ABBREVIATIONS GENERAL NOTES SYMBOLS NEW WORK 1. THE NEW TELECOMMUNICATIONS SYSTEMS WILL CONSIST OF VOICE, DATA, CABLE TV, SECURITY CAMERAS, AND 3 AUDIO SYSTEMS. THE AUDIO SYSTEMS ARE LABELED ON THE PLAN AS SUCH: 3. THE BUILDING WIDE PUBLIC ADDRESS SYSTEM IS DESIGNED TO HAVE A CONTROLLER THAT SITS AT THE MAIN RECEPTION DESK. THE CONTROLLER IS CAPABLE OF A BUILDING WIDE PAGE OR INDIVIDUAL ZONE PAGES. THE ZONES WILL SPLIT AS FOLLOWS: GENERAL PURPOSE (A), OFFICE AREA (B), WEIGHTS/CARDIO (C), GYMNASIUM (D), AND POOL (E). FOR EACH ZONE, (1) 2 PAIR 18 AWG CABLE WILL BE DAISY CHAINED FROM SPEAKER TO SPEAKER AND BE RUN TO THE FLOOR MOUNT AV RECEPTACLE AT THE MAIN RECEPTION DESK. 4. THERE WILL BE A DEDICATED AUDIO SYSTEM FOR THE WEIGHTS/CARDIO AREA. THIS SYSTEM WILL HAVE SEPARATE SPEAKERS THAT CONNECT BACK TO THE WALL MOUNT RACK IN THE AV ROOM. THIS SYSTEM IS DESIGNED SO A CD OR MP3 PLAYER CAN BE PLUGGED INTO THE RACK MOUNT AUDIO SYSTEM AND PLAY MUSIC IN THE WEIGHTS/CARDIO ROOM. 5. THE GYMNASIUM AUDIO SYSTEM HAS TWO LARGE BOX SPEAKERS THAT ARE MOUNTED AT CENTER COURT FACING OPPOSITE EACH OTHER MOUNTED 25' ABOVE THE FLOOR. THE SPEAKERS WILL BE FASTENED TO THE STRUCTURAL SUPPORT BEAMS BUT MAY NOT HANG DOWN BELOW 25'. THESE SPEAKERS WILL BE WIRED TO THE FLOOR MOUNTED AV OUTLET JUST OFF CENTER COURT. A 1" CONDUIT WILL CONNECT THE SPEAKERS AND PLUG AN ANNOUNCING SYSTEM CONTROLLER INTO THE AV OUTLET FOR A GYMNASIUM WIDE PA SYSTEM. TO A 4x4 WALL MOUNTED DEVICE BOX. ANOTHER 1" CONDUIT WILL CONNECT THE WALL BOX TO THE 4x4 FLOOR MOUNTED AV OUTLET. THE SYSTEM IS DESIGNED TO SET UP A PRESS BOX TABLE JUST OFF THE COURT 2. THE CABINET IN THE TELECOMMUNICATIONS ROOM (RM. 125) SHALL HAVE VERTICAL CABLE MANAGEMENT ON BOTH SIDES. EACH COPPER PATCH PANEL SHALL HAVE SIEMON WM-BK TYPE REAR WIRE MANAGEMENT. (1) - BUILDING PUBLIC ADDRESS SYSTEM (2) - WEIGHTS/CARDIO MUSIC SYSTEM (3) - GYMNASIUM ANNOUNCING SYSTEM NOTE: SEE SPEAKER SYMBOL ON THIS PAGE (4) - MULTI-PURPOSE ROOM A MUSIC SYSTEM (5) - MULTI-PURPOSE ROOM B MUSIC SYSTEM 6. THE MULTI-PURPOSE ACTIVITY ROOM IS ONE LARGE ROOM THAT HAS A RETRACTABLE WALL IN THE MIDDLE. WHEN THE WALL IS CLOSED, THE ROOMS OPERATE INDIVIDUALLY AND REQUIRE TWO SEPARATE AUDIO SYSTEMS. WHEN THE WALL IS OPEN, ONE AUDIO SYSTEM MUST BE CAPABLE OF CONTROLLING THE SPEAKERS FOR BOTH ROOMS. THE LAYOUT WILL CONSIST OF AN AUDIO VISUAL JACK IN THE FRONT OF THE ROOM, A 54" CABINET THIS ALLOWS THE SPEAKERS IN ROOM 114B TO BE TURNED OFF IF THE PARTITION WALL IS IN THE CLOSED POSITION. FOR ELECTRONICS, AND CEILING MOUNTED SPEAKERS. THE AUDIO VISUAL JACK AND THE SPEAKERS WILL BE WIRED TO THE ELECTRONICS IN THE CABINET. THE ELECTRONICS IN EOOM 114A MUST HAVE A TWO ZONE CONTROL (A & B). 7. FOR CCTV LOCATIONS, PROVIDE 1" CONDUIT TO NEAREST TELECOM CABLE TRAY OR DIRECTLY TO TELECOM ROOM. FIBER OPTIC FO WS WP WA UTP UPS UL UG TR TMGB TIA TGB TER TBB STR SM RM PVC PR PBX PB P/P OSP NFPA NEMA N/A NEC mm MM MHz M LEC LAN EMT EMI EIA CAT 3 C BLDG BB AWG ANSI AFF WORKSTATION WEATHERPROOF WORK AREA UNSHIELDED TWISTED PAIR UNINTERRUPTIBLE POWER SUPPLY MICRON OR MICROMETER UNDERWRITERS LABORATORIES UNDERGROUND CONDUIT TELECOMMUNICATIONS ROOM TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TELECOMMUNICATIONS INDUSTRY ASSOCIATION TELECOMMUNICATIONS GROUNDING BUSBAR TELECOMMUNICATIONS ENTRANCE ROOM TELECOMMUNICATION BONDING BACKBONE STRAND SINGLEMODE ROOM POLYVINYL CHLORIDE PAIR PRIVATE BRANCH EXCHANGE PULL BOX PATCH PANEL OUTSIDE PLANT NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NATIONAL ELECTRICAL CODE NOT APPLICABLE MILLIMETER MULTIMODE MEGAHERTZ METER LOCAL EXCHANGE CARRIER LOCAL AREA NETWORK ELECTRICAL METALLIC TUBING ELECTROMAGNETIC INTERFERENCE ELECTRONIC INDUSTRIES ALLIANCE CATEGORY 3 CONDUIT BUILDING BACKBONE AMERICAN WIRE GAUGE AMERICAN NATIONAL STANDARDS INSTITUTE ABOVE FINISH FLOOR P/C PATCH CORD TBD TO BE DETERMINED CAT 6 CATEGORY 6 CATV COMMUNITY ANTENNA TELEVISION SYSTEM RMU RACK MOUNTED UNIT GOVERNMENT FURNISHED, GOVERNMENT INSTALLED GFGI CONNECTION TO ELECTRICAL SERVICE EQUIPMENT (PANEL OF SWITCHBOARD) GROUND BUS. GROUNDING ELECTRODE SYSTEM EQUIPMENT ROOM ER ACCESS PROVIDER AP RUNWAY TYPE CABLE TRAY. SEE CABLE TRAY SCHEDULE FOR MORE INFORMATION. RIGID GALVANIZED STEEL RGS CP CONSOLIDATION POINT HORIZONTAL CROSS CONNECT HC CONDUIT SLEEVE 'UP' CONDUIT SLEEVE 'DOWN' LPP LIGHTNING PRIMARY PROTECTOR GOVERNMENT FURNISHED EQUIPMENT GFE XX CROSS-CONNECT NEW WORK - TELECOMMUNICATIONS 1. RACEWAY SECTIONS INCLUDES (2) TWO OR MORE 90 DEGREE SWEEPING BENDS OR EQUIVALENT. 2. LENGTH OF RACEWAY SECTION IS GREATER THAN 100 FEET. 1 CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED PLAN REFERENCE NOTE, REFER TO NOTE No. INDICATED. THE DRAWING WHERE DETAIL IS SHOWN. DETAIL SYMBOL, LETTER INDICATES DETAIL DESIGNATION. MAX MAXIMUM MIN MINIMUM DEMARC DEMARCATION CONDUIT ROUTED IN CEILING AND TERMINATED WITH BUSHING. PRIMARY EQUIPMENT PROTECTOR THE DRAWING WHERE DETAIL IS TAKEN. SPLITTER (QTY OF TAPS AS REQUIRED PER DROPS SERVED) AMPLIFIER DIRECTIONAL COUPLER (QTY OF TAPS AS REQUIRED PER DROPS SERVED) GROUNDING ELECTRODE CONDUCTOR GEC PLYWOOD. REFER TO EQUIPMENT SCHEDULE. TELECOMMUNICATIONS BOND TO BUILDING STEEL CONDUIT SLEEVE PENETRATING WALL IN CEILING. 4"C. UNO. GROUNDING EQUALIZER GE CT CABLE TRAY X TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) TMGB (1) 4-PORT FACEPLATE, (2) 8-POSITION CAT 6 RJ-45 JACKS (ONE VOICE & ONE DATA). 18" AFF, U.N.O. (1) 8-POSITION CAT 6 RJ-45 JACK W/PLATE, (VOICE ONLY). 18" AFF, U.N.O. ALSO FAX OR STE AS INDICATED. TV OUTLET, F-SERIES CONNECTOR ON SINGLE GANG FACEPLATE, WALL FLUSH MOUNTED 18" AFF. (1) 8-POSITION CAT 6 RJ-45 JACK W/PLATE, WALL PHONE (VOICE ONLY). 40" AFF. W TV TV OUTLET, F-SERIES CONNECTOR ON SINGLE GANG FACEPLATE, WALL FLUSH MOUNTED 65" AFF. TV W (X) WEATHERPROOF EMERGENCY TELEPHONE. PROVIDE RECESSED JUNCTION BOX IN WALL WITH CONDUIT UP WP CROSS CONNECT FIELD. 110 BLOCKS, 4 PAIR UTP PATCH PANEL, OR FIBER OPTIC PATCH PANEL. PROVIDE 6 INCHES OF CLEARANCE AROUND FACEPLATE. TELECOM EQUIPMENT DESIGNATOR. REFER TO EQUIPMENT SCHEDULE. V VOICE W WIRELESS DATA CABINET (WITH DOOR OPEN) WAP WIRELESS ACCESS POINT HEIGHT HT VERT VERTICAL FIBER OPTIC PATCH PANEL FOPP LOCATE +6" ABOVE BACK SPLASH/COUNTERTOP. COORDINATE WITH FURNITURE PLAN. * UON UNLESS OTHERWISE NOTED CAB CABINET COMM COMMUNICATION TYP TYPICAL TO CABLE TRAY. (1) 4-PORT FACEPLATE, (4) 8-POSITION CAT 6 RJ-45 JACKS (FOUR DATA). 18" AFF, U.N.O. (1) 2-PORT FACEPLATE, (2) 8-POSITION CAT 6 RJ-45 JACKS (TWO DATA). 18" AFF, U.N.O. 2 S SECURITY GRADE FACEPLATE AV S S PTZ CEILING SPEAKER, (X) DENOTES WHICH AUDIO SYSTEM SPEAKER CONNECTS TO. (Y) DENOTES WHICH ZONE THE SPEAKER BELONGS TO. SPEAKER MOUNTING HEIGHT IS DETERMINED BY WHICH AREA (X) (Y) PAN, TILT, ZOOM CAMERA. CAMERA MOUNTING HEIGHT IS DETERMINED BY AREA CAMERA IS LOCATED. AUDIO/VISUAL FLOOR BOX. SEE PLAN DRAWINGS FOR MORE DETAILS. (X) DENOTES WHICH AUDIO (X) (Y) THE (X) DENOTES THE AMOUNT OF F-CONNECTORS TO BE INSTALELD AT THIS LOCATION. THE SPEAKER IS LOCATED. WALL SPEAKER, (X) DENOTES WHICH AUDIO SYSTEM SPEAKER CONNECTS TO. (Y) DENOTES WHICH ZONE THE SPEAKER BELONGS TO. MOUNT SPEAKER 96" AFF. IN ALL OUTSIDE PLANT CONDUIT RUNS , 1 OF THE 4 CONDUITS SHALL CONTAIN (3) 1-1/4" INNERDUCTS FOR FIBER CABLE. FACTORY FIELD BENDS SHALL HAVE AN INTERNAL BEND RADIUS OF NOT LESS THAN (10) TIMES THE DIAMETER FOR CONDUIT WITH DIAMETER OF TWO INCHES OR LARGER. FACTORY FIELD BENDS SHALL HAVE AN INTERNAL BEND RADIUS OF NOT LESS THAN (6) TIMES THE DIAMETER FOR CONDUIT WITH DIAMETER OF TWO INCHES OR SMALLER . LIMITS OF ENLARGED PLAN. REFER TO DETAIL SYMBOL FOR LOCATION WHERE DETAIL CAN BE FOUND. LABEL ALL TELECOMMUNICATION SYSTEMS PER TIA/EIA-606A. DO NOT USE ELBOWS, LB BOXES, ETC. FOR CONDUIT DIRECTION CHANGES. WHEN PULL BOXES ARE NOT USED, ONLY SWEEPING BENDS SHOULD BE USED. FURNISH ADDITIONAL MATERIALS AS IDENTIFIED HEREIN AND WITHIN PROJECT SPECIFICATIONS. MOUNT D-RINGS EVERY 12 INCHES ALONG CABLE RUNS TO SUPPORT ENTERING AND EXITING WIRING FIELDS. UTILIZE VELCRO CABLE TIES TO ATTACH CABLES TO WIRE MANAGEMENT, D-RINGS AND OTHER SUPPORT MEANS. LABEL ALL CABLES WITHIN 4 INCHES OF EACH TERMINATION. PROVIDE WARNING OR CAUTION LABELS ON ALL ENCLOSURES THAT USE OR CONTAIN FIBER OPTIC CABLING. CONDUITS HAVE BEEN SIZED BASED ON THE ANSI/EIA/TIA -569-B. WHERE INSTALLATIONS VARIES, INCREASE CONDUITS SIZES ACCORDING TO MAXIMUM NUMBER OF CABLES BASED ON ALLOWABLE FILL TABLE. PROVIDE METALLIC CONDUIT WITH INSULATED BUSHINGS AT TERMINATIONS. INSTALL TELECOMMUNICATIONS PULL BOXES IN STRAIGHT SECTIONS OF CONDUIT. DO NOT USE BOXES IN LIEU OF SWEEPING BENDS. NOT ALL TELECOMMUNICATIONS PULL BOXES ARE SHOWN. BEYOND THOSE SHOWN PROVIDE BOXES WHEN: ALL TELECOMMUNICATIONS BONDING BACKBONE CONDUCTORS SHALL BE INSULATED, COPPER CONDUCTORS. WHERE TBB CONDUCTORS ARE INSTALLED IN METALLIC CONDUIT, BOND BOTH ENDS WITH A LISTED BONDING BUSHING. TERMINATE TBB AND GE CONDUCTORS ON TMGB AND TGBs WITH A LISTED TWO-HOLE COMPRESSION CONNECTOR. UNLESS NOTED OTHERWISE (UNO), ALL CONDUITS SHALL BE INSTALLED CONCEALED UNDER FLOOR SLABS, ABOVE THE CEILING AND WITHIN THE FINISHED WALLS. ALL OUTLET BOXES SHALL BE INSTALLED FLUSH MOUNTED WITHIN FINISHED WALLS, CEILINGS OR FLOORS. PROVIDE NYLON PULL CORD HAVING AT LEAST A 198 POUNDS FORCE TENSILE STRENGTH IN ALL TELECOMMUNICATIONS CONDUITS. ALL PENETRATIONS SHALL BE SEALED WITH AN APPROVED SEALANT OR UL LISTED PENETRATION DEVICE THAT WILL MAINTAIN THE FIRE, SMOKE AND WATERPROOF OR OTHER APPLICABLE RATINGS OF THE TYPE OF CONSTRUCTION BEING PENETRATED. COORDINATE WITH ARCHITECTURAL PLANS TO DETERMINE PENETRATION LOCATIONS THAT REQUIRE FIRE RATED SEALANTS. ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN USED ON THE PLANS. SYMBOLS NOT LISTED IN LEGEND ARE IDENTIFIED WHERE THEY OCCUR. xxxx TGB um OF OPTICAL FIBER AV AUDIO/VISUAL WALL OUTLET. SEE PLAN DRAWINGS FOR MOUNTING HEIGHTS. (X) DENOTES WHICH AUDIO ALL VERTICAL SEGMENTS OF CABLE TRAY WILL UTILIZE WATERFALL TYPE ACCESSORIES TO TRANSITION BETWEEN HORIZONTAL AND VERTICAL RUNS. CABLE WILL BE FASTENED TO CABLE TRAY WITH VELCRO ON ALL VERTICAL CABLE TRAY RUNS. CAMERA AND CABLE ARE GFGI. FIXED CAMERA. CAMERA MOUNTING HEIGHT IS DETERMINED BY AREA CAMERA IS LOCATED.(GFGI) FLOOR BOX, FLUSH MTD. WITH POWER AND COMMUNICATIONS BARRIERS. PROVIDE (1) 4-PORT FACEPLATE, (4) 8-POSITION CAT6 RJ-45 JACK (UNIVERSAL). (X) (X) SYSTEM OUTLET IS USED WITH. SEE DESCRIPTION UNDER NEW WORK # 1. SYSTEM OUTLET IS USED WITH. SEE DESCRIPTION UNDER NEW WORK # 1. STE SECURE TELEPHONE EQUIPMENT QTY QUANTITY AHJ AUTHORITY HAVING JURISDICTION (1) 4-PORT FACEPLATE, (2) 8-POSITION CAT 6 RJ-45 JACKS (ONE VOICE & ONE DATA). INSTALLED IN WALKERDUCT RACEWAY. NEW TELECOM MANHOLE/HANDHOLE. 2 2 2 1 1 1 3 3 3 4 4 4 5 5 5 2 2 2 1 1 1 3 3 3 4 4 4 5 5 5 C C C B B B A A A D D D C C C B B B A A A D D D APPR APPR APPR APPR DATE DATE DATE DATE DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION SYM SYM SYM SYM DES DES DES DES DRW DRW DRW DRW CHK CHK CHK CHK SHEET OF SHEET OF SHEET OF SHEET OF SCALE: SCALE: SCALE: SCALE: EPROJECT NO. EPROJECT NO. EPROJECT NO. EPROJECT NO. CONSTR. CONTR. NO. CONSTR. CONTR. NO. CONSTR. CONTR. NO. CONSTR. CONTR. NO. NAVFAC DRAWING NO. NAVFAC DRAWING NO. NAVFAC DRAWING NO. NAVFAC DRAWING NO. CHIEF ENG/ARCH CHIEF ENG/ARCH CHIEF ENG/ARCH CHIEF ENG/ARCH BRANCH MANAGER BRANCH MANAGER BRANCH MANAGER BRANCH MANAGER PM PM PM PM DEPARTMENT OF THE NAVY DEPARTMENT OF THE NAVY DEPARTMENT OF THE NAVY DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND NAVAL FACILITIES ENGINEERING COMMAND NAVAL FACILITIES ENGINEERING COMMAND NAVAL FACILITIES ENGINEERING COMMAND NAVAL FACILITIES ENGINEERING COMMAND ~ MID-ATLANTIC FIRE PROTECTION FIRE PROTECTION FIRE PROTECTION FIRE PROTECTION SATISFACTORY TO SATISFACTORY TO SATISFACTORY TO SATISFACTORY TO DATE DATE DATE DATE FOR COMMANDER NAVFAC FOR COMMANDER NAVFAC FOR COMMANDER NAVFAC FOR COMMANDER NAVFAC ACTIVITY ACTIVITY ACTIVITY ACTIVITY APPROVED APPROVED APPROVED APPROVED N40085-09-D-5000 N40085-09-D-5000 N40085-09-D-5000 N40085-09-D-5000 796454 796454 796454 796454 NAVAL STATION - NORFOLK, VIRGINIA NAVAL STATION - NORFOLK, VIRGINIA NAVAL STATION - NORFOLK, VIRGINIA NAVAL STATION - NORFOLK, VIRGINIA MCNC IPT MCNC IPT MCNC IPT MCNC IPT JACKSONVILLE, NC JACKSONVILLE, NC JACKSONVILLE, NC JACKSONVILLE, NC MARINE CORPS AIR STATION NEW RIVER MARINE CORPS AIR STATION NEW RIVER MARINE CORPS AIR STATION NEW RIVER MARINE CORPS AIR STATION NEW RIVER NONE NONE NONE NONE 285 285 285 285 A. LABIDI A. LABIDI A. LABIDI A. LABIDI B. ABBOTT B. ABBOTT B. ABBOTT B. ABBOTT S. NEWSOME S. NEWSOME S. NEWSOME S. NEWSOME R. DALEY R. DALEY R. DALEY R. DALEY CJF CJF CJF CJF CJF CJF CJF CJF MJG MJG MJG MJG P-714 PHYSICAL FITNESS CENTER 275 275 275 275 12582250 12582250 12582250 12582250 T-001 LEGEND, NOTES, AND ABBREVIATIONS LEGEND, NOTES, AND ABBREVIATIONS LEGEND, NOTES, AND ABBREVIATIONS LEGEND, NOTES, AND ABBREVIATIONS
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
ABBREVIATIONSGENERAL NOTES SYMBOLS
NEW WORK
1. THE NEW TELECOMMUNICATIONS SYSTEMS WILL CONSIST OF VOICE, DATA, CABLE TV, SECURITY CAMERAS,
AND 3 AUDIO SYSTEMS. THE AUDIO SYSTEMS ARE LABELED ON THE PLAN AS SUCH:
3. THE BUILDING WIDE PUBLIC ADDRESS SYSTEM IS DESIGNED TO HAVE A CONTROLLER THAT SITS AT THE MAIN
RECEPTION DESK. THE CONTROLLER IS CAPABLE OF A BUILDING WIDE PAGE OR INDIVIDUAL ZONE PAGES. THE
ZONES WILL SPLIT AS FOLLOWS: GENERAL PURPOSE (A), OFFICE AREA (B), WEIGHTS/CARDIO (C), GYMNASIUM (D),
AND POOL (E). FOR EACH ZONE, (1) 2 PAIR 18 AWG CABLE WILL BE DAISY CHAINED FROM SPEAKER TO SPEAKER
AND BE RUN TO THE FLOOR MOUNT AV RECEPTACLE AT THE MAIN RECEPTION DESK.
4. THERE WILL BE A DEDICATED AUDIO SYSTEM FOR THE WEIGHTS/CARDIO AREA. THIS SYSTEM WILL HAVE
SEPARATE SPEAKERS THAT CONNECT BACK TO THE WALL MOUNT RACK IN THE AV ROOM. THIS SYSTEM
IS DESIGNED SO A CD OR MP3 PLAYER CAN BE PLUGGED INTO THE RACK MOUNT AUDIO SYSTEM AND PLAY
MUSIC IN THE WEIGHTS/CARDIO ROOM.
5. THE GYMNASIUM AUDIO SYSTEM HAS TWO LARGE BOX SPEAKERS THAT ARE MOUNTED AT CENTER COURT
FACING OPPOSITE EACH OTHER MOUNTED 25' ABOVE THE FLOOR. THE SPEAKERS WILL BE FASTENED TO THE
STRUCTURAL SUPPORT BEAMS BUT MAY NOT HANG DOWN BELOW 25'. THESE SPEAKERS WILL BE WIRED TO
THE FLOOR MOUNTED AV OUTLET JUST OFF CENTER COURT. A 1" CONDUIT WILL CONNECT THE SPEAKERS
AND PLUG AN ANNOUNCING SYSTEM CONTROLLER INTO THE AV OUTLET FOR A GYMNASIUM WIDE PA SYSTEM.
TO A 4x4 WALL MOUNTED DEVICE BOX. ANOTHER 1" CONDUIT WILL CONNECT THE WALL BOX TO THE 4x4
FLOOR MOUNTED AV OUTLET. THE SYSTEM IS DESIGNED TO SET UP A PRESS BOX TABLE JUST OFF THE COURT
2. THE CABINET IN THE TELECOMMUNICATIONS ROOM (RM. 125) SHALL HAVE VERTICAL CABLE MANAGEMENT
ON BOTH SIDES. EACH COPPER PATCH PANEL SHALL HAVE SIEMON WM-BK TYPE REAR WIRE MANAGEMENT.
(1) - BUILDING PUBLIC ADDRESS SYSTEM
(2) - WEIGHTS/CARDIO MUSIC SYSTEM
(3) - GYMNASIUM ANNOUNCING SYSTEM NOTE: SEE SPEAKER SYMBOL ON THIS PAGE(4) - MULTI-PURPOSE ROOM A MUSIC SYSTEM(5) - MULTI-PURPOSE ROOM B MUSIC SYSTEM
6. THE MULTI-PURPOSE ACTIVITY ROOM IS ONE LARGE ROOM THAT HAS A RETRACTABLE WALL IN THE MIDDLE.
WHEN THE WALL IS CLOSED, THE ROOMS OPERATE INDIVIDUALLY AND REQUIRE TWO SEPARATE AUDIO SYSTEMS.
WHEN THE WALL IS OPEN, ONE AUDIO SYSTEM MUST BE CAPABLE OF CONTROLLING THE SPEAKERS FOR BOTH
ROOMS. THE LAYOUT WILL CONSIST OF AN AUDIO VISUAL JACK IN THE FRONT OF THE ROOM, A 54" CABINET
THIS ALLOWS THE SPEAKERS IN ROOM 114B TO BE TURNED OFF IF THE PARTITION WALL IS IN THE CLOSED POSITION.
FOR ELECTRONICS, AND CEILING MOUNTED SPEAKERS. THE AUDIO VISUAL JACK AND THE SPEAKERS WILL BE WIRED
TO THE ELECTRONICS IN THE CABINET. THE ELECTRONICS IN EOOM 114A MUST HAVE A TWO ZONE CONTROL (A & B).
7. FOR CCTV LOCATIONS, PROVIDE 1" CONDUIT TO NEAREST TELECOM CABLE TRAY OR DIRECTLY TO TELECOM ROOM.
FIBER OPTICFO
WSWP
WA
UTPUPS
ULUG
TR
TMGBTIATGBTER
TBBSTR
SM
RM
PVCPRPBX
PBP/P
OSP
NFPANEMA
N/ANEC
mmMMMHz
M
LECLAN
EMTEMIEIA
CAT 3
CBLDG
BBAWG
ANSI
AFF
WORKSTATIONWEATHERPROOF
WORK AREA
UNSHIELDED TWISTED PAIRUNINTERRUPTIBLE POWER SUPPLY
MICRON OR MICROMETERUNDERWRITERS LABORATORIESUNDERGROUND CONDUIT
TELECOMMUNICATIONS ROOM
TELECOMMUNICATIONS MAIN GROUNDING BUSBARTELECOMMUNICATIONS INDUSTRY ASSOCIATIONTELECOMMUNICATIONS GROUNDING BUSBARTELECOMMUNICATIONS ENTRANCE ROOM
TELECOMMUNICATION BONDING BACKBONESTRAND
SINGLEMODE
ROOM
POLYVINYL CHLORIDEPAIRPRIVATE BRANCH EXCHANGE
PULL BOXPATCH PANEL
OUTSIDE PLANT
NATIONAL FIRE PROTECTION ASSOCIATIONNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNATIONAL ELECTRICAL CODENOT APPLICABLEMILLIMETERMULTIMODEMEGAHERTZ
CEILING SPEAKER, (X) DENOTES WHICH AUDIO SYSTEM SPEAKER CONNECTS TO. (Y) DENOTES WHICH
ZONE THE SPEAKER BELONGS TO. SPEAKER MOUNTING HEIGHT IS DETERMINED BY WHICH AREA(X) (Y)
PAN, TILT, ZOOM CAMERA. CAMERA MOUNTING HEIGHT IS DETERMINED BY AREA CAMERA IS LOCATED.
AUDIO/VISUAL FLOOR BOX. SEE PLAN DRAWINGS FOR MORE DETAILS. (X) DENOTES WHICH AUDIO
(X) (Y)
THE (X) DENOTES THE AMOUNT OF F-CONNECTORS TO BE INSTALELD AT THIS LOCATION.
THE SPEAKER IS LOCATED.
WALL SPEAKER, (X) DENOTES WHICH AUDIO SYSTEM SPEAKER CONNECTS TO. (Y) DENOTES WHICH
ZONE THE SPEAKER BELONGS TO. MOUNT SPEAKER 96" AFF.
IN ALL OUTSIDE PLANT CONDUIT RUNS , 1 OF THE 4 CONDUITS SHALL CONTAIN (3) 1-1/4" INNERDUCTS FOR FIBER CABLE.
FACTORY FIELD BENDS SHALL HAVE AN INTERNAL BEND RADIUS OF NOT LESS THAN (10) TIMES THE DIAMETER FORCONDUIT WITH DIAMETER OF TWO INCHES OR LARGER.
FACTORY FIELD BENDS SHALL HAVE AN INTERNAL BEND RADIUS OF NOT LESS THAN (6) TIMES THE DIAMETER FORCONDUIT WITH DIAMETER OF TWO INCHES OR SMALLER .
LIMITS OF ENLARGED PLAN. REFER TO DETAIL SYMBOL FOR LOCATIONWHERE DETAIL CAN BE FOUND.
LABEL ALL TELECOMMUNICATION SYSTEMS PER TIA/EIA-606A.
DO NOT USE ELBOWS, LB BOXES, ETC. FOR CONDUIT DIRECTION CHANGES. WHEN PULL BOXES ARE NOT USED,ONLY SWEEPING BENDS SHOULD BE USED.
FURNISH ADDITIONAL MATERIALS AS IDENTIFIED HEREIN AND WITHIN PROJECT SPECIFICATIONS.
MOUNT D-RINGS EVERY 12 INCHES ALONG CABLE RUNS TO SUPPORT ENTERING AND EXITING WIRING FIELDS.
UTILIZE VELCRO CABLE TIES TO ATTACH CABLES TO WIRE MANAGEMENT, D-RINGS AND OTHER SUPPORTMEANS.
LABEL ALL CABLES WITHIN 4 INCHES OF EACH TERMINATION.
PROVIDE WARNING OR CAUTION LABELS ON ALL ENCLOSURES THAT USE OR CONTAIN FIBER OPTIC CABLING.
CONDUITS HAVE BEEN SIZED BASED ON THE ANSI/EIA/TIA -569-B. WHERE INSTALLATIONS VARIES, INCREASECONDUITS SIZES ACCORDING TO MAXIMUM NUMBER OF CABLES BASED ON ALLOWABLE FILL TABLE.
PROVIDE METALLIC CONDUIT WITH INSULATED BUSHINGS AT TERMINATIONS.
INSTALL TELECOMMUNICATIONS PULL BOXES IN STRAIGHT SECTIONS OF CONDUIT. DO NOT USE BOXES IN LIEU OFSWEEPING BENDS. NOT ALL TELECOMMUNICATIONS PULL BOXES ARE SHOWN. BEYOND THOSE SHOWN PROVIDE BOXESWHEN:
ALL TELECOMMUNICATIONS BONDING BACKBONE CONDUCTORS SHALL BE INSULATED, COPPER CONDUCTORS. WHERETBB CONDUCTORS ARE INSTALLED IN METALLIC CONDUIT, BOND BOTH ENDS WITH A LISTED BONDING BUSHING.TERMINATE TBB AND GE CONDUCTORS ON TMGB AND TGBs WITH A LISTED TWO-HOLE COMPRESSION CONNECTOR.
UNLESS NOTED OTHERWISE (UNO), ALL CONDUITS SHALL BE INSTALLED CONCEALED UNDER FLOOR SLABS, ABOVE THECEILING AND WITHIN THE FINISHED WALLS. ALL OUTLET BOXES SHALL BE INSTALLED FLUSH MOUNTED WITHIN FINISHEDWALLS, CEILINGS OR FLOORS.
PROVIDE NYLON PULL CORD HAVING AT LEAST A 198 POUNDS FORCE TENSILE STRENGTH IN ALL TELECOMMUNICATIONSCONDUITS.
ALL PENETRATIONS SHALL BE SEALED WITH AN APPROVED SEALANT OR UL LISTED PENETRATION DEVICE THAT WILLMAINTAIN THE FIRE, SMOKE AND WATERPROOF OR OTHER APPLICABLE RATINGS OF THE TYPE OF CONSTRUCTION BEINGPENETRATED. COORDINATE WITH ARCHITECTURAL PLANS TO DETERMINE PENETRATION LOCATIONS THAT REQUIRE FIRERATED SEALANTS.
ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN USED ON THE PLANS. SYMBOLS NOT LISTED IN LEGEND AREIDENTIFIED WHERE THEY OCCUR.
xxxx
TGB
um
OF OPTICAL FIBER
AVAUDIO/VISUAL WALL OUTLET. SEE PLAN DRAWINGS FOR MOUNTING HEIGHTS. (X) DENOTES WHICH AUDIO
ALL VERTICAL SEGMENTS OF CABLE TRAY WILL UTILIZE WATERFALL TYPE ACCESSORIES TO TRANSITION BETWEEN
HORIZONTAL AND VERTICAL RUNS.
CABLE WILL BE FASTENED TO CABLE TRAY WITH VELCRO ON ALL VERTICAL CABLE TRAY RUNS.
CAMERA AND CABLE ARE GFGI.
FIXED CAMERA. CAMERA MOUNTING HEIGHT IS DETERMINED BY AREA CAMERA IS LOCATED.(GFGI)
FLOOR BOX, FLUSH MTD. WITH POWER AND COMMUNICATIONS BARRIERS. PROVIDE (1) 4-PORT FACEPLATE, (4)
8-POSITION CAT6 RJ-45 JACK (UNIVERSAL).
(X)
(X)
SYSTEM OUTLET IS USED WITH. SEE DESCRIPTION UNDER NEW WORK # 1.
SYSTEM OUTLET IS USED WITH. SEE DESCRIPTION UNDER NEW WORK # 1.
STE SECURE TELEPHONE EQUIPMENT
QTY QUANTITY
AHJ AUTHORITY HAVING JURISDICTION
(1) 4-PORT FACEPLATE, (2) 8-POSITION CAT 6 RJ-45 JACKS (ONE VOICE & ONE DATA). INSTALLED IN WALKERDUCT RACEWAY.