CES IM – Safety Fire & Smoke Actuators
Key Takeaways
2
Fire and smoke- Protecting people and tangible assets in case of a fire.
Goal: Create awareness that users can retrofit failed fire and smoke actuators without replacing
the entire damper assembly.
1. UL does not regulate replacements, the Authority Having Jurisdiction (AHJ) does.
2. Actuators must be replaced with one that is UL555 (fire) and/or UL555S (smokes) Listed.
3. Belimo offers training materials with the conformance test checklist for service technicians.
CESIM Training - Americas
CESIM Fire & Smoke ( just read no slide shown)
CESIM Training - Americas 3
To a certain degree safety and quality are sides of the same coin.
C F&S dampers can be used for balancing – comfort and IAQ
E Our FS actuators consume low power
S Belimo provides safety by protecting life and tangible assets and
preventing financial harm in case of fire
I Direct couple mounting installation takes a fraction of the time of old linkage motors
M Belimo promotes adherence to code required testing and has retrofit instructions that help
maintenance
Smoke Control
NFPA reports that near 80% of deaths
in fires are due to smoke inhalation.
5CESIM Training - Americas
Toxicity of Smoke
Both fire & smoke are killers, but smoke
inhalation leads to unconsciousness & burns
6CESIM Training - Americas
Benefits of Smoke Control
10CESIM Talk 2019
Cools the fire compartment and delays the
flash-over by exhausting the hot gases
Supports the evacuation of people and
animals (smoke free escape routes)
Supports the rescue and fire fighting work
Protects asset values and the infrastructure
Dampers
Four main types of fire and smoke dampers:
Ceiling Radiation
Fire
Smoke
Combination Fire & Smoke
Variations:
Corridor
Multiblade Fire Damper
Various Fitting & Connection Methods
12CESIM Training - Americas
Ceiling Radiation
Heat & Fire Dampers
13
CurtainFusible Links
(Photographs courtesy United Enertech, Greenheck, & Ruskin)
Multiblade Fire
Non-actuated, mechanically released
Typically spring loaded with fusible link release.
CESIM Training - Americas
Actuated Life Safety Dampers
Actuated
Fire Damper
Combination
Fire & Smoke
Smoke
Damper
14CESIM Training - Americas
(Photographs courtesy Greenheck, Nailor, & TAMCO)
(Photograph courtesy Nailor Industries, Inc.)
Combination Fire & Smoke Dampers
Primary heat
sensitive device
BAE165 US
15
Sleeve
Thermal
sensors
Actuator
Jackshaft
Blade
CESIM Training - Americas
1. To maintain compartmentation, duct smoke detectors
will close dampers preventing the spread of smoke; 85%
containment.
2. As part of an engineered smoke control system,
dampers can be re-opened and controlled by the 15%
Fire Fighter Smoke Control System.
.
Applications
17CESIM Training - Americas
Compartmentation
Shafts – up to 50% of dampers
Regardless if HVAC fans are shutdown, without smoke
dampers, smoke will travel throughout the building via
both the supply and return damper shafts.
SMOKE WILL PASS OUT OF FIRE ZONE
INTO UNPROTECTED ZONES.
18CESIM Training - Americas
Containment Fire & Smoke Dampers
Barrier Walls
85% of installed fire & smoke dampers
are for containment.
Dampers in walls & ducts stop fire
and smoke.
COMPARTMENTATION IS INTACT.
19CESIM Training - Americas
Engineered Smoke Control Systems
Stairwells, underground buildings, exit corridors,
stages and auditoriums, elevator shafts, atria,
large spaces
15% of installed fire& smoke dampers are in
smoke control systems.
20CESIM Training - Americas
Fire & Smoke Damper Actuators
28
FSAFB(-SR)
180 in-lbs
250˚F
FSNF
70 in-lbs
350˚F
FSLF
30 in-lbs
350˚F
FSTF
18 in-lbs
250˚F
FSAF*A
180 in-lbs
350˚F
CESIM Training - Americas