Top Banner
Optimum Operasi dan Keandalan Sistem Tenaga Listrik Oleh : Prof. Ontoseno Penangsang, Ph.D Dr. Eng. Rony Seto Wibowo Laboratorium Simulasi Sistem Tenaga Listrik Teknik Elektro – ITS Surabaya
38

Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Dec 28, 2015

Download

Documents

wahyudwi14
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Optimum Operasi dan KeandalanSistem Tenaga Listrik

Oleh :Prof. Ontoseno Penangsang, Ph.D

Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya

Page 2: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Contents

• Basic Probability Theory• Application of Binomial Distribution• Generation System Reliability Analysis• Transmission System Reliability Analysis• Distribution System Reliability Analysis

Page 3: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

DAFTAR PUSTAKA

• Roy Billinton, Ronald N Allan, “Reliability Evaluation of Engineering Systems” Plenum Press : New York, 1992

• Roy Billinton, Ronald N Allan, “Reliability Evaluation of Power Systems” Plenum Press : New York, 1996

• Robert L. Sullivan, “Power System Planning”, McGraw-Hill, 1977

Page 4: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Basic Probability Theory

Oleh :Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya

Page 5: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Probability Concept

• Mathematically, it is a numerical index that can vary between zero to unity

• Probability of success and failure can formulated as follows:

Page 6: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• Anggap kita melempar dua buah dadusekaligus, berapa peluang kita mendapatkanangka total dadu 9?

Page 7: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Permutations and Combinations

• The number of permutations of n different items is the number of ways these items can be arranged

• The number of combinations of n different items is the number of different selections of r items, each without regard to the order or arrangement of the items in the groups

Page 8: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• Anggap kita mempunyai 3 buah buku dengannama A, B dan C. Berapa kemungkinan kitamenyusun ketiga buku tersebut?

• Berapa kemungkinan komposisi panitia yang terdiri dari 3 orang, dimana jumlah orang yang akan kita pilih adalah 4 orang?

Page 9: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Rules for Combining Probabilities

• Rule 1 – Independent events• Rule 2 – Mutually exclusive events• Rule 3 – Complementary events• Rule 4 – Conditional events• Rule 5 – Simultaneous occurrence of events• Rule 6 – Occurrence of at least one if two

events• Rule 7 – Application of conditional probability

Page 10: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• Suatu pabrik mempunyai 2 plant. Plant 1 membuat 70% barang yang dibutuhkan danplant lainnya menghasilkan 30%. Jika 90 % produk plant 1 memenuhi standard dan 80% produk plant 2 memenuhi standard. Berapapeluang pabrik tersebut menghasilkan produkyang memenuhi standard?

Page 11: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Probability Density Function• The summation of

probabilities should equal unity

• Probability density Function (a) Separate data (b) Grouped data

Page 12: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Probability Distributions Function

• PDF is obtained by summating the density function (numerically, integrating)

• Discrete random variable : (a) Separate data (b) Grouped data

Page 13: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Probability Distributions

• Continuous random variable : (a) Probability distribution function f(x) (b) Probability density function F(x)

Page 14: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Mathematical Expectation

• Moments of distribution, also known as expected value, is referred to as the average value or population mean

Page 15: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• The data of copper length measurement are as follows :

5,97 5,97 5,98 5,98 5,98 5,99 5,99 5,99 5,99 5,99 6 6 6 6 6 6,01 6,01 6,02 6,02 6,02

• Determine the average length of the copper?

Page 16: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Variance and Standard Deviation

• A measure of dispersion of a distribution is defined as Variance V(x)

• Standard deviation

Page 17: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• The data of copper length measurement are as follows :

5,97 5,97 5,98 5,98 5,98 5,99 5,99 5,99 5,99 5,99 6 6 6 6 6 6,01 6,01 6,02 6,02 6,02

• Determine the variance and standard deviation?

Page 18: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Application of the Binomial Distribution

Oleh :Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya

Page 19: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

General Characteristic

• Binomial distribution can be represented by general expression :

(p+q)2

• Required conditions are :– Fixed number of trial– Two possible outcomes : success ad failure– Probabilities of success and failure are remain

constant– All trial must be independent

Page 20: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

Page 21: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Binomial Coefficients

• One essential aspect of the binomial distribution is to evaluate nCr

11 1

1 2 11 3 3 1

1 4 6 4 1

Page 22: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Expected value

• Expected value of binomial distribution can be expressed as follows:

• Finally,E(x) = np

Page 23: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Example

• A small generating plant is to be designed to satisfy a constant 10 MW load. Four alternatives are being considered:1. 1 x 10 MW unit2. 2 x 10 MW unit3. 3 x 5 MW unit4. 4 x 3 1/3 MW unitUnavailable probability of each unit is equal to0.02 and therefore, the probability of available is0.98. Please develop capacity outage probabilitytables.

Page 24: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Capacity Outage Probability

Page 25: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Expected Load Losses

Page 26: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Investment Costs of Plant

Page 27: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Expected Load Curtailment

Page 28: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Effect of Unavailability

Page 29: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

System Risk with One Unit in Reserve

Page 30: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik
Page 31: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Generation System Reliability Analysis

Oleh :Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya

Page 32: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Introduction

• Generation system planning is one of the crucial steps in modern electric utility.

• Generation expansion plan must satisfy customer needs for reasonably price, reliable and quality.

• The electricity industry is a very capital intensive industry

• Expansion plan should attract new investors

Page 33: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Expansion Plan Consideration

• Uncertainty of load in the future• Unit reliability and maintenance schedules• Fuel Costs• Environment Issues• Construction Costs• Construction Times• Financial Support

Page 34: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Reliability Indices

Reliability indices mostly used in generation system expansion are :

• Loss of Load Probability (LOLP)• Expected Value of Demand not served (DNS)• Frequency and Duration (FD)

Page 35: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Practical Generation Planning

In Practical, the considerations are :• Load Growth• Construction Time• Availability of Sites• Availability of Fuelthen, detailed reliability analysis is required to ensure that all satisfying the desired reliability level

Page 36: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Probabilistic Generating Unit Models

Mainly, generation systems consist of many type of generators. They can be categorized as the following :• Based Load units. Capacity factor : 90 – 95 %.

Nuclear, Coal Steam Turbine units• Midrange units. Capacity factor : 30 – 75 %.

Combine Cycle units, Steam Turbine Units• Peakers. Capacity factor : 5 – 10 %. Gas

turbines and Hydro units

Page 37: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Transmission System Reliability Analysis

Oleh :Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya

Page 38: Optimum Operasi Dan Keandalan Sistem Tenaga Listrik

Distribution System Reliability Analysis

Oleh :Dr. Eng. Rony Seto Wibowo

Laboratorium Simulasi Sistem Tenaga ListrikTeknik Elektro – ITS Surabaya