STANDARPT PLN (PERSERO)
SPLN S5.001: 2008Lampiran Surat Keputusan Direksi PT PLN
(PERSERO) No: 168.K/DIR/2009
TELEINFORMASI DATA UNTUK OPERASI JARINGAN TENAGA LISTRIK
PT PLN (PERSERO)JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU
JAKARTA SELATAN 12160
TELEINFORMASI DATA UNTUK OPERASI JARINGAN TENAGA LISTRIK
Disusun oleh: Kelompok Bidang SCADA dengan Surat Keputusan
Direksi PT PLN (PERSERO) No.094.K/DIR/2006
Kelompok Kerja Kaidah Rancangan Dasar Sistem SCADA Untuk Operasi
Jaringan tenaga Listrik dengan Surat Keputusan General Manager PT
PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan No.
006.K/LITBANG/2007
Diterbitkan oleh: PT PLN (PERSERO) Jalan Trunojoyo Blok M-I
/135, Kebayoran Baru Jakarta Selatan
Susunan Kelompok Bidang SCADA StandardisasiSurat Keputusan
Direksi PT PLN (PERSERO) No: 094.K/DIR/20061. 2. 3. 4. 5. 6. 7. 8.
9. Ir. Nur Pamudji, M.Eng, MPM : Ir. Harry Hartoyo, MM, MPM Ir.
Hernadi Buhron Novrizal Erdiansyah, ST Ir. Solida Ir. Sudibyo Agus
H Maulana, ST Ir. Joko Pramono Ir. A. Sugeng Sugarjito : : : : : :
: : : : : : : : Sebagai Ketua merangkap Anggota Sebagai Wakil Ketua
merangkap Anggota Sebagai Sekretaris merangkap Anggota Sebagai
Wakil Sekretaris merangkap Anggota Sebagai Anggota Sebagai Anggota
Sebagai Anggota Sebagai Anggota Sebagai Anggota Sebagai Anggota
Sebagai Anggota Sebagai Anggota Sebagai Anggota Sebagai Anggota
Sebagai Anggota
10. Ir. Yarid Pabisa 11. Ir. Ruly Chaerul 12. Ir. Herry Santoso
13. Ir. Yanuar I. Prakoso 14. Ir. Hesti Sayoga 15. Ir. Deany EA
Rumengan
Susunan kelompok kerja Kaidah Rancangan Dasar Sistem SCADA Untuk
Operasi Jaringan Tenaga ListrikSurat Keputusan General Manager PT
PLN (Persero) Litbang Ketenagalistrikan No: 006.K/LITBANG/20071. 2.
3. 4. 5. 6. 7. 8. Ir. Solida Novrizal Erdiansyah, ST Ir. A. Sugeng
Sugarjito Ir. Ruly Chaerul Tri Hardimasyar, ST Ir. Yarid Pabisa Ir.
Joko Pramono Ir. Denden Ruhdani : Sebagai Ketua merangkap Anggota :
Sebagai Sekretaris merangkap Anggota : Sebagai Anggota : Sebagai
Anggota : Sebagai Anggota : Sebagai Anggota : Sebagai Anggota :
Sebagai Anggota
SPLN S5.001: 2008
DAFTAR ISIDaftar Isi
......................................................................................................................................i
Daftar Tabel
...............................................................................................................................
iii Daftar Gambar
...........................................................................................................................iv
Daftar Lampiran
..........................................................................................................................v
Prakata
.....................................................................................................................................
vii 1. 2. 3. 4. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12
4.13 4.14 4.15 4.16 4.17 5. 5.1 5.2 5.3 5.4 Ruang
Lingkup..............................................................................................................
1
Tujuan...........................................................................................................................
1 Acuan Normatif
.............................................................................................................
1 Istilah dan
Definisi.........................................................................................................
1
Alarm.............................................................................................................................
1 Control
center................................................................................................................
2 Distribution control center (DCC)
..................................................................................
2 Feeder colouring
...........................................................................................................
2 Gardu hubung
...............................................................................................................
2 Gardu tengah
................................................................................................................
2 Earth Fault Indicator
(EFI).............................................................................................
2 Inter distribution control center
(IDCC)..........................................................................
2 Inter regional control center (IRCC)
..............................................................................
2 Keypoint
........................................................................................................................
2 National control center (NCC)
.......................................................................................
2 Regional control center (RCC)
......................................................................................
2 Supervisory control and data acquisition
(SCADA)....................................................... 3
Telecontrol
....................................................................................................................
3
Telesignal......................................................................................................................
3 Telemetering
.................................................................................................................
3 Teleprotection
...............................................................................................................
3 Umum
...........................................................................................................................
3 Fasilitas
SCADA............................................................................................................
3 Teleinformasi
data.........................................................................................................
3 Struktur informasi
..........................................................................................................
4 Simbol dan warna
.........................................................................................................
4
i
SPLN S5.001: 2008
6. 6.1 6.2
Perbatasan Kebutuhan Teleinformasi Data
..................................................................4
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC
................................4 Perbatasan kebutuhan
teleinformasi data antara RCC dan DCC
.................................5
Lampiran A Daftar Teleinformasi
(Transmisi).........................................................................7
Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai
Konfigurasi Gardu Induk) .....15 Lampiran C Daftar Teleinformasi
(Distribusi)
.......................................................................89
Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai
Konfigurasi Jaringan Distribusi)
...........................................................................................95
Lampiran E Struktur
Informasi............................................................................................118
Lampiran F Simbol dan
Warna...........................................................................................126
ii
SPLN S5.001: 2008
DAFTAR TABEL
Tabel 1. Struktur
informasi...............................................................................................119
Tabel 2. Level tegangan
..................................................................................................121
Tabel 3. Nama bay atau feeder
.......................................................................................122
Tabel 4. Kode tegangan dari primer dan sekunder trafo
.................................................122 Tabel 5. Kode
nama
peralatan/alarm/elemen..................................................................123
Tabel 6. Warna
tampilan..................................................................................................129
iii
SPLN S5.001: 2008
DAFTAR GAMBARGambar 1. Batas wewenang antara IRCC dengan RCC
(Tipe-a)....................................... 5 Gambar 2. Batas
wewenang antara IRCC dengan RCC
(Tipe-b)....................................... 5 Gambar 3. Batas
wewenang antara RCC dengan DCC
..................................................... 6 Gambar 4.
Struktur informasi khusus (bay
diameter)...................................................... 124
Gambar 5. Struktur informasi khusus (gardu induk 1 breaker)
.................................... 125 Gambar 6. Simbol gambar
..............................................................................................
127 Gambar 7. Tampilan status
.............................................................................................
128
iv
SPLN S5.001: 2008
DAFTAR LAMPIRAN
Lampiran A Daftar Teleinformasi (Transmisi)
........................................................................
7 A-1:
Telesignal......................................................................................................................................
8 A-2: Telemeasurement
.......................................................................................................................11
A-3: Tap changer position
..................................................................................................................12
A-4: Remote control digital
.................................................................................................................13
A-5: Remote control analog
...............................................................................................................14
Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai
Konfigurasi Gardu Induk) .... 15 TA-01: Konfigurasi umum pada 1
breaker
....................................................................................16
TA-02: Konfigurasi umum pada double busbar
...............................................................................20
TA-03: Konfigurasi umum pada single busbar
................................................................................25
TB-01: Generator combined cycle pada konfigurasi 1 breaker
..................................................30 TB-02: 2
generator terhubung ke MTR 3-belitan pada konfigurasi 1 breaker
..........................32 TB-03: 2 generator terhubung ke MTR
3-belitan pada konfigurasi double busbar .....................34
TB-04: 2 generator terhubung ke MTR 3-belitan pada konfigurasi
single busbar ......................36 TB-05: 1 generator terhubung
ke MTR 2-belitan pada konfigurasi 1 breaker
..........................38 TB-06: 1 generator terhubung ke MTR
2-belitan pada konfigurasi double busbar .....................40
TB-07: 1 generator terhubung ke MTR 2-belitan pada konfigurasi
single busbar ......................42 TB-08: 2 generator terhubung
ke MTR 2-belitan pada konfigurasi 1 breaker
..........................44 TB-09: 2 generator terhubung ke MTR
2-belitan pada konfigurasi double busbar .....................46
TB-10: 2 generator terhubung ke MTR 2-belitan pada konfigurasi
single busbar ......................48 TB-11: Interbus transformer
(secondary side connected to 1
breaker)......................................................................................50
TB-12: Interbus transformer (secondary side connected to double
busbar).................................................................................52
TB-13: Interbus transformer (secondary side connected to single
busbar)
..................................................................................54
TB-14: Interbus transformer (secondary side connected to 1 breaker
dilengkapi shunt reaktor pada kumparan tersier)
.................................................................................56
TB-15: Interbus transformer (secondary side connected to double
busbar dilengkapi shunt reaktor pada kumparan tersier)
.................................................................................58
TB-16: Interbus transformer (secondary side connected to single
busbar dilengkapi shunt reaktor pada kumparan tersier)
.................................................................................60
TB-17: Bay trafo tenaga pada konfigurasi 1 breaker
...................................................................62
TB-18: Bay trafo tenaga pada konfigurasi double busbar
..............................................................64
TB-19: Bay trafo tenaga pada konfigurasi single busbar
...............................................................66
TB-20: Bay reaktor pada konfigurasi 1 breaker
..........................................................................68
TB-21: Bay reaktor pada konfigurasi double busbar
......................................................................69
TB-22: Bay reaktor pada konfigurasi single busbar
........................................................................70
TB-23: Bay capasitor pada konfigurasi double busbar
...................................................................71
TB-24: Bay capasitor pada konfigurasi single busbar
....................................................................72
TB-25: Bay penghantar pada konfigurasi 1 breaker
...................................................................73
TB-26: Bay penghantar pada konfigurasi double busbar
...............................................................75
TB-27: Bay penghantar pada konfigurasi single busbar
................................................................77
TB-28: Bay penghantar paralel dengan reaktor pada konfigurasi
double busbar .......................79 TB-29: Bay penghantar
paralel dengan 1 reaktor pada konfigurasi 1 breaker
........................81 TB-30: Bay penghantar paralel dengan 2
reaktor seri pada konfigurasi 1 breaker .................83 TB-31:
Bay kopel pada konfigurasi double busbar
.........................................................................85
TB-32: Bus section
..............................................................................................................................86
v
SPLN S5.001: 2008
TB-33: Bay diameter pada konfigurasi 1 breaker
........................................................................87
TB-34: Bus bar
....................................................................................................................................88
Lampiran C Daftar Teleinformasi (Distribusi)
.......................................................................89
C-1: Telesignal
....................................................................................................................................90
C-2: Telemeasurement
.......................................................................................................................92
C-3: Tap changer position
..................................................................................................................93
C-4: Remote control digital
................................................................................................................94
Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai
Konfigurasi Jaringan
Distribusi)............................................................................................95
DA-01: Konfigurasi umum pada double busbar
..............................................................................96
DA-02: Konfigurasi umum pada single busbar
................................................................................99
DB-01: Trafo 150/20 kV dan 70/20 kV tipe 1
.................................................................................102
DB-02: Trafo 150/20 kV dan 70/20 kV tipe 2
.................................................................................103
DB-03: Trafo 150/20 kV dan 70/20 kV tipe 3
.................................................................................104
DB-04: Generator pada konfigurasi double busbar
......................................................................105
DB-05: Generator pada konfigurasi single busbar
........................................................................106
DB-06: Feeder 20 kV tipe 1
.............................................................................................................107
DB-07: Feeder 20 kV tipe 2
.............................................................................................................108
DB-08: Feeder 20 kV Tipe 3
............................................................................................................109
DB-09: Bus Section 20 kV tipe 1
.....................................................................................................110
DB-10: Bus section 20 kV tipe
2......................................................................................................111
DB-11: Kopel
.....................................................................................................................................112
DB-12: Capacitor bay
.......................................................................................................................113
DB-13: SUTM radial dengan keypoint dan PBO
...........................................................................114
DB-14: SUTM radial dengan keypoint tanpa PBO
........................................................................115
DB-15: SUTM loop dengan beberapa
keypoint.............................................................................116
DB-16: Spindle 20 kV
.......................................................................................................................117
Lampiran E Struktur
Informasi............................................................................................118
A. Nomor ID
.......................................................................................................................................119
B. Time stamp
...................................................................................................................................121
C. Nama
GI/GH/GT...........................................................................................................................121
D. Level Tegangan
............................................................................................................................121
E. Nama Bay / Feeder
......................................................................................................................122
F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen
................................................123 G. Status
Peralatan atau Status Alarm
..........................................................................................123
H. Nama user yang melakukan aksi
...............................................................................................123
I. Prioritas Alarm
................................................................................................................................124
Struktur Informasi Khusus
................................................................................................................124
Lampiran F Simbol dan
Warna...........................................................................................126
vi
SPLN S5.001: 2008
PRAKATAStandar SCADA ini merupakan pengganti dari Pola SCADA
SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan
teknologi SCADA. Standar ini menjelaskan mengenai master station,
komunikasi dan remote station yang terdiri dari enam bagian, yaitu:
1. 2. 3. 4. 5. 6. S3.001: 2008 S5.001: 2008 S5.002: 2008 S4.001:
2008 S6.001: 2008 S7.001: 2008 Peralatan SCADA sistem tenaga
listrik Teleinformasi data untuk operasi jaringan tenaga listrik
Teleinformasi data untuk pemeliharaan instalasi sistem tenaga
listrik Pengujian sistem SCADA Perencanaan dan pembangunan sistem
SCADA Operasi dan pemeliharaan sistem SCADA
Keenam standar di atas adalah yang telah diselesaikan dalam
tahun 2008 dan direncanakan akan ditambah dengan beberapa standar
lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat
keras, perangkat lunak, kebutuhan teleinformasi data, pengujian,
kinerja, kajian kelayakan dalam pembangunan, operasi dan
pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar
ini dapat menjadi acuan dalam setiap perencanaan, pembangunan,
operasi dan pemeliharaan sistem SCADA di PT PLN (PERSERO) secara
nasional.
vii
SPLN S5.001: 2008
Teleinformasi Data Untuk Operasi Jaringan Tenaga Listrik
1.
Ruang Lingkup
Teleinformasi data terdiri dari telecontrol, telesignal dan
telemetering. Sesuai dengan penggunaannya, teleinformasi data
dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan.
Standar ini dimaksudkan untuk menetapkan standar teleinformasi data
untuk kepentingan operasi dan mencakup sistem transmisi dan sistem
distribusi. Standar ini berlaku untuk sistem SCADA: a. National
Control Center, disingkat NCC; b. Inter Regional Control Center,
disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter
Distribution Control Center, disingkat IDCC; e. Distribution
Control Center, disingkat DCC.
2.
Tujuan
Standar ini ditujukan untuk memberikan pedoman yang terarah dan
seragam dalam penerapan teleinformasi data bagi kebutuhan operasi
sistem transmisi dan sistem distribusi tenaga listrik yang
mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan
acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem
SCADA yang telah ada.
3.
Acuan Normatif
Dokumen normatif berikut berisi persyaratan-persyaratan yang
menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data
Untuk Operasi Jaringan Tenaga Listrik. a. SNI 04-7021.1.1-2004:
2004, Peralatan dan Sistem Telekontrol Bagian 1: Pertimbangan Umum
Seksi 1: Prinsip Umum; b. Keputusan Menteri Energi dan Sumberdaya
Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga
Listrik Jawa-Madura-Bali;
4. 4.1
Istilah dan Definisi Alarm
Perubahan kondisi dari peralatan atau sistem yang telah
terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh
operator/dispatcher, atau kegagalan peralatan untuk merespon secara
benar. Indikasi alarm berupa audible atau visual, atau
keduanya.
1
SPLN S5.001: 2008
4.2
Control center
Pusat kendali pengoperasian sistem tenaga listrik dimana master
station ditempatkan.
4.3
Distribution control center (DCC)
Pusat kendali jaringan distribusi.
4.4
Feeder colouring
Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi
bertegangan.
4.5
Gardu hubung
Gardu yang mempunyai fungsi utama melakukan manuver antar
feeder.
4.6
Gardu tengah
Gardu yang merupakan titik tengah beban atau titik tengah
feeder.
4.7
Earth Fault Indicator (EFI)
Penunjukan arah dari indikator gangguan tanah.
4.8
Inter distribution control center (IDCC)
Pusat kendali yang terhubung dengan beberapa distribution
control center.
4.9
Inter regional control center (IRCC)
Pusat kendali yang terhubung dengan beberapa regional control
center.
4.10
Keypoint
Peralatan switching dimana bisa dilakukan manuver antara dua
feeder atau lebih.
4.11
National control center (NCC)
Pusat kendali yang terhubung dengan beberapa inter regional
control center.
4.12
Regional control center (RCC)
Pusat kendali jaringan transmisi tegangan tinggi.
2
SPLN S5.001: 2008
4.13
Supervisory control and data acquisition (SCADA)
Sistem yang mengawasi dan mengendalikan peralatan proses yang
tersebar secara geografis. [ IEC 870-1-3 ]
4.14
Telecontrol
Kendali peralatan operasional jarak jauh menggunakan transmisi
informasi dengan teknik telekomunikasi. [IEV 371-01-01]CATATAN:
Telekontrol dapat berisi kombinasi perintah, alarm, indikasi,
metering/pengukuran, proteksi dan fasilitas tripping, tidak
menggunakan pesan suara.
4.15
Telesignal
Pengawasan status dari peralatan operasional dalam jarak
tertentu dengan menggunakan teknik telekomunikasi seperti kondisi
alarm, posisi switch atau posisi katup. [IEV 371-0104]
4.16
Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik
telekomunikasi. [IEV 371-01-03]
4.17
Teleprotection
Peralatan komunikasi yang diperlukan oleh sistem proteksi yang
berfungsi untuk pengamanan peralatan sistem tenaga listrik.
5. 5.1
Umum Fasilitas SCADA
Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu
tengah, key point dan fasilitas sistem tenaga listrik yang baru
harus dapat dipantau dari control center dan dilakukan pengujian
sebelum diintegrasikan ke sistem transmisi atau sistem distribusi
tenaga listrik.
5.2
Teleinformasi data
Standar ini membedakan teleinformasi data untuk transmisi dan
distribusi. Teleinformasi data untuk operasi jaringan tenaga
listrik dapat dilihat pada Lampiran A Daftar Teleinformasi
(Transmisi) sampai dengan Lampiran D - Bidang Distribusi
(Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi).
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu
organisasi, maka master station dapat digunakan untuk fungsi RCC
dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada
teleinformasi data transmisi dan distribusi.
3
SPLN S5.001: 2008
Teleinformasi data untuk kepentingan operasi jaringan tenaga
listrik ditampilkan pada workstation dispatcher. Setiap pembangunan
SCADA untuk fasilitas sistem tenaga listrik, kebutuhan
teleinformasi datanya harus mengacu pada SPLN S5.001: 2008
Teleinformasi data untuk operasi jaringan tenaga listrik dan SPLN
S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem
tenaga listrik.
5.3
Struktur informasi
Event dan alarm merupakan pemberitahuan kepada dispatcher atau
operator tentang kejadian pada peralatan sistem tenaga listrik yang
tampil di monitor dan disimpan di data historikal. Struktur
informasi event dan alarm SCADA dapat dilihat pada Lampiran E
Struktur Informasi.
5.4
Simbol dan warna
Simbol dan warna diperlukan untuk penyajian diagram sistem
tenaga listrik pada monitor dan layar tayang. Simbol dan warna
untuk tiap jenis dan kondisi peralatan bersifat informatif dan
dipilih sedemikian rupa sehingga jenis dan kondisi peralatan
tersebut mudah dikenali oleh dispatcher. Simbol dan warna dapat
dilihat pada Lampiran F Simbol dan Warna.
6.
Perbatasan Kebutuhan Teleinformasi Data
Teleinformasi data yang dikirim ke/dari suatu control center
ditentukan oleh kewenangannya dalam operasi sistem, sehingga
dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC
serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan
teleinformasi data antara IRCC dan RCC serta antara RCC dan
DCC.
6.1
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC
adalah di titik pelayanan tegangan ekstra tinggi atau tegangan
tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2.
4
SPLN S5.001: 2008
a. Bila sisi sekunder IBT terhubung dengan konfigurasi double
busbar.BUSBAR TET/TT
IRCC
RCC BUSBAR TT
Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a)
b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1
Breaker.B U S B A R T E T /T T
BUSBAR TT
IR C C
RCC
BUSBAR TT
Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b)
6.2
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di
gardu induk ditunjukkan pada Gambar 3.
5
SPLN S5.001: 2008
BUSBAR TT
L /R P Q V I RCC
DCC
BUSBAR TM
Gambar 3. Batas wewenang antara RCC dengan DCC
Untuk daerah yang fungsi transmisi dan distribusi masih dalam
satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka
perbatasan kebutuhan teleinformasi data dapat mengacu pada
perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang
berlaku di daerah tersebut.
6
SPLN S5.001: 2008
Lampiran A Daftar Teleinformasi (Transmisi)
7
SPLN S5.001: 2008
A-1: TelesignalSingle (S) or Double (D) Indication Suggested
Alarm (A) or Event/Indication (I)
No
Kode
Fungsi
Implementasi Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor
Capasitor Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor RTU
Gardu induk, Kopel, Feeder, Diameter Gardu induk Kopel, Feeder,
Trafo, Diameter, Capasitor, Reaktor Generator Generator Generator
Generator Feeder, Trafo Gardu induk, Kopel, Feeder, Trafo,
Diameter, Capasitor, Reaktor Trafo Generator Distribution
Transformer Gardu induk Gardu induk, Kopel, Feeder, Trafo, Diameter
Trafo Trafo Transformer Generator Feeder Feeder Generator
1
BI
Bus isolator switch closed/opened
D
I
2
CAM
Capasitor Auto/Manual
D
I
3
CB
Circuit breaker closed/opened
D
I
4 5 6
CD CSO DCBC
Control disable switch Check synchronizing override Dummy
breaker closed/opened
D D D
I I I
7
ES
Earth Switch Closed/Opened
D
I
8 9 10 11 12
GUC LFA LFC LFR LI
Generator unit run/stop Load frequency available/not available
Load frequency control on/off switch Load frequency request on/off
Line isolator switch closed/opened
D D D D D
I I I I I
13
LR
Local remote
D
I
14 15 16 17 18 19 20 21 22 23 24 25
LRT PSO RACK RMT SAM TC TCC TFAM AQR AR ARO AVR
Local remote switch for tapchanger Power station operated
Circuit Breaker Rack-In/Rack-Out Reset Master Trip Synchronization
Auto/Manual Tap changer raise/lower Tap changer auto/manual
Transformer Fan Auto/Manual Automatic power factor regulator active
Circuit breaker auto reclose Auto reclose off Automatic voltage
regulator on/off
D D D D D D D D S S S S
I I I I I I I I I I I I
8
SPLN S5.001: 2008
No
Kode
Fungsi
Implementasi Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor
Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor Kopel, Feeder,
Trafo, Diameter, Capasitor, Reaktor, Generator Gardu induk Gardu
induk Generator Trafo Generator Generator Busbar Busbar Feeder
Feeder Trafo, Capasitor, Reaktor Trafo Feeder Feeder Feeder Kopel,
Feeder, Trafo, Capasitor, Reaktor Kopel, Feeder, Trafo, Capasitor,
Reaktor Diameter Gardu induk Gardu induk Reactor Reactor Reactor
RTU Gardu induk Trafo Trafo Trafo Trafo Trafo
Single (S) or Double (D) Indication
Suggested Alarm (A) or Event/Indication (I)
26
BF
Bay fault dc
S
A
27
BRF
Breaker fault
S
A
28
CBTR
Circuit breaker trip
S
A
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
COM CSP GOV GTT LFF OVR P1BP P1CD P1DEF P1DIF P1REF P1Z1 P1Z2
P1Z3 P2GFR
Communication faulty Check synchronizing in progress Free acting
governor active Generator transformer trip Load frequency control
unit failure Over voltage relay operate Busbar protection Current
defferential Directional earth fault Differential Restricted earth
fault Distance protection zone 1 Distance protection zone 2
Distance protection zone 3 Ground fault relay
S S S S S S S S S S S S S S S
A I I A A A A A A A A A A A A
44 45 46 47 48 49 50 51 52 53 54 55 56 57
P2OCR P3DTT PTF PHA RA RF RT RTUA SYNF TAF TCA TCH TCL TEA
Over current relay Direct transfer trip Protection faulty
Peripheral alarm Reactor alarm Reactor failure Reactor Trip RTU
alarm Synchronizing failure Tranformer AVR failure Tap changer
alarm Tap changer high limit Tap changer low limit Temperature
alarm
S S S S S S S S S S S S S S
A A A A A A A A A A A A A A
9
SPLN S5.001: 2008
No 58 59 60 61 62 63 64 65 66 67 68 69 70 71
Kode TET TRA TRT TTR TTT UT UVR VACF VDCF VS SIB IEDF SOTF
MTO
Fungsi Temperature trip Transformer alarm Transformer trip
Teleprotection trip receive Teleprotection trip transmit Unit trip
Under voltage relay Vac failure Vdc failure Voltage status Software
interlocking bypass IED Faulty Switch on to fault Master Trip
Operate
Implementasi Trafo Trafo Trafo Feeder Feeder Generator Busbar
Gardu induk Gardu induk Busbar Gardu Induk Gardu Induk Gardu Induk
Gardu Induk
Single (S) or Double (D) Indication S S S S S S S S S S S S S
S
Suggested Alarm (A) or Event/Indication (I) A A A I I A A A A I
A A A A
Keterangan: A = I =
Announciation of abnormal condition (audible alarm, flashing
display, etc) Event/Indication (normal condition)
10
SPLN S5.001: 2008
A-2: Telemeasurement
No
Kode
Fungsi
Implementasi
1
F
Frekuensi
Gardu induk Feeder, InterBus Transformer, Generator Transformer,
Kopel Feeder, Transformer, Generator Generator Generator Feeder,
Transformer, Generator, Capasitor, Reaktor Feeder, InterBus
Transformer, Generator, Busbar
2 3 4 5 6 7
I P POAQ PRAQ Q V
Arus Daya Aktif Real power setting Maksimum power variation
setting Daya Reaktif Tegangan
11
SPLN S5.001: 2008
A-3: Tap changer positionNo 1 Kode TPI Fungsi Tap position
indication Transformer Implementasi
12
SPLN S5.001: 2008
A-4: Remote control digitalNo 1 BI Kode Fungsi Bus isolator
switch closed/opened Implementasi Kopel, Feeder, Transformer,
Capasitor, Reaktor, Diameter Kopel, Feeder, Transformer, Capasitor,
Reaktor, Diameter Gardu induk
2
CB
Circuit breaker closed/opened
3
CSO
Check synchronizing override
4
DCBC
Dummy circuit breaker closed/opened
RTU
5
GUC
Generator Unit Run/Stop
Generator
6
LFR
Load frequency request on/off
Generator
7
TC
Tap changer raise/lower
Interbus Transformer
8
TCC
Tap changer auto/manual
Interbus Transformer
13
SPLN S5.001: 2008
A-5: Remote control analogNo 1 2 3 N POOP PROP Kode Fungsi Load
frequency control N_level Real power set point Maksimum power
variation set point Implementasi Generator Generator Generator
14
SPLN S5.001: 2008
Lampiran B Bidang Transmisi (Teleinformasi pada Berbagai
Konfigurasi Gardu Induk)
15
SPLN S5.001: 2008
TA-01: Konfigurasi umum pada 1 breakerTA-01
KONFIGURASI UMUM PADA 1 BREAKERBAY REAKTOR BAY GENERATOR
P Q V
LFC (Po,Pr,N)
Q
P Q I BUSBAR - A V L/R L/R
L/R
L/R
L/R
L/R
L/R
L/R
BUSBAR - B V L/R P Q V IBAY TRANSMISI
P Q
P Q V I
L/R
BAY IBT
BAY TRAFO TENAGA
16
SPLN S5.001: 2008
Teleinformasi Data Untuk Konfigurasi Umum Pada 1 Breaker Group
Bay Data No Kode Fungsi TM 1 F Frekuensi 29 COM Communication alarm
46 PTF Protection faulty 47 PHA Peripheral alarm 51 RTUA RTU alarm
52 SYNF Synchronizing failure TSS 65 VACF Vac failure 66 VDCF Vdc
failure 68 SIB Software interlocking bypass GARDU INDUK 69 IEDF IED
faulty 70 SOTF Switch on to fault 71 MTO Master Trip Operate 4 CD
Control disable switch 5 CSO Check synchronizing override TSD 6
DCBC Dummy breaker closed/opened 13 LR Local remote 3 CSO Check
synchronizing override RCD 4 DCBC Dummy breaker closed/opened TM 7
V Tegangan 26 BF Bay fault DC 34 OVR Over voltage relay operate
BUSBAR TSS 35 P1BP Busbar protection 64 UVR Under voltage relay 67
VS Voltage status 27 BRF Breaker fault TSS 28 CBTR CB trip 30 CSP
Check synchronizing in progress 1 BI Bus isolator switch DIAMETER 3
CB Circuit breaker closed/opened TSD 5 CSO Check synchronizing
override 13 LR Local remote 1 BI Bus isolator switch RCD 2 CB
Circuit breaker closed/opened BAY 2 I Arus TRANSMISI 3 P Daya aktif
TM 6 Q Daya reaktif 7 V Tegangan TSS 23 AR *) Circuit breaker auto
reclose 24 ARO *) Auto reclose on/off 26 BF Bay fault DC 30 CSP
Check synchronizing in progress 36 P1CD Current differential 37
P1DEF Directional earth fault 40 P1Z1 *) Distance zone 1 *) 41 P1Z2
Distance zone 2 *) 42 P1Z3 Distance zone 3 43 P2GFR Ground fault
relay 44 P2OCR Over current relay 45 P3DTT*) Direct transfer
trip
Tipe A A A A A A A A A A A I I I I
A A A A A A A I I I I I
I I A I A A A A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 6 3 3
3 6 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
17
SPLN S5.001: 2008
Group Bay
Data
TSD TC TM
TSS BAY IBT
TSD
RCD TM
BAY TRAFO TENAGA
TSS
BAY REAKTOR
TSD TM
TSS
No 61 62 12 1 2 3 6 7 26 27 28 30 38 39 43 44 53 54 55 56 57 58
59 60 3 12 13 14 20 2 7 8 3 6 26 38 39 43 44 57 58 59 60 12 6 26 38
43 44 49
Kode TTR TTT LI TPI I P Q V BF BRF CBTR CSP P1DIF P1REF P2GFR
P2OCR TAF TCA TCH TCL TEA TET TRA TRT CB LI LR LRT TCC CB TC TCC P
Q BF P1DIF P1REF P2GFR P2OCR TEA TET TRA TRT LI Q BF P1DIF P2GFR
P2OCR RF
Fungsi Teleprotection trip receive Teleprotection trip transmit
Line isolator switch closed/opened Tap position indication Arus
Daya aktif Daya reaktif Tegangan Bay fault DC Breaker fault Circuit
breaker trip Check synchronizing in progress Differential
Restricted earth fault Ground fault relay Over current relay
Tranformer avr failure Tap changer alarm Tap changer high limit Tap
changer low limit Temperature alarm Temperature trip Transformer
alarm Transformer trip Circuit breaker closed/opened Line isolator
switch closed/opened Local remote Local/remote switch for
tapchanger Tap changer auto/remote Circuit breaker closed/opened
Tap changer raise/lower Tap changer auto/manual Daya aktif Daya
reaktif Bay fault DC Differential Restricted earth fault Ground
fault relay Over current relay Temperature alarm Temperature trip
Transformer alarm Transformer trip Line isolator switch
closed/opened Daya reaktif Bay fault DC Differential Ground fault
relay Over current relay Reactor failure
Tipe I I I I
A A A I A A A A A A A A A A A A I I I I I I
A A A A A A A A A I A A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
18
SPLN S5.001: 2008
Group Bay
Data TSD
TM
TSS BAY GENERATOR
TSD
RCD RCA
No 12 2 3 4 5 6 7 19 25 26 30 31 32 33 63 8 9 10 11 12 15 5 6 1
2 3
Kode LI I P POAQ PRAQ Q V AQR AVR BF CSP GOV GTT LFF UT GUC LFA
LFC LFR LI PSO GUC LFR N POOP PROP
Fungsi Line isolator switch closed/opened Arus Daya aktif Real
power setting Maksimum power variation setting Daya reaktif
Tegangan Automatic power factor regulator on/off Automatic voltage
regulator on/off Bay fault DC Check synchronizing in progress Free
acting governor active Generator transformer trip Load frequency
control unit failure Unit trip Generator unit run/stop Load
frequency control available Load frequency control on/off switch
Load frequency request on/off Line isolator switch closed/opened
Power set on/off switch Generator unit run/stop Load frequency
request on/off Load frequency control N_level Real power set point
Maksimum power variation set point
Tipe I
I I A I I A A A I I I I I I
Jmh 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi
diatas adalah rincian per bay.
19
SPLN S5.001: 2008
TA-02: Konfigurasi umum pada double busbarTA-02
KONFIGURASI UMUM PADA DOUBLE BUSBARBAY REAKTOR BAY GENERATOR
P Q V
LFC (Po,Pr,N)
Q
P Q IBAY KOPEL
L/R
L/R
L/R
BUSBAR - A V
BUSBAR - B V
L/R
L/R
L/R
P Q P Q V IBAY TRANSMISI BAY TRAFO TENAGA
L/R P Q V IBAY IBT
20
SPLN S5.001: 2008
Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar
Group Bay Data No Kode Fungsi TM 1 F Frekuensi 29 COM Communication
alarm 46 PTF Protection faulty 47 PHA Peripheral alarm 51 RTUA RTU
alarm 52 SYNF Synchronizing failure TSS 65 VACF Vac failure 66 VDCF
Vdc failure 68 SIB Software interlocking bypass GARDU INDUK 69 IEDF
IED faulty 70 SOTF Switch on to fault 71 MTO Master Trip Operate 4
CD Control disable switch 5 CSO Check synchronizing override TSD 6
DCBC Dummy breaker closed/opened 13 LR Local remote 3 CSO Check
synchronizing override RCD 4 DCBC Dummy breaker closed/opened TM 7
V Tegangan 26 BF Bay fault DC 34 OVR Over voltage relay operate
BUSBAR TSS 35 P1BP Busbar protection 64 UVR Under voltage relay 67
VS Voltage status 26 BF Bay fault DC 27 BRF Breaker fault 28 CBTR
CB trip TSS 30 CSP Check synchronizing in progress 43 P2GFR Ground
fault relay 44 P2OCR Over current relay KOPEL 1 BI Bus isolator
switch 3 CB Circuit breaker closed/opened TSD 5 CSO Check
synchronizing override 13 LR Local remote 1 BI Bus isolator switch
RCD 2 CB Circuit breaker closed/opened BAY 2 I Arus TRANSMISI 3 P
Daya aktif TM 6 Q Daya reaktif 7 V Tegangan TSS 23 AR *) Circuit
breaker auto reclose 24 ARO *) Auto reclose on/off 26 BF Bay fault
DC 27 BRF Breaker fault 28 CBTR Circuit breaker trip 30 CSP Check
synchronizing in progress 36 P1CD Current differential 37 P1DEF
Directional earth fault 40 P1Z1 *) Distance zone 1
Tipe A A A A A A A A A A A I I I I
A A A A A A A A I A A I I I I
I I A A A I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 1 1 1 1 1 1
2 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
21
SPLN S5.001: 2008
Group Bay
Data
TSD
RCD TC TM
TSS BAY IBT
TSD
RCD BAY TRAFO TENAGA
TM TSS
No 41 42 43 44 45 61 62 1 3 5 12 13 1 2 1 2 3 6 7 26 27 28 30 38
39 43 44 53 54 55 56 57 58 59 60 1 3 13 14 20 1 2 7 8 3 6 26 27 28
38
Kode P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT BI CB CSO LI LR
BI CB TPI I P Q V BF BRF CBTR CSP P1DIF P1REF P2GFR P2OCR TAF TCA
TCH TCL TEA TET TRA TRT BI CB LR LRT TCC BI CB TC TCC P Q BF BRF
CBTR P1DIF
Fungsi Distance zone 2 Distance zone 3 Ground fault relay Over
current relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Bus isolator switch Circuit breaker
closed/opened Check synchronizing override Line isolator switch
closed/opened Local remote Bus isolator switch Circuit breaker
closed/opened Tap position indication Arus Daya aktif Daya reaktif
Tegangan Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Differential Restricted earth fault
Ground fault relay Over current relay Tranformer avr failure Tap
changer alarm Tap changer high limit Tap changer low limit
Temperature alarm Temperature trip Transformer alarm Transformer
trip Bus isolator switch Circuit breaker closed/opened Local remote
Local/remote switch for tapchanger Tap changer auto/remote Bus
isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Daya aktif Daya reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential
Tipe A A A A A I I I I I I I
I
A A A I A A A A A A A A A A A A I I I I I
A A A A
Jmh 1 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1
22
SPLN S5.001: 2008
Group Bay
Data
TSD RCD TM
TSS BAY REAKTOR TSD RCD BAY GENERATOR TM
TSS
TSD
RCD
No 39 43 44 57 58 59 60 1 3 13 1 2 6 26 27 28 38 43 44 49 1 3 13
1 2 2 3 4 5 6 7 22 25 26 27 28 30 31 32 33 63 1 3 8 9 10 11 13 15
1
Kode P1REF P2GFR P2OCR TEA TET TRA TRT BI CB LR BI CB Q BF BRF
CBTR P1DIF P2GFR P2OCR RF BI CB LR BI CB I P POAQ PRAQ Q V AQR AVR
BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR PSO BI
Fungsi Restricted earth fault Ground fault relay Over current
relay Temperature alarm Temperature trip Transformer alarm
Transformer trip Bus isolator switch Circuit breaker closed/opened
Local remote Bus isolator switch Circuit breaker closed/opened Daya
reaktif Bay fault DC Breaker fault Circuit breaker trip
Differential Ground fault relay Over current relay Reactor failure
Bus isolator switch Circuit breaker closed/opened Local remote Bus
isolator switch Circuit breaker closed/opened Arus Daya aktif Real
power setting Maksimum power variation setting Daya reaktif
Tegangan Automatic power factor regulator on/off Automatic voltage
regulator on/off Bay fault DC Breaker fault Circuit breaker trip
Check synchronizing in progress Free acting governor active
Generator transformer trip Load frequency control unit failure Unit
trip Bus isolator switch Circuit breaker closed/opened Generator
unit run/stop Load frequency control available Load frequency
control on/off switch Load frequency request on/off Local remote
Power set on/off switch Bus isolator switch
Tipe A A A A A A A I I I
A A A A A A A I I I
I I A A A I I A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 2 1 1 2
1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 2
23
SPLN S5.001: 2008
Group Bay
Data
RCA
No 2 5 6 1 2 3
Kode CB GUC LFR N POOP PROP
Fungsi Circuit breaker closed/opened Generator unit run/stop
Load frequency request on/off Load frequency control N level Real
power set point Maksimum power variation set point
Tipe
Jmh 1 1 1 1 1 1
KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi
diatas adalah rincian per bay
24
SPLN S5.001: 2008
TA-03: Konfigurasi umum pada single busbarTA-03
KONFIGURASI UMUM PADA SINGLE BUSBARBAY REAKTOR BAY GENERATOR
P Q V P Q I L/R L/R
LFC (Po,Pr,N)
Q
BUSBAR V
L/R
L/R
L/R
P Q P Q V IBAY TRANSMISI BAY TRAFO TENAGA
L/R P Q V IBAY IBT
25
SPLN S5.001: 2008
Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar
Group Bay Data No Kode Fungsi TM 1 F Frekuensi 29 COM Communication
alarm 46 PTF Protection faulty 47 PHA Peripheral alarm 51 RTUA RTU
alarm 52 SYNF Synchronizing failure TSS 65 VACF Vac failure 66 VDCF
Vdc failure 68 SIB Software interlocking bypass GARDU INDUK 69 IEDF
IED faulty 70 SOTF Switch on to fault 71 MTO Master Trip Operate 4
CD Control disable switch 5 CSO Check synchronizing override TSD 6
DCBC Dummy breaker closed/opened 13 LR Local remote 3 CSO Check
synchronizing override RCD 4 DCBC Dummy breaker closed/opened TM 7
V Tegangan 26 BF Bay fault DC 34 OVR Over voltage relay operate
BUSBAR TSS 35 P1BP Busbar protection 64 UVR Under voltage relay 67
VS Voltage status 26 BF Bay fault DC 27 BRF Breaker fault 28 CBTR
CB trip TSS 30 CSP Check synchronizing in progress 43 P2GFR Ground
fault relay 44 P2OCR Over current relay KOPEL 1 BI Bus isolator
switch 3 CB Circuit breaker closed/opened TSD 5 CSO Check
synchronizing override 13 LR Local remote 1 BI Bus isolator switch
RCD 2 CB Circuit breaker closed/opened BAY 2 I Arus TRANSMISI 3 P
Daya aktif TM 6 Q Daya reaktif 7 V Tegangan TSS 23 AR *) Circuit
breaker auto reclose 24 ARO *) Auto reclose on/off 26 BF Bay fault
DC 27 BRF Breaker fault 28 CBTR Circuit breaker trip 30 CSP Check
synchronizing in progress 36 P1CD Current differential 37 P1DEF
Directional earth fault 40 P1Z1 *) Distance zone 1
Tipe A A A A A A A A A A A I I I I
A A A A A A A A I A A I I I I
I I A A A I A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
26
SPLN S5.001: 2008
Group Bay
Data
TSD
RCD TC TM
TSS BAY IBT
TSD
RCD BAY TRAFO TENAGA
TM TSS
No 41 42 43 44 45 61 62 1 3 5 12 13 1 2 1 2 3 6 7 26 27 28 30 38
39 43 44 53 54 55 56 57 58 59 60 1 3 13 14 20 1 2 7 8 3 6 26 27 28
38
Kode P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT BI CB CSO LI LR
BI CB TPI I P Q V BF BRF CBTR CSP P1DIF P1REF P2GFR P2OCR TAF TCA
TCH TCL TEA TET TRA TRT BI CB LR LRT TCC BI CB TC TCC P Q BF BRF
CBTR P1DIF
Fungsi Distance zone 2 Distance zone 3 Ground fault relay Over
current relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Bus isolator switch Circuit breaker
closed/opened Check synchronizing override Line isolator switch
closed/opened Local remote Bus isolator switch Circuit breaker
closed/opened Tap position indication Arus Daya aktif Daya reaktif
Tegangan Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Differential Restricted earth fault
Ground fault relay Over current relay Tranformer avr failure Tap
changer alarm Tap changer high limit Tap changer low limit
Temperature alarm Temperature trip Transformer alarm Transformer
trip Bus isolator switch Circuit breaker closed/opened Local remote
Local/remote switch for tapchanger Tap changer auto/remote Bus
isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Daya aktif Daya reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential
Tipe A A A A A I I I I I I I
I
A A A I A A A A A A A A A A A A I I I I I
A A A A
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
27
SPLN S5.001: 2008
Group Bay
Data
TSD RCD TM
TSS BAY REAKTOR TSD RCD BAY GENERATOR TM
TSS
TSD
RCD
No 39 43 44 57 58 59 60 1 3 13 1 2 6 26 27 28 38 43 44 49 1 3 13
1 2 2 3 4 5 6 7 22 25 26 27 28 30 31 32 33 63 1 3 8 9 10 11 13 15
1
Kode P1REF P2GFR P2OCR TEA TET TRA TRT BI CB LR BI CB Q BF BRF
CBTR P1DIF P2GFR P2OCR RF BI CB LR BI CB I P POAQ PRAQ Q V AQR AVR
BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR PSO BI
Fungsi Restricted earth fault Ground fault relay Over current
relay Temperature alarm Temperature trip Transformer alarm
Transformer trip Bus isolator switch Circuit breaker closed/opened
Local remote Bus isolator switch Circuit breaker closed/opened Daya
Reaktif Bay fault DC Breaker fault Circuit breaker trip
Differential Ground fault relay Over current relay Reactor failure
Bus isolator switch Circuit breaker closed/opened Local remote Bus
isolator switch Circuit breaker closed/opened Arus Daya aktif Real
power setting Maksimum power variation setting Daya reaktif
Tegangan Automatic power factor regulator on/off Automatic voltage
regulator on/off Bay fault DC Breaker fault Circuit breaker trip
Check synchronizing in progress Free acting governor active
Generator transformer trip Load frequency control unit failure Unit
trip Bus isolator switch Circuit breaker closed/opened Generator
unit run/stop Load frequency control available Load frequency
control on/off switch Load frequency request on/off Local remote
Power set on/off switch Bus isolator switch
Tipe A A A A A A A I I I
A A A A A A A I I I
I I A A A I I A A A I I I I I I I I
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
28
SPLN S5.001: 2008
Group Bay
Data
RCA
No 2 5 6 1 2 3
Kode CB GUC LFR N POOP PROP
Fungsi Circuit breaker closed/opened Generator unit run/stop
Load frequency request on/off Load frequency control n level Real
power set point Maksimum power variation set point
Tipe
Jmh 1 1 1 1 1 1
KETERANGAN: *) = Khusus untuk OHL Feeder A = Alarm I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator. Rincian Teleinformasi
diatas adalah rincian per bay
29
SPLN S5.001: 2008
TB-01: Generator combined cycle pada konfigurasi 1
breakerGENERATOR COMBINED CYCLE PADA KONFIGURASI 1 BREAKERTB-01
LFC (Po,Pr,N)
Joint Control
P Q V
P Q V
P Q V
P Q V
P Q I
P Q I
P Q I
BUSBAR- A
BUSBAR- B
30
SPLN S5.001: 2008
Teleinformasi Data Untuk Generator Combined Cycle Pada
Konfigurasi 1 Breaker Data No 2 3 4 5 6 7 22 25 26 30 31 32 33 63 3
8 9 10 11 12 15 5 6 1 2 3 Kode I P POAQ PRAQ Q V AQR AVR BF CSP GOV
GTT LFF UT CB GUC LFA LFC LFR LI PSO GUC LFR N POOP PROP Fungsi
Arus Daya aktif Real power setting Maksimum power variation setting
Daya reaktif Tegangan Automatic power factor regulator on/off
Automatic voltage regulator on/off Bay fault DC Check synchronizing
in progress Free acting governor active Generator transformer trip
Load frequency control unit failure Unit trip Circuit breaker
closed/opened Generator unit run/stop Load frequency control
available Load frequency control on/off switch Load frequency
request on/off Line isolator switch closed/opened Power set on/off
switch Generator unit run/stop Load frequency request on/off Load
frequency control N level Real power set point Maksimum power
variation set point Tipe Jmh 3 7 1 1 7 4 4 4 3 3 4 3 1 4 2 4 1 1 1
3 4 4 1 1 1 1
TM
TSS
TSD
I I A I I A A A I I I I I I I
RCD RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
31
SPLN S5.001: 2008
TB-02: 2 generator terhubung ke MTR 3-belitan pada konfigurasi 1
breaker
TB-02
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN PADA KONFIGURASI 1
BREAKER
LFC (Po,Pr,N) P Q V P Q V
LFC (Po,Pr,N)
P Q IBUSBAR - A
BUSBAR - B
32
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan
Pada Konfigurasi 1 Breaker Data No 2 3 4 5 6 7 22 25 26 30 31 32 33
63 3 8 9 10 11 12 15 5 6 1 2 3 Kode I P POAQ PRAQ Q V AQR AVR BF
CSP GOV GTT LFF UT CB GUC LFA LFC LFR LI PSO GUC LFR N POOP PROP
Fungsi Arus Daya aktif Real power setting Maksimum power variation
setting Daya reaktif Tegangan Automatic power factor regulator
on/off Automatic voltage regulator on/off Bay fault DC Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip
Circuit breaker closed/opened Generator unit run/stop Load
frequency control available Load frequency control on/off switch
Load frequency request on/off Line isolator switch closed/opened
Power set on/off switch Generator unit run/stop Load frequency
request on/off Load frequency control N level Real power set point
Maksimum power variation set point Tipe Jmh 1 3 1 1 3 2 2 2 1 1 2 1
2 2 2 2 2 2 2 1 2 2 2 2 2 2
TM
TSS
TSD
I I A I I A A A I I I I I I I
RCD RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
33
SPLN S5.001: 2008
TB-03: 2 generator terhubung ke MTR 3-belitan pada konfigurasi
double busbar
TB-03
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN PADA KONFIGURASI DOUBLE
BUSBAR
LFC (Po,Pr,N) P Q V P Q V
LFC (Po,Pr,N)
P Q I L/R
BUSBAR - A
BUSBAR - B
34
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan
Pada Konfigurasi Double Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 12 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 3 1 1 3 2 2 2 1 1 1 1 2 1 2 2 2 3 2
2 2 2 1 2 2 1 2 2 2 2 2
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
35
SPLN S5.001: 2008
TB-04: 2 generator terhubung ke MTR 3-belitan pada konfigurasi
single busbar
TB-04
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN PADA KONFIGURASI SINGLE
BUSBAR
LFC (Po,Pr,N) P Q V P Q V
LFC (Po,Pr,N)
P Q I L/R
BUSBAR
36
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan
Pada Konfigurasi Single Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 13 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 3 1 1 3 2 2 2 1 1 1 1 2 1 2 2 1 3 2
2 2 2 1 2 1 1 2 2 2 2 2
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
37
SPLN S5.001: 2008
TB-05: 1 generator terhubung ke MTR 2-belitan pada konfigurasi 1
breaker
TB-05
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN PADA KONFIGURASI 1
BREAKER
P Q V
LFC (Po,Pr,N)
P Q IBUSBAR - A
BUSBAR - B
38
SPLN S5.001: 2008
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi 1 Breaker Data No 2 3 4 5 6 7 22 25 26 30 31 32 33
63 8 9 10 11 12 15 5 6 1 2 3 Kode I P POAQ PRAQ Q V AQR AVR BF CSP
GOV GTT LFF UT GUC LFA LFC LFR LI PSO GUC LFR N POOP PROP Fungsi
Arus Daya aktif Real power setting Maksimum power variation setting
Daya reaktif Tegangan Automatic power factor regulator on/off
Automatic voltage regulator on/off Bay fault DC Check synchronizing
in progress Free acting governor active Generator transformer trip
Load frequency control unit failure Unit trip Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Line isolator switch
closed/opened Power set on/off switch Generator unit run/stop Load
frequency request on/off Load frequency control n level Real power
set point Maksimum power variation set point Tipe Jmh 1 2 1 1 2 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
TSD
I I A I I A A A I I I I I I
RCD RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
39
SPLN S5.001: 2008
TB-06: 1 generator terhubung ke MTR 2-belitan pada konfigurasi
double busbar
TB-06
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN PADA KONFIGURASI DOUBLE
BUSBAR
P Q V P Q I L/R
LFC (Po,Pr,N)
BUSBAR - A
BUSBAR - B
40
SPLN S5.001: 2008
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi Double Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 13 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 2 1 1
1 1 1 1 1 2 1 1 1 1 1 1
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
41
SPLN S5.001: 2008
TB-07: 1 generator terhubung ke MTR 2-belitan pada konfigurasi
single busbar
TB-07
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN PADA KONFIGURASI SINGLE
BUSBAR
P Q V P Q I L/R
LFC (Po,Pr,N)
BUSBAR
42
SPLN S5.001: 2008
Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi Single Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 13 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
43
SPLN S5.001: 2008
TB-08: 2 generator terhubung ke MTR 2-belitan pada konfigurasi 1
breaker
44
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi 1 Breaker Data No 2 3 4 5 6 7 22 25 26 30 31 32 33
63 3 8 9 10 11 12 15 5 6 1 2 3 Kode I P POAQ PRAQ Q V AQR AVR BF
CSP GOV GTT LFF UT CB GUC LFA LFC LFR LI PSO GUC LFR N POOP PROP
Fungsi Arus Daya aktif Real power setting Maksimum power variation
setting Daya reaktif Tegangan Automatic power factor regulator
on/off Automatic voltage regulator on/off Bay fault DC Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip
Circuit breaker closed/opened Generator unit run/stop Load
frequency control available Load frequency control on/off switch
Load frequency request on/off Line isolator switch closed/opened
Power set on/off switch Generator unit run/stop Load frequency
request on/off Load frequency control n level Real power set point
Maksimum power variation set point Tipe Jmh 1 2 1 1 2 1 2 2 1 1 2 1
2 2 2 2 2 2 2 1 2 2 2 2 2 2
TM
TSS
TSD
I I A I I A A A I I I I I I I
RCD RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
45
SPLN S5.001: 2008
TB-09: 2 generator terhubung ke MTR 2-belitan pada konfigurasi
double busbar
TB-09
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN PADA KONFIGURASI DOUBLE
BUSBAR
LFC (Po,Pr,N) P Q V
LFC (Po,Pr,N)
P Q I L/R
BUSBAR - A
BUSBAR - B
46
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi Double Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 13 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 2 1 1 2 1 2 2 1 1 1 1 2 1 2 2 2 3 2
2 2 2 1 2 2 1 2 2 2 2 2
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
47
SPLN S5.001: 2008
TB-10: 2 generator terhubung ke MTR 2-belitan pada konfigurasi
single busbar
TB-10
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN PADA KONFIGURASI SINGLE
BUSBAR
LFC (Po,Pr,N) P Q V P Q I
LFC (Po,Pr,N)
L/R
BUSBAR
48
SPLN S5.001: 2008
Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan
Pada Konfigurasi Single Busbar Data No 2 3 4 5 6 7 22 25 26 27 28
30 31 32 33 63 1 3 8 9 10 11 13 15 1 2 5 6 1 2 3 Kode I P POAQ PRAQ
Q V AQR AVR BF BRF CBTR CSP GOV GTT LFF UT BI CB GUC LFA LFC LFR LR
PSO BI CB GUC LFR N POOP PROP Fungsi Arus Daya aktif Real power
setting Maksimum power variation setting Daya reaktif Tegangan
Automatic power factor regulator on/off Automatic voltage regulator
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Free acting governor active Generator
transformer trip Load frequency control unit failure Unit trip Bus
isolator switch Circuit breaker closed/opened Generator unit
run/stop Load frequency control available Load frequency control
on/off switch Load frequency request on/off Local remote Power set
on/off switch Bus isolator switch Circuit breaker closed/opened
Generator unit run/stop Load frequency request on/off Load
frequency control n level Real power set point Maksimum power
variation set point Tipe Jmh 1 2 1 1 2 1 2 2 1 1 1 1 2 1 2 2 1 3 2
2 2 2 1 2 1 1 2 2 2 2 2
TM
TSS
TSD
I I A A A I I A A A I I I I I I I I
RCD
RCA
KETERANGAN: Untuk LFC ditampilkan di tabel LFC Generator.
49
SPLN S5.001: 2008
TB-11: Interbus transformer (secondary side connected to 1
breaker)
INTERBUS TRANSFORMER Secondary Side Connected to 1 BreakerBUSBAR
(IRCC)
TB-11
L/R
BUSBAR - A
P Q V I
Dioperasikan dari IRCC
Dioperasikan dari RCC
Download to RCC
BUSBAR - B
50
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to 1 Breaker) Data TC TM No 1 2 3 6 7 26 30 38 39 43 44
53 54 55 56 57 58 59 60 12 13 14 20 7 8 Kode TPI I P Q V BF CSP
P1DIF P1REF P2GFR P2OCR TAF TCA TCH TCL TEA TET TRA TRT LI LR LRT
TCC TC TCC Fungsi Tap position indication Arus Daya aktif Daya
reaktif Tegangan Bay fault DC Check synchronizing in progress
Differential Restricted earth fault Ground fault relay Over current
relay Tranformer avr failure Tap changer alarm Tap changer high
limit Tap changer low limit Temperature alarm Temperature trip
Transformer alarm Transformer trip Line isolator switch
closed/opened Local remote Local/remote switch for tapchanger Tap
changer auto/remote Tap changer raise/lower Tap changer auto/manual
Tipe I Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
TSS
TSD
A I A A A A A A A A A A A A I I I I
RCD
51
SPLN S5.001: 2008
TB-12: Interbus transformer (secondary side connected to double
busbar)
INTERBUS TRANSFORMER Secondary Side Connected to Double
BusbarBUSBAR (IRCC or RCC)
TB-12
L/R
P Q V I
Operation Responsibility by IRCC or RCC
L/R
Operation Responsibility by RCC
Download to RCC
BUSBAR - A
BUSBAR - B
52
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to Double Busbar) Data TC TM No 1 2 3 6 7 26 27 28 30 38
39 43 44 53 54 55 56 57 58 59 60 1 3 12 13 14 20 1 2 7 8 Kode TPI I
P Q V BF BRF CBTR CSP P1DIF P1REF P2GFR P2OCR TAF TCA TCH TCL TEA
TET TRA TRT BI CB LI LR LRT TCC BI CB TC TCC Fungsi Tap position
indication Arus Daya aktif Daya reaktif Tegangan Bay fault DC
Breaker fault Circuit breaker trip Check synchronizing in progress
Differential Restricted earth fault Ground fault relay Over current
relay Tranformer avr failure Tap changer alarm Tap changer high
limit Tap changer low limit Temperature alarm Temperature trip
Transformer alarm Transformer trip Bus isolator switch Circuit
breaker closed/opened Line isolator switch closed/opened Local
remote Local/remote switch for tapchanger Tap changer auto/remote
Bus isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Tipe I Jmh 1 1 1 1 1 1 1-2 *)
1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 2-4 *) 1-2 *) 1-0 *) 1-2 *) 1 1
2-4 *) 1-2 *) 1 1
TSS
TSD
A A A I A A A A A A A A A A A A I I I I I I
RCD
KETERANGAN: *) = (Primary Side Connected to 1 Breaker)(Primary
Side Connected to Double Busbar)
53
SPLN S5.001: 2008
TB-13: Interbus transformer (secondary side connected to single
busbar)
TB-13
INTERBUS TRANSFORMER Secondary Side Connected to Single
BusbarBUSBAR (IRCC or RCC)
L/R
P Q V IOperation Responsibility by IRCC or RCC
L/R
Operation Responsibility by RCC
Download to RCC
BUSBAR
54
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to Single Busbar) Data TC TM No 1 2 3 6 7 26 27 28 30 38
39 43 44 53 54 55 56 57 58 59 60 1 3 12 13 14 20 1 2 7 8 Kode TPI I
P Q V BF BRF CBTR CSP P1DIF P1REF P2GFR P2OCR TAF TCA TCH TCL TEA
TET TRA TRT BI CB LI LR LRT TCC BI CB TC TCC Fungsi Tap position
indication Arus Daya aktif Daya reaktif Tegangan Bay fault DC
Breaker fault Circuit breaker trip Check synchronizing in progress
Differential Restricted earth fault Ground fault relay Over current
relay Tranformer avr failure Tap changer alarm Tap changer high
limit Tap changer low limit Temperature alarm Temperature trip
Transformer alarm Transformer trip Bus isolator switch Circuit
breaker closed/opened Line isolator switch closed/opened Local
remote Local/remote switch for tapchanger Tap changer auto/remote
Bus isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Tipe I Jmh 1 1 1 1 1 1 1-2 *)
1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1-3 *) 1-2 *) 1-0 *) 1-2 *) 1 1
1-3 *) 1-2 *) 1 1
TSS
TSD
A A A I A A A A A A A A A A A A I I I I I I
RCD
KETERANGAN: *) = (Primary Side Connected to 1 Breaker)(Primary
Side Connected to Double Busbar)
55
SPLN S5.001: 2008
TB-14: Interbus transformer (secondary side connected to 1
breaker dilengkapi shunt reaktor pada kumparan tersier)
56
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to 1 Breaker Dilengkapi Shunt Reaktor Pada Kumparan
Tersier) Data TC TM No 1 2 3 6 7 26 30 38 39 43 44 53 54 55 56 57
58 59 60 12 13 14 20 7 8 Kode TPI I P Q V BF CSP P1DIF P1REF P2GFR
P2OCR TAF TCA TCH TCL TEA TET TRA TRT LI LR LRT TCC TC TCC Fungsi
Tap position indication Arus Daya aktif Daya reaktif Tegangan Bay
fault DC Check synchronizing in progress Differential Restricted
earth fault Ground fault relay Over current relay Tranformer avr
failure Tap changer alarm Tap changer high limit Tap changer low
limit Temperature alarm Temperature trip Transformer alarm
Transformer trip Line isolator switch closed/opened Local remote
Local/remote switch for tapchanger Tap changer auto/remote Tap
changer raise/lower Tap changer auto/manual Tipe I Jmh 1 1 1 2 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1
TSS
TSD
A I A A A A A A A A A A A A I I I I
RCD
57
SPLN S5.001: 2008
TB-15: Interbus transformer (secondary side connected to double
busbar dilengkapi shunt reaktor pada kumparan tersier)
58
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan
Tersier) Data TC TM No 1 2 3 6 7 26 27 28 30 38 39 43 44 53 54 55
56 57 58 59 60 1 3 12 13 14 20 1 2 7 8 Kode TPI I P Q V BF BRF CBTR
CSP P1DIF P1REF P2GFR P2OCR TAF TCA TCH TCL TEA TET TRA TRT BI CB
LI LR LRT TCC BI CB TC TCC Fungsi Tap position indication Arus Daya
aktif Daya reaktif Tegangan Bay fault DC Breaker fault Circuit
breaker trip Check synchronizing in progress Differential
Restricted earth fault Ground fault relay Over current relay
Tranformer avr failure Tap changer alarm Tap changer high limit Tap
changer low limit Temperature alarm Temperature trip Transformer
alarm Transformer trip Bus isolator switch Circuit breaker
closed/opened Line isolator switch closed/opened Local remote
Local/remote switch for tapchanger Tap changer auto/remote Bus
isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Tipe I Jmh 1 1 1 2 1 1 1-2 *)
1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 2-4 *) 1-2 *) 2-1 *) 1-2 *) 1 1 *)
2-4 1-2 *) 1 1
TSS
TSD
A A A I A A A A A A A A A A A A I I I I I I
RCD
KETERANGAN: *) = (Primary Side Connected to 1 Breaker)(Primary
Side Connected to Double Busbar)
59
SPLN S5.001: 2008
TB-16: Interbus transformer (secondary side connected to single
busbar dilengkapi shunt reaktor pada kumparan tersier)
INTERBUS TRANSFORMER Secondary Side Connected to Single Busbar
Dilengkapi Shunt Reaktor Pada Kumparan TersierBUSBAR (IRCC or
RCC)
TB-16
L/R
Q
P Q V IOperation Responsibility by IRCC or RCC
L/R
Operation Responsibility by RCC
Download to RCC
BUSBAR
60
SPLN S5.001: 2008
Teleinformasi Data Untuk Interbus Transformer (Secondary Side
Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan
Tersier) Data TC TM No 1 2 3 6 7 26 27 28 30 38 39 43 44 53 54 55
56 57 58 59 60 1 3 12 13 14 20 1 2 7 8 Kode TPI I P Q V BF BRF CBTR
CSP P1DIF P1REF P2GFR P2OCR TAF TCA TCH TCL TEA TET TRA TRT BI CB
LI LR LRT TCC BI CB TC TCC Fungsi Tap position indication Arus Daya
aktif Daya reaktif Tegangan Bay fault DC Breaker fault Circuit
breaker trip Check synchronizing in progress Differential
Restricted earth fault Ground fault relay Over current relay
Tranformer avr failure Tap changer alarm Tap changer high limit Tap
changer low limit Temperature alarm Temperature trip Transformer
alarm Transformer trip Bus isolator switch Circuit breaker
closed/opened Line isolator switch closed/opened Local remote
Local/remote switch for tapchanger Tap changer auto/remote Bus
isolator switch Circuit breaker closed/opened Tap changer
raise/lower Tap changer auto/manual Tipe I Jmh 1 1 1 2 1 1 1-2 *)
1-2 *) 1 1 1 1 1 1 1 1 1 1 1 1 1 1-3 *) 1-2 *) 2-1 *) 1-2 *) 1 1 *)
1-3 1-2 *) 1 1
TSS
TSD
A A A I A A A A A A A A A A A A I I I I I I
RCD
KETERANGAN: *) = (Primary Side Connected to 1 Breaker)(Primary
Side Connected to Double Busbar)
61
SPLN S5.001: 2008
TB-17: Bay trafo tenaga pada konfigurasi 1 breaker
62
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1
Breaker Data TM No 3 6 26 38 39 43 44 57 58 59 60 12 Kode P Q BF
P1DIF P1REF P2GFR P2OCR TEA TET TRA TRT LI Fungsi Daya aktif Daya
reaktif Bay fault DC Differential Restricted earth fault Ground
fault relay Over current relay Temperature alarm Temperature trip
Transformer alarm Transformer trip Line isolator switch
closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1
TSS
TSD
A A A A A A A A A I
63
SPLN S5.001: 2008
TB-18: Bay trafo tenaga pada konfigurasi double busbar BAY TRAFO
TENAGA PADA KONFIGURASI DOUBLE BUSBARBUSBAR - A TB-18
BUSBAR - B
L/R P Q
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
64
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi
Double Busbar Data TM No 3 6 26 27 28 38 39 43 44 57 58 59 60 1 3
13 1 2 Kode P Q BF BRF CBTR P1DIF P1REF P2GFR P2OCR TEA TET TRA TRT
BI CB LR BI CB Fungsi Daya aktif Daya reaktif bay fault DC breaker
fault circuit breaker trip Differential restricted earth fault
ground fault relay over current relay temperature alarm temperature
trip transformer alarm transformer trip bus isolator switch circuit
breaker closed/opened local remote Bus isolator switch Circuit
breaker closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2
1
TSS
TSD RCD
A A A A A A A A A A A I I I
65
SPLN S5.001: 2008
TB-19: Bay trafo tenaga pada konfigurasi single busbar BAY TRAFO
TENAGA PADA KONFIGURASI SINGLE BUSBARBUSBAR TB-19
L/R P Q
TEGANGAN TINGGI
Batas wewenang
TEGANGAN MENENGAH
DOUBLE BUSBAR
66
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi
Single Busbar Data TM No 3 6 26 27 28 38 39 43 44 57 58 59 60 1 3
13 1 2 Kode P Q BF BRF CBTR P1DIF P1REF P2GFR P2OCR TEA TET TRA TRT
BI CB LR BI CB Fungsi Daya aktif Daya reaktif Bay fault DC Breaker
fault Circuit breaker trip Differential Restricted earth fault
Ground fault relay Over current relay Temperature alarm Temperature
trip Transformer alarm Transformer trip Bus isolator switch Circuit
breaker closed/opened Local remote Bus isolator switch Circuit
breaker closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
TSS
TSD RCD
A A A A A A A A A A A I I I
67
SPLN S5.001: 2008
TB-20: Bay reaktor pada konfigurasi 1 breaker
TB-20
BAY REAKTOR PADA KONFIGURASI 1 BREAKERBUSBAR - A
BUSBAR - B
Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 Breaker
Data TM No 6 26 38 43 44 49 12 Kode Q BF P1DIF P2GFR P2OCR RF LI
Fungsi Daya Reaktif Bay fault DC Differential Ground fault relay
Over current relay Reactor failure Line isolator switch
closed/opened Tipe A A A A A I Jmh 1 1 1 1 1 1 1
TSS
TSD
68
SPLN S5.001: 2008
TB-21: Bay reaktor pada konfigurasi double busbar
BAY REAKTOR PADA KONFIGURASI DOUBLE BUSBAR
TB-21
BUSBAR - A
BUSBAR - B
L/R Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double
Busbar Data TM No 6 26 27 28 38 43 44 49 1 3 13 1 2 Kode Q BF BRF
CBTR P1DIF P2GFR P2OCR RF BI CB LR BI CB Fungsi Daya Reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential Ground
fault relay Over current relay Reactor failure Bus isolator switch
Circuit breaker closed/opened Local remote Bus isolator switch
Circuit breaker closed/opened Tipe A A A A A A A I I I Jmh 1 1 1 1
1 1 1 1 2 1 1 2 1
TSS
TSD RCD
69
SPLN S5.001: 2008
TB-22: Bay reaktor pada konfigurasi single busbar
BAY REAKTOR PADA KONFIGURASI SINGLE BUSBARBUSBAR
TB-22
L/R
Q
Reaktor
Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single
Busbar Data TM No 6 26 27 28 38 43 44 49 1 3 13 1 2 Kode Q BF BRF
CBTR P1DIF P2GFR P2OCR RF BI CB LR BI CB Fungsi Daya Reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential Ground
fault relay Over current relay Reactor failure Bus isolator switch
Circuit breaker closed/opened Local remote Bus isolator switch
Circuit breaker closed/opened Tipe A A A A A A A I I I Jmh 1 1 1 1
1 1 1 1 1 1 1 1 1
TSS
TSD RCD
70
SPLN S5.001: 2008
TB-23: Bay capasitor pada konfigurasi double busbar
BAY KAPASITOR PADA KONFIGURASI DOUBLE BUSBAR
TB-23
BUSBAR - A
BUSBAR - B
L/R Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double
Busbar Data TM No 6 26 27 28 38 43 44 1 2 3 13 1 2 Kode Q BF BRF
CBTR P1DIF P2GFR P2OCR BI CAM CB LR BI CB Fungsi Daya Reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential Ground
fault relay Over current relay Bus isolator switchCapasitor
Auto/Manual
Tipe A A A A A A I I I I
TSS
TSD
RCD
Circuit breaker closed/opened Local remote Bus isolator switch
Circuit breaker closed/opened
Jmh 1 1 1 1 1 1 1 2 1 1 1 2 1
71
SPLN S5.001: 2008
TB-24: Bay capasitor pada konfigurasi single busbar
BAY KAPASITOR PADA KONFIGURASI SINGLE BUSBARBUSBAR
TB-24
L/R
Q
Capasitor
Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single
Busbar Data TM No 6 26 27 28 38 43 44 1 2 3 13 1 2 Kode Q BF BRF
CBTR P1DIF P2GFR P2OCR BI CAM CB LR BI CB Fungsi Daya Reaktif Bay
fault DC Breaker fault Circuit breaker trip Differential Ground
fault relay Over current relay Bus isolator switchCapasitor
Auto/Manual
Tipe A A A A A A I I I I
TSS
TSD
RCD
Circuit breaker closed/opened Local remote Bus isolator switch
Circuit breaker closed/opened
Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1
72
SPLN S5.001: 2008
TB-25: Bay penghantar pada konfigurasi 1 breaker BAY PENGHANTAR
PADA KONFIGURASI 1 BREAKERBUSBAR - A TB-25
BUSBAR - B
P Q V I
73
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1
Breaker Data TM No 2 3 6 7 23 24 26 30 36 37 40 41 42 43 44 45 61
62 12 Kode I P Q V AR *) ARO *) BF CSP P1CD P1DEF *) P1Z1 P1Z2 *)
P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT LI Fungsi Arus Daya aktif Daya
reaktif Tegangan Circuit breaker auto reclose Auto reclose on/off
Bay fault DC Check synchronizing in progress Current differential
Directional earth fault Distance zone 1 Distance zone 2 Distance
zone 3 Ground fault relay Over current relay Direct transfer trip
Teleprotection trip receive Teleprotection trip transmit Line
isolator switch closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1
TSS
TSD
I I A I A A A A A A A A I I I
KETERANGAN: *) =
Khusus untuk OHL Feeder
74
SPLN S5.001: 2008
TB-26: Bay penghantar pada konfigurasi double busbar BAY
PENGHANTAR PADA KONFIGURASI DOUBLE BUSBARTB-26
BUSBAR - A
BUSBAR - B
L/R P Q V I
75
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double
Busbar Data TM No 2 3 6 7 23 24 26 27 28 30 36 37 40 41 42 43 44 45
61 62 1 3 5 12 13 1 2 Kode I P Q V AR *) ARO *) BF BRF CBTR CSP
P1CD P1DEF P1Z1 *) P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT BI
CB CSO LI LR BI CB Fungsi Arus Daya aktif Daya reaktif Tegangan
Circuit breaker auto reclose Auto reclose on/off Bay fault DC
Breaker fault Circuit breaker trip Check synchronizing in progress
Current differential Directional earth fault Distance zone 1
Distance zone 2 Distance zone 3 Ground fault relay Over current
relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Bus isolator switch Circuit breaker
closed/opened Check synchronizing override Line isolator switch
closed/opened Local remote Bus isolator switch Circuit breaker
closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1
1 1 1 2 1
TSS
TSD
I I A A A I A A A A A A A A I I I I I I I
RCD
KETERANGAN: *) =
Khusus untuk OHL Feeder
76
SPLN S5.001: 2008
TB-27: Bay penghantar pada konfigurasi single busbar
77
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single
Busbar Data TM No 2 3 6 7 23 24 26 27 28 30 36 37 40 41 42 43 44 45
61 62 1 3 5 12 13 1 2 Kode I P Q V AR *) ARO *) BF BRF CBTR CSP
P1CD P1DEF P1Z1 *) P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT BI
CB CSO LI LR BI CB Fungsi Arus Daya aktif Daya reaktif Tegangan
Circuit breaker auto reclose Auto reclose on/off Bay fault DC
Breaker fault Circuit breaker trip Check synchronizing in progress
Current differential Directional earth fault Distance zone 1
Distance zone 2 Distance zone 3 Ground fault relay Over current
relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Bus isolator switch Circuit breaker
closed/opened Check synchronizing override Line isolator switch
closed/opened Local remote Bus isolator switch Circuit breaker
closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1
TSS
TSD
I I A A A I A A A A A A A A I I I I I I I
RCD
KETERANGAN: *) =
Khusus untuk OHL Feeder
78
SPLN S5.001: 2008
TB-28: Bay penghantar paralel dengan reaktor pada konfigurasi
double busbar BAY PENGHANTAR PARALEL DENGAN REAKTOR PADA
KONFIGURASI DOUBLE BUSBARBUSBAR - A TB-28
BUSBAR - B
L/R P Q V I
Q
79
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor
Pada Konfigurasi Double Busbar Data TM No 2 3 6 7 23 24 26 27 28 30
36 37 40 41 42 43 44 45 61 62 1 3 5 12 13 1 2 Kode I P Q V AR *)
ARO *) BF BRF CBTR CSP P1CD P1DEF P1Z1 *) P1Z2 *) P1Z3 *) P2GFR
P2OCR P3DTT*) TTR TTT BI CB CSO LI LR BI CB Fungsi Arus Daya aktif
Daya reaktif Tegangan Circuit breaker auto reclose Auto reclose
on/off Bay fault DC Breaker fault Circuit breaker trip Check
synchronizing in progress Current differential Directional earth
fault Distance zone 1 Distance zone 2 Distance zone 3 Ground fault
relay Over current relay Direct transfer trip Teleprotection trip
receive Teleprotection trip transmit Bus isolator switch Circuit
breaker closed/opened Check synchronizing override Line isolator
switch closed/opened Local remote Bus isolator switch Circuit
breaker closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 2 1 1 2 1 2 1
TSS
TSD
I I A A A I A A A A A A A A I I I I I I I
RCD
KETERANGAN: *) =
Khusus untuk OHL Feeder
80
SPLN S5.001: 2008
TB-29: Bay penghantar paralel dengan 1 reaktor pada konfigurasi
1 breaker BAY PENGHANTAR PARALEL DENGAN 1 REAKTOR PADA KONFIGURASI
1 BREAKERBUSBAR - A TB-29
BUSBAR - B
Q L/R
P Q V I
81
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor
Pada Konfigurasi 1 Breaker Data TM No 2 3 6 7 23 24 26 27 28 30 36
37 40 41 42 43 44 45 61 62 3 12 13 2 Kode I P Q V AR *) ARO *) BF
BRF CBTR CSP P1CD P1DEF P1Z1 *) P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*)
TTR TTT CB LI LR CB Fungsi Arus Daya aktif Daya reaktif Tegangan
Circuit breaker auto reclose Auto reclose on/off Bay fault DC
Breaker fault Circuit breaker trip Check synchronizing in progress
Current differential Directional earth fault Distance zone 1
Distance zone 2 Distance zone 3 Ground fault relay Over current
relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Circuit breaker closed/opened Line
isolator switch closed/opened Local remote Circuit breaker
closed/opened Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
1 1
TSS
TSD RCD*)
I I A A A I A A A A A A A A I I I I I
KETERANGAN: *) =
Khusus untuk OHL Feeder
82
SPLN S5.001: 2008
TB-30: Bay penghantar paralel dengan 2 reaktor seri pada
konfigurasi 1 breaker BAY PENGHANTAR PARALEL DENGAN 2 REAKTOR SERI
PADA KONFIGURASI 1 BREAKERBUSBAR- A TB-30
BUSBAR- B Q Q P Q V I
83
SPLN S5.001: 2008
Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor
seri Pada Konfigurasi 1 Breaker Data TM No 2 3 6 7 23 24 26 30 36
37 40 41 42 43 44 45 61 62 12 Kode I P Q V AR *) ARO *) BF CSP P1CD
P1DEF P1Z1 *) P1Z2 *) P1Z3 *) P2GFR P2OCR P3DTT*) TTR TTT LI Fungsi
Arus Daya aktif Daya reaktif Tegangan Circuit breaker auto reclose
Auto reclose on/off Bay fault DC Check synchronizing in progress
Current differential Directional earth fault Distance zone 1
Distance zone 2 Distance zone 3 Ground fault relay Over current
relay Direct transfer trip Teleprotection trip receive
Teleprotection trip transmit Line isolator switch closed/opened
Tipe Jmh 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2
TSS
TSD
I I A I A A A A A A A A I I I
KETERANGAN: *) =
Khusus untuk OHL Feeder
84
SPLN S5.001: 2008
TB-31: Bay kopel pada konfigurasi double busbar
BAY KOPEL PADA KONFIGURASI DOUBLE BUSBAR
TB-31
L/R
IBUSBAR - A
BUSBAR - B
Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double
Busbar Data TM No 1 26 27 28 30 43 44 1 3 5 13 1 2 Kode I BF BRF
CBTR CSP P2GFR P2OCR BI CB CSO LR BI CB Fungsi Arus Bay fault DC
Breaker fault CB trip Check synchronizing in progress Ground fault
relay Over current relay Bus isolator switch Circuit breaker
closed/opened Check synchronizing override Local re