PAGE 1 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 ADDENDUM #1 DATE: October 8, 2018 TO CONTRACT DOCUMENTS ENTITLED: HEARNES CHILLER REPLACEMENT MU PROJECT NUMBER: CP181141 At University of Missouri Columbia, Missouri 65211 ADVERTISEMENT DATE: Monday, October 8, 2018 PREPARED FOR: The Curators of the University of Missouri CONSULTANT Ross & Baruzzini, Inc. 6 South Old Orchard St. Louis, Missouri 63119 314-918-8383 Drawings and Specifications for the above noted project and the work covered thereby are herein modified as follows, and except as set forth herein, otherwise remain unchanged and in full force and effect: Specifications: 1. 22 01 00 – Basic Plumbing Materials and Methods: a. Modify the footer on all five (5) pages as follows: BASIC PLUMBING MATERIALS AND METHODS 22 0100. 2. 23 09 00 – Control Systems: a. ADD: 1.1 D to end of paragraph: Owner shall disconnect, tag and remove all controllers where device is called out to be re-used on sheet M701. b. ADD: 2.3 A to end of paragraph: All control valves shall be line size only. c. ADD: 2.3.B.aa to read: i. Disconnect ii. 1) Provide 16amp, non-metallic, watertight, unfused disconnect (Model number 69-952). iii. 2) Enclosure: Exterior NEMA 3R, Interior NEMA 1. All with locking quarter-turn latch and key. Drawings: 1. There is a total of forty-three (43) drawings in design documents. This submittal incorrectly included duplicates of drawings A601 DUMPSTER ENCLOSURE PLANS, ELEVATIONS AND DETAILS and A701 CONSTRUCTION DETAILS, SCHEDULES, PLANS, AND ELEVATIONS. a. REMOVE one copy of A601 DUMPSTER ENCLOSURE PLANS, ELEVATIONS AND DETAILS and one copy of A701 CONSTRUCTION DETAILS, SCHEDULES, PLANS, AND ELEVATIONS from design documents. 2. M100: a. MODIFY MECHANICAL SITE WORK – COOLING TOWER DEMO AND NEW WORK PLAN: Add keyed note 9 to plan. 3. M700:
12

ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

Aug 08, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

PAGE 1 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1

ADDENDUM #1 DATE: October 8, 2018 TO CONTRACT DOCUMENTS ENTITLED:

HEARNES CHILLER REPLACEMENT MU PROJECT NUMBER: CP181141 At University of Missouri Columbia, Missouri 65211

ADVERTISEMENT DATE: Monday, October 8, 2018 PREPARED FOR: The Curators of the University of Missouri CONSULTANT Ross & Baruzzini, Inc. 6 South Old Orchard St. Louis, Missouri 63119 314-918-8383 Drawings and Specifications for the above noted project and the work covered thereby are herein modified as follows, and except as set forth herein, otherwise remain unchanged and in full force and effect:

Specifications:

1. 22 01 00 – Basic Plumbing Materials and Methods:

a. Modify the footer on all five (5) pages as follows: BASIC PLUMBING MATERIALS AND METHODS 22 0100.

2. 23 09 00 – Control Systems: a. ADD: 1.1 D to end of paragraph: Owner shall disconnect, tag and remove all

controllers where device is called out to be re-used on sheet M701. b. ADD: 2.3 A to end of paragraph: All control valves shall be line size only. c. ADD: 2.3.B.aa to read:

i. Disconnect ii. 1) Provide 16amp, non-metallic, watertight, unfused disconnect (Model

number 69-952). iii. 2) Enclosure: Exterior NEMA 3R, Interior NEMA 1. All with locking

quarter-turn latch and key. Drawings:

1. There is a total of forty-three (43) drawings in design documents. This submittal incorrectly included duplicates of drawings A601 DUMPSTER ENCLOSURE PLANS, ELEVATIONS AND DETAILS and A701 CONSTRUCTION DETAILS, SCHEDULES, PLANS, AND ELEVATIONS.

a. REMOVE one copy of A601 DUMPSTER ENCLOSURE PLANS, ELEVATIONS AND DETAILS and one copy of A701 CONSTRUCTION DETAILS, SCHEDULES, PLANS, AND ELEVATIONS from design documents.

2. M100: a. MODIFY MECHANICAL SITE WORK – COOLING TOWER DEMO AND NEW WORK

PLAN: Add keyed note 9 to plan. 3. M700:

Page 2: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1

a. MODIFY CONTROLS: Modify controls of exhaust fan EF-1 and refrigerant alarm for chillers C-1 and C-2.

b. MODIFY CONTROLS: Modify control of refrigerant alarm for chiller C-3.

4. M701: a. MODIFY CONTROLS: Modify controls of exhaust fan EF-1.

5. M702:

a. ADD CONTROLS: Add detail D-EXHAUST FAN START DETAIL. b. ADD CONTROLS: Add REFRIGERANT LEAK DETECTION CHILLER ROOM 115C

SEQUENCE OF OPERATION. c. ADD CONTROLS: Add REFRIGERANT LEAK DETECTION CHILLER ROOM 115E

SEQUENCE OF OPERATION. d. ADD CONTROLS: Add EXHAUST FAN (EF-1) SEQUENCE OF OPERATION.

6. M703:

a. ADD CONTROLS: ADD detail H-DDC PANEL MOUNTING DETAIL. b. MODIFY CONTROLS: ADD detail DDC PANEL LAYOUT.

7. E100:

a. ADD branch circuit and connections to mechanical control valves at existing cooling towers.

8. E200: a. ADD branch circuits and connections to mechanical control valves as shown. b. REVISE pushbutton and disconnect switch location for SE4 due to relocation of doors to

electrical room. c. ADD branch circuits and connections to mechanical refrigerant alarm panels. d. ADD branch circuits and connections to mechanical flow meters and electrical energy

meters. e. ADD receptacle outlets for existing mechanical chemical treatment tank and owner

provided brominator.

9. E300: a. ADD feeders to MCC4 and MS4 for mechanical control valves. b. REVISE new to existing work connections for existing tower fans, TF-1, 2, 3, and 4. c. REVISE keynote 5 for clarification purposes. d. ADD VFD schedule.

10. E600:

a. REVISE CTP1 panel schedule to incorporate branch circuiting for mechanical control valves at existing cooling towers.

Attachments:

1. M100 – MECHANICAL SITE WORK – COOLING TOWER DEMO AND NEW WORK PLAN 2. M700 – CONTROLS 3. M701 – CONTROLS 4. M702 - CONTROLS 5. M703 – CONTROLS 6. E100 – ENLARGED PARTIAL SITE PLAN – NEW WORK 7. E200 – ENLARGED CHILLER ROOM PLAN – NEW WORK 8. E300 – ELECTRICAL ONE-LINE 9. E600 – ELECTRICL SCHEDULES

Page 3: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

PAGE 3 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1

END OF ADDENDUM 1

Page 4: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

CR

CR

CS CS

CR

CS

I

I

I

I

EXISTING COOLING TOWER - DEMO PLAN

1/8" = 1'-0"

A

COOLING TOWER MODEL: MARLEY NC8312F-4SM (4 CELLS)

SERIAL NUMBER: 237738

LOCATION: HEARNES CENTER - COLUMBIA, MISSOURI

PROJECT BACKGROUND

THE EXISTING REFERENCED COOLING TOWER WAS INSTALLED 2004. THE

COOLING TOWER CONSTRUCTION IS FROM 100% STAINLESS STEEL AND

ORIGINAL DESIGN CONDITIONS OF 6,800 GPM WITH 100 DEG F EWT - 85 DEG F

LWT AT 80 DEG WB. THE COOLING TOWER IS BEING UPGRADED TO ACHIEVE

7,620 GPM WITH 97.12 DEG F EWT, 85.3 DEG F LWT AT 81 DEG WB.

SCOPE OF WORK BID AS ALTERNATE 1

THE COOLING TOWER PVC FILL AND DRIFT ELIMINATOR REPLACEMENT

PROJECT SHALL BE PERFORMED ON ALL FOUR (4) CELLS. THE EXISTING PVC

FILL MEDIA AND DRIFT ELIMINATORS SHALL BE REMOVED FROM THE COOLING

TOWER. REMOVED MATERIALS SHALL BE DISPOSED IN DUMPSTERS

PROVIDED BY CONTRACTOR. NEW MARLEY OEM MX75 FILL SHALL BE

INSTALLED PER FACTORY GUIDELINES. NEW MARLEY OEM TU12 DRIFT

ELIMINATORS SHALL BE INSTALLED. REPLACE 378 HOT WATER DISTRIBUTION

BASIN METERING NOZZLES, PER CELL, TO ACCOMMODATE NEW FLOW RATE

OF 7,620 GPM OVER THE FOUR (4) CELLS.

MATERIALS

4 NC8312 FILL KIT D46535

4 TOP MODULE DRIFT ELIMINATOR KIT D47159

4 BOTTOM MODULE DRIFT ELIMINATOR KIT D47160

1,512 HOT WATER BASIN METERING NOZZLES D44542

ONLY MARLEY OEM MATERIALS ARE ACCEPTABLE, NO SUBSTITUTIONS WILL

BE ALLOWED.

CONTRACTOR SHALL PROVIDE MARLEY WARRANTY CERTIFICATE OF

PERFORMANCE UPON COMPLETION.

ALTERNATE 2 - NOTES:

*

KEYED NOTES:

1. EXISTING CHEMICAL TREATMENT TANKS. ONLY SHOWN AS REFERENCE.

OWNER SHALL REMOVE AS REQUIRED.

2. COMPLETELY DEMOLISH EXISTING AIR COOLED CONDENSING UNIT, PIPING,

AND ALL ACCESSORIES. EXISTING REFRIGERANT PIPING ROUTED BELOW

GRADE FROM BUILDING TO EQUIPMENT SHALL BE ABANDONED IN PLACE. CAP

PIPING A MINIMUM 6-INCH BELOW GRADE AT UNITS. CONTRACTOR SHALL

PROVIDE ROCK COVER MATCHING EXISTING WHERE EXISTING CONCRETE

PADS HAVE BEEN REMOVED. ALL EXISTING REFRIGERANT SHALL BE CLAIMED

BY OWNER PRIOR TO REMOVAL OF EQUIPMENT. COORDINATE WITH OWNERS

REPRESENTATIVE. EXISTING CONCRETE PAD SHALL REMAIN.

3. DISCONNECT AND REMOVE EXISTING CONTROL VALVE.

4. INSTALL NEW CONTROL VALVE. REUSE WIRE ON EXISTING DDC POINTS

WHERE DEVICE IS LOCATED AT THE COOLING TOWER.

5. INSTALL NEW ELECTRIC BASIN HEATER. EACH BASIN SHALL HAVE A

SEPARATE CONTROLLER AND ELECTRICAL FEED. REFER TO SPECIFICATIONS

AND CONTROL DRAWINGS (SERIES M700s). COORDINATE WITH DIVISION 26.

6. INSTALL NEW HEAT TRACE ON EXISTING CONDENSER WATER SUPPLY AND

RETURN PIPING (CS AND CR) EXPOSED BELOW COOLING TOWER TO BASIN.

INSTALL ON PIPING TO A MINIMUM 42-INCHES DEEP BELOW GRADE. REFER

TO SPECIFICATIONS FOR INSTALLATION REQUIREMENTS. COORDINATE WITH

DIVISION 26. RETURN GRADE TO MATCH EXISTING CONDITIONS.

7. EXISTING INTERNAL CR PIPING SHALL HAVE 3/16-INCH WEEP HOLE TO ALLOW

RISERS TO DRAIN TO BASIN UPON NO PUMP FLOW.

8. CONTRACTOR'S OPTION: AREA WITHIN COOLING TOWER ENCLOSURE IS

AVAILABLE FOR CONTRACTOR TO USE AS LAY-DOWN AND STORAGE OF

MATERIALS AND EQUIPMENT THROUGH THE DURATION OF THE

CONSTRUCTION PROJECT. IF CONTRACTOR SHALL SO CHOOSE TO USE AREA,

CONTRACTOR SHALL INSTALL TEMPORARY FENCING WITHIN COOLING TOWER

ENCLOSURE AREA TO PROTECT OWNER'S EQUIPMENT (COOLING TOWER AND

CHEMICAL TREATMENT). UPON COMPLETION OF CONSTRUCTION

CONTRACTOR SHALL REMOVE TEMPORARY FENCING AND RESTORE AREA TO

MATCH EXISTING CONDITIONS. COORDINATE WITH OWNERS

REPRESENTATIVE.

9. EXISTING DRAWINGS SHOW TWO (2) EXISTING 3-INCH DIRECT BURIED

CONTROL CONDUITS EXIST FROM TOWERS TO BASEMENT MECHANICAL

ROOM. ROUTE NEW CONTROLS FOR BASIN HEATERS FROM COOLING

TOWERS INTO MECHANICAL ROOM BASEMENT. CONTROLS WILL TERMINATE

ON NEW DDC CONTROLS IN BASEMENT MECHANICAL ROOM.

1

M300

SECTION - EXISTING COOLING TOWER ENCLOSURE - DEMO PLAN

1/8" = 1'-0"

1

EXISTING AIR COOLED

CONDENSING UNIT

EXISTING AIR COOLED

CONDENSING UNIT

1

1

1

1

1

1

1

1

2

2

10" CR LOCATED ON TOP

OF EXISTING COOLING

TOWER

10" CR LOCATED ON TOP

OF EXISTING COOLING

TOWER

10" CR LOCATED ON TOP

OF EXISTING COOLING

TOWER

10" CR LOCATED ON TOP

OF EXISTING COOLING

TOWER

CR

CR

CR

CR

10" CR10" CR 10" CR10" CR

10" CS

16" CS

16" CR

18" CR 18" CS

18" CS

16" CR

10" CR

10" CS

10" CS10" CS3 3 3 3

CR

CR

CS CS

CR

CS

I

I

I

I

EXISTING COOLING TOWER - NEW WORK PLAN

1/8" = 1'-0"

B

2

M300

SECTION - EXISTING COOLING TOWER ENCLOSURE - NEW WORK PLAN

1/8" = 1'-0"

2

1

1

CR

CR

CR

CR

10" CR10" CR 10" CR10" CR

10" CS

16" CS

16" CR

18" CR 18" CS

18" CS

16" CR

10" CR

10" CS

10" CS10" CS

CV

10

CV

11

CV

12

CV

13

4444

55

6

6

6

6

6

6

6

6

5 5

66

7777

EXISTING CT-4 EXISTING CT-3 EXISTING CT-2 EXISTING CT-1 EXISTING CT-4 EXISTING CT-3 EXISTING CT-2 EXISTING CT-1

8

8

CONTRACTOR'S OPTIONAL

LAY-DOWN AREA

5555

EXISTING CT-4 EXISTING CT-3 EXISTING CT-2 EXISTING CT-1EXISTING CT-4 EXISTING CT-3 EXISTING CT-2 EXISTING CT-1

3" CONTROL CONDUIT3" CONTROL CONDUIT 3" CONTROL CONDUIT3" CONTROL CONDUIT

9

1

ADD #1

1

ADD #1

1

ADD #1

6 S

OU

TH

O

LD

O

RC

HA

RD

ST

. L

OU

IS

, M

O 63

11

9

T 31

4.9

18.838

3

F 31

4.9

18.176

6

ww

w.ro

ssba

r.com

MU PROJ. NO:

© ROSS & BARUZZINI, INC 2018

ISSUE DATE:

RB PROJ. NO.:

CHECKED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal sealappear on this document, assumes responsibility only forwhat appears hereon, and disclaims responsibility for all otherplans, specifications, estimates, reports, documents orinstruments not sealed by the Professional Engineer relatingto, or intended to be used for, any part or parts of theengineering project to which this document refers. Printssealed by the Engineer bear the embossed or wet seal of theEngineer across the signature and date. Copies of thisdocument, as signed and sealed, have been retained by theProfessional Engineer. The Professional Engineer will not beresponsible for subsequent changes to this document, unlessthe changes are made by the Engineer or with the Engineer'swritten authorization.

ROSS & BARUZZINIMISSOURI STATE CERTIFICATE

OF AUTHORITY #000148

1 INCH

DATE DESCRIPTION

SOAMISSOURI STATE CERTIFICATE OF

AUTHORITY #000826

2801

WOO

DARD

DRI

VE, S

UITE

103

COLU

MBIA

, MO

6520

2T:

573-

443-

1407

www.

soa-

inc.co

m

HE

AR

NE

S - C

HIL

LE

R R

EP

LA

CE

ME

NT

UM

P

RO

JE

CT

N

UM

BE

R C

P1

81

14

1

CO

LU

MB

IA

, M

IS

SO

UR

I

505-111

UN

IV

ER

SIT

Y O

F M

IS

SO

UR

I

10/1/2018

DESIGNED BY:

CP181141

ASDGMISSOURI STATE CERTIFICATE OF

AUTHORITY #2003024243

1009

LINC

OLN

HIGH

WAY

FAIR

VIEW

HEI

GHTS

, IL 62

208

T: 61

8-62

8-08

87ww

w.as

dgllc

.com

RANDY J. DIEMER

ENG. LIC. NO. PE-2017015702

10/1/2018

RJD

JRC

M100

MECHANICAL SITE WORK -

COOLING TOWER DEMO

AND NEW WORK PLAN

10/8/181

ADDENDUM 1

Page 5: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

DECOUPLER

TT

CH1S-T

CH1R-T

CP-1

104

103

FM 101

TT

TT

CH1-F

M

M

PP

LP-1

MVFD

VFD

FM

710

LP1-KW

707

114

108

CP1-SC

CP1-KW

CP1-S

EMON

EMON

116

CP1-SS

LOOP

CHILLED WATER SUPPLY

LOOP

CHILLED WATER RETURN

704

EMON

CHILLER 1

CH2S-T

CH2R-T

CP-2

204

203

FM 201

TT

TT

PP

CH2-F

MVFD

708

214

208

CP2-SC

CP2-KW

CP2-S

EMON

216

CP2-SS

705

EMON

CHILLER

VFDCHILLER

CONTROL PANEL

BACnet CARD

CHILLER 2

CH2-ALM

CH2-S

CH2-ENB

CH2-HAND

CH2-AUTO

O

H A

210

209

215

207

211

CH2-BACNET

702

CH3S-T

CH3R-T

CP-3

304

303

FM 301

TT

PP

TT

PP

CH3-F

MVFD

709

314

308

CP3-SC

CP3-KW

CP3-S

EMON

316

CP3-SS

706

EMON

CHILLER 3

CH3-ALM

CH3-S

CH3-ENB

CH3-HAND

CH3-AUTO

O

H A

310

309

315

307

311

CH3-BACNET

703

M LP-2

VFD

LP2-KW

EMON

M LP-3

VFD

712

LP3-KW

EMON

M M

EXISTING COOLING TOWER

VFD

716

VFD

715

TF1-KW

TF2-KW

EMON

EMON

VFD

718

VFD

717

TF3-KW

TF4-KW

EMON

EMON

M

TP-1

VFD

713

TP1-KW

EMON

TP-2

M

VFD

714

TP2-KW

EMON

M

CHM-P

M

CH

MP

-S

CH

MP

-S

S

611605

FCL

TW-FCL

604

HEARNES

BUILDING LOADS

M

M

FM

TT

TT TT

BROMINATOR

M

OX-SS

OX-S

FM202

CH2TW-F

CH2TWR-T

206TT

CH2TWS-T

205

M

CH2TW-V

213

M M M M

TT

PP

FM302

CH3TW-F

CH3TWR-T

306

PP

TT

CH3TWS-T

305TT

PP

M

CH3TW-V

313

FM102

CH1TW-F

CH1TWR-T

106

PP

TT

CH1TWS-T

105TT

PP

M

CH1TW-V

113

608

613

BLOWDOWN

DRAIN

BLWDWN-SS

P

612

TWS-PRS

502

P

TWR-PRS

503

CH

3-R

EF

AL

M

312

REFRIG.

MON.

TT

TT

535

TW-BSN-HT

OA

-T

411

CHILLER SYSTEM EMCS CONTROL SCHEMATIC

NO SCALE

A

1. COORDINATE THIS DRAWING WITH DDC CONTROL POINTS LISTS.

2. SEE SPECIFICATIONS FOR DEVICE SPECIFICATIONS.

3. COORDINATE THIS DRAWING WITH FLOW DIAGRAM.

4. COORDINATE THIS DRAWING WITH CONTROLS DETAILS.

5. ANY DEVICE REQUIRING POWER MUST BE POWERED BY

CONTRACTOR.

6. REFER TO DDC POINTS LISTS FOR NEW/EXISTING DESIGNATIONS.

NOTES:

1

KEYED NOTES:

SEE START CIRCUIT DETAIL.

COORDINATE WITH CHEMICAL TREATMENT DETAILS.

INSTALL PETE'S PLUG TEMPERATURE PORTS NEAR EACH TEMPERATURE

SENSOR/TRANSMITTER.

E-MON KW METER BACNET DEVICE ON FC BUS.

REUSE WIRE ON EXISTING DDC POINTS WHERE DEVICE IS LOCATED AT THE

COOLING TOWER.

PROVIDED BY OWNER. INSTALLED BY OWNER. POWER, CONTROL, AND PIPING

CONNECTIONS PROVIDED BY CONTRACTOR.

FIELD COORDINATE INJECTION POINTS WITH OWNER. INJECTION POINTS

SHALL BE SEPARATED BY A MINIMUM OF 2 FEET.

2

3

4

5

6

7

4

1

4

3

3

2

26

3

3

3

3

5555

5

5

5 5 5

1

4

1

4

1

4

1

4

6

2

2

4

4

4

3

3

1

1

4

4

3

3

1

1

4

3

3

1

1

1

4

1

4

1

4

3

3

CHILLER

VFDCHILLER

CONTROL PANEL

BACnet CARD

CHILLER

VFDCHILLER

CONTROL PANEL

BACnet CARD

TW

-B

SN

-H

T

536

TW

-B

SN

-H

T

537

538

TW-BSN-HT

1

MR

-T

801

S

MECHANICAL

ROOM

1

ADD #1

1

ADD #1

CH1-REFALM

112

AIR

EXHAUST

802

EF

1-S

M

EF-1

REFRIG.

MON.

805

EF

1-S

S

EF1-HAND

EF1-AUTO

O

H A

804

803

1

1

ADD #1

6 S

OU

TH

O

LD

O

RC

HA

RD

ST

. L

OU

IS

, M

O 63

11

9

T 31

4.9

18.838

3

F 31

4.9

18.176

6

ww

w.ro

ssba

r.com

MU PROJ. NO:

© ROSS & BARUZZINI, INC 2018

ISSUE DATE:

RB PROJ. NO.:

CHECKED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal sealappear on this document, assumes responsibility only forwhat appears hereon, and disclaims responsibility for all otherplans, specifications, estimates, reports, documents orinstruments not sealed by the Professional Engineer relatingto, or intended to be used for, any part or parts of theengineering project to which this document refers. Printssealed by the Engineer bear the embossed or wet seal of theEngineer across the signature and date. Copies of thisdocument, as signed and sealed, have been retained by theProfessional Engineer. The Professional Engineer will not beresponsible for subsequent changes to this document, unlessthe changes are made by the Engineer or with the Engineer'swritten authorization.

ROSS & BARUZZINIMISSOURI STATE CERTIFICATE

OF AUTHORITY #000148

1 INCH

DATE DESCRIPTION

SOAMISSOURI STATE CERTIFICATE OF

AUTHORITY #000826

2801

WOO

DARD

DRI

VE, S

UITE

103

COLU

MBIA

, MO

6520

2T:

573-

443-

1407

www.

soa-

inc.co

m

HE

AR

NE

S - C

HIL

LE

R R

EP

LA

CE

ME

NT

UM

P

RO

JE

CT

N

UM

BE

R C

P1

81

14

1

CO

LU

MB

IA

, M

IS

SO

UR

I

505-111

UN

IV

ER

SIT

Y O

F M

IS

SO

UR

I

10/1/2018

DESIGNED BY:

CP181141

ASDGMISSOURI STATE CERTIFICATE OF

AUTHORITY #2003024243

1009

LINC

OLN

HIGH

WAY

FAIR

VIEW

HEI

GHTS

, IL 62

208

T: 61

8-62

8-08

87ww

w.as

dgllc

.com

RANDY J. DIEMER

ENG. LIC. NO. PE-2017015702

10/1/2018

CONTROLS

M700

RJD

JRC

10/8/181

ADDENDUM 1

Page 6: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

LOOP PUMPS

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

401 AI PCW-F PRODUCTION CHW FLOW MAGNETIC FLOWMETER NEW REUSE EXISTING

402 AI PCWS-T PROD CHW SUPPLY TEMP RTD/TRANSMITTER NEW REUSE EXISTING

403 AI PCWR-T PROD CHW RETURN TEMP RTD/TRANSMITTER NEW REUSE EXISTING

404 AI LCW-DP LOOP CHW DIFF PRESSURE DIFFERENTIAL PRESSURE TRANSMITTER EXISTING REUSE EXISTING

405 AI LPR-PRS LOOP CHW RET PRESSURE PRESSURE TRANSMITTER EXISTING REUSE EXISTING

406 AI BCW-F BUILDING CHW FLOW MAGNETIC FLOWMETER NEW REUSE EXISTING

407 AI BCWS-T1 BUILDING CHW SUPPLY TEMP 1 RTD/TRANSMITTER NEW REUSE EXISTING

408 AI BCWS-T2 BUILDING CHW SUPPLY TEMP 2 RTD/TRANSMITTER NEW REUSE EXISTING

409 AI BCWR-T BUILDING CHW RETURN TEMP RTD/TRANSMITTER NEW REUSE EXISTING

410 AI BCW-DP BUILDING CHW DIFF PRESSURE DIFFERENTIAL PRESSURE TRANSMITTER EXISTING REUSE EXISTING

411 AI OA-T BUILDING OUTSIDE AIR TEMP RTD EXISTING REUSE EXISTING

412 BI LP1-S LOOP PUMP 1 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

413 BI LP2-S LOOP PUMP 2 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

414 BI LP3-S LOOP PUMP 3 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

415 BI BP1-S BUILDING PUMP 1 STATUS VFD AUX. CONTACT/CONTROL RELAY EXISTING REUSE EXISTING

416 BI BP2-S BUILDING PUMP 2 STATUS AUX. CONTACT/CONTROL RELAY EXISTING REUSE EXISTING

417 AO LP1-SC LOOP PUMP 1 SPEED CTRL VFD NEW REUSE EXISTING

418 AO LP2-SC LOOP PUMP 2 SPEED CTRL VFD NEW REUSE EXISTING

419 AO LP3-SC LOOP PUMP 3 SPEED CTRL VFD NEW REUSE EXISTING

420 AO BCW-V1 BUILDING CHW VALVE 1 ELECTRIC ACTUATOR NEW REUSE EXISTING

421 AO BCW-V2 BUILDING CHW VALVE 2 ELECTRIC ACTUATOR NEW REUSE EXISTING

422 AO BP1-SC BUILDING PUMP 1 SPEED CTRL VFD EXISTING REUSE EXISTING

423 BO LP1-SS LOOP PUMP 1 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

424 BO LP2-SS LOOP PUMP 2 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

425 BO LP3-SS LOOP PUMP 3 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

426 BO BP1-SS BUILDING PUMP 1 START/STOP VFD AUX. CONTACT/CONTROL RELAY EXISTING REUSE EXISTING

427 BO BP2-SS BUILDING PUMP 2 START/STOP AUX. CONTACT/CONTROL RELAY EXISTING REUSE EXISTING

428 BO LP1-VLV LOOP PUMP 1 VALVE ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

429 BO LP2-VLV LOOP PUMP 2 VALVE ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

430 BO LP3-VLV LOOP PUMP 3 VALVE ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

TOWER SYSTEM

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

501 AI TW-LVL TOWER BASIN WATER LEVEL ULTRASONIC LEVEL TRANSMITTER EXISTING REUSE EXISTING

502 AI TWS-PRS TOWER SUPPLY HEADER PRESS. PRESSURE TRANSMITTER NEW NEW

503 AI TWR-PRS TOWER RETURN HEADER PRESS. PRESSURE TRANSMITTER NEW NEW

504 AI TWMU-F TOWER MAKE UP FLOW MAGNETIC FLOWMETER EXISTING REUSE EXISTING

505 AI TWS-T TOWER SUPPLY TEMP RTD/TRANSMITTER NEW REUSE EXISTING

506 AI TWR-T TOWER RETURN TEMP RTD/TRANSMITTER NEW REUSE EXISTING

507 BI TP1-S TOWER PUMP 1 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

508 BI TP2-S TOWER PUMP 2 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

509 BI TF1-S TOWER FAN 1 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

510 BI TF2-S TOWER FAN 2 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

511 BI TF3-S TOWER FAN 3 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

512 BI TF4-S TOWER FAN 4 STATUS VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

513 BI TF1-VIB TWR FAN 1 VIBRATION SWITCH VIBRATION SWITCH EXISTING REUSE EXISTING

514 BI TF2-VIB TWR FAN 2 VIBRATION SWITCH VIBRATION SWITCH EXISTING REUSE EXISTING

515 BI TF3-VIB TWR FAN 3 VIBRATION SWITCH VIBRATION SWITCH EXISTING REUSE EXISTING

516 BI TF4-VIB TWR FAN 4 VIBRATION SWITCH VIBRATION SWITCH EXISTING REUSE EXISTING

517 AO TP1-SC TOWER PUMP 1 SPEED CNTL VFD NEW REUSE EXISTING

518 AO TP2-SC TOWER PUMP 2 SPEED CNTL VFD NEW REUSE EXISTING

519 AO TF1-SC TOWER FAN 1 SPEED CNTL VFD NEW REUSE EXISTING

520 AO TF2-SC TOWER FAN 2 SPEED CNTL VFD NEW REUSE EXISTING

521 AO TF3-SC TOWER FAN 3 SPEED CNTL VFD NEW REUSE EXISTING

522 AO TF4-SC TOWER FAN 4 SPEED CNTL VFD NEW REUSE EXISTING

523 AO TWBYP-V TOWER BYPASS VALVE ELECTRIC ACTUATOR NEW REUSE EXISTING

524 AO TWMU-V TOWER MAKE UP VALVE ELECTRIC ACTUATOR EXISTING REUSE EXISTING

525 BO TP1-SS TOWER PUMP 1 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

526 BO TP2-SS TOWER PUMP 2 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

527 BO TF1-SS TOWER FAN 1 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

528 BO TF2-SS TOWER FAN 2 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

529 BO TF3-SS TOWER FAN 3 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

530 BO TF4-SS TOWER FAN 4 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW REUSE EXISTING

531 BO TW-V1 TOWER VALVE 1 ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

532 BO TW-V2 TOWER VALVE 2 ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

533 BO TW-V3 TOWER VALVE 3 ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

534 BO TW-V4 TOWER VALVE 4 ELECTRIC ACTUATOR/CONTROL RELAY NEW REUSE EXISTING

535 BO TW-BSN-HT TOWER BASIN HEAT START/STOP ELECTRIC BASIN HEATERS NEW

536 BO TW-BSN-HT TOWER BASIN HEAT START/STOP ELECTRIC BASIN HEATERS NEW

537 BO TW-BSN-HT TOWER BASIN HEAT START/STOP ELECTRIC BASIN HEATERS NEW

538 BO TW-BSN-HT TOWER BASIN HEAT START/STOP ELECTRIC BASIN HEATERS NEW

BACNET POINTS (RESIDE ON FC BUS)

TAG# TYPE POINT NAME DESCRIPTION DEVICE

7O1 FC CH1-BACNET CHILLER PANEL CHILLER MFG. BACNET CARD

7O2 FC CH2-BACNET CHILLER PANEL CHILLER MFG. BACNET CARD

7O3 FC CH3-BACNET CHILLER PANEL CHILLER MFG. BACNET CARD

704 FC CH1-KW CHILLER 1 COMPRESSOR ELEC. E-MON BACNET KW METER

705 FC CH2-KW CHILLER 2 COMPRESSOR ELEC. E-MON BACNET KW METER

706 FC CH3-KW CHILLER 3 COMPRESSOR ELEC. E-MON BACNET KW METER

707 FC CP1-KW CHILLER PUMP 1 ELEC. E-MON BACNET KW METER

708 FC CP2-KW CHILLER PUMP 2 ELEC. E-MON BACNET KW METER

709 FC CP3-KW CHILLER PUMP 3 ELEC. E-MON BACNET KW METER

710 FC LP1-KW LOOP PUMP 1 ELEC. E-MON BACNET KW METER

711 FC LP2-KW LOOP PUMP 2 ELEC. E-MON BACNET KW METER

712 FC LP3-KW LOOP PUMP 3 ELEC. E-MON BACNET KW METER

713 FC TP1-KW TOWER PUMP 1 ELEC. E-MON BACNET KW METER

714 FC TP2-KW TOWER PUMP 2 ELEC. E-MON BACNET KW METER

715 FC TF1-KW TOWER FAN 1 ELEC. E-MON BACNET KW METER

716 FC TF2-KW TOWER FAN 2 ELEC. E-MON BACNET KW METER

717 FC TF3-KW TOWER FAN 3 ELEC. E-MON BACNET KW METER

718 FC TF4-KW TOWER FAN 4 ELEC. E-MON BACNET KW METER

TOWER TREATMENT

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

601 AI TW-PH TOWER PH LEVEL NALCO TRASAR EXISTING REUSE EXISTING

602 AI TW-COND TOWER CONDUCTIVITY NALCO TRASAR EXISTING REUSE EXISTING

603 AI TW-ORP TOWER ORP LEVEL NALCO TRASAR EXISTING REUSE EXISTING

604 AI TW-FCL TOWER FREE CHLORINE FREE CHLORINE ANALYZER NEW NEW

605 BI CHMP-S CHEM CIRC PUMP STATUS CURRENT SWITCH NEW NEW

606 BI ACID-S ACID PUMP STATUS NALCO TRASAR/CONTROL RELAY EXISTING REUSE EXISTING

607 BI INHIB-S INHIBITOR PUMP STATUS NALCO TRASAR/CONTROL RELAY EXISTING REUSE EXISTING

608 BI OX-S OXIDIZER PUMP STATUS CONTROL RELAY NEW NEW

609 BI NONOX-S NONOX PUMP STATUS NALCO TRASAR/CONTROL RELAY EXISTING REUSE EXISTING

610 BI BLWDWN-S BLOW DOWN STATUS NALCO TRASAR/CONTROL RELAY EXISTING REUSE EXISTING

611 BO CHMP-SS CHEM CIRC PUMP START/STOP CONTROL RELAY NEW NEW

612 BO BLWDWN-SS BLOW DOWN START/STOP CONTROL RELAY/NCSR ELC ACTUATOR EXISTING NEW

613 BO OX-SS OXIDIZER PUMP START/STOP CONTROL RELAY/SOLENOID NEW NEW

CHILLER NO.1

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

101 AI CH1-F CHILLER 1 FLOW MAGNETIC FLOWMETER NEW NEW

102 AI CH1TW-F CHILLER 1 TOWER FLOW MAGNETIC FLOWMETER NEW NEW

103 AI CH1S-T CHILLER 1 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

104 AI CH1R-T CHILLER 1 RETURN TEMP RTD/TRANSMITTER NEW NEW

105 AI CH1TWS-T CHILLER 1 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

106 AI CH1TWR-T CHILLER 1 RETURN TEMP RTD/TRANSMITTER NEW NEW

107 BI CH1-S CHILLER 1 STATUS CHILLER PANEL NEW NEW

108 BI CP1-S CHILLER 1 PUMP STATUS VFD AUX. CONTACT/CONTROL RELAY NEW NEW

109 BI CH1-HAND CHILLER 1 IN HAND HOA SWITCH NEW NEW

110 BI CH1-AUTO CHILLER 1 IN AUTO HOA SWITCH NEW NEW

111 BI CH1-ALM CHILLER 1 ALARM CHILLER PANEL NEW NEW

112 BI CH1-REFALM CHILLER 1 REFRIGERANT ALARM SHERLOCK REFRIGERANT ALARM NEW REUSE EXISTING

113 AO CH1TW-V CHILLER 1 TOWER ISO VALVE MODULATING ELECTRIC ACTUATOR NEW NEW

114 AO CP1-SC CHILLER PUMP 1 SPEED CNRL VFD NEW NEW

115 BO CH1-ENB CHILLER 1 ENABLE CONTROL RELAY NEW NEW

116 BO CP1-SS CHILLER PUMP 1 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW NEW

CHILLER NO.2

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

201 AI CH2-F CHILLER 2 FLOW MAGNETIC FLOWMETER NEW NEW

202 AI CH2TW-F CHILLER 2 TOWER FLOW MAGNETIC FLOWMETER NEW NEW

203 AI CH2S-T CHILLER 2 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

204 AI CH2R-T CHILLER 2 RETURN TEMP RTD/TRANSMITTER NEW NEW

205 AI CH2TWS-T CHILLER 2 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

206 AI CH2TWR-T CHILLER 2 RETURN TEMP RTD/TRANSMITTER NEW NEW

207 BI CH2-S CHILLER 2 STATUS CHILLER PANEL NEW NEW

208 BI CP2-S CHILLER 2 PUMP STATUS VFD AUX. CONTACT/CONTROL RELAY NEW NEW

209 BI CH2-HAND CHILLER 2 IN HAND HOA SWITCH NEW NEW

210 BI CH2-AUTO CHILLER 2 IN AUTO HOA SWITCH NEW NEW

211 BI CH2-ALM CHILLER 2 ALARM CHILLER PANEL NEW NEW

212 NOT USED

213 AO CH2TW-V CHILLER 2 TOWER ISO VALVE MODULATING ELECTRIC ACTUATOR NEW NEW

214 AO CP2-SC CHILLER PUMP 2 SPEED CNRL VFD NEW NEW

215 BO CH2-ENB CHILLER 2 ENABLE CONTROL RELAY NEW NEW

216 BO CP2-SS CHILLER PUMP 2 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW NEW

CHILLER NO.3

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

301 AI CH3-F CHILLER 3 FLOW MAGNETIC FLOWMETER EXISTING REUSE EXISTING

302 AI CH3TW-F CHILLER 3 TOWER FLOW MAGNETIC FLOWMETER EXISTING REUSE EXISTING

303 AI CH3S-T CHILLER 3 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

304 AI CH3R-T CHILLER 3 RETURN TEMP RTD/TRANSMITTER NEW NEW

305 AI CH3TWS-T CHILLER 3 SUPPLY TEMP RTD/TRANSMITTER NEW NEW

306 AI CH3TWR-T CHILLER 3 RETURN TEMP RTD/TRANSMITTER NEW NEW

307 BI CH3-S CHILLER 3 STATUS CHILLER PANEL NEW NEW

308 BI CP3-S CHILLER 3 PUMP STATUS VFD AUX. CONTACT/CONTROL RELAY NEW NEW

309 BI CH3-HAND CHILLER 3 IN HAND HOA SWITCH NEW NEW

310 BI CH3-AUTO CHILLER 3 IN AUTO HOA SWITCH NEW NEW

311 BI CH3-ALM CHILLER 3 ALARM CHILLER PANEL NEW NEW

312 BI CH3-REFALM CHILLER 3 REFRIGERANT ALARM SHERLOCK REFRIGERANT ALARM NEW NEW

313 AO CH3TW-V CHILLER 3 TOWER ISO VALVE MODULATING ELECTRIC ACTUATOR NEW NEW

314 AO CP3-SC CHILLER PUMP 3 SPEED CNRL VFD NEW NEW

315 BO CH3-ENB CHILLER 3 ENABLE CONTROL RELAY NEW NEW

316 BO CP3-SS CHILLER PUMP 3 START/STOP VFD AUX. CONTACT/CONTROL RELAY NEW NEW

EMCS DDC POINT LISTS

NO SCALE

A

EXHAUST FAN EF-1

TAG# TYPE POINT NAME DESCRIPTION DEVICE TYPE DEVICE CONDUIT

801 AI MR-T MECHANICAL ROOM TEMP ZONE TEMP SENSOR NEW NEW

802 BI EF1-S EXHAUST FAN 1 STATUS CURRENT SWITCH NEW NEW

803 BI EF1-HAND EXHAUST FAN 1 IN HAND HOA SWITCH NEW NEW

804 BI EF1-AUTO EXHAUST FAN 1 AUTO HOA SWITCH NEW NEW

805 BO EF1-SS EXHAUST FAN 1 START/STOP CONTROL RELAY NEW NEW

1

ADD #1

6 S

OU

TH

O

LD

O

RC

HA

RD

ST

. L

OU

IS

, M

O 63

11

9

T 31

4.9

18.838

3

F 31

4.9

18.176

6

ww

w.ro

ssba

r.com

MU PROJ. NO:

© ROSS & BARUZZINI, INC 2018

ISSUE DATE:

RB PROJ. NO.:

CHECKED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal sealappear on this document, assumes responsibility only forwhat appears hereon, and disclaims responsibility for all otherplans, specifications, estimates, reports, documents orinstruments not sealed by the Professional Engineer relatingto, or intended to be used for, any part or parts of theengineering project to which this document refers. Printssealed by the Engineer bear the embossed or wet seal of theEngineer across the signature and date. Copies of thisdocument, as signed and sealed, have been retained by theProfessional Engineer. The Professional Engineer will not beresponsible for subsequent changes to this document, unlessthe changes are made by the Engineer or with the Engineer'swritten authorization.

ROSS & BARUZZINIMISSOURI STATE CERTIFICATE

OF AUTHORITY #000148

1 INCH

DATE DESCRIPTION

SOAMISSOURI STATE CERTIFICATE OF

AUTHORITY #000826

2801

WOO

DARD

DRI

VE, S

UITE

103

COLU

MBIA

, MO

6520

2T:

573-

443-

1407

www.

soa-

inc.co

m

HE

AR

NE

S - C

HIL

LE

R R

EP

LA

CE

ME

NT

UM

P

RO

JE

CT

N

UM

BE

R C

P1

81

14

1

CO

LU

MB

IA

, M

IS

SO

UR

I

505-111

UN

IV

ER

SIT

Y O

F M

IS

SO

UR

I

10/1/2018

DESIGNED BY:

CP181141

ASDGMISSOURI STATE CERTIFICATE OF

AUTHORITY #2003024243

1009

LINC

OLN

HIGH

WAY

FAIR

VIEW

HEI

GHTS

, IL 62

208

T: 61

8-62

8-08

87ww

w.as

dgllc

.com

RANDY J. DIEMER

ENG. LIC. NO. PE-2017015702

10/1/2018

CONTROLS

M701

10/8/181

ADDENDUM 1

Page 7: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

24 VAC

R1

TRASAR ACID PUMP

AUX CONTACT

1/2" CPVC THREADED

TO SOCKET (OWNER

PROVIDED)

1/2" NIPPLE

INJECTION QUILL

3/4"-1/2" BUSHING

1/2" CHECK VALVE

1/2" ANGLE VALVE

1/2" SCHED 80 CPVC PIPE (TYP)

CPVC UNION (TYP)

3/4" THREADOLET

STAINLESS STEEL

TOWER RETURN

PIPE

SWITCHED OUTLET

EXISTING

INHIBITOR/NONOX TANKS

INJECTION PUMP

LMI MODEL

711-825

SUCTION

CHECK VALVE

DISCHARGE

CHECK VALVE

UNION

TOP DISCHARGE

WITH FOOT FOOT VALVE

2" SCHD. 10S SS

M

120 VAC

ACID

PUMP

ROTAMETER TYPE FLOWMETER

BALL VALVE

CHECK VALVE

LEGEND

COUPON HANGERS

CHMP

METASYS

(NONOX-S)

R9

R6

INHIB

PUMP

R7

R1

R2

OX

SOLENOID VALVE

R8

R3

METASYS

(BLWDWN-S)

R10

R2

R3

R4

METASYS

(ACID-S)

R6

METASYS

(INHIB-S)

R7

METASYS

(OX-S)

R8

TO METASYS

1" CONDUIT

POWER

2" SCHD. 10S SS

CIRCUIT SETTER

ISOLATION VALVE (TYP)

NALCO

TRASAR

TRASAR INHIBITOR PUMP

AUX CONTACT

METASYS

(OX-SS)

TRASAR NONOX PUMP

AUX CONTACT

R5

METASYS

(BLWDWN-SS)

NALCO

PANEL

4-20 mA

TO

METASYS

REQUIRED POWER

BY CONTRACTOR

FREE

CHLORINE

ANALYZER

OWNER PROVIDED

PANEL

2" BASKET STRAINER

EXISTING

STAINLESS STEEL

TOWER

RETURN HEADER

EXISTING

STAINLESS STEEL

TOWER

RETURN HEADER

1. ALL COMPONENTS PROVIDED BY CONTRACTOR EXCEPT NALCO TRASAR, NALCO PANEL, FREE

CHLORINE ANALYZER, FREE CHLORINE ANALYZER PANEL.

2. ALL COMPONENTS INSTALLED BY CONTRACTOR EXCEPT NALCO TRASAR, NALCO PANEL, FREE

CHLORINE ANALYZER, FREE CHLORINE ANALYZER PANEL.

3. ALL POWER REQUIREMENTS SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR.

4. ALL WIRING SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR.

5. ALL PIPING AND PIPING COMPONENTS SHALL BE PROVIDED BY THE CONTRACTOR.

6. SYSTEM SHALL BE COMMISSIONED BY OWNER.

NOTES:

M

M

NONOX

PUMP

R9

R4

R10

R5

BLOW DOWN

VALVE

KEYED NOTES:

1 NEW

2 EXISTING DEVICE, NEW CIRCUIT

3 EXISTING DEVICE, EXISTING CIRCUIT

2

S

3

1

3

3

3

3

1

3

2

3

3

1

3

2

INJECTION PUMP DETAIL

NO SCALEA

CHEMICAL TREATMENT SLIPSTREAM DETAIL

NO SCALEC

WATER TREATMENT COMMAND CIRCUIT DETAIL

NO SCALEB

EXHAUST FAN START DETAIL

NO SCALED

R1

24 VAC

ES

END SWITCH RELAY

R2

24 VAC CONTROL RELAY

CURRENT TRANSFORMER (SWITCH)

HAND-OFF-AUTO SWITCH

24 VAC EP VALVE (OA DMPR)

DAMPER END SWITCH

HAND-OFF-AUTO SWITCH

NC MOMENTARY PUSH BUTTON SWITCH

SOLID STATE TIMER-CONTACTS CLOSE FOR

2 MIN. WHEN PWR IS APPLIED

DEVICES (SEE SPECS):

R

CT

HOA

EP

ES

HOA

S

TD

REFRIG. MON

(EF-S)

R5

STATUS RELAY

R4

(CT-1)

EX FAN

STATUS RELAY

R3

(EF-SS)

METASYS

OFF

AUTO

HAND

R3 R2

COIL

MS

FAN

EXHAUST

OLS

MS

R4

ISOLATION DAMPER RELAY

TD-2

2 1

3

METASYS

(EF-S)

R4

R5

PROVIDE REFRIGERANT LEAK DETECTORS AS SPECIFIED AND SHOWN ON THE DRAWINGS.

THESE DETECTORS SHALL CONTINUOUSLY MONITOR AND REPORT THE AMBIENT LEVEL OF

THE SPECIFIC REFRIGERANT (R-134A) IN THE CHILLER ROOM 115C, EXPRESSED IN PARTS

PER MILLION (PPM). THE EMCS SHALL CONTINUOUSLY RECORD AND LOG THE AMBIENT

CHILLER ROOM REFRIGERANT LEVEL SO THAT PERSONNEL EXPOSURE CAN BE TRACKED.

UPON REFRIGERANT LEVEL ABOVE SETPOINT (INITIALLY 50 PPM, ADJUSTABLE), THE

FOLLOWING SHALL OCCUR:

1. ANNUNCIATE A REFRIGERANT LEAK ALARM AT THE EMCS.

2. AUDIBLY ANNUNCIATE A REFRIGERANT LEAK ALARM IN THE CHILLER ROOM 115C.

3. VISUALLY ANNUNCIATE A REFRIGERANT LEAK ALARM IN THE CHILLER ROOM, USING A

STROBE DEVICE MEETING ADA REQUIREMENTS, TO WARN HEARING-IMPAIRED

MAINTENANCE PERSONNEL.

4. INCREASE CHILLER ROOM EXHAUST FAN (EF-1) TO MAXIMUM SPEED (MAXIMUM

SPEED SHALL BE SET DURING BALANCING TO MEET MAXIMUM CFM AS SCHEDULED).

EMCS SHALL LOCK OUT ALL OTHER CONTROLS OF EXHAUST FAN AND RUN AT

MAXIMUM SPEED UNTIL MANUAL RESET OF DEVICES TO NORMAL OPERATION.

5. CONTINUOUSLY REPORT THE AMBIENT LEVEL OF THE SPECIFIC REFRIGERANT

(R-134A).

SEQUENCE OF OPERATION:

CHILLER ROOM 115C

EXHAUST FAN (EF-1) SHALL BE UNDER THE CONTROL OF THE ENERGY MANAGEMENT

CONTROL SYSTEM (EMCS).

A SPACE TEMPERATURE SENSOR SHALL BE PROVIDED IN THE CHILLER ROOM AND SHALL

BE MONITORED BY THE EMCS.

UPON RECEIVING A SIGNAL FROM THE EMCS TO BEGIN OPERATION, THE EXHAUST FAN

SHALL BE ACTIVATED.

NORMAL OPERATION: EXHAUST FAN SHALL RUN CONTINUOUSLY AT LOW SPEED (LOW

SPEED SHALL BE SET DURING BALANCING TO MEET MINIMUM CFM AS SCHEDULED).

WHEN SPACE TEMPERATURE RISES ABOVE SETPOINT (85 DEG F, ADJUSTABLE) THE EMCS

SHALL INCREASE THE SPEED OF THE EXHAUST FAN. WHEN SPACE TEMPERATURE FALLS

BELOW SETPOINT, THE EMCS SHALL RETURN THE EXHAUST FAN SPEED TO LOW SPEED.

THE EMCS SHALL MONITOR FAN STATUS, VIA CURRENT SENSOR.

SAFETIES: THE FOLLOWING DEVICES SHALL BE HARDWIRED TO RUN THE EXHAUST FAN AT

MAXIMUM SPEED AND SHALL REQUIRE A MANUAL RESET AT THE DEVICE FOR A RETURN TO

NORMAL OPERATION.

CHILLERS (C1 AND C2) REFRIGERANT LEAK DETECTION

SEQUENCE OF OPERATION:

EXHAUST FAN (EF-1)

REFRIGERANT LEAK DETECTION

PROVIDE REFRIGERANT LEAK DETECTORS AS SPECIFIED AND SHOWN ON THE DRAWINGS.

THESE DETECTORS SHALL CONTINUOUSLY MONITOR AND REPORT THE AMBIENT LEVEL OF

THE SPECIFIC REFRIGERANT (R-134A) IN THE CHILLER ROOM 115E, EXPRESSED IN PARTS

PER MILLION (PPM). THE EMCS SHALL CONTINUOUSLY RECORD AND LOG THE AMBIENT

CHILLER ROOM REFRIGERANT LEVEL SO THAT PERSONNEL EXPOSURE CAN BE TRACKED.

UPON REFRIGERANT LEVEL ABOVE SETPOINT (INITIALLY 50 PPM, ADJUSTABLE), THE

FOLLOWING SHALL OCCUR:

1. ANNUNCIATE A REFRIGERANT LEAK ALARM AT THE EMCS.

2. AUDIBLY ANNUNCIATE A REFRIGERANT LEAK ALARM IN THE CHILLER ROOM 115E.

3. VISUALLY ANNUNCIATE A REFRIGERANT LEAK ALARM IN THE CHILLER ROOM, USING A

STROBE DEVICE MEETING ADA REQUIREMENTS, TO WARN HEARING-IMPAIRED

MAINTENANCE PERSONNEL.

4. CONTINUOUSLY REPORT THE AMBIENT LEVEL OF THE SPECIFIC REFRIGERANT

(R-134A).

SEQUENCE OF OPERATION:

CHILLER ROOM 115E

REFRIGERANT LEAK DETECTION

1

ADD #1

6 S

OU

TH

O

LD

O

RC

HA

RD

ST

. L

OU

IS

, M

O 63

11

9

T 31

4.9

18.838

3

F 31

4.9

18.176

6

ww

w.ro

ssba

r.com

MU PROJ. NO:

© ROSS & BARUZZINI, INC 2018

ISSUE DATE:

RB PROJ. NO.:

CHECKED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal sealappear on this document, assumes responsibility only forwhat appears hereon, and disclaims responsibility for all otherplans, specifications, estimates, reports, documents orinstruments not sealed by the Professional Engineer relatingto, or intended to be used for, any part or parts of theengineering project to which this document refers. Printssealed by the Engineer bear the embossed or wet seal of theEngineer across the signature and date. Copies of thisdocument, as signed and sealed, have been retained by theProfessional Engineer. The Professional Engineer will not beresponsible for subsequent changes to this document, unlessthe changes are made by the Engineer or with the Engineer'swritten authorization.

ROSS & BARUZZINIMISSOURI STATE CERTIFICATE

OF AUTHORITY #000148

1 INCH

DATE DESCRIPTION

SOAMISSOURI STATE CERTIFICATE OF

AUTHORITY #000826

2801

WOO

DARD

DRI

VE, S

UITE

103

COLU

MBIA

, MO

6520

2T:

573-

443-

1407

www.

soa-

inc.co

m

HE

AR

NE

S - C

HIL

LE

R R

EP

LA

CE

ME

NT

UM

P

RO

JE

CT

N

UM

BE

R C

P1

81

14

1

CO

LU

MB

IA

, M

IS

SO

UR

I

505-111

UN

IV

ER

SIT

Y O

F M

IS

SO

UR

I

10/1/2018

DESIGNED BY:

CP181141

ASDGMISSOURI STATE CERTIFICATE OF

AUTHORITY #2003024243

1009

LINC

OLN

HIGH

WAY

FAIR

VIEW

HEI

GHTS

, IL 62

208

T: 61

8-62

8-08

87ww

w.as

dgllc

.com

RANDY J. DIEMER

ENG. LIC. NO. PE-2017015702

10/1/2018

CONTROLS

M702

10/8/181

ADDENDUM 1

Page 8: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

THERMOWELL INSERTION DEPTH U

16'-7.8"

PROBE INSERTION

DEPTH U + 1.5"

3'-3.954"

1/2" NPT

1/2" NPT PROCESS THREAD

0.625"

1'-7.98"

1/2" NPT

CONDUIT THREAD

RTD INSERTION LENGTH S

SEE SCHEDULE

5.0" +/- 0.75"

0.250" DIAMETER

1. FLOW COMPUTER SHALL BE LOCATED NEXT TO THE ASC PANEL.

2. FLOW METER SHALL BE INSTALLED BY CONTRACTOR. AFTER INSTALLATION,

THE OWNER SHALL PERFORM ANY NECESSARY CALIBRATIONS. AFTER

CALIBRATION, THE CONTRACTOR SHALL INSULATE THE ENTIRE ASSEMBLY.

3. FLOW METER SHALL BE INSTALLED IN ACCORDANCE TO MFG. INSTALLATION

PROCEDURE.

METER HEAD MUST BE MOUNTED

MINIMUM OF 5 PIPE DIAMETERS

OF STRAIGHT PIPE UP STREAM

MINIMUM OF 3 PIPE DIAMETERS

OF STRAIGHT PIPE DOWN STREAM

(5 PIPE DIAMETERS IF

BI-DIRECTIONAL FLOW)

CAUTION: DO NOT

DAMAGE LINER

DURING INSTALLATION

VERTICALLY STRAIGHT UP

OUTPUT TO ASC

LIGHT SWITCH FOR

POWER DISCONNECT

4-20 mA DC

COMPUTER

FLOW

JUNCTION BOX WITHIN 2ft.

OF TRANSDUCERS.

3/4" CONDUIT FOR

FLW MTR CABLE.

2' x 6" WIRE TROUGH

1/2" EMT

1/2" SEAL TIGHT

FOXBORO

(CH1-ENB)

CH1-AUTO (BI)

OFF

HAND

AUTO

ON TERMINAL BOARD

CHILLER REMOTE S/S

CH1-HAND (BI)

METASYS

COORDINATE WITH CHILLER MFD

VFD

F-CC

R2R1

ST-CC

(TF1-SC)

METASYS

IV-CC

(TF1-SS)

VFD RUN

CONTACT

METASYS

24 VAC

AUX CONTACTS

LOCAL DISCONNECT

SWITCH

VIBRATION

TWR FAN TWR FAN

24 VAC CONTROL RELAY

CURRENT TRANSFORMER (SWITCH)

HAND-OFF-AUTO SWITCH

VARIABLE FREQUENCY DRIVE

DEVICES (SEE SPECS):

R

CT

HOA

VFD

R2

START RELAY

R3

STATUS RELAY

R1

METASYS

(TF1-S)

R3

VFD

F-CC

R2R1

ST-CC

(LP1-SC)

METASYS

IV-CC

(LP1-SS)

METASYS

START RELAY

START RELAY

AUX CONTACTS

LOCAL DISCONNECT

LOOP PUMP 1

24 VAC

(TF1-VIB)

METASYS

AUX CONTACTS

TWR FAN 1

VIB SWITCH

RUN CONTACT

VFD

STATUS RELAY

24 VAC CONTROL RELAY

CURRENT TRANSFORMER (SWITCH)

HAND-OFF-AUTO SWITCH

VARIABLE FREQUENCY DRIVE

DEVICES (SEE SPECS):

R

CT

HOA

VFD

METASYS

LP1-S)

R3

VFD

F-CC

R2R1

ST-CC

(CP1-SC)

METASYS

IV-CC

START RELAY

START RELAY

AUX CONTACTS

LOCAL DISCONNECT

CHILLER PUMP 1

24 VAC

RUN CONTACT

VFD

STATUS RELAY

24 VAC CONTROL RELAY

CURRENT TRANSFORMER (SWITCH)

HAND-OFF-AUTO SWITCH

VARIABLE FREQUENCY DRIVE

DEVICES (SEE SPECS):

R

CT

HOA

VFD

METASYS

(CP1-S)

PUMP START

REMOTE CHLR

CHILLER PANEL

(CP1-SS)

METASYS

PIPE SIZE U DEPTH S LENGTH

4" & DOWN 2" 3.5"

5" 2.5" 4"

6" 3" 4.5"

8" 4" 5.5"

10" 5" 6.5"

12" 6" 7.5"

14" 7" 8.5"

16" 8" 9.5"

18" 9" 10.5"

FOR PIPE SMALLER THAN 4" BUSHING

AND/OR TEE WILL BE REQUIRED.

INSERTION DEPTH SCHEDULE

CHILLED WATER RTD/THERMOWELL DETAIL

NO SCALEA

WATER MAGNETIC FLOW DETAIL

NO SCALEB

GENERAL NOTES:

CHILLER H-O-A START DETAIL

NO SCALEC

COOLING TOWER FANS START DETAIL

NO SCALED

CHILLER PUMP START DETAIL

NO SCALEE

LOOP PUMP DETAIL AND TOWER PUMP START DETAIL

NO SCALEF

BACNET FC BUS SCHEMATIC DIAGRAM

NO SCALE

G

FIBER

PANEL

24X24X12

J-BOX

CH3CH1NAE CH2

CH3 CP1

KW

CP2

KW

CP3

KW

EXISTING

CH1

KW

CH3

KW

CH2

KW

CHEM

TREAT

TOWER LOOP

PUMPS

CH2CH1

LP2

KW

LP3

KW

TF1

KW

TP1

KW

LP1

KW

TP2

KW

TF2

KW

TF3

KW

TF4

KW

1. FC BUS TO BE CONTINUOUS DAISY CHAIN. SEE PLANS FOR QUANTITY AND

LOCATIONS OF CONTROLLERS.

2. OWNER WILL MAKE TERMINATION CONNECTIONS AT PANELS.

3. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED

SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED AS 22-03

OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE

CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.

4. COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.

NOTES:

1

KEYED NOTES:

DDC CONTROLLER.

MFG PROVIDED BACNET CARD ON FC BUS.

E-MON BACNET KW METER ON FC BUS.

2

3

111111

333333

333333333

222

4

CONTRACTOR PROVIDED AND

INSTALLED EMT CONNECTIONS

CONTRACTOR PROVIDED

AND INSTALLED EMT

CONNECTIONS

1

ADD #1

2" MIN. CONDUIT (2)

1-1/2" UNISTRUT

CHANNEL (2)

WIRE

TROUGH

3/4" CONDUIT

4'x4'x3/4" PLYWOOD (MIN)

(PAINT FRONT, ENDS, AND BACK

MACHINE GRAY)

EXP. ANCHORS

POST BASE (2)

BRACE

FITTING (2)

DDC

DDC PANEL MOUNTING DETAIL

NO SCALEH

SIDE VIEW - FLOOR MOUNT

1. KEEP ALL LOW VOLTAGE CONTROL WIRING ( UNDER 25V) AND LOW VOLTAGE

POWER WIRING (OVER 25V) SEPARATED. (RUN IN SEPARATE CONDUIT).

2. PLYWOOD SIZE IS BASED ON THE NUMBER OF CONTROLLERS IN EACH

LOCATION. COORDINATE WITH OWNERS REPRESENTATIVE.

4'x4'x3/4" PLYWOOD (MIN)

(PAINT FRONT AND

ENDS MACHINE GRAY.)

1-1/2" UNISTRUT

CHANNEL (2)

3/4" CONDUIT

1" CONDUIT

MINIMUM

WIRE

TROUGH

1-1/2" UNISTRUT

CHANNEL (2)

4'x4'x3/4" PLYWOOD (MIN)

(PAINT FRONT AND ENDS

MACHINE GRAY)

3/4" CONDUIT

2" MIN. CONDUIT

(2)

GENERAL NOTES:

FRONT VIEW SIDE VIEW - WALL MOUNT

1

KEYED NOTES:

DDC CONTROLLERS ARE SUPPLIED BY OWNER AND MOUNTED BY CONTRACTOR.

1

1

120 VAC INPUT POWER

DEDICATED 15A CIRCUIT

BY DIVISION 26

1

120 V

NEW 6"x6" WIRE TROUGH

CH-2 TOWER

FLOOR

LOOP

PUMPS

8"

EXISTING FIBER PATCH

8"

(TYPICAL)

1 1 1 2

MINIMUM 6'-0"

2'-0"

DDC PANEL LAYOUT

NO SCALE

I

1. COORDINATE WITH DDC PANEL MOUNT DETAIL.

2. COORDINATE WITH FIBER PANEL DETAIL.

GENEREAL NOTES:

1

KEYED NOTES:

PROVIDED BY OWNER, INSTALLED BY CONTRACTOR.

PROVIDED AND INSTALLED BY CONTRACTOR.

PROVIDED AND INSTALLED BY OWNER.

2

3

CH-1

CHEM

TREAT

2

WALL MOUNT BACK PLANE

3

4

" THICK

PLYWOOD PAINT FRONT AND SIDES

MACHINE GRAY

2" CONDUIT

(TYPICAL FOR ALL)

EX

NAE

EX

FIBER

OPTIC

PANEL

EXISTING 3"

INCOMING CONDUIT

EXISTING DEDICATED

20A CIRCUIT

1

ADD #1

6 S

OU

TH

O

LD

O

RC

HA

RD

ST

. L

OU

IS

, M

O 63

11

9

T 31

4.9

18.838

3

F 31

4.9

18.176

6

ww

w.ro

ssba

r.com

MU PROJ. NO:

© ROSS & BARUZZINI, INC 2018

ISSUE DATE:

RB PROJ. NO.:

CHECKED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal sealappear on this document, assumes responsibility only forwhat appears hereon, and disclaims responsibility for all otherplans, specifications, estimates, reports, documents orinstruments not sealed by the Professional Engineer relatingto, or intended to be used for, any part or parts of theengineering project to which this document refers. Printssealed by the Engineer bear the embossed or wet seal of theEngineer across the signature and date. Copies of thisdocument, as signed and sealed, have been retained by theProfessional Engineer. The Professional Engineer will not beresponsible for subsequent changes to this document, unlessthe changes are made by the Engineer or with the Engineer'swritten authorization.

ROSS & BARUZZINIMISSOURI STATE CERTIFICATE

OF AUTHORITY #000148

1 INCH

DATE DESCRIPTION

SOAMISSOURI STATE CERTIFICATE OF

AUTHORITY #000826

2801

WOO

DARD

DRI

VE, S

UITE

103

COLU

MBIA

, MO

6520

2T:

573-

443-

1407

www.

soa-

inc.co

m

HE

AR

NE

S - C

HIL

LE

R R

EP

LA

CE

ME

NT

UM

P

RO

JE

CT

N

UM

BE

R C

P1

81

14

1

CO

LU

MB

IA

, M

IS

SO

UR

I

505-111

UN

IV

ER

SIT

Y O

F M

IS

SO

UR

I

10/1/2018

DESIGNED BY:

CP181141

ASDGMISSOURI STATE CERTIFICATE OF

AUTHORITY #2003024243

1009

LINC

OLN

HIGH

WAY

FAIR

VIEW

HEI

GHTS

, IL 62

208

T: 61

8-62

8-08

87ww

w.as

dgllc

.com

RANDY J. DIEMER

ENG. LIC. NO. PE-2017015702

10/1/2018

CONTROLS

M703

10/8/181

ADDENDUM 1

Page 9: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of
Page 10: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

T T

E

E

E

EEE

E

E

E

EE

E

E E

MCC1

LP-H1MCC4

EF

1

MCC4

TP

21

TP

CP

3

2

1

CP

CP

PD

C

1

C

2

MCC4

MCC4

MCC4

2 1

LP LP

MS3

EXISTING SERVICE ENTRANCE CONDUITS TO MS3

MCC3

MCC4

C

3

LP

3

MCC4 MCC4 MCC4

MS4

MCC4

MS4

M MM MM MM MM

EMON METERING LINE UP(16)

1

TRANSITION SECTION

1

E403

2

E403

LP-H1-1

6

EXISTING TRANSFORMER

2000A SANDWICH TYPE BUSWAY

2

PULLBOX

6

E400

3

TF-4 TF-2TF-3 TF-1

3

LP-H1-2

4

4

5

3

SE4

MS4

4

MS3

CV

3

CV

8

CV

9

CV

6

CV

5

CV

4

CV

7

CV

2

CV

1

MCC3-3

3

3

3

3 3 3

3

MS4-1

1

1

1

1

1

LP-H1-10

8

1

LP-H1-167

3

LP-H1-8

7

1

LP-H1-14

2

1

LP-H1-12

2

1

6 S

OU

TH

OLD

OR

CH

AR

DS

T. LO

UIS

, M

O 6

3119

T 3

14.9

18.8

383

F 314.9

18.1

766

ww

w.r

ossbar.

com

CHECKED BY:

© ROSS & BARUZZINI, INC. 2018

ISSUE DATE:

RB PROJ. NO.:

DESIGNED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal seal appear on

this document, assumes responsibility only for what appears hereon, and

disclaims responsibility for all other plans, specifications, estimates,

reports, documents or instruments not sealed by the Professional Engineer

relating to, or intended to be used for, any part or parts of the engineering

project to which this document refers. Prints sealed by the Engineer bear

the embossed or wet seal of the Engineer across the signature and date.

Copies of this document, as signed and sealed, have been retained by the

Professional Engineer. The Professional Engineer will not be responsible

for subsequent changes to this document, unless the changes are made

by the Engineer or with the Engineer's written authorization.

2801

WO

OD

AR

D D

RIV

E,

SU

ITE

103

CO

LUM

BIA

, M

O 6

5202

T:

573-

443-

1407

ww

w.s

oa-in

c.co

m

1 INCH

DATE DESCRIPTION

SOA

MISSOURI STATE CERTIFICATE OF AUTHORITY #000826

ASDG

MISSOURI STATE CERTIFICATE OF AUTHORITY #200302424

1009

LIN

CO

LN H

IGH

WA

YF

AIR

VIE

W H

EIG

HT

S,

IL 6

2208

T:

618-

628-

0887

ww

w.a

sdgl

lc.c

om

MU PROJ. NO.:

ROSS & BARUZZINI

MISSOURI STATE CERTIFICATE OF AUTHORITY #000148

MARK H. KUHLMAN

ENG. LIC. NO. PE-2017000321

10/8

/201

8 1

:35:4

8 P

M

505-111

E200

Checker

HE

AR

NE

S -

CH

ILLE

R R

EP

LA

CE

ME

NT

UM

PR

OJE

CT

NU

MB

ER

CP

181141

CO

LU

MB

IA, M

ISS

OU

RI

ENLARGED CHILLER ROOMPLAN - NEW WORK

UN

IVE

RS

ITY

OF

MIS

SO

UR

I

Designer

10/1/2018

CP181141

10/1/2018

1/4" = 1'-0"1

ELEC ENLARGED CHILLER ROOM - NEWWORK

SHEET KEYNOTES#

1. REFER TO DETAIL ON SHEETS E400 AND E401 FOR VFD MOUNTING REQUIREMENTS.

2. SEE RISER DIAGRAM, E300 FOR FEEDER SIZES AND OVERCURRENT PROTECTION DETAILS.

GENERAL NOTES:

PLAN NORTH

1. EXISTING CONDUITS ARE LOCATED IN CEILING SPACE.

2. PROVIDE 2#12, 1#12 GRD IN A 3/4" CONDUIT AND CONNECT TO EXISTNG PANEL LP-H1. PROVIDE 1P-20A SPARE CIRCUIT BREAKER IN NEXT AVAILABLE SPACE TO ALLOW FOR CONNECTION. MATCH CIRCUIT BREAKER TYPE AND INTERRUPTING RATING WITH EXISTING.

3. WORK SHOWN ASSOICATED WITH CHILLER 3, CP 3, AND (2) ASSOCIATED METERS SHALL BE PART OF ALTERNATE #1.

4. INTEGRAL VFD BY DIVISION 23.

5. FOR MORE INFORMATION ABOUT THE SER MAIN CIRCUIT BREKAER REFER TO SPECIFICATION SECTION 262500.

6. PROVIDE 2#12, 1#12 GRD IN A 3/4" CONDUIT AND CONNECT TO CONTROL POWER DISCONNECT AND CONNECT TO LP-H1.

7. PROVIDE 2#12, 1#12 GRD IN A 3/4" CONDUIT FOR REFRIGERANT ALARM REMOTE ANNUNCIATOR. CONNECT TO EXISTNG PANEL LP-H1 AND PROVIDE 1P-20A SPARE CIRCUIT BREAKER IN NEXT AVAILABLE SPACE TO ALLOW FOR CONNECTION. MATCH CIRCUIT BREAKER TYPE AND INTERRUPTING RATING WITH EXISTING.

8. PROVIDE 2#12, 1#12 GRD IN A 3/4" CONDUIT FOR FLOW AND ENERGY METERS. CONNECT TO EXISTNG PANEL LP-H1 AND PROVIDE 1P-20A SPARE CIRCUIT BREAKER IN NEXT AVAILABLE SPACE TO ALLOW FOR CONNECTION. MATCH CIRCUIT BREAKER TYPE AND INTERRUPTING RATING WITH EXISTING.

1 10/08/18 ADDENDUM 1

1

Page 11: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

VFD VFD VFD VFD VFD

VFDVFD

J J J J

VFD VFD VFD

MBDM

VFD VFD VFD VFDVFD

FEEDER SCHEDULE

FEEDERNUMBER T

OT

AL S

ET

S

EA

CH

PH

AS

EC

ON

DU

CT

OR

IN E

AC

H S

ET

NE

UT

RA

LC

ON

DU

CT

OR

IN E

AC

HS

ET

EQ

UIP

ME

NT

GR

OU

ND

ING

CO

ND

UC

TO

RIN

EA

CH

SE

T

EM

T C

ON

DU

ITS

IZE

(IN

CH

ES

FO

RE

AC

H S

ET

)

REMARKS

2000/N/G 6 500kcmil 500kcmil 250kcmil 3

1600/-/G 5 500kcmil - 4/0 3

1000/-/G 3 500kcmil 2/0 3

250/-/G 1 250kcmil - 4 2

225/-/G 1 4/0 - 4 2

80/-/G 1 4 - 8 1

60/-/G 1 6 - 10 3/4

60/N/G 1 6 6 10 1

50/N/G 1 8 8 10 3/4

20/-/G 1 12 - 12 3/4

#

RM

C C

ON

DU

ITS

IZE

(IN

CH

ES

FO

RE

AC

H S

ET

)

3 1/2

3

3

2

2

1

3/4

1

3/4

3/4

PV

C 4

0 C

ON

DU

ITS

IZE

(IN

CH

ES

FO

R E

AC

H S

ET

)

3

3

2

2

1

3/4

1

3/4

3/4

-

1000/-/G

22

5/-

/G

22

5/-

/G

22

5/-

/G

20

/-/G

60/N/G

25

0/-

/G

25

0/-

/G

80

/-/G

60

/-/G

60

/-/G

1600/-/G

BY DIV 23BY DIV 23

1000/-/G

BY DIV 23

ELECTRICALLYOPERATEDBREAKER

3 1/2

100/-/G 1 3 - 8 1 1 1

60/N/G 100/-/G

60A 60A 100A 400A 400A 400A 400A 400A30A100A 100A 100A 100A

3 40 40 60 150 150 125 125 125

20

/-/G

20/-/G

20

/-/G

20/-/G

2000/N/G

20

00

A B

US

WA

Y

THE EQUIPMENT GROUNDING CONDUCTOR IS FOR CIRCUITS IMMEDIATELY DOWNSTREAM OF ANOVERCURRENT DEVICE. USE A SUPPLY SIDE BONDING JUMPER, SIZED IN ACCORDANCE WITH NEC 250.102, IFTHE FEEDER CONNECTS A SEPARATELY DERIVED SYSTEM (SUCH AS FROM A TRANSFORMER SECONDARY) TOA DISCONNECTING MEANS NOT IN THE SAME ENCLOSURE AS THE SEPARATELY DERIVED SYSTEM, INSTEAD OFTHE EQUIPMENT GROUNDING CONDUCTOR.

VFD

ONE-LINE DIAGRAM - DEMOLITION

ONE-LINE DIAGRAM - NEW WORK

ONE-LINE DIAGRAM GENERAL NOTES

ONE-LINE DIAGRAM SYMBOLS

SHEET KEYNOTES

TP-2TP-1

250/3 250/3

EF-1 LP-1

225/3

LP-2

225/3 225/3

EXISTING "MCC3"

65,000 AIC600A BUS480/277V,3PH,4W

CWP-H2CWP-H1

CHWP-H5CHWP-H4CHWP-H3CHWP-H2CHWP-H1CU-H1 CU-H2

CH-H3CH-H4 CH-H1CH-H2

100/3

VFD VFD

450/3 450/3

20/3 20/3 80/3 80/3 90/3 250/3 250/3

(7 MOTORCONNECTIONS)

EF-H1

VFDVFD

50/3 50/3 30/3 30/3 200/3

800/3 800/3

7.5 7.5 30 4030

150 150

EXISTING, 4-WAY MEDIUM VOLTAGE SWITCH S&CPMU-9

LCWP-01

225/3

VFD

75

LCWP-02

225/3

VFD

75

LCWP-03

225/3

VFD

75

SP

AR

E

LP-3

C-3

C-1C-2

60/3 60/3 70/3

CP-1 CP-2 CP-3

ISOLATIONTRANSFORMER.TYPICAL

100/360/3

CTP1 CTP2

100%

RATED

CONTROL

VALVE

ACTUATORS

(CVs)

SEE PLANS

30

AF

/20

AT

CONTROL

VALVE

ACTUATORS

(CVs)

SEE PLANS

30

AF

/20

AT

(2)

800

A

SP

AR

E

SP

AR

E

SP

AC

E

80

0A

SP

AC

E

(4)

200

AS

PA

CE

TO EXISTINGSOFTBALL FIELDSERVICEENTRANCETRANSFORMER

EXISTINGELECTRICALMANHOLE"EMH-294"

EXISTING 13.8kVCAMPUS LOOP

(2)

800

A

SP

AR

E

SP

AR

E

SP

AC

E

80

0A

SP

AC

E

(4)

200

AS

PA

CE

TO EXISTINGSOFTBALL FIELDSERVICEENTRANCETRANSFORMER

EXISTINGELECTRICALMANHOLE"MH-294"

EXISTING 13.8kVCAMPUS LOOP

EXISTING "MCC3"

65,000 AIC600A BUS480/277V,3PH,4W

6-WAY MEDIUMVOLTAGE SWITCH S&C

2

SP

AR

E

SP

AR

E

SP

AR

E

SP

AR

E

1

T11500kVA PAD

MOUNTEDTRANSFOMER

13.8KV-480Y/277V3PH, 4W

43

SE RATED2000A, 480V

REMOTEMAIN CIRCUIT

BREAKER

MS4

2000A, 480/277V, 3PH, 4W

10

00

AF

/10

00

AT

16

00

AF

/16

00

AT

5

40

0A

SP

AC

E

555

1. SHORT CIRCUIT CURRENT AND AIC RATINGS LISTED FOR ELECTRICAL EQUIPMENT ARE

THE MINIMUM REQUIREMENTS FOR THE BUS BRACING AND DEVICE RATINGS. ALL

EQUIPMENT SHALL BE FULLY RATED. ELECTRICAL CONTRACTOR IS REQUIRED TO

PROVIDE ARC FLASH HAZARD AND PERSONNEL PROTECTIVE EQUIPMENT LABELS FOR

EACH INDICATED PIECE OF ELECTRICAL EQUIPMENT. REFER TO SPECIFICATION

SECTION 260573 FOR ADDITIONAL INFORMATION.

2. ALL FUSED SWITCHES AND CIRCUIT BREAKERS SHOWN ON ONE-LINE DIAGRAM ARE

3-POLE. UNLESS NOTED OTHERWISE.

3. THE VARIABLE FREQUENCY DRIVE AND DISCONNECT SCHEME SHOWN ON ONE-LINE

DIAGRAM REQUIRES SPECIFIC INTERLOCKING OF EQUIPMENT. IT IS THE ELECTRICAL

CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL REQUIRED AUXILIARY CONTACTS

OF EQUIPMENT AND FURNISH AND INSTALL ALL CABLES, CONDUIT, TERMINATIONS, ETC.

FOR A COMPLETE INTERLOCKING SYSTEM.

4. "AF" INDICATES CIRCUIT BREAKER FRAME SIZE. "AT" INDICATES CIRCUIT BREAKER TRIP

SETTING (FOR ADJUSTABLE TRIP TYPE CIRCUIT BREAKERS).

5. ALL DISCONNECT SWITCHES ARE NON FUSED.

SURGE PROTECTION DEVICE

N

VOLTAGE TRANSFORMER

POWER TRANSFORMER

CURRENT TRANSFORMER

NEUTRAL BUS

GROUND BUS

MICROPROCESSOR BASED DIGITAL MONITOR

MOTOR STARTER

CIRCUIT BREAKER (FRAME/TRIP)XX/XX

GROUND

G

GROUND FAULT

ELECTRICAL SERVICE METER

60/3LSIG

LSIG

SE4

6

80E

20

00

AF

/18

00

AT

LSIG

8

9

7

77

7 7 7 7 7 7 7 7

7

NEW WORK

TO BE DEMOLISHED

7 7 7

55

10

11

11 11 11

ELECTRONIC TRIP UNIT WITH ADJUSTABLE LONGTIME PICKUP, LONG TIME DELAY, SHORT TIMEPICKUP, SHORT TIME DELAY, INSTANTANEOUS,AND GROUND FAULT PROTECTION SETTINGS.

TERMINATIONS BY OWNER

TERMINATION BY OWNERTERMINATION BYCONTRACTOR

10

00

AF

/10

00

AT

LSIG

NEW TO EXISTING CONNECTION

DISCONNECT SWITCH

12 12

EXISTING MEDIUM VOLTAGE PAD MOUNTED SWITCHGEAR SHALL BE DISCONNECTED,

REMOVED, AND RETURNED TO OWNER AT STORAGE YARD AT NORTH END OF

POWER PLANT. SALVAGE EXISTING FUSES AND TURN OVER TO OWNER. PRESERVE

AND PROTECT EXISTING FEEDERS SHOWN TO REMAIN ABOVE GRADE AND

PRESERVE EXISTING SWITCHGEAR PAD TO ALLOW FOR NEW WORK. REMOVAL OF

EXISTING SWITCHGEAR SHALL BE COORDINATED WITH OWNER.

S&C VISTA MEDIUM VOLTAGE PADMOUNTED SWITCHGEAR FURNISHED BY OWNER

AND INSTALLED BY CONTRACTOR. CONTRACTOR SHALL PICK UP NEW SWITCHGEAR

FROM OWNER'S STORAGE YARD AT NORTH END OF THE POWER PLANT AND

DELIVER TO SITE. SET AND INSTALL ON MODIFIED PAD PER DETAIL 3/E401. EXISTING

MEDIUM VOLTAGE FEEDERS MADE AVAILABLE BY DEMOLITION SERVING SOFTBALL

FIELD AND EXISTING CHILLER PLANT TRANSFORMERS AND LOOP FEEDS SHALL BE

RE-TERMINATED BY OWNER. NEW FEEDER CONNECTIONS SHOWN TO NEW CHILLER

PLANT TRANSFORMER SHALL BE TERMINATED BY ELECTRICAL CONTRACTOR.

15kV (3)1/C #4/0, (1) 600V #2 STRANDED GND IN EXISTING (SPARE) 4"C.

15kV (3)1/C #4/0, (1) 600V #2 STRANDED GND IN 4"C VIA DUCTBANK. REFER TO SHEET

E100 AND DETAIL 2/E400.

PROVIDE CIRCUIT BREAKER IN SPACES MADE AVAILABLE BY DEMOLITION OR

UTILIZE EXISTING BUS SPACES. MATCH CIRCUIT BREAKER TYPE AND INTERRUPTING

PUSHBUTTON CONTROL DEVICE. REFER DETAIL 6/E400. SEE E200 FOR LOCATION.

PROVIDE EMON METER FOR EQUIPMENT. REFER TO E200 FOR LOCATION. REFER TO

SPECIFICATION SECTION 260913 FOR ADDITIONAL INFORMATION.

PROVIDE SERVICE ENTRANCE METER. REFER TO SHEET E100 FOR LOCATION AND

DETAIL 1/ E401 FOR WIRING DIAGRAM.

ROUTE SERVICE ENTRANCE FEEDER VIA DUCTBANK. REFER TO SHEET E100 FOR

ROUTING AND DETAIL 3/E400.

PRESERVE EXISTING FEEDERS TO ALLOW FOR CONNECTION OF NEW VFDS IN SAME

LOCATION. SEE NEW WORK ONE-LINE DIAGRAM THIS SHEET.

CONNECT VFD AND DISCONNECT SWITCH TO EXISTING FEEDER MADE AVAILABLE BY

DEMOLITION. MODIFY EXISTING FEEDER, EXTEND, AND CONNECT TO VFD AS

REQUIRED.

SEE SHEET E600 FOR PANEL SCHEDULES.

WORK SHOWN IN HEAVY, DASHED LINE SHALL BE PART OF ALTERNATE #1.

7

5

RATING WITH EXISTING.

N

D

EXISTING "MCC4"480/277V,3PH,4W1200A BUS65,000 AIC

SP

AR

E

EXISTING OIL FILLED 2000KVA

13.8KV-480Y/277V3PH, 4W

TRANSFORMER

SP

AR

E

SP

AR

E

EXISTING MS#3

4000A BUS65,000 AIC

480/277V,3PH,4W

100/3 100/3 100/3 100/3S

PA

RE

100/3

600/3GG

30/3 30/3 200/320/3 50/3

1200/3

40404040

200/3

4000/3

GF

600/3M

T

LP-H1

N

D

EXISTING "MCC4"480/277V,3PH,4W1200A BUS65,000 AIC

EXISTING OIL FILLED 2000KVA

13.8KV-480Y/277V3PH, 4W

TRANSFORMER

EXISTING MS#3

4000A BUS65,000 AIC

480/277V,3PH,4W

100/3 100/3 100/3 100/3

600/3GG

20/3 50/3

1200/3

40404040

200/3

4000/3

G

600/3M

T

LP-H1

TF-1 TF-2 TF-3 TF-4

TF-1 TF-2 TF-3 TF-4

G

VFD VFD VFD VFD

SPD

GF

M

LSIG

SPD

M

M

M M M M M M M MM M

M

M M M

M

VARIABLE FREQUENCY DRIVE SCHEDULE

DISCONNECT SWITCH-DS

LINE DISCONNECT TYPE:

ACCESSORIESMANUFACTURER/

CATALOG #REMARKS

VFDHORSEPOWER

RATINGDISCONNECT

TYPEPLANMARK

DS 40HP SEE SPECIFICATION - YASKAWA

CP-2

CP-3

EF-1

LP-1

LP-2

LP-3

TF-1

TF-2

TF-3

TF-4

TP-1

TP-2

DS

DS

DS

DS

DS

DS

DS

DS

DS

DS

DS

DS

40HP

60HP

3HP

125HP

125HP

125HP

150HP

150HP

40HP

40HP

40HP

40HP

CP-1

-

-

-

-

-

-

-

-

-

-

-

-

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

YASKAWA

PRIMARYVOLTAGE

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

480/3

SEE DETAILS ON SHEETS E400AND E401

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

1

2

3

4

5

6

7

8

9

10

11

#

12

13

13

13

1

1

1

1

6 S

OU

TH

OLD

OR

CH

AR

DS

T.

LO

UIS

, M

O 6

31

19

T 3

14

.91

8.8

383

F

314

.91

8.1

76

6w

ww

.ro

ssba

r.co

m

CHECKED BY:

© ROSS & BARUZZINI, INC. 2018

ISSUE

RB PROJ. NO.:

DESIGNED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS

REPRODUCED AT ORIGINAL

SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal seal appear on

this document, assumes responsibility only for what appears hereon, and

disclaims responsibility for all other plans, specifications, estimates,

reports, documents or instruments not sealed by the Professional

Engineer relating to, or intended to be used for, any part or parts of the

engineering project to which this document refers. Prints sealed by the

Engineer bear the embossed or wet seal of the Engineer across the

signature and date. Copies of this document, as signed and sealed, have

been retained by the Professional Engineer. The Professional Engineer

will not be responsible for subsequent changes to this document, unless

the changes are made by the Engineer or with the Engineer's written

authorization.

280

1 W

OO

DA

RD

DR

IVE

, SU

ITE

103

CO

LUM

BIA

, MO

652

02T

: 573

-443

-140

7w

ww

.soa

-inc.

com

1 INCH

DATE DESCRIPTION

SOA

MISSOURI STATE CERTIFICATE OF AUTHORITY #000826

ASDG

MISSOURI STATE CERTIFICATE OF AUTHORITY #200302424

100

9 LI

NC

OLN

HIG

HW

AY

FA

IRV

IEW

HE

IGH

TS

, IL

6220

8T

: 618

-628

-088

7w

ww

.asd

gllc

.com

MU PROJ. NO.:

ROSS & BARUZZINI

MISSOURI STATE CERTIFICATE OF AUTHORITY #000148

MARK H. KUHLMAN

ENG. LIC. NO. PE-2017000321

10/6

/201

8 9

:53:4

9 A

M

505-111

E300

Checker

HE

AR

NE

S -

CH

ILLE

R R

EP

LA

CE

ME

NT

UM

PR

OJE

CT

NU

MB

ER

CP

181141

CO

LU

MB

IA, M

ISS

OU

RI

ELECTRICAL ONE-LINE

UN

IVE

RS

ITY

OF

MIS

SO

UR

I

Designer

10/1/2018

CP181141

10/1/2018

NO SCALE1

ELECTRICAL ONE LINE

1 10/08/18 ADDENDUM 1

1

Page 12: ADDENDUM #1operations-webapps.missouri.edu/pdc/adsite/projects... · 2018-10-08 · PAGE 2 CP181141/ HEARNES CHILLER REPLACEMENT Addendum #1 a. MODIFY CONTROLS: Modify controls of

6 S

OU

TH

OLD

OR

CH

AR

DS

T.

LO

UIS

, M

O 6

31

19

T 3

14

.91

8.8

383

F

314

.91

8.1

76

6w

ww

.ro

ssba

r.co

m

CHECKED BY:

© ROSS & BARUZZINI, INC. 2018

ISSUE

RB PROJ. NO.:

DESIGNED BY:

DRAWING TITLE:

DRAWING NO.:

WHEN THIS DRAWING IS REPRODUCED AT ORIGINAL SCALE THIS BAR = 1 INCH

REVISIONS:

The Professional Engineer, whose signature and personal seal appear on

this document, assumes responsibility only for what appears hereon, and

disclaims responsibility for all other plans, specifications, estimates,

reports, documents or instruments not sealed by the Professional

Engineer relating to, or intended to be used for, any part or parts of the

engineering project to which this document refers. Prints sealed by the

Engineer bear the embossed or wet seal of the Engineer across the

signature and date. Copies of this document, as signed and sealed, have

been retained by the Professional Engineer. The Professional Engineer

will not be responsible for subsequent changes to this document, unless

the changes are made by the Engineer or with the Engineer's written

authorization.

280

1 W

OO

DA

RD

DR

IVE

, SU

ITE

103

CO

LUM

BIA

, MO

652

02T

: 573

-443

-140

7w

ww

.soa

-inc.

com

1 INCH

DATE DESCRIPTION

SOA

MISSOURI STATE CERTIFICATE OF AUTHORITY #000826

ASDG

MISSOURI STATE CERTIFICATE OF AUTHORITY #200302424

100

9 LI

NC

OLN

HIG

HW

AY

FA

IRV

IEW

HE

IGH

TS

, IL

6220

8T

: 618

-628

-088

7w

ww

.asd

gllc

.com

MU PROJ. NO.:

ROSS & BARUZZINI

MISSOURI STATE CERTIFICATE OF AUTHORITY #000148

MARK H. KUHLMANENG. LIC. NO. PE-2017000321

10/6

/201

8 9

:53:4

9 A

M

505-111

E600

Checker

HE

AR

NE

S -

CH

ILLE

R R

EP

LA

CE

ME

NT

UM

PR

OJE

CT

NU

MB

ER

CP

181141

CO

LU

MB

IA, M

ISS

OU

RI

ELECTRICAL SCHEDULES

UN

IVE

RS

ITY

OF

MIS

SO

UR

I

Designer

10/1/2018

CP181141

10/1/2018

Total Est. Demand: 87 A

Total Conn.: 87 A

Total Est. Demand: 72000 VA

Total Conn. Load: 72000 VA

Panel Totals

Total Amps: 87 A 87 A 87 A

Total Load: 24000 VA 24000 VA 24000 VA

11 6000... 6000... 12

9 6000... 6000... 10

7

BASIN HEATER 30 A 3

6000... 6000...

3 30 A BASIN HEATER

8

5 6000... 6000... 6

3 6000... 6000... 4

1

BASIN HEATER 30 A 3

6000... 6000...

3 30 A BASIN HEATER

2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: 3R STAINLESS MCB Rating:

Mounting: UNISTRUT Wires: 3 Mains Rating: 100 A

Supply From: MCC3 Phases: 3 Mains Type: MLO

Location: Volts: 480/277V A.I.C. Rating:

Branch Panel: CTP2

Total Est. Demand: 7 A

Total Conn.: 7 A

Total Est. Demand: 6054 VA

Total Conn. Load: 6054 VA

Panel Totals

Total Amps: 9 A 4 A 9 A

Total Load: 2418 VA 1218 VA 2418 VA

11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12

9 SPACE -- -- 0 VA 0 VA -- -- SPACE 10

7 RAYCHEM HEAT TRACE (30mA GFI) 0 A 1 0 VA 0 VA -- -- SPACE 8

5 RAYCHEM HEAT TRACE 20 A 1 1200... 1218... 6

3 RAYCHEM HEAT TRACE (30mA GFI) 0 A 1 0 VA 1218... 4

1 RAYCHEM HEAT TRACE 20 A 1 1200... 1218...

3 20 A CONTROL VALVE ACTUATORS

2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: 3R STAINLESS MCB Rating:

Mounting: UNISTRUT Wires: 4 Mains Rating: 60 A

Supply From: MCC3 Phases: 3 Mains Type: MLO

Location: Volts: 480Y/277V A.I.C. Rating:

Branch Panel: CTP1

480V

COOLING TOWER

COOLING TOWER

1 10/08/18 ADDENDUM 1

1