whether the liquid and gas pipes are open.Firmly close the wrench part cap of the service valve.

Precaution when blocking the water cooling type Multi V main power- While using the product (Air conditioning season/Heating season), always connect the main power of the outdoor

unit. - During the test run operation after installing the product or during the operation after blocking the outdoor unit

main power (Power outage etc.), you must always connect the power 6 hours prior to heating the crank caseheater. If the crank case is not preheated for more than 6 hours with the electric heater, it can cause a burn onthe compressor. (Heating the bottom part of the compressor with the crank case heater is to evaporate the refrigerant included inthe oil inside the compressor.)

• Always check whether the water supply is flowing smoothly before the test run. (If sufficient amountof water is not flowing, it can burn the product.)

• During the initial test run after installing the product, leaving the product for more than 3 days orafter replacing the compressor, power must be connected 6 hours prior to the operation to heat thecompressor heater. (If the product is not heated sufficiently, it can burn the product.)

WARNING

Page 114: Multi V Water PDB(08.04.10_)final .pdf

Installation 4444

12.2 How to Cope with Abnormal Test Run

The phenomena from main component failure

Whether water issupplied

CH32

CH180

Water is not supplied orflux is low (During airconditioning operation)

Water is not supplied orflux is low (During heat-ing operation)

Check whether the water supply pump isoperating.

Check whether the water supply pipe isclogged. (Strainer cleaning, valve lock,valve error, air clog etc.)

Check whether the water supply pump isoperating.

Check whether the water supply pipe isclogged. (Strainer cleaning, valve lock,valve error, air clog etc.)

Item Phenomenon Cause Check and troubleshooting method

When the water supply is not smoothly flowing, CH32 or CH180 error can occur. Check whether water supply is flowing smoothly.

Page 115: Multi V Water PDB(08.04.10_)final .pdf

Installation4545

10.4 Self-Diagnosis FunctionError Indicator• This function indicates type of failure in self-diagnosis and occurrence of failure for air condition. • Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit

control board as shown in the table. • If more than two troubles occur simultaneously, low number of error code is first displayed. • After error occurrence, if error is released, error LED is also released simultaneously.

Error display method1st and 2nd LED of 7-segment refers to the error number and the 3rd LED refers to the outdoor unit number.Ex) 011: Error No. 1 of outdoor unit No. 1011‡051: Error No. 105 of outdoor unit No. 1

Indoor unit air temperature sensor disconnection or short circuit

Indoor unit pipe inlet temperature sensor disconnection or short circuit

Occurs when indoor unit communication signal is not received from thewired remote controller

Drain pump and float switch error

When the indoor unit does not receive the outdoor communication signalcontinuously for 5 minutes or more

Indoor unit pipe outlet temperature sensor disconnection or short circuit

When operated in different operating mode than the one first operated

Communication error between MICOM and EEPROM or when there is no indoor unit EEPROM data

When motor connector is removed or defective

When the communication is working but cannot be called from the out-door unit (must be readdressed)

Master outdoor unit inverter compressor drive IPM error

Slave outdoor unit inverter compressor drive IPM error

DC voltage is not charged after master outdoor unit operating relay isturned on

DC voltage is not charged after slave outdoor unit operating relay isturned on

Compressor maintenance by master outdoor unit high pressure switch

Compressor maintenance by slave outdoor unit high pressure switch

Master outdoor unit input voltage of 487V or above or 270V or less

Slave outdoor unit input voltage of 487V or above or 270V or less

Initial operation failure due to master outdoor unit inverter compressorerror

Initial operation failure due to slave outdoor unit inverter compressor error

Compressor turned Off due to master outdoor unit inverter DC voltageover-charge

Display Error item Root cause of errornumber

1 Indoor unit air temperature sensor error

2 Indoor unit pipe inlet temperature sensor error

3Communication error between wired remote con-troller and indoor unit

4 Indoor unit drain error

5Communication error between outdoor unit andindoor unit

6 Indoor unit pipe outlet temperature sensor error

7 Different mode operation

9Indoor unit EEPROM error

10 Indoor unit BLDC motor feedback signal error

11Communication error between indoor unit/outdoorunit

211 Master outdoor unit inverter compressor IPM fault

212 Slave outdoor unit inverter compressor IPM fault

231Master outdoor unit inverter compressor DC linkunder-voltage

232Slave outdoor unit inverter compressor DC linkunder-voltage

241 Master outdoor unit high pressure switch

242 Master outdoor unit high pressure switch

251Master outdoor unit input voltage over-voltage/under-voltage

252Slave outdoor unit input voltage over-voltage/under-voltage

261Master outdoor unit inverter compressor operationfailure error

262Slave outdoor unit inverter compressor operationfailure error

281Master outdoor unit inverter DC link over-voltageerror

Indo

or u

nit

Out

door

uni

t

Page 116: Multi V Water PDB(08.04.10_)final .pdf

Installation 4646

Display Error item Root cause of errornumber

Compressor turned Off due to slave outdoor unit inverter DC voltageover-charge

Master outdoor unit inverter compressor error or operating component(IPM) error operation

Slave outdoor unit inverter compressor error or operating component(IPM) error operation

Compressor turned off due to master outdoor unit inverter CT under-cur-rent

Compressor turned off due to slave outdoor unit inverter CT under-current

Compressor turned off due to master outdoor unit inverter compressordischarge temperature over-rise

Compressor turned off due to slave outdoor unit inverter compressor dis-charge temperature over-rise

Compressor turned off due to master outdoor unit static speed compres-sor discharge temperature over-rise

Compressor turned off due to slave outdoor unit static speed compressordischarge temperature over-rise

Compressor turned off due to master outdoor unit high pressure over-rise

Compressor turned off due to slave outdoor unit high pressure over-rise

Compressor turned off due to master outdoor unit low pressure over-drop.

Compressor turned off due to slave outdoor unit low pressure over-drop.

Master outdoor unit PFC MICOM or inverter MICOM error

Slave outdoor unit PFC MICOM or inverter MICOM error

Master outdoor unit inverter compressor current detection (CT) sensordisconnection or short circuit

Slave outdoor unit inverter compressor current detection (CT) sensor dis-connection or short circuit

Master outdoor unit inverter compressor discharge temperature sensordisconnection or short circuit

Slave outdoor unit inverter compressor discharge temperature sensor dis-connection or short circuit

Master outdoor unit under-voltage sensor disconnection or short circuit

Slave outdoor unit under-voltage sensor disconnection or short circuit

Master outdoor unit over-voltage sensor disconnection or short circuit

Slave outdoor unit over-voltage sensor disconnection or short circuit

Master outdoor unit air temperature sensor disconnection or short circuit

Slave outdoor unit air temperature sensor disconnection or short circuit

Master outdoor unit heat exchange temperature sensor (A) disconnectionor short circuit

Slave outdoor unit heat exchange temperature sensor (A) disconnectionor short circuit

Master outdoor unit suction temperature sensor disconnection or short cir-cuit

Slave outdoor unit suction temperature sensor disconnection or short cir-cuit

282Slave outdoor unit inverter DC link over-voltageerror

291Master outdoor unit inverter compressor over-cur-rent

292Slave outdoor unit inverter compressor over-cur-rent

311Master outdoor unit inverter CT under-currenterror

312 Slave outdoor unit inverter CT under-current error

321Master outdoor unit inverter compressor dischargetemperature over-rise

322Slave outdoor unit inverter compressor dischargetemperature over-rise

331Master outdoor unit static speed compressor dis-charge temperature over-rise

332Slave outdoor unit static speed compressor dis-charge temperature over-rise

341 Master outdoor unit high pressure over-rise

342 Slave outdoor unit high pressure over-rise

351 Master outdoor unit low pressure over-drop.

352 Slave outdoor unit low pressure over-drop.

391Communication error between master outdoor unitPFC circuit and inverter board

392Communication error between slave outdoor unitPFC circuit and inverter board

401Master outdoor unit inverter compressor CT sen-sor error

402Slave outdoor unit inverter compressor CT sensorerror

411Master outdoor unit inverter compressor dischargetemperature sensor error

412Slave outdoor unit inverter compressor dischargetemperature sensor error

421 Master outdoor unit under-voltage sensor error

422 Slave outdoor unit under-voltage sensor error

431 Master outdoor unit over-voltage sensor error

432 Slave outdoor unit over-voltage sensor error

441 Master outdoor unit air temperature sensor error

442 Slave outdoor unit air temperature sensor error

451Master outdoor unit heat exchange temperaturesensor (A) error

452Slave outdoor unit heat exchange temperaturesensor (A) error

461Master outdoor unit suction temperature sensorerror

462Slave outdoor unit suction temperature sensorerror

Out

door

uni

t

Page 117: Multi V Water PDB(08.04.10_)final .pdf

Installation4747

Display Error item Root cause of errornumber

Master outdoor unit static speed compressor discharge temperature sen-sor disconnection or short circuit

Slave outdoor unit static speed compressor discharge temperature sensordisconnection or short circuit

Master outdoor unit static speed compressor discharge temperature sen-sor disconnection or short circuit

Slave outdoor unit static speed compressor discharge temperature sensordisconnection or short circuit

Master outdoor unit heat exchanger temperature sensor (B) disconnectionor short circuit

Slave outdoor unit heat exchanger temperature sensor (B) disconnectionor short circuit

Master outdoor unit power line phase missing

Slave outdoor unit power line phase missing

Excessive connection of indoor unit connection display value (Differentfrom outdoor unit)

When the inverter controller signal is not received from the master out-door unit inverter controller

When the inverter controller signal is not received from the slave outdoorunit inverter controller

When the indoor unit control signal is not received from the master out-door unit controller

Master outdoor unit 3 phase power reverse phase connection

Slave outdoor unit 3 phase power reverse phase connection

Master outdoor unit inverter PCB EEPROM ACCESS error

Slave outdoor unit inverter PCB EEPROM ACCESS error

Master outdoor unit static speed CT sensor disconnection or short circuit

Slave outdoor unit static speed CT sensor disconnection or short circuit

Master outdoor unit inverter PCB input instant over-current (Peak)exceeded

Slave outdoor unit inverter PCB input instant over-current (Peak) exceed-ed

When the master outdoor unit inverter PCB input current is different

When the slave outdoor unit inverter PCB input current is different

Communication error between master outdoor unit master MICOM andEEPROM or EEPROM missing

Communication error between slave outdoor unit master MICOM andEEPROM or EEPROM missing

When signal from slave outdoor unit is not received from master outdoorunit master MICOM

When signal from slave outdoor unit is not received from slave outdoorunit master MICOM

Master outdoor unit liquid pipe temperature sensor disconnection or shortcircuit

Slave outdoor unit liquid pipe temperature sensor disconnection or shortcircuit

471Master outdoor unit static speed compressor dis-charge temperature sensor error

472Slave outdoor unit static speed compressor dis-charge temperature sensor error

481Master outdoor unit static speed compressor dis-charge temperature sensor error

482Slave outdoor unit static speed compressor dis-charge temperature sensor error

491Master outdoor unit heat exchanger temperaturesensor (B) error

492Slave outdoor unit heat exchanger temperaturesensor (B) error

501 Master outdoor unit 3 phase power missing

502 Slave outdoor unit 3 phase power missing

51Over-capacity (Indoor unit capacity sum is excessive) connection

521Communication error with master outdoor unitinverter controller

522Communication error with slave outdoor unitinverter controller

53Communication error with master outdoor unitcontroller and indoor unit

541 Master outdoor unit 3 phase power reverse phase

542 Slave outdoor unit 3 phase power reverse phase

601 Master outdoor unit inverter PCB EEPROM error

602 Slave outdoor unit inverter PCB EEPROM error

701 Master outdoor unit static speed CT sensor error

702 Slave outdoor unit static speed CT sensor error

731Master outdoor unit inverter PCB input instantover-current (Peak)

732Slave outdoor unit inverter PCB input instant over-current (Peak)

741Master outdoor unit inverter PCB phase imbal-ance

742 Slave outdoor unit inverter PCB phase imbalance

861Master outdoor unit master PCB EEPROM error

862Slave outdoor unit master PCB EEPROM error

1041Communication error between master outdoor unitand outdoor unit

1042Communication error between slave outdoor unitand outdoor unit

1131Master outdoor unit liquid pipe temperature sensorerror

1132Slave outdoor unit liquid pipe temperature sensorerror

Out

door

uni

t

Page 118: Multi V Water PDB(08.04.10_)final .pdf

Installation 4848

Refer to the troubleshooting guide of service technical manual for each error.

Display Error item Root cause of errornumber

Master outdoor unit over-cooling inlet temperature sensor disconnectionor short circuit

Slave outdoor unit over-cooling inlet temperature sensor disconnection orshort circuit

Master outdoor unit over-cooling outlet temperature sensor disconnectionor short circuit

Slave outdoor unit over-cooling outlet temperature sensor disconnectionor short circuit

Outdoor unit 4 way valve switch error

Master outdoor unit static speed compressor burn, locking and over-cur-rent

Slave outdoor unit static speed compressor burn, locking and over-current

Plate type heat exchanger freeze prevention error

Water temperature sensor open/short

Communication error between main MICOM and sub MICOM

1141Master outdoor unit over-cooling inlet temperaturesensor error

1142Slave outdoor unit over-cooling inlet temperaturesensor error

1151Master outdoor unit over-cooling outlet tempera-ture sensor error

1152Slave outdoor unit over-cooling outlet temperaturesensor error

151 Outdoor unit 4 way valve switch failure

1731Master outdoor unit static speed compressor error

1732 Slave outdoor unit static speed compressor error

180 Plate type heat exchanger freeze prevention

181 Water temperature sensor error

182 Communication error between MICOMs

Out

door

uni

t

Page 119: Multi V Water PDB(08.04.10_)final .pdf

Installation4949

11. Site air conditioner/heater management sheet

Outdoor unit No.

Location Zone kg

SVC Call %

Model : Model : Model : Model :

Name : Name : Name : Name :

Remote controller: Remote controller: Remote controller: Remote controller:

Ex) Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

Date/ Error Action Checked Time result by

[Diagram] [Check record]

Outdoor unitmodel

Additional refrigerant(R410A)

Combination percentage

Page 120: Multi V Water PDB(08.04.10_)final .pdf

Installation 5050

12. Water cooling type cooling tower applied method

[Open type cooling tower + Middle heat exchanger] Heat exchanger is installed between the coolingtower and outdoor unit system piping, and the tem-perature difference between 1st side and 2nd sideis maintained constantly

[Closed type cooling tower] Cooling water of the cooling tower is supplieddirectly to the outdoor unit system.

Open typecooling tower Closed type

cooling tower 1st side 2nd side

Heat exchange

Page 121: Multi V Water PDB(08.04.10_)final .pdf

Installation5151

13. Caution For Refrigerant LeakThe installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large tosuch an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.

Limiting concentration

Check limiting concentration along following steps and take appropriate measure depending on the situation.

Calculate amount of all the replenished refrigerant (kg) per each refrigerantsystem.

Calculate minimum room capacity

Calculate room capacity by regarding a portion as one room or the smaller room.

(1) Without partition (2) With partition and with opening which serve aspassage of air to adjoining room

13.1 Introduction

13.2 Checking procedure of limiting concentration

Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken with-out hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in theunit of kg/m3 (Freon gas weight per unit air volume) for facilitating calculation.

Limiting concentration: 0.44kg/m3(R410A)

Outdoor unit

(No.1 system)Flow of refrigerant

Indoor unit Room where refrigerant leaks(Refrigerant of the whole No.1 system flows out.)

Amount of additionalreplenished refrigerant

Total amount of replenished refrigerant in refrigerant facility (kg)

+ =

Note : In case one refrigerant facility is divided into 2 or more refrigerant systems and each system is independent, amount of replenished refrigerant of each system shall be adopted.

Outdoor unit

Indoor unit

Outdoor unit

Indoor unitOpening

Partition

In the case of opening without door , or 0.15 % or more openings (to floor space) both above and below door)

Amount of replenished refrigerant per one outdoor unit system

Amount of replenished refrigerant at factory shipment

Amount of additionally replenished refrigerant depending on piping length or piping diameter at customer

Page 122: Multi V Water PDB(08.04.10_)final .pdf

Installation 5252

(3) With partition and without opening which serve as passage of air to adjoining room

Calculate refrigerant concentration

In case the concentration exceeds the limit

When the concentration exceeds the limit, change original plan or take one of the countermeasuresshown below:

• Countermeasure 1Provide opening for ventilation.Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.

• Countermeasure 2Provide gas leak alarm linked with mechanical ventilator.Reducing the outdoor refrigerant qty.

Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant isheavier than air.

Outdoor unit

Indoor unit

Smallestroom

(R410A)

= Refrigerant concentration(kg/m3)

Total amount of replenishedrefrigerant in refrigerant facility (kg)

Capacity of smallest room whereindoor unit is installed (m3)

In case the result of calculation exceeds the limiting concentration, perform the same calculations by shifting to the second smallest, and the third smallest rooms until at last the result is below the limiting concentration.

Countermeasure 2Gas leak alarm

Mechanical ventilator

Countermeasure 1 Opening effective to ventilation

Indoor unit

Page 123: Multi V Water PDB(08.04.10_)final .pdf

P/No.: 3828A20892J

Air Conditioner20 Yeouido-dong, Yeongdeungpo-gu,Yeouido P.O.Box 335 Seoul, 150-721, Korea.http://www.lgeaircon.com

All rights reservedPrinted in Korea April/2008The specifications, designs, andinformation in this brochure are subject to change without notice.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.

File No. : A8974 Volume:1

Certificate No. :E00626/1