Replacement Actuator Issues for Fire and Smoke Dampers April 2008 1 Fire & Smoke Replacemen tActuators 1. Technical Issues 2. Standards and Codes
Mar 31, 2015
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 1
Fire & Smoke ReplacementActuators
1. Technical Issues
2. Standards and Codes
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 2
Fire & Smoke Actuator Replacement Starts with the Damper
Five methods were used in past
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 3
1.
Single spring for actuator and fusible link.
A thermal disc sensor must be retrofitted.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 4
SPRING NEEDS TO BE DISCONNECTED
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 5
The knee-lock is loosened to disconnect the fusible link and spring. Thermal disc is installed with a Belimo.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 6
If a fusible link is on the damper,insert a carriage bolt into the spring arm.Do not remove the other bolt.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 7
An HS10 high limit sensor must be installed.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 8
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 9
2. Dual springs – one for fusible link fire function and one for actuator smoke function. This was very common.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 10
Remove the linkage, motor, springs, and mount Belimo. Depending on damper, mounting may require a plate.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 11
Remove the linkage, motor, springs, and mount Belimo. Depending on damper, mounting may require a plate.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 12
3. Single spring with a, thermal disc sensor.
No fusible link. The actuator springs closed for smoke and for fire. Ruskin MA220, MA230 motors. Phillips 150.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 13
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 14
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 15
Remove spring mechanism.
DANGER. Not typically under extreme load, but could release.
Damper now ready to mount new actuator.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 16
Select orientation to avoid running screws into damper frame and allow available flex to reach.
New flex to ½” connector
Anti-rotation strap
Standard clamp has insert for ½”, 5/8” or remove for 1”
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 17
T150 Phillips – No Spring in Motor
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 18
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 19
4. Modern dampers have spring in actuator.
Some older motors also had the spring in the motor – e.g., MA418.
Some older motors had an obvious external spring.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 20
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 21
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 22
Prefco
McCabe Link®
If a shaft exists, Belimo can be used.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 23
McCabe® Link
Bimetal
Motor ArmEngaged in Link
The motor arm is engaged in the McCabe® Link above.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 24
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 25
Chase nipple & Wiring
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 26
OEM bracket hung out in air on small damper.
Anti-rotation strap can be attached to bracket, 4 x 4 plate, or sheet metal bracket.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 27
Best to mount the Belimo anti-rotation strap perpendicular to the actuator to allow for movement on non-concentric shaft. This may be why the HW’s fail.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 28
Variety of ways to use the anti-rotation straps.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 29
5. Oldest original dampers used a number of methods.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 30
Prefco’s that cannot use Belimo for replacement due to mounting and applications.
Rebuild damper or replace.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 31
Actuator is no longer made.
Motors, Crank-arm, and negator spring no longer made.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 32
Air Balance has instruction sheet on how to change to modern thermodisc.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 33
Negator spring version of Air Balance
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 34
Fusible rod instead of fusible link.
Note negator springs.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 35
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 36
The spring was on the damper blades on fire/smoke dampers. A second door spring added to the actuator when it was used on smoke dampers. The springs must be removed before Belimo installed.
MP2781
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 37
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 38
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 39
The linkage is technically inferior the correct practice is:
Replace the damper.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 40
We could go on and on.
Bottom line:
Take a picture if you can. Get not only make and model of the old motor, but also the make and model of the damper.
Replacement starts with the damper, not the motor.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 41
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 42
Fire Department needs to be consulted. The actuator is connected to the alarm system.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 43
Considerations
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 44
Replacement Rules:
1. Replacement actuator should be UL555S listed with the damper manufacturer.
2. Obey the TTT-VAT rules:
a. Temperature rating of replacement must be equal or better.
b. Torque should be equal or better
c. Time should be same or better.
d. Voltage must be the same
e. Amperage draw should be equal or less than original.
f. TEST the damper, controls, and actuator when finished.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 45
Torque
OB = 6-10 in- # / sq. ft.
PB = 8-14 in- # / sq. ft.
If in doubt use the highest for estimating. Manufacturers vary significantly.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 46
Breaker loading (20A Emergency circuit)
(15A – other loads) / 1 actuator amp draw
= Number of Actuators
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 47
Damper blade switches are subject to broken coat hanger connection.
Actuator aux switches are subject to less problems.
The jackshaft linkage is more solid.
Auxiliary SwitchesNew construction and retrofit issue.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 48
Actuator aux switches are technically equal or superior depending on details.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 49
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 50
Codes require all the components be checked. Typically, only the alarm functions are verified.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 51
Now damper is ready for testing. Typically:
1. Apply power and let damper drive open. Cut power and ensure spring closes damper completely. Repeat three times to check assembly.
2. Use heat gun to check thermal sensor. Reset manually.
3. Replace fusible link if required.
4. Other tests per damper manufacturer or local codes.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 52
CODES
UL clearly states in their Marking Guide that they do not regulate replacement market.
NFPA 80 & 105 state clearly that defective dampers should be repaired ASAP.
Local Authority Having Jurisdiction (AHJ) sets the requirements. Almost all administrative and life safety codes state all systems must be kept in operating order.
Codes do not cover replacement in detail since they are new construction oriented.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 53
Local codes vary. In general:
• Fire & Smoke Dampers must be repaired.
• Fire Marshal is informed via form if replacement of actuator only.
• If any alarm or smoke control wires are removed and reinstalled, an inspection is required.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 54
Call AHJ and ask if a permit is required if:
a. Replacement is an actuator that is UL555S Listed with the damper manufacturer,
b. No alarm wiring is being touched,
c. Damper will be conformance tested using manufacturer instructions,
d. A notice form for Fire Marshal will be left on premises. Form has testing checklist.
Remember: LAPF
Possibly the worst pneumonic device ever!
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 55
MEA 197-07-M
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 56
MEA 197-07-M
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 57
MEA 197-07-M
City of New York MEA Belimo documents available:
www.belimo.us/sh/firesmoke/imates/1_MEA_Tag_Regulations.pdf
…2_MEA_F&S_Replacement_Data_&_Cross_ Reference.pdf
…3_MEA_Fire_Marshal_Form F&S_Actuators.pdf
Individual damper manufacturer instructions are available also.
Replacement Actuator Issues for Fire and Smoke Dampers April 2008 58
Thank you