X-VOLT RHZ1-OL 18/30 kV AL
1 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit Approved: F. Daz Rubio
1. Object This document defines the design and manufacturing
characteristics of the cables type RHZ1-OL 18/30 kV Al+H16
manufactured by Top Cable. 2. Design This type of cables is
designed, manufactured and tested according to UNE-HD 620-5E1 and
IEC 60502-2. 3. Applications Cables for fixed installations.
Suitable for transport and distribution of electric power in medium
voltage networks. Halogen free. These cables are suitable for
indoor, outdoor and buried installations. 4. Characteristics
Nominal voltage: 18/30 (36) kV
Minimum service temperature: -15 C
Maximum conductor temperature: 90 C
Maximum short-circuit temperature: 250 C (maximum 5 s)
Minimum bending radius: 15 x cable
Halogen free: according EN 50267 / IEC 60754
HCl content < 0,5 %
pH > 4,3
conductivity < 10 S/mm.
-
X-VOLT RHZ1-OL 18/30 kV AL
2 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit Approved: F. Daz Rubio
5. General make-up of the cable 5.1 Conductor Electrolytic
annealed aluminium conductor, class 2 according to EN 60228 / IEC
60228. Optionally, hygroscopic tapes can be applied in order to
achieve longitudinal watertightness on the conductor (cable type
-2OL) 5.2 Inner semi-conducting screen Cross-linked semiconductor
screen applied over conductor in a triple-extrussion process. 5.3
Insulation Cross-linked polyethylene insulation, type DIX-3
according to HD 620-1 and type XLPE according to IEC 60502-2;
natural color. Cross-linked in catenary line with nitrogen
atmosphere. 5.4 Outer semi-conducting screen Cross-linked
semiconductor screen applied over insulation in a triple-extrussion
process. Strippable. Optionally, under customer request, it can
supplied non strippable (bonded to insulation). 5.5 Metalic screen
Metalic screen made with Cu wires and Cu binder tape, applied over
the outer semi-conducting layer. With 16 mm2 minimum cross-section.
5.6 Water blocking Hygroscopic tape applied over metalic screen.
5.7 Outer sheath Polyolefine outer sheath, type DMZ1 according to
HD 620-1 and type ST7 according to IEC 60502-2; red color.
-
X-VOLT RHZ1-OL 18/30 kV AL
3 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit Approved: F. Daz Rubio
5.8 Diagram representation
6. Current-carrying capacities 6.1 Nominal current-carrying
capacities Table 1 show the current-carrying capacities and
electric parameters detailed for every cable. Current-carrying
capacities, in ampers, are calculated according to UNE 211435 and
for the following conditions:
- Open air installation: three single-core cables in trefoil
formation and ambient temperature of 40 C; protected from direct
sun radiation and with adequate ventilation (supported by cleats
and hangers or on perforated tray).
- Buried installation: three single-core cables in trefoil
formation direct buried at a depth of
1 m, ground temperature of 25 C and soil thermal resistivity of
1,5 Km/W. - In all cases it is supossed a three-phase circuit.
Reactance (X) is calculated at 50 Hz and for three single-core
cables (in triangle or trefoil formation). For conditions other
than this apply the adequate correction factors (point 6.3).
-
X-VOLT RHZ1-OL 18/30 kV AL
4 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit Approved: F. Daz Rubio
Cross-section X C Open air Buried installation mm2 /km F/km A
A
1 x 50 0,148 0,134 170 140
1 x 70 0,141 0,147 210 170
1 x 95 0,135 0,160 255 205
1 x 120 0,130 0,171 295 235
1 x 150 0,126 0,183 335 260
1 x 185 0,122 0,197 385 295
1 x 240 0,116 0,217 455 345
1 x 300 0,112 0,236 520 390
1 x 400 0,107 0,262 610 445
1 x 500 0,102 0,292 720 510
1 x 630 0,097 0,333 840 580
Table 1
6.2 Short-circuit current-carrying capacities The maximum
short-circuit current that a cable can withstand depend on the time
of reaction of the protection elements installed in the line
(calculated for 240 mm2 cable).
Time (s) 0,2 0,5 1 2
A 51.100 32.500 23.100 16.450
Table 2
6.3 Correction factors The current-carrying capacities must be
multiplied with the adequate correction factor when the
installation conditions differs from point 6.1 Correction factors
for air temperatures other than 40C.
Air Temp. (C) 20 25 30 35 40 45 50 55 60
Factor 1,18 1,14 1,10 1,05 1 0,95 0,89 0,84 0,77
Table 3
-
X-VOLT RHZ1-OL 18/30 kV AL
5 of 5
TECHNICAL SPECIFICATION
Rev. 1 27 May 2009
Issued: M. Canovas Margarit Approved: F. Daz Rubio
Correction factors for ground temperatures other than 25C.
Ground T. (C) 10 15 20 25 30 35 40 45 50
Factor 1,11 1,07 1,04 1 0,96 0,92 0,88 0,83 0,78
Table 4
Correction factors for soil thermal resistivity, that depend of
damp, other than 1,5 Km/W (calculated for 240 mm2 cable). Moisture
degree of soil Very damp
Slightly damp
Slightly dry Dry Very dry Very dry
Thermal resist. (Km/W) 0,8 1,0 1,5 2,0 2,5 3,0
Factor 1,29 1,18 1 0,88 0,80 0,73
Table 5
7. Dimensions Table 6 show diameters and weight detailed for
every cable.
Cross-section Outer Weight
mm2 mm kg/km
1 x 50 35,5 1100
1 x 70 36,5 1190
1 x 95 37,9 1290
1 x 120 39,0 1400
1 x 150 40,4 1520
1 x 185 41,9 1680
1 x 240 44,4 1920
1 x 300 46,7 2170
1 x 400 49,5 2630
1 x 500 54,4 2995
1 x 630 58,1 3580
Table 6