1. TITLE:H.P. Feed-Water Heater Performance
2. ABSTRACT:Facing to the paradoxical situation of increasing
the efficiency of power plant at lesser cost, it is an urgent
necessity to improve the performances of the accessories including
that of the feed-water heaters. Hence, immediate implementation of
measures to achieve higher performances of heaters & their
analysis is of utmost importance. The present work outlines the
salient features of feed-water heaters, HP Heaters in particular
& the probable causes of the discrepancy between the actual
performance & design performance along with methods to minimize
losses.
3. OBJECTIVE:The objectives of analysis of the performance high
pressure feed water heater are: 1. Prior to an outage, to provide
information to determine whether corrective action is required to
maintain optimum feed-water heater performance & provide
guidance in determining materials, tools & equipment, workers,
cost estimates & scheduling. 2. Following an outage, provide
information to allow evaluation of the effect of the work on the
feed water heater. 3. During normal operation, provide information
to allow identification of abnormal changes in heater performance
& provide information to assist in identifying the source of
the change. 4. During normal operation, provide information to
assist in optimizing the operation of the heater. 5. During normal
operation, provide information to allow accounting for the
contribution of the heater performance deficiencies on unit heat
rate & capacity.
4. SCOPE:The present project envisages the necessity of High
Pressure feed-water heaters & extends the analysis for the
selection of heater type, its construction & design aspect. The
performance parameters & the proper functioning of the heaters
depend on the construction, tube material selection, arrangement,
location & this has been discussed briefly. Taking into view
the constraints, the scope can be extended for further technical
analysis in selection of the above parameters. Further, the same
concept has been simultaneously extended for designing of Low
Pressure heaters as they are of similar type (non-mixing type
heaters).
1
5. INTRODUCTION:In modern thermal power plants the feed-water
heaters play a vital role by way of increasing the average
temperature of heat addition and hence improving the cycle
efficiency. In order to prevent thermal shock caused by cold
feed-water and improve unit efficiency, feed-water heaters are used
to heat the incoming feed-water prior to flowing through the
economizer section of a boiler. For example, by increasing the
feed-water temperature by ten degrees, the unit efficiency
increases by one percent. Good performance of these heaters is thus
crucial for the overall performance of the plant. Present work aims
at performance prediction of HP feed-water heater of horizontal
configuration, which is the most commonly used configuration in
present day power plants. The three zones in an HP heater viz.
de-superheating zone, condensing zone and drain cooling zone can be
modeled separately and simulation of the three is used to
theoretically predict the heat transfer rate. While Delaware method
is conventionally used for de-superheating and drain cooling zones,
more detailed simulation is carried out for condensing zone for
which Delaware method is strictly not applicable. The control
volume approach accounts for the variation in heat transfer
coefficient and fluid properties along the flow and hence is
expected to be more accurate than a model using a uniform heat
transfer coefficient in the entire condensing zone.
Fig.1. Different zones of Shell & tube type heat
exchanger
2
The feed-water heaters increase the plant efficiency by making
the process regenerative. This is accomplished by using extraction
steam pulled from the high, intermediate and low-pressure sections
of the steam turbine. The condensate from each heater has a
considerable amount of energy and is also used to heat the incoming
feedwater. Figure 1 shows a cross section of a shell and tube heat
exchanger that utilizes both steam and the successive heater
drains. A cascading heater arrangement is the most common type of
heater arrangement found in a power plant. These rely on extraction
steam that is at or very near saturated conditions to heat the
incoming feed-water. The condensate formed from the heating action
is still at saturated conditions and is then sent to the next
heater. A control valve is used to maintain heater level and will
cause the draining condensate to flash, which increases the
efficiency of heat transfer. In a power plant, there are two sets
of feed-water heaters. Low-pressure heaters use extraction steam
pulled from the low-pressure turbine and are located after the
condensate pumps. The condensate is routed through the low-pressure
heaters into an open heater called a deaerator. In the deaerator,
the heating action drives off gases that can become corrosive to
piping and associated equipment at elevated temperatures. The
deaerator provides the suction for the main boiler feed-pumps,
which sends the feedwater through a series of high pressure heaters
prior to the economizer that, are fed by extraction steam from the
high and intermediate pressure turbines. Figure 2 shows the high
pressure and low-pressure heater arrangement.
Fig.2. Arrangement of feed-water heaters in a Power Plant 3
Feed Water heaters are used to achieve thermodynamic gain by
bleeding steam from the turbine & heating the incoming feed
water, thereby, tending to make the cycle a regenerative one. The
steam in turn gets condensed in the shell of the heaters raising
the temperature of the feed water & drains are cascaded from
heater to heater (higher to lower pressure). With increased thermal
rating of the power plants, Feed-Water Heaters are subjected to
very high pressure & temperature, especially; the high pressure
feed water heaters, which are located just after the Boiler Feed
Pump. The severe operating conditions, demands proper selection of
Feed-Water Heaters, which have high degree of equipment
reliability.
6. SELECTION OF FEED WATER HEATER TYPE:The design of Feed-Water
Heater has developed considerably since the first generation of the
power station, but the basic type of heaters remained to be:
Surface type Direct contact type The condensation mechanism,
occurring in the direct contact type heaters, is the same as in
surface contact type, although, the cooling medium is not separated
by a metal wall from the mixture of heating vapour as in the later
type. These heaters have got a certain specific advantages over the
surface type heaters. These are1. Higher thermal efficiency, since
there is no metal barrier to the heat transfer between steam &
water 2. Low cost & maintenance But, direct contact type
feed-water heaters require larger number of condensate pumps &
larger space due to their bigger size compared to surface type
heaters. Due to the above reason, they are not commonly used in
power plants. The only direct contact type heater used in the feed
heating line is Deaerator. There are two types of surface type feed
water heaters used in thermal power plants. One is a U-tube type or
straight tube heater & another is a coiled tube type heater.
The coiled tube type HP heaters are used for 210MW & lesser
capacity power stations. They have helical coils tubes, which are
welded to the feed-water inlet & outlet headers. Main advantage
of this type is that, there is no tube plate, thereby, ensuring
excellent thermal transient capability. But, these heaters require
complicated maintenance practices. U-tube, shell & tube type
heaters with tube plates are extensively being used for HP Heaters
& LP Heaters. These heaters can be mounted either vertically or
horizontally. When the heaters are double pass, U-tubes are used
& for single pass straight tubes are used. These heaters have
the following advantages(i) Requires less space, as these heaters
are compact.
4
(ii) Maintenance is easy because tubes can be plugged without
dismantling the heater. (iii) Wide choice of tube materials. (iv)
High reliability. Considering the above advantages, U-tube shell
& tube type HP Heaters, LP Heaters & Drain Cooler are
selected for TSTPP, Stage-II, 4x500 MW units.
7. DESIGN CRITERIA:The Feed-Water Heaters shall be designed as
per design code-HEI standard (USA) for closed Feed-Water Heaters
& Indian Boiler Regulation (IBR). The design criteria are
discussed below:
7.1. DESIGN PRESSURE:The shell design pressure of the heater,
taking extraction from Cold-Reheat (CRH) line shall be same as the
CRH piping design pressure. The shell design pressure of all other
heaters shall be that corresponding to safety relief valve set
pressure + 10% extra margin on the pressure, for safety precaution.
The safety relief valve set pressure shall be computed based on 7%
blow-down pressure (i.e., the pressure at which the valve closes)
& shall not be, in any case, less than the maximum operating
pressure. The maximum operating pressure is determined basing on
the worst operating conditions. For all LP Heaters & Drain
Cooler the minimum shell thickness shall be 10mm, excluding the
corrosion allowance. The shell side of the heaters shall be
designed for full vacuum also, to prevent them from imploding. The
tube side & water-box design pressure of HP Heaters shall be
the maximum design pressure of the inter-connecting Boiler Feed
Pump (BFP) discharge line or the maximum pressure to which feed
water is subjected to under worst operating condition. The tube
side & water box design pressure of LP Heaters shall be the
Condensate Extraction Pump (CEP) shut-off head under 3% over
frequency operation.
7.2. DESIGN TEMPERATURE:The design temperature of the shell
skirt, shell barrel & tube side of HP & LP Heaters shall be
based on HEI Standard for closed feed water heaters. While applying
the above design criteria, as per HEI Standard, the normal
operating conditions to be considered is 500 MW output with 3%
make-up & back pressure at design cooling water inlet
temperature. The maximum operating pressure shall be decided
considering operating conditions as brought out above for design
pressure. In all heaters which would be exposed to superheated
steam, irrespective of whether a de-superheating section is
provided or not, the margin on design temperature for tubes as per
HEI shall be applied & the tubes (in all the zones) shall be
designed to this temperature. In the case of LPH-1 mounted in the
condenser neck, the design temperature shall be same as the
condenser design temperature. The design temperature of water-box
of the heaters shall be the 5
maximum temperature of the feed water/main condensate leaving
the heater rounded off to the next higher 50C.
7.3. TUBE VELOCITY & TUBE DIAMETER:The velocity of the feed
water shall be restricted to 3.05 m/s under all operating
conditions. However, the use of SS304 tubes permits that tube
velocities may be maintained as high as economically feasible in
order to preclude stagnation including localized pitting. The
velocity of 3.05 m/s is chosen to optimize the pump power
requirement, entry erosion & stagnation induced localized
pitting. Minimum size of tubes shall be 15.875 mm O.D. Average wall
thickness of the tube shall not be less than 20 BWG (0.89) after
bending. The tube thickness shall be increased to compensate for
tube wall thinking on the inner rows of the tube bundle.
7.4. FOULING RESISTANCE:Fouling resistance for the tube side
& shell side shall be taken as per HEI.
8. OPTIMUM DEGREE OF REGENERATION:
Fig.3. Optimization of regenerative feed-water heater (T-s
diagram of Rankine Cycle)
6
Fig.4. Rankine Cycle as shown in Mollier diagram Complete
Carnotization of Rankine Cycle is not possible with finite number
of heaters. If there is one feed water heater used, m kg of steam
is extracted from the turbine for each kg of steam entering it to
the heat the feed water heater from state 5 to state 6 (Fig.3.) so
that by energy balance, m(h2-h6) = (1-m)(h6-h5) Or m = h6-h5 =
h6-h4 h2-h5 h2-h4 Therefore, the thermal efficiency of the cycle is
= 1 - (1-m)(h3-h4) = 1 - [1- (h6 h4) ](h3-h4) = 1- (h2-h6)(h3-h4)
(h1-h6) __(h2 -h4)_______ (h2-h4) (h1-h6) (h1-h6) Following
Haywood[1], Horlock[3] & Salisbury[4] it may be approximately
assumed that turbine expansion line follows a path on the diagram
such that (h- h f) = constant = , where h is the local enthalpy on
the expansion line at a given pressure, & hf is the enthalpy of
saturated water at that pressure. Therefore, as seen from the
Fig.3., h1-h8 = h2-h6= h3- h4 = = constant. Let the enthalpy rise
of feed water in the heater is , which is equal to (h6-h4). Now,
h2-h4 = h2-h6+h6-h4 = + If the total enthalpy rise of feed water is
equal to = h8-h4, then, h1-h6 = h1-h8+h8-h4+h4-h6 = +- Therefore,
equation can be written in the form = 12_____ [(+)(+-)]
7
Here, & are fixed & is a variable. So, there is an
optimum value of for which is maximum. On differentiation, d =
2[(+-)-(+)] =0 d Or, = /2. The cycle efficiency is maximum when
total enthalpy rise of feed water (h8-h4) from the condenser
temperature to the boiler saturation temperature is divided equally
between the feed water heater & the economizer (i.e.,h8-h6 =
h6-h4) in a single bleed cycle. So, the temperature rise of feed
water in the heater is, t = (tboiler saturation tcondenser) &
the corresponding cycle efficiency is = 12 = 12 = 2 + 4__
[(+/2)(+-/2)] (+/2)2 (+2)2 For a non-regenerative cycle, 0 = 1 -
(h3-h4) (h1-h4) Now, h3-h4 = & h1-h4 = h1-h8+h8-h4 = + 0 = 1 =
__ (+) (+) The efficiency gain due to regeneration, = - 0 = 2 + 4 _
= 2____ (+2)2 (+) (+)(+2)2 This indicates that is a positive
quantity, justifying the fact that due to regeneration the cycle
efficiency increases.
Fig.5. Heater train of a steam power plant ( = /2) 8
In the heater train, the feed water enters the economizer
section of the boiler at state F (Fig.5.), where feed water is
heated to the saturation temperature (G) at the boiler pressure.
Assuming the economizer also as a feed water heater (where feed
water is heated by the outgoing flue gases, instead of by the bled
turbine steam, the total enthalpy rise (hG-h3) or temperature rise
from the condenser to the boiler saturation temperature is dividing
equally among the feed water heaters for maximum gain in
efficiency. The enthalpy rise per heater (including the economizer)
is thus, hper heater = hG h3 (n+1) where n is number of heaters
& 1 stands for the economizer. Therefore, the total enthalpy
rise of the feed water for n heaters by regenerative feed heating
is htotal = n (hG-h3) (n+1) Thus, the total temperature rise of
feed water, tfw, due to regeneration for the maximum cycle
efficiency is given by tfw = n tOA (n+1) where the overall
temperature difference is given by tOA = boiler saturation
temperature-condenser temperature More is the number of heater,
more is the total temperature rise of the feed water, tfw , by
regeneration, less become the heat addition to the water in the
boiler, more becomes the mean temperature of heat addition, &
more is the cycle efficiency. From Eq. () If n=0, tfw0 = 0 If n=1,
tfw1 = tOA If n=2, tfw2 = tOA If n=3, tfw3 = tOA If n=4, tfw3 = 4/5
tOA & so on. By the use of first heater, the gain is tfw1 -
tfw0 = tOA By the use of second heater, the gain is tfw2 - tfw1 =
tOA - tOA = 1/6 tOA By the use of third heater, the gain is tfw3 -
tfw2 = tOA - tOA = 1/12 tOA By the use of fourth heater, the gain
is tfw4 - tfw3 = 4/5 tOA - tOA = 1/20 tOA & so on. Since the
gain in cycle efficiency is proportional to the gain in feed water
temperature, the efficiency law follows the law of diminishing
return with the increase in number of heaters. In fact, the
greatest increment in efficiency is brought by addition of the
first heater. The increments for each additional heater
successively diminish (Fig.6.). The number of heaters is fixed up
by heat balance of the whole plant where it is found that cost of
adding another heater does not justify the saving in the heat
supply Q 1 or the marginal increase in cycle efficiency. An
increase in feed water temperature tfw reduces the heat absorption
in the outgoing flue gases from the economizer & may cause a
reduction in boiler efficiency. The number of heater & hence,
the degree of regeneration thus get optimized.
9
Fig.6. Variation of cycle efficiency with increase in no. of
feed-water heaters
9. PERFORMANCE:The heater shall perform satisfactorily under
turbine throttle valve wide open condition, 3% make-up without any
over pressure, 100% TMCR load & part load operation of the
plant. Beside the satisfactory operation throughout the load range,
heaters shall also be capable of operation without any problem
whatever so under all abnormal conditions, i.e., HP Heaters
bypassed, LP Heaters bypassed at full load; HP-LP bypass operation
full load at minimum cooling water temperature, etc.
10. CONSTRUCTIONAL FEATURES:The feed water heaters shall be all
welded construction, i.e., shell to tube plate joint, tube-to-tube
sheet joint, tube plate to channel joint are welded. The feed water
inlet & outlet lines, extraction steam line & condensate
extraction lines are also welded to channel & shell,
respectively. All welded heaters offers freedom from leakage, even
at high pressure & temperature. All the critical areas get
safeguarded against the leakages. These heaters are also able to
withstand the transient conditions more efficiently than any other
type of design. The maintenance, inspection & cleaning of all
welded feed water heater is easy.
10
10.1. TUBE MATERIAL:Both copper alloys & non-ferrous alloys
are used for the LP Heaters & HP Heaters tubes. Copper alloys
are used extensively in the LP Heaters tubes. These alloys have got
excellent thermal conductivity but on the other hand these alloys
have problems of copper carry over & ammonia attack, which may
require a complex boiler cleaning after short intervals. Copper
alloys are also affecter by ammonium sulphide & oxygen in the
feed water, which can result in failures due to stress corrosion
cracking, exfoliation, dezincification & denikelification. To
avoid all the above problems, the stainless steel tubes are
invariably used for LP Heaters. Stainless steel is unaffected at
all operating conditions, except that, it is susceptible to
chloride induced stress corrosion. Most common materials used for
HP Heaters are carbon steel, stainless steel & monel metal. The
carbon steel is the least expensive. It has good heat transfer
properties & high allowable stresses. But, carbon steel can
corrode rapidly if the pH value falls below 8.5. The carbon steel
tubes are also susceptible to the entry erosion near the tube
plates. Moreover, it is highly susceptible to oxidization when wet
system is opened during shutdown. Of all the alloys, the carbon
steel is the most likely to sustain erosion damage in the
de-superheating zone as well as in the drain sub-cooling zone due
to the bad level control problem. Type 304 stainless steel
mitigates all the above problems although it is costlier than the
carbon steel tubes. SS-304 type stainless steel has got an
excellent corrosion resistance property & is unaffected at
nearly all operating conditions. Hence, welded type 304 stainless
steel tubes, although costlier, are used quiet extensively for the
HP Heaters. When stainless steel tubes are used for HP Heaters
& LP Heaters, condensate & feed water lines becomes
completely ferrous & so, it is no longer necessary to maintain
different pH of the water on pre-deaeration & post-deaeration
sections. Thus, pH control becomes easier. A pH of 9.2-9.4, right
from the Condensate Polishing Unit outlet to the economizer inlet,
will be adequate to take care of corrosion in the total condensate
feed water line. Due to the above considerations, welded/seamless
tubes of stainless steel type 304 are selected for both LP & HP
Heaters.
10.2. TUBE TO TUBE PLATE JOINT:The low pressure heater tubes
shall be roller expanded to the tube sheet. The HP Heater tubes
shall be welded to tube sheet & then roller expanded. The tubes
are passed through the tube plate, fillet welded at their ends
& then, roller expanded in the tubes with care to avoid
stressing in the weld. The expansion will help in preventing tube
vibration, which could cause failure of welding. It also gives
strength to the joints.
10.3. WATER BOXES:The full access bolted type or self-sealing
type of water boxes shall be used for Drain Cooler & LP Heater.
The shape of the water box can be cylindrical or 11
hemispherical. It should be designed to reduce entry losses
& entry attack on the tube ends. The flow inside the water box
should be smooth without any water hammer. When full access bolted
type of water boxes are used for HP Heaters, prevention of leakage
at the cover joint is a major problem. With rapid feed water
temperature changes, joint pressure can be released, since the
studs are not in contact with water & cool more slowly than the
tube plates & cover. A careful assessment of the tension
required in the studs is necessary to avoid leakage during the
transient conditions. To avoid all such problems, self-sealing type
of water boxes with elliptical manhole shall be held shut by the
presence of water in the heater. As there is no bolting used to
keep the water box leak-proof, the problems of unsymmetrical
sealing pressure & leakage of gasket does not exist. The water
boxes for the HP Heaters shall be elliptical or hemispherical head
design. The water boxes for HP Heaters & LP Heaters shall have
sufficient straight barrel length to provide access for the tube
ends. The pass partition plate of the heaters shall be bolted type
to facilitate removal & access to the tube sheet.
10.4. TUBE SHEET:The tube sheet of LP Heater & Drain Cooler
shall be of carbon steel & shall be welded to water box &
shell. The tube sheet of the HP Heater shall be overlaid with
stainless steel with a minimum thickness of of 6.35mm. The overlay
is necessary as the HP Heater tubes are welded to the tube sheet.
Where joints are not to be welded, tube hold shall be grooved.
Grooves are not required for welded tube-to-tube sheet joints.
10.5. SHELL:For HP & LP Heaters all welded constructions
shall be used. This design eliminates flanges in the critical areas
& reduces the possibility of leakage. It is light in weight
& has a smooth unobstructed shape that simplifies the
application of insulation. In installations where there are wide
variation in operating conditions the advantages of all the welded
shell is particularly striking when a joint is subjected to a large
temperature difference, such as between de-superheating zone &
the drain cooling zone, the joint will be flexed by difference in
expansion between two zones. With all welded shall, this is not a
problem. But, with a gasket joint, frequent cycling may lead to
leakage.
10.6. TUBE VIBRATION:Several tube failures have occurred in feed
water heater in & adjacent to desuperheating zone. In many
instances, the failures can be attributed to tube vibration in
which the tube appears to have exhibited & suffered corrosion
damage with adjacent tubes or worn circumferentially at baffle
holes. While designing a heater a careful consideration shall be
given to the baffle pitching, tube hole clearances, steam velocity,
etc., to minimize the tube vibration. The heater shall be checked
for any undue vibration that can damage the heater tubes. 12
11. CONSTRUCTION: The three arrangements generally used in
construction of feed water heaters are: The head-up vertical
arrangement (wherein the head of the feed water heater is located
on the top). The head-down vertical arrangement (wherein the head
of the feed water heater is located at the base). The horizontal
design. In all the above three types of heaters, it is desirable to
minimize the diameter of the heater & to achieve the required
heating surface by adding length. This approach helps in minimizing
the thickness of the forged tube sheet & shell wall thickness.
The functional requirement of the feed water heater viz.,
condensation, de-superheating & drain cooling have different
design requirement on each type of feed water heater. The nature of
these designs consideration & their impact is discussed
below.
11.1. CONDENSATION:The condensation operation in a feed water
heater does not call for any significantly different design
consideration on the above arrangements. Consequently, this is not
a major factor in deciding the type of a feed water heater.
11.2. DE-SUPERHEATING:The de-superheating section does not
present any serious design problem with head-up vertical heaters
& horizontal heaters. However, if the de-superheater is
installed in a head-down vertical heater, there is a potential
problem associated with the draining of the condensate,
specifically, during the operation of the feed water, to drain
towards the base of the heater. In order to prevent its entry into
the de-superheating section, which may also be located at the base
because, that is, where the hot feed water exist, a baffle is
installed at the top of the de-superheating section for shedding
condensate into de-superheating area. However, tube holes, which
pass through & are intended to accommodate the passage &
feed water tubes, cannot be gas tight, as they must allow for
expansion of heater. Consequently, a certain amount of steam passes
through these clearances & where this steam has considerable
turbulence, it has a tendency to erode. To avoid erosion, the two
extreme ends baffles of de-superheating & drain cooling zone
shall be sealed properly to ensure leakage against steam &
condensate in the condensing zone.
11.3. DRAIN COOLING:Installation of a drain cooler into a
vertical feed water heater poses practical problems. But, in
horizontal type heaters, the design of drain cooling portion is
relatively simpler. In head-up design, it is necessary to duct the
drains from the base of the feed water heater, which is farthest
away from the head, up through the length of the feed 13
water heater to the drain outlet location just below the heads.
The consequence of this design is that, a high-pressure
differential is required between the shell pressure & the drain
cooler outlet. This pressure differential is required to lift the
condensate from the bottom of the shell, up through the drain
cooler to drain outlet. At part load operations the drain
accumulates in the base of the feed water heaters until there is
sufficient pressure differential to deliver the condensate out of
the drain. A design feature, which may be implemented to avoid this
flooding of the condensate section, is to install an auxiliary
drain at the base of the heater, which would open at low loads
& allow the condensate to leave without passing through the
drain section. In head-down arrangement the drain cooler section is
located at the base of feed water heater. If no de-superheater is
installed as with the low-pressure heater, a substantial section of
the potential condensing tube is removed by flooding of the drain
cooling section. Utilizing a separate drain cooler can eliminate
this problem, although it must be noted that, this approach
compromises the saving associated with the reduced floor space
requirement of the vertical heaters.
12. LOCATION:The location of the vertical feed water heater must
consider the need to service the heater for maintenance. Because of
their height, possibly as high as 12 m, it is necessary to locate
the feed water heater below the operating floor. Otherwise, units
cannot be handled with the turbine hall crane & must be
serviced through a hole located in the turbine-building roof.
Hence, it is impossible to stagger the elevation of the heater in
such a manner as to assist the cascading mode of drain operation.
This potential problem should only occur with the lower pressure
feed water heaters, as the shell pressure differential between the
high pressure feed water heaters & the deaerator should be
sufficient to implement cascading drain operation through most of
the plant operation range. Horizontal feed water heaters, however,
may be staggered in their elevation so as to assist cascading to
very low plant loads.
13. OPERATION: 13.1. PERFORMANCE:The elevation of the vertical
low pressure feed water heater shall be set so as to assist in
cascading mode of drain operation. Because the shell pressure
differentials between the low pressure feed water heaters may
become extremely low, particularly at reduced plant load operation,
it may become necessary to utilize alternate means of draining feed
water heater other than cascading. These are as follows: Direct the
drain to the condenser at part load but it will affect the part
load heat rate. Use a separate drain cooler. Compromise has to be
done with space advantage. Use heater drain pump. This will result
in additional rotary equipment & also increase the maintenance
requirements. Use of a flash tank. This will increase capital cost
& occupy additional space.
13.2. CONTROL:14
In a horizontal heater installation, the surface capacitance is
adequate to allow sufficient dwell time for low-level control.
Therefore, level controller can be designed so as to provide a
stable & high-resolution signal to the control valve, thus
allowing the valve to position itself without hunting. In a
vertical heater installation, however the surface capacitance of
the drain fluid is much reduced, resulting in potentially rapid
fluctuation of level during unit load changes. In order to
compensate for this rapid flow changes through the heaters, the
controller must be such as to dampen the signal to the control
valve. As a consequence of this requirement, the valve setting may
at a given time be inappropriate for the water level in the heater.
As a result, the pressure drop through the valve under a given set
of operating circumstances may be inadequate to prevent flashing in
the drain lines of the valve or conversely, may result in a
temporarily high level in the feed water heater.
14. ARRANGEMENT OF HEATERS:The heaters can be arranged either
vertically or horizontally. The principal advantage associated with
the vertical type feed water heaters, is the considerable reduction
in the floor space compared with that required for horizontal feed
water heaters. This reduction in the floor space can be achieved
only if the considerations do not dictate the installation of
equivalent floor space. Specifically, it is necessary to either
relocate the deaerator so that the auxiliary bay can be eliminated
or the space within the auxiliary bay must be utilized for other
purpose. Horizontal high-pressure heaters are usually placed in the
operating floor & low pressure feed water heaters are placed in
the mezzanine. The controlling parameters for the determination of
permissible elevation are again the shell pressure shown on the
heat diagram. The low-pressure heater shell pressures are adequate
to support the heaters located on the mezzanine floor & the
lowest pressure heater on condenser neck. The placement of the
low-pressure heater in the mezzanine floor subsequently allows the
location of the high-pressure heaters on the operating floor. It
allows more convenient access & removal procedures if
maintenance of these heaters is required. The above arrangement of
the feed water heater will operate over entire load range with
little or no component maintenance or attention from plant
operator. The performance of HP Heaters can be analysed by
monitoring the terminal temperature difference (TTD), drain cooler
approach (DCA), the pressure drop on the feed-water side & the
temperature rise across the heater. To monitor these, it is
desirable to carry out simplified routine performance test on feed
water heaters at a specified frequency. This will help in
identifying the level of deviations & trending the
performance.
15. H.P. HEATER DESIGN DATA:15
Station: TSTPP Sl. No. 1 2 3 4 5 6 7 8 9 10 11 Description Unit
Capacity Heater Position (Horizontal/ Vertical) HP Heater No. No.
of Zones (Desuperheating, Condensing, Drain Cooling Surface Area
Extraction steam pressure Pressure drop (water side) Operating
level (Minimum /Normal/ Maximum) Terminal Temp. difference Drain
Cooler Approach temp. Temperature rise Unit MW Values 500
Horizontal HPH-5 3 m2 kg/cm2 kg/cm2 mm0 0
Unit: 5
HPH-6 3 1278 85.5 0.85 -625/ -540/ -110 - 0.3 4.8 50.13
1063 16.88 0.85 -625/ -540/ -110 - 0.3 4.8 37.83
C C C
0
HP HEATER 5A & 5B Description SHELL SIDE TUBE SIDE Medium
Steam & Drain Feed Water 2 Design Pr. (Kg/cm ) 24 & Full
330 & Full vacuum vacuum Design Temp.( C) 224 224/244 Test
Pr.(Kg/cm2) 36 495 Test Temp. ( C) Ambient Ambient Flow Quantity
(T/Hr) 42.591 749.267 Inlet Temp.( C) 412.583 165.5 Outlet Temp.(
C) 170.3 203.33 No of passes/Zones 3 2 No.of Tubes --------1347
Tube size (O.D. x --------OD x 13 Thickness),mm BWG min MATERIALS
Shell/Channel SA 516 Gr 70 /SA 387 Gr.12CL.1 Tubes SA 688 TP 304
Tube plate(s) SA 350 LF2 Flanges SA 105 Nozzles(Tube side) SA 106
GR. B Nozzles(Shell side) SA 182 F11/SA Gr B.
HP HEATER 6A & 6B SHELL SIDE TUBE SIDE Steam & Drain
Feed Water 57 & Full 330 & Full vacuum vacuum 273 273/293
85.5 495 Ambient Ambient 78.068 749.267 335.25 203.27 208.1 191.927
3 2 ----------1347 ----------15.88 x 13 BWG min SA 516 Gr 70 SA 688
TP 304 SA 350 LF2 SA 105 SA 350 LF2 SA 350 LF2 & SA 106 Gr
B
16
16. H.P. HEATER TEST DATA:Station: TSTPP Sl. No. 1 2 3 4 5 6 7 8
15 16 5 6 7 8 9 10 11 12 Measurement FW temp. at HPH-5 inlet(5A/
5B) Pr. of FW at HPH-5 inlet(5A/ 5B) FW temp. at HPH-6 inlet(6A/
6B) Pr. of FW at HPH-6 inlet(6A/ 6B) FW temp. at HPH-5 outlet(5A/
5B) Pr. of FW at HPH-5 outlet(5A/ 5B) FW temp. at HPH-6 outlet(6A/
6B) Pr. of FW at HPH-6 outlet(6A/ 6B) HPH-5 level (5A/ 5B) HPH-6
level (6A/ 6B) HPH-5 shell pressure(5A/ 5B) HPH-6 shell
pressure(6A/ 6B) HPH-5 extraction temp. (5A/ 5B) HPH-6 extraction
temp. (6A/ 6B) HPH-5 extraction pressure(5A/ 5B) HPH-6 extraction
pressure(6A/ 6B) HPH-5 drain temp. (5A/ 5B) HPH-6 drain temp. (6A/
6B) Unit:5 Unit0
Test Date: 09/08/05 Run 1 168.98 200.84 203.63 198.03 204.15
198.57 253.06 196.82 -543.6 -555.7 16.87 42.08 418.97 339.69 16.88
42.10 172.22 212.43 168.86 200.77 199.86 197.97 203.57 198.50
250.06 196.18 -550.4 -544.6 16.98 41.94 416.36 332.34 17.00 41.94
172.69 209.68 Run 2 168.97 197.43 203.46 197.22 203.85 196.35
252.91 196.27 -547.2 -549.7 16.76 42.25 416.69 332.20 16.78 42.27
173.66 208.22 168.04 198.17 199.28 196.98 201.90 197.23 251.62
195.53 -553.2 -556.9 16.57 40.76 414.13 327.16 16.57 40.87 173.37
208.83
C kg/cm2 0 C kg/cm2 0 C kg/cm2 0 C kg/cm2 mm mm kg/cm2 kg/cm2 0
C 0 C kg/cm2 kg/cm2 0 C 0 C
CONTROL ROOM READINGS: Station: TSTPP Sl.No. Description 1 2 3 4
5 6 7 8 9 Load Main steam temp. MS pressure Feed water Flow SH
attemperation flow RH attemperation flow BFP disch. hdr. pr.
Condenser vaccum Barometric pr. Unit: 5 Test Readings Units MW 0 C
kg/cm2 T/hr T/hr T/hr kg/cm2 mm of Hg. kg/cm2 Run 1 499.5 532.37
165.78 1586 23.21 11.34 201.4 -0.91 1.01 Test Date: 09/08/05 Run 2
485.6 539.67 164.86 1578 17.32 4.63 201.9 -0.91 1.01
17
OTHER TECHNICAL SPECIFICATIONS: WEIGHTS HPH 5A & 5B HPH 6A
& 6B Dry (Kgs) 45250 58050 During Operation (Kgs) 49300 62550
Floaded (Kgs) 56250 70100
17. CALCULATION:For a closed feed water heater, the Terminal
Temperature Difference (TTD) is defined as: TTD = saturation
temperature of bled steam feed water temperature at heater outlet.
If the value of TTD for a heater is too small, it is good for plant
efficiency, but the heater size increases. If the value is too
small, the cycle efficiency will be reduced. The extracted steam on
condensation gets sub-cooled in the drain cooler & is removed
as drip. The Drain Cooler Approach Temperature (DCA) is defined as:
DCA = Drip outlet temperature Feed water inlet temperature The
results obtained are shown in tabular form as below:Sl.No (i) (ii)
(iii) (iv) (v) Heater No Pressure of bled steam(ksc) Saturated temp
corresponding to bled pr. (0C) FW temp at heater outlet (0C) FW
inlet temp (0C) Drip outlet temp (0C) TTD (0C) DCA (0C) FW pressure
drop (ksc) HPH5A Run 1 Run 2 16.87 16.76 203.8 9 204.1 5 168.9 8
172.2 2 -0.26 3.24 2.27 203.5 6 203.8 5 168.9 7 173.6 6 -0.29 4.69
1.08 HPH5B Run 1 Run 2 16.98 16.57 204.2 1 203.5 7 168.8 6 172.6 9
0.64 3.83 2.27 202.9 9 201.9 0 168.0 4 173.3 7 1.09 5.33 0.94 HPH6A
Run 1 Run 2 42.08 42.25 253.2 2 253.1 6 203.6 3 212.4 3 0.06 8.88
1.21 253.4 6 252.9 1 203.4 6 208.2 2 0.55 4.76 0.97 HPH6B Run 1 Run
2 41.94 40.76 253.0 4 253.0 6 199.8 6 209.6 8 -0.02 9.82 1.79
251.43 251.62 199.28 208.83 -0.19 9.55 1.45
18. FAULT ANALYSIS:An increase in either the TTD or DCA, and/or
a decrease in the temperature rise indicate the problem with the
heater. This deterioration in the performance could be the result
of any or all of the following causes: a. Fouled heater tubes
(either steam or water side or both). b. Internal leakage (leakage
through the water box partition plate resulting in a partial
internal bypassing of the heater, or, tube-to-tube sheet leakage
resulting in feed water leaking to the steam side). c. External
leakage (through the bypass valve).
18
d. Plugged tubes (reducing the heat transfer area, while
increasing tube velocity). The detailed Fault tree is shown in the
adjoining Fish-Bone diagram drawn.
Fig.7. Cause-Effect Diagram for Feed-Water Heater
Performance
TTD is an indication of the ability of the surface to transmit
heat under a given set of conditions. This ability is determined by
the overall heat transfer coefficient. The principal factors
affecting the heat transfer coefficient are: Tube material,
diameter, length & arrangement Feed water velocity Tube
cleanliness
19
Non-condensable gases in the steam or water spaces of the
heater
Steam usually contains non-condensable gases, which if allowed
to accumulate, will affect the performance of the heater. To make
certain that such condition does not occur, the vent valves should
be adjusted so that sufficient quantity of escapes to cause the
temperature rise of the water passing through the heater to remain
both maximum & constant. This usually provides adequate
assurance that no heating surface is blanketed with non-condensable
gases. Tight shutoff is a necessity for these applications to
protect the integrity of the valve trim. The normal heater drain
should be supplied with tight shutoff for situations where the
heater is bypassed and leakage between heaters is possible. Tight
shutoff will ensure that damage such as wire draw will be
prevented. Heater efficiency will also be maintained as the warm
condensate will not be lost to the condenser and additional
extraction steam will not have to be taken from the turbine. There
are two valves that must be addressed on each heater. These are the
normal heater drain valves and the emergency or high-level dump
drain valves. Both of these valves can dramatically affect unit
efficiency. The normal heater drain valve is used to control the
condensate level in the heater and the flow of condensate to the
next successive heater. As stated above, the incoming condensate is
under saturated conditions. As the condensate passes through the
valve, the condensate flashes to steam to aid in the heat transfer
process. Flashing of steam can lead to severe erosion effects due
to the high velocity steam carrying entrained water droplets. The
emergency heater drain can have a similar impact on unit
performance. This valve is used only on high level alarms;
therefore, tight shutoff is necessary to ensure proper performance.
Any condensate that leaks through the valve will go directly to the
condenser, which requires additional extraction steam to provide
the proper heating. With the outlet flow going directly to the
condenser, flashing will occur during valve operation. In order to
combat the flashing damage while providing proper control, Fisher
recommends the use of an angle valve with a downstream liner. Since
flashing is directly related to the downstream pressure, there is
no way to eliminate it from occurring. Therefore, it is necessary
to protect the valve and associated equipment from any of the
damaging effects. The angle valve design directs the flow into the
center of the valve away from the valve body and downstream pipe
walls.
19. RECOMMENDATIONS:Based on the above discussions, following
are the recommendations for feed water heaters: 1. All the HP
Heater tubes shall be welded to tube sheets & then roller
expanded. LP Heater tubes shall be roller expanded to tube
sheet.
20
2. The water box or channel section of all heaters shell should
be of carbon steel, fabricated or forged construction. Water box
should be of hemispherical shape. Sufficient space area should be
provided in between water box & tube plate for efficient &
smooth entry of feed water & ease maintenance of the tubes. 3.
Water box of all the HP Heaters & LP Heaters shall be welded to
the tube plate. 4. The shells of all the heaters shall be welded to
the tube plate. 5. All connections for drains, feed water &
steam at the heaters shall be welded to leak-tight. 6. In the HP
Heaters the steam leaving the de-superheater section at the full
duty shall be above the saturation temperature by a sufficient
margin to ensure that no condensation will occur in the tubes under
normal operating conditions & steam leaving the de-superheating
section will not cause droplet impingement in the condensing
section. 7. To avoid excessive velocity in the drain cooling
section during emergency draining operation to condenser &
lower heater, a separate drain cooler bypass connection shall be
provided on the shell of the heater. 8. All openings on the HP
Heater channel shall be self-sealing type. 9. The fouling factors
on the tube side & the shell side in different zone shall be as
per HEI standards. 10. Periodical checking should be done to avoid
any leakage or accumulation of non-condensable gases. For this
proper venting has to be ensured during the operating condition of
the heaters. 11. Heater water level & operating condition
should be maintained as close as possible to the designed
values.
20. CONCLUSION:The importance of feed-water heater is judged not
only from the role they play in increasing the cycle efficiency, by
making the cycle consistently approach towards a regenerative one,
but also, from the fact that they reduces thermal stresses in the
pipelines & water-wall tubes by increasing the inlet
temperature of the drum. Moreover, their performance is a direct
indication in saving of equivalent amount of fuel cost, there by
adding towards the economic running of the plant. Hence, proper
monitoring of the feedwater heater parameters is a must for
efficient & economic running of the power plants
21. BIBILOGRAPHY:1. R.W.Haywood, Analysis of Engineering Cycles,
Pergamon Press, Oxford, 1975 2. P.K.Nag, Engineering
Thermodynamics, Tata McGraw-Hill, New Delhi, Second edition, 1995
3. J.H.Horlock, Combined Heat & Power, Pergamon Press, Oxford,
1984 4. J.K.Salisbury, Steam Turbines and Their Cycles, John Wiley,
New Work, 1950
21
22. APPENDIX:
22