BI-TORQ ® Valve Automation • PO Box 309 • 1N050 Linlar Dr. • La Fox, IL 60147 • tel: 630-208-9343 • fax: 630-232-6235 • www.bitorq.com 3 TORQUE OUTPUT 300 INCH POUNDS/35 NEWTON METERS SUPPLY VOLTAGE 12VAC/DC 24VAC/DC 120VAC 230VAC MAX INRUSH CURRENT 3.0A 0.8A 1.5A 1.0A RUNNING CURRENT 0.5A 0.6A 0.5A 0.3A CYCLE TIME 15 SEC 15 SEC 12 SEC 13 SEC DUTY CYCLE (ON-OFF) 75% 75% 25%-50% 25%-50% WEIGHT 5 POUNDS/2 KILOGRAMS MECHANICAL CONNECTIONS ISO 5211 F03/F05 14MM ELECTRICAL ENTRY (2) 1/2” NPT ENCLOSURE RATING NEMA 4/4X MANUAL OVERRIDE 8MM SOCKET DRIVE CONTROL ON-OFF/JOG, 4-20MA PROPORTIONAL ENCLOSURE MATERIAL POWDER COATED ALUMINUM AMBIENT TEMPERATURE RATING -22°F TO +150°F -30°C TO +65°C F03/05 ISO Flange Easily distinguishable yellow/red position indicator Heavy Duty Drive Motor Easily accessible switch & cam stacks ModularControl Cards Aluminum Casting 4X Protection Aluminum Casting 4X Protection NEMA 4 Cover Seal On/Off Control (2) 1/2” EMT Ports Proportional Control PALADIN SERIES P1 ELECTRIC ACTUATOR SPECIFICATIONS P1 ELECTRIC ACTUATOR DIMENSIONS P1 ELECTRIC ACTUATOR EXPLODED VIEW
2
Embed
MODEL NO. SERIAL NO. AVK CARBO-BOND INC . aladin erieS series electrics.pdfAVK CARB O-BOND INC. LA FOX IL. 6014 7 C L O S E D ... Cover Seal (Typical) Switch sequencing data is provided
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
BI-TORQ® Valve Automation • PO Box 309 • 1N050 Linlar Dr. • La Fox, IL 60147 • tel: 630-208-9343 • fax: 630-232-6235 • www.bitorq.com
3
SERIAL NO.MODEL NO.
AVK CARBO-BOND INC.LA FOX IL. 60147
CLOSED
TORQUE OUTPUT 300 INCH POUNDS/35 NEWTON METERS
SUPPLY VOLTAGE 12VAC/DC 24VAC/DC 120VAC 230VAC
MAX INRUSH CURRENT 3.0A 0.8A 1.5A 1.0A
RUNNING CURRENT 0.5A 0.6A 0.5A 0.3A
CYCLE TIME 15 SEC 15 SEC 12 SEC 13 SEC
DUTY CYCLE (ON-OFF) 75% 75% 25%-50% 25%-50%
WEIGHT 5 POUNDS/2 KILOGRAMS
MECHANICAL CONNECTIONS ISO 5211 F03/F05 14MM
ELECTRICAL ENTRY (2) 1/2” NPT
ENCLOSURE RATING NEMA 4/4X
MANUAL OVERRIDE 8MM SOCKET DRIVE
CONTROL ON-OFF/JOG, 4-20MA PROPORTIONAL
ENCLOSURE MATERIAL POWDER COATED ALUMINUM
AMBIENT TEMPERATURE RATING -22°F TO +150°F-30°C TO +65°C
P1 Series Dimensional Data
F03/05 ISO Flange
Easily distinguishable yellow/red position
indicator
Heavy Duty Drive Motor
Easily accessible switch & cam stacks
ModularControlCards
Aluminum Casting4X Protection
Aluminum Casting4X Protection
NEMA 4Cover Seal
On/OffControl
P1 Series Exploded View
(2) 1/2” EMTPorts
14 V
er D
073
008
ProportionalControl
Paladin SerieS
P1 electric actuator SPecificationS
P1 electric actuator dimenSionS
P1 electric actuator exPloded View
BI-TORQ® Valve Automation • PO Box 309 • 1N050 Linlar Dr. • La Fox, IL 60147 • tel: 630-208-9343 • fax: 630-232-6235 • www.bitorq.com
4
SERIAL NO.MODEL NO.
AVK CARBO-BOND INC.LA FOX IL. 60147
CLOSED
Application Notes:1. These actuators are designed to be used in either a horizontal or upright position. Do NOT mount the actuator with the top below a horizontal position. 2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4x integrity of the housing. 4. The internal heater is to be used in ALL applications. 5. Do NOT install the actuator outdoors or in humid environments unless it is powered up and the heater is functioning. 6. Use proper wire size to prevent actuator failure (see chart below for proper wire sizing). 7. Mechanical travel stops are factory calibrated for 90 degree operation. These stops are NOT designed to adjust mechanical rotation by more than +/- 3 degrees.
Wire sizing data is provided in the table below to assist in the selection of the proper wire size for P2/3 series actuators using various wire sizes over distance. Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model.
P2/3 Series Dimensional Data
Page 2 of 4 P2/3 HV AC Series
F07 ISO Flange
Switch Logic Map and Switch/Cam Arrangement
}}
3456791012
-5o 0 o 85o5 o 90o 95o
TB1
Term
inal
ID#
SW1 CLOSE Stop(Factory Set - Fixed)
SW2 OPEN Stop(Factory Set - Fixed)
AUX SW3(Factory Set - Adj)
AUX SW4(Factory Set - Adj)}
}
P Series Exploded View
Easily distinguishable yellow/red position
indicator
Worm Drive
Heavy Duty Drive Motor
Easily accessible switch & cam stacks
ModularControlCards
Clutchless OverrideHandwheel
Aluminum Casting4X Protection
Aluminum Casting4X Protection
NEMA 4Cover Seal
(Typical)
Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. Switches for terminals 3 thru 6 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are for terminals 7 thru 12 and those setpoints may be modifi ed if need be. When so optioned, SW5 & SW6 auxiliary switches are initially set to function the same as auxiliary switches SW3 & SW4.
SD
08_P
23F0
78P
22 H
V A
C V
er D
121
808
Wire Sizing DataMAX distance between Actuator
and Supply (feet)
P2/3-2301.5A
10561659268141006970
10403
P2/3-1203.0A275433699
107018182714
WireGage18161412108
TORQUE OUTPUT 800 INCH POUNDS/90 NEWTON METERS
SUPPLY VOLTAGE 120VAC 230VAC
MAX INRUSH CURRENT 3.0A 1.5A
RUNNING CURRENT 1.0A 0.5A
CYCLE TIME 15 SEC 17 SEC
DUTY CYCLE (ON-OFF) 25% - 50% 25% - 50%
WEIGHT 25 POUNDS/11 KILOGRAMS
MECHANICAL CONNECTIONS ISO 5211 F07 22MM
ELECTRICAL ENTRY (2) 3/4” NPT
ENCLOSURE RATING NEMA 4/4X
MANUAL OVERRIDE 5” HANDWHEEL
CONTROL ON-OFF/JOG, 4-20MA PROPORTIONAL
ENCLOSURE MATERIAL POWDER COATED ALUMINUM
AMBIENT TEMPERATURE RATING -22°F TO +150°F-30°C TO +65°C