Contents
Panelboards 1
P
anelboard
s
Description Page
EZ Box and EZ Trim
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
Product Selection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-4
Product Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-5
Application Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-6
Standards and Certifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-8
Technical Data and Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-9
Type PRL1a Lighting Panelboard, 240 Vac Maximum
. . . . . . . . . . . . . . . . . . 14-21
Type PRL2a Lighting Panelboard, 480Y/277 Vac Maximum
. . . . . . . . . . . . . 14-23
Type PRL3a Lighting or Small Power Panelboard, 600 Vac Maximum
. . . . 14-25
Type PRL4 Power Distribution Panelboard, 600 Vac Maximum
. . . . . . . . . . 14-28
Type PRL1a-LX Column Type Panelboard, 240 Vac Maximum
. . . . . . . . . . . 14-39
Type PRL2a-LX Column Type Panelboard, 480Y/277 Vac Maximum
. . . . . . 14-42
Box Trim and Pricing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-45
Modifications (1a, 2a, 3a, 4, Column Type)
. . . . . . . . . . . . . . . . . . . . . . . . . . . 14-46
Type PRL5P Power Distribution Panelboard, 600 Vac Maximum, Plug-on
. . . . 14-53Pow-R-Command
Lighting Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-60
Renovation Panelboard PRL1R
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-75
Metering Service Sections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-84
Pow-R-Stock Plus Program
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-86
Regional Manufacturing Facilities
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-87
Type PRL1a Panelboard
7/13/2019 Tb 01400001 e
2/89
February 2007
14-2
For more information visit: www.eaton.com
CA08101001E
Panelboards
4
EZ Box and EZ Trim
EZ
Box and EZ Trim
Flange Detail
Eatons new EZ box and EZ trimrepresents the first significant change
in panelboard box and trim designs inmore than a half-century. The EZ boxand EZ trim have been designed forfaster, more secure and safer installa-tions. The new EZ box and EZ trim areprovided standard for Cutler-HammerPow-R-Line 1a and Pow-R-Line 2alighting panelboards, as well as ourPow-R-Line 3a mid-range panelboard.
Features
Virtually eliminates sharp edges.
Trim installs in seconds ratherthan minutes.
Door-in-door is standard.
Ability to adjust flush box to wallirregularities.
Trim installs without the needfor tools.
No exposed hardware (becausethere is none).
Multipoint door latch over breakers.
The EZ box flanges are bent andpainted, which virtually eliminatesthe sharp edges associated withtraditional boxes. Additionally, all steelpanelboard chassis parts are painted.This significantly reduces potentialinjury for material handlers and install-ers. Each flange is adjustable outward
up to 3/4 inch. This feature allowsthe installer to adjust flush boxapplications to be level and flat with
the finished wall after the wallmaterial is installed to help correctwall irregularities. The new box flangealso provides the means for attachingthe EZ trim.
Corner Flange Detail
Stand-alone Trim and Bottom Flange Hanger with Notch
7/13/2019 Tb 01400001 e
3/89
February 2007
CA08101001E For more information visit: www.eaton.com
1Panelboards
EZ Box and EZ Trim
Fast Installation
The EZ trim incorporates a patent pending, ground breakingdesign that installs in seconds, rather than minutes. Thestandard trim features include door-in-door construction;no exposed hardware and no tools are required forinstallation.
Each EZ trim includes hangers attached on the right side.The bottom trim hanger has a notch in its base. To install,the bottom hanger is inserted into the bottom right sidebox flange opening, resting the notch on the flange.
Trim Hanger Inserted Into Box Flange
The balance of the hangers are aligned with the other flangeopenings and pushed in. When all hangers are in the boxflange, the trim is lifted up slightly to clear the notch on thebottom hanger, and the trim in self-supported on the EZ box.
The installation is completed by swinging the trim to theclosed position, then lifting and pushing slightly to the right.The trim will drop into place totally secured. The multi-pointcatches on the left side of the trim will lock into the left side
box flange openings.
To prevent the trim from being removed by non-authorizedpersons, a unique sliding means automatically latchesin place when the trim door is closed. For added safety, ascrew is provided to secure the latch for those who requireextra security.
The new EZ trim utilizes an exclusive catch systemthat fastens the door to multiple points. Along with a newlock, the EZ trim offers a high degree of door security.
Standards
When used with Eatons Cutler-Hammer panelboard chassis,EZ boxes and EZ trims meet the following applicableindustry standards:
UL
50 listed.
NEMA
Standard PB1.
Federal specifications.
National Electrical Code
.
Trim Hanging on Surface Mounted Box
Trim Installed with Door Open and Trim Sliding Latch
New Lock
7/13/2019 Tb 01400001 e
4/89
February 2007
14-4
For more information visit: www.eaton.com
CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Product Selection
Product Types
Type PRL1a
Bolt-on or Plug-on Circuit Breakers240 Vac Maximum
Main Lugs Only400 amperes maximum.
Main Circuit Breaker400 amperes maximum.
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL1a
Type PRL2a
Bolt-on Circuit Breakers240 V or 480Y/277 Vac; 125/250 Vdc Maximum
Main Lugs Only400 amperes maximum.
Main Circuit Breaker400 amperes maximum.
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL2a
Type PRL3a
Bolt-on Circuit Breakers240 V, 480 V or 600 Vac; 250 Vdc Maximum
Main Lugs Only800 amperes maximum.
Main Circuit Breaker600 amperes maximum.
Branch Circuit Breakers225 amperes maximum,1-, 2- and 3-pole.
Type PRL3a
Type PRL4
Circuit Breakers or Fusible Switches240 V, 480 V or 600 Vac; 250 Vdc Maximum
Main Lugs Only1200 amperes maximum.
Main Circuit Breaker1200 amperes maximum.
Main Fusible Switch1200 amperes maximum.
Branch Circuit Breakers1200 amperes maximum,1-, 2- and 3-pole.
Branch Fusible Switches1200 amperes maximum,2- and 3-pole.
Type PRL4
Type PRL5P
Plug-on Circuit Breakers240 V, 480 V or 600 Vac; 250 Vdc Maximum
Main Lugs Only1200 amperes maximum.
Main Circuit Breaker1200 amperes maximum.
Branch Circuit Breakers1200 amperes maximum,1-, 2- and 3-pole.
Type PRL5P
Pow-R-Command
Bolt-on Circuit Breakers240 V or 480Y/277 Vac
Main Lugs Only400 amperes maximum.
Main Circuit Breaker400 amperes maximum.
Branch Circuit Breakers225 amperes maximum,1-, 2- and 3-pole.
Integral Power Switching Controls.
Pow-R-Command
7/13/2019 Tb 01400001 e
5/89
February 2007
CA08101001E For more information visit: www.eaton.com
1Panelboards
Pow-R-Line C Panelboards
Product Description
Product Types (Continued)
Type PRL1a-LX Column Type
Bolt-on Circuit Breakers 240 Vac Maximum
Main Lugs Only
225 amperes maximum.
Main Circuit Breaker225 amperes maximum.
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL1a-LX Column Type
Type PRL2a-LX Column Type
Bolt-on Circuit Breakers240 V or 480Y/277 Vac; 125/250 Vdc Maximum
Main Lugs Only225 amperes maximum.
Main Circuit Breaker225 amperes maximum.
Branch Circuit Breakers100 amperes maximum,1-, 2- and 3-pole.
Type PRL2a-LX, Column Type
Renovation Panelboard PRL-IR
Bolt-on Circuit Breakers 240 Vac Maximum
Main Lugs Only225 amperes maximum.
Main Circuit Breaker
225 amperes maximum.
Branch Circuit Breakers100 amperes maximum,1-, 2 and 3-pole.
Renovation Panel
Metering Service Section
Bolt-on Circuit Breaker or Fusible Switch240 V, 480 V or 600 Vac
Service entrance panels combininga main disconnect with a powercompany metering compartment.400 1200 amperes.
Metering Service Section
Product Description
Lighting and DistributionPanelboards
Eatons Cutler-Hammer
assembled
panelboards are designed forsequence phase connection of branchcircuit devices. This allows completeflexibility of circuit arrangement(1-, 2- or 3-poles) to allow balance ofthe electrical load on each phase.
Sturdy, rigid chassis assembly ensuresaccurate alignment of interior withpanel front; prevents flexing andminimizes possibility of looseningor damage to current carrying partsduring and after installation.
Four-point in-and-out adjustment ofpanel interior is provided to meet criti-cal depth dimensions on flush installa-
tions. This compensates for possiblemisalignment of box at installation.
Main lugs are mechanical solderlesstype and approved for copper oraluminum conductors.
Enclosures
Boxes are code-gauge galvanized steelexcept for column type panelboardswhich include a painted box finished inANSI-61 light gray to match the trim.
Standard panelboard cabinets aredesigned for indoor use. Alternatetypes are available for indoor andspecial purpose applications.
All enclosures are furnished in accor-dance with Underwriters Laboratoriesstandards and include wiring gutterswith proper wire bending space.Special cabinets can be providedat an additional charge.
The box dimensions shown are insidedimensions. For outside dimensions,add 1/4-inch (6.4 mm).
Standard panelboard boxes are supplied
without knockouts (blank endwalls).
Fronts
Fronts (trims) for all panelboards are
made of code-gauge steel and havea high durability ANSI-61 light grayfinish applied by a baked-on polyesterpowder coating paint system.
7/13/2019 Tb 01400001 e
6/89
February 2007
14-6
For more information visit: www.eaton.com
CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Application Description
The fronts for lighting and appliancebranch circuit panelboards and smallpower distribution panelboards includea door with rounded corners and con-cealed hinges. A flush-type latch andlock assembly is included. All locks arekeyed alike. These trims are available inboth surface and flush mounted designs.
EZ Trim Features Standard Door-in-Doorwith No Exposed Hardware or Sharp Edges(no Tools are Required for Installation)
The Three-Piece Trim for Larger PowerDistribution Panelboards Provides for EasyHandling and Installation
Fronts for power distribution panel-boards utilize a unique breaker frontcover design in which each device hasa dedicated bolt-on steel cover. Theindividual covers form a single dead-front for the panelboard that is usedin conjunction with two wiring guttercovers to complete the trim. A dooris not finished as part of the standardoffering on these panelboards but canbe provided, for an additional charge,using a deeper than standard box.
Application Description
Panelboard Selection FactorsIn selecting a panelboard, the follow-ing factors must be considered:
Service (voltage and frequency). Interrupting capacity (fully or
series rated).
Ampere rating of main.
Ampere ratings of branches.
Environment.
Panelboard Short Circuit RatingThe short circuit rating of EatonsCutler-Hammer assembled panel-boards are test verified by, and listedwith, Underwriters Laboratories(UL).Generally, these ratings are that ofthe lowest interrupting rated devicein the panel.
Certain exceptions to this rule existwhere branch devices have been ULtested in combination with specificmain devices having a higher inter-rupting rating. Where these definedmain devices and branch breaker com-binations are utilized, the Series ShortCircuit Ratingof the assembled panel-board will be the same as the testedrating of the approved rated maindevice in series with the branches.Available main and branch breakercombinations are tabulated startingon Page 14-12. All combinationsshown are UL tested and listed.
These series ratings apply to panelshaving main devices, or main lugonly panelboards fed remotely bythe device listed in the series ratingschart as the main, for which UL listedtests were conducted.
Service Entrance EquipmentThe National Electrical Code (NEC)requires that:
A panel used as service entranceequipment must be located near thepoint where the supply conductorsenter the building.
A panelboard having main lugs onlyshall have a maximum of six servicedisconnects to de-energize theentire panelboard from the supplyconductors. Where more thansix disconnects are required, amain service disconnect mustbe provided.
A disconnectable electrical bondmust be provided between theneutral and ground.
A service entrance type UL labelmust be factory installed.
Ground fault protection of equip-ment shall be provided for each ser-vice disconnect rated 1000 amperesor more if the electrical service is
a solidly grounded wye systemof more than 150 volts to groundbut not exceeding 600 volts phase-to-phase.
Note: Service entrance panels must beidentified as such on the order.
Panelboard ClassificationsPanelboards are classified by NEC andUL in two general categories: Lightingand Appliance Panels and PowerDistribution Panels.
Lighting and Appliance PanelboardsLighting and appliance branch circuit
panelboards are defined in NEC(Article 408) as one having more than10 percent of its overcurrent devicesrated 30 amperes or less for whichneutral connections are provided.Article 408 also limits the number ofovercurrent devices (branch circuit-poles) to a maximum of 42 in any onecabinet. This rule applies to all paneltypes including PRL4 when the panelcircuitry comes within the scope of thisdefinition. When the 42 devices (poles)are exceeded, two or more separatepanels are required.
Power Distribution PanelboardsDistribution panelboards (all othersnot defined as lighting and appliancebranch circuit panelboards) arerestricted only to practical physicallimitations such as standard boxheights and widths. It is importantto note that the NEC requires thatthe operating handle of the topmostmounted device be no more than6 feet 7 inches (2006.6 mm) abovethe finished floor.
Additional boxes and fronts arerequired when the componentsrequired for one panelboard exceedthe standard box dimensions.
Multi-Section PanelboardsWhen more than 42 overcurrentprotective devices are required (See,Lighting and Appliance Panelboards),two or more separate enclosures arerequired. Separate fronts for each boxare standard. A common front canbe furnished at additional charge.
7/13/2019 Tb 01400001 e
7/89
February 2007
CA08101001E For more information visit: www.eaton.com
1PanelboardsPow-R-Line C Panelboards
Interconnecting Multi-SectionPanelboardsWhen a panelboard, for connection toone feeder, must be furnished in morethan one section (Box), each sectionmust be furnished with main bus andterminals of the same rating, unlessa main overcurrent device is providedin each section.
Sub-feed or through-feed provisionsmust also be included (and priced) toprovide connection capability to thesecond section.
Note: Sub-feed or through-feed lugs can-not be used on any panelboard that is notprotected by a single main overcurrentdevice either in the panelboard or immedi-ately upstream, i.e., service entrance panel-boards with main lugs only using the sixdisconnect rule.
Sub-Feed LugsSub-feed lugs (see Figure 14-1) areone means of interconnecting multi-section panels. The sub-feed (secondset of) lugs are mounted directlybeside the main lugs. These arerequired in each section except the lastpanel in the lineup. The feeder cablesare brought into the wiring gutter ofthe first section and connected to themain lugs. Another set of the samesize cables are connected to the sub-feed lugs (Section 1) and are carriedover to the main lugs of the adjacentpanel. Cross connection cables are notfurnished by Eaton. Sub-feed lugs areonly available on main lug only panels.
Note: Sub-feed lugs may not be used onmain lug only (six disconnect rule) serviceentrance panels.
Figure 14-1. Sub-Feed Lugs
Through-Feed LugsThrough-feed lugs (see Figure 14-2)are another method to interconnectmulti-section panelboards. The incom-ing feeder cables are connected to themain lugs or main breaker at the bot-
tom of panel (Section 1). Another setof lugs (through-feed) are located atthe opposite end of the main bus. Theinterconnecting cables are connectedto the through-feed lugs in Section 1and are carried over to the main lugsin Section 2. The connection arrange-ment could be reversed, i.e., main lugsat top; through-feed lugs at bottomend of panel. Cross cables are notfurnished by Eaton.
Note: Through-feed lugs may not beused on main lug only (six disconnect rule)service entrance panels.
Figure 14-2. Through-Feed Lugs
Multiple Section Panelboard Flush MountedShown below is the standard methodfor flush mounting multiple sectionlighting and distribution panelboardsusing standard flush trims.
Figure 14-3. Multiple Section PanelboardFlush Mounted Dimensions in Inches (mm)
Overcurrent ProtectionThe following requirements will befound in the NEC:
Each lighting and appliance branchcircuit panelboard shall be individuallyprotected on the supply side by notmore than two main circuit breakers ortwo sets of fuses having a combinedrating not greater than that on thepanelboard.
Box Box
Conduit
Neutra Neutra
Panel
anel
Section 1 Section 2
Section 1 Section 2
Box Box
Conduit
Neutral
Panel
Panel
Neutral
a nLugs
Thru-FeedLugs
MainLugs
Cross Cables
Incoming Feeder Cables
Contractor to Mount Boxes1-1/2-inch (38.1 mm) Apart toAllow for 3/4-inch (19.1 mm)Extension on Both Flush Trims
Two SectionPanelboard(Flush Mounting)
rim Extends 3/4-inch(19.1 mm) Beyond Outside
f Box on All Four Sides
Outside Edge of Boxrim
W ll WallTrim Trim
onduit Nipple for Cross Wiring by Contractor
3/4(19.1)
3/4(19.1)
1 1/238.1)
Top SectionView
3/4(19.1)
3/4(19.1)
3/4(19.1)
3/4(19.1)
3/419.1)
3/419.1)
3/4(19.1)
3/419.1)
7/13/2019 Tb 01400001 e
8/89
February 2007
14-8
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Standards and Certifications
Branch Circuit Loading for Lightingand Appliance PanelsThe size of mains and branches shouldbe selected based on the following:
Lighting and distribution circuits:
NEC Article 210, 215, 220 and 240. Motor circuits: NEC Article 430.
Diversity factor.
Provision for future loading.
Exception Number 1:Individual pro-tection for a lighting and appliancepanelboard is not required when thepanelboard feeder has overcurrentprotection not greater than that ofthe panelboard.
Exception Number 2:For existinginstallations, individual protection forlighting and appliance branch circuitpanelboards is not required where
such panelboards are used as serviceequipment in supplying an individualresidential occupancy and where anybus supplying 15 or 20 ampere circuitsis protected on the supply side by anovercurrent device.
Ambient TemperaturesThe primary function of an overcurrentdevice is to protect the conductor andits insulation against overheating. Inselecting the size of the devices andconductors, consideration should begiven to the ambient temperature sur-rounding the conductors within andexternal to the panelboard. Cumula-
tive heating within the panelboardmay cause premature operation ofthe overcurrent protective devices.
Underwriters Laboratories testprocedures are based, in part, on 80%loading of panelboard branch circuitdevices. The NEC limits the loading ofovercurrent devices in panelboards to80% of rating where in normal opera-tion the load will continue for threehours or more. Further derating maybe required, depending on such factorsas ambient temperature, duty cycle,frequency or altitude.
Exception:There is one exception tothis rule in both UL and NEC. It appliesto assemblies and overcurrent deviceswhich have been approved for contin-uous duty at 100% of its rating.
Special ConditionsStandard panelboards, assembledwith standard components, are ade-quate for most applications. However,special consideration should be givento those required for application under
special conditions such as:
Excessive vibration or shock.
Frequencies above 60 cycles.
Altitudes above 6600 feet (2011.7 m).
Damp environment (possible fungusgrowth).
Compliance with federal, stateand municipal electrical codesand standards.
Seismic ConsiderationsThe Uniform Building Codeand theInternational Building Code 2003, aswell as local and state building codes,
place an emphasis on seismic buildingdesign requirements. Electricaldistribution systems are treatedas attachments to the building andtherefore, fall into this category.
All Eatons Cutler-Hammer panel-boards are seismic qualified at thehighest possible level, Seismic Zone 4,and have been tested in accordancewith ANSI C37.81. This standard quan-tifies actual earthquake conditions, aswell as equipment seismic capability.
Harmonic CurrentsStandard panelboard neutrals are
rated for 100% of the panelboardcurrent. However, since harmoniccurrents can cause overheatedneutrals, an option is provided forneutrals to be rated at 200% (1200ampere maximum neutral for 600ampere main bus) of the panelboardphase current.
Panelboards with the 200% ratedneutral are UL listed as suitable foruse with non-linear loads.
Prior to specifying the 200% ratedneutral, Eaton recommends a harmonicsurvey be conducted of the distributionsystem, be it new or existing.
Transient Voltage Surge SuppressionThe quality of power feeding sensitiveelectronic loads is critical to the reliableoperation of any facility. In modernoffices, hospitals, and manufacturingfacilities, the most frequent causes ofmicroprocessor-based equipmentdowntime and damage are voltagetransients and electrical noise.
Electrical loads and microprocessor-based equipment are highly susceptibleto both high and low energy transients.High energy transients include lightninginduced surges and power companyswitching. These high energy transientscan destroy components instantly.
More frequently the electrical systemexperiences low energy transients andhigh frequency noise.
The effects of continual low energytransients and high frequency noisecan cause erratic equipment perfor-mance or sudden failure of electroniccircuit board components.
Eaton can provide protective and diag-nostic systems integral to panelboards.The Clipper Power System Visor Seriesis integrated into the panelboardsusing a zero lead length direct busbar connection.
Pow-R-Line 4
The CPS Visor Series providesTransient Voltage Surge Suppression(TVSS) and active hybrid filtering.The CPS protects sensitive electronicequipment from the damaging effectsof high and low energy transients,as well as high frequency noise.
Standards and Certifications
Eatons Cutler-Hammer panelboardsare designed to meet the followingapplicable industry standards, exceptwhere noted:
Underwriters Laboratories:
Panelboards: UL 67
Cabinets and Boxes: UL 50
Note: Only panelboards containingUL listed devices can be UL labeled.
National Electrical Code.
NEMAStandards: PB 1.
Federal Specification W-P-115c:
Circuit Breakers Type I Class I
Fusible Switch Type II Class I
7/13/2019 Tb 01400001 e
9/89
February 2007
CA08101001E For more information visit: www.eaton.com
1PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Technical Data and Specifications
Selection GuideTable 14-1. Panelboard Selection Guide
Terminal Wire Ranges, Pressure-TypeAl/Cu Terminals Except as NotedNote: All terminal sizes are based on wireampacities corresponding to those shown inNEC Table 310-16 under the 75C insulationcolumns (75C wire). The use of smaller size,(in circular mills), regardless of insulationtemperature rating, is not permitted.
Where copper-aluminum terminals aresupplied on designated panelboardtypes, best results are obtained if asuitable joint compound is appliedwhen aluminum conductors are used.
Check Eatons Cutler-Hammer standardterminal sizes versus customerrequirements. In particular, 400 and
800 ampere breakers often requirenonstandard lugs.
Optional 750 kcmil mechanicalscrew-type terminals are availableupon request. Panelboard dimensionsmay be affected, refer to Eaton.
Table 14-2. Standard Main Lug Terminals
PanelboardType
DeviceType
MaximumVoltage Rating
Maximum MainRating (Amperes)
Branch CircuitsAmpere Range
Sub-Feed BreakerMaximum Amperes
AC Interrupting Capacityrms Symmetrical Amperes (kA)
ac dc MLO Main Device Fully Rated Series Rated
PRL1a Breaker 240 400 400 15 100 400 10 22 22 100
PRL2a BreakerBreaker
240480Y/277
250250
400 400
400 400
15 10015 100
400400
65 14
65 20022 150
PRL3a BreakerBreakerBreaker
240480600
250250250
800 800 800
600 600 600
15 22515 22515 225
600600600
10 200 14 100 14 35
22 20022 150
PRL4B BreakerBreakerBreaker
240480600
250250250
120012001200
120012001200
15 120015 120015 1200
10 200 14 200 14 200
22 20022 150
PRL4F FusibleFusible
240600
250250
12001200
12001200
30 120030 1200
100 200100 200
PRL1a-LX Breaker 240 225 225 15 100 10 22 22 100
PRL2a-LX BreakerBreaker
240480Y/277
250250
225 225
225 225
15 10015 100
65 14
65 20022 150
PRC100/50PRC25
BreakerBreaker
240480Y/277
400 400
400 400
15 22515 225
10 65 14
22 10065 100
PRL5P BreakerBreakerBreaker
240480600
250250250
120012001200
120012001200
15 120015 120015 1200
10 200 14 200 14 200
22 20022 150
PanelType
Wire Size Ranges for Ampere Capacity
100 Ampere 225 Ampere 250 Ampere 400 Ampere 600 Ampere 800 Ampere 1200 Ampere
PRL1aPRL2aPRL3aPRL4
#12 #1/0#12 #1/0#12 #1/0
#6 300 kcmil#6 300 kcmil
#6 350 kcmil#4 500 kcmil
(2) #4 500 kcmil(2) #4 500 kcmil(2) #4 500 kcmil(2) #4 500 kcmil
(2) #4 500 kcmil(2) #4 500 kcmil
(3) #4 500 kcmil(3) #4 500 kcmil
(4) #4 500 kcmil
PRL1a-LXPRL2a-LX
#12 #1/0#12 #1/0
#6 300 kcmil#6 300 kcmil
PRC100PRC50
#12 #1/0 #6 350 kcmil (2) #4 500 kcmil
PRC25 #12 #1/0 #6 300 kcmil (2) #4 500 kcmil
PRL5P (1) #1/0 500 kcmilor(2) #1/0 250 kcmil
(2) #4 500 kcmil (2) #2 500 kcmilor(3) #2 400 kcmil
(4) #4 750 kcmil
7/13/2019 Tb 01400001 e
10/89
February 2007
4-10
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Selection Guide (Continued)
Table 14-3. Standard Circuit Breaker Terminals
BreakerType
AmpereRating
WireRange
BAB, QBHWHQP, QPHW
15 70 90 100
#14 #4 #8 #1/0
EDB, EDS, ED,EDH, EDC
100 225 #4 4/0 or #6 300 kcmil
EHD, FDB, FD,HFD, FDC
15 100 125 225
#14 1/0 #4 4/0
FCL 15 100 #14 1/0
GHB, HGHB, GHQ 15 20 25 100
#14 #10#10 1/0
JD,HJD, JDC
70 250 #4 350 kcmil
DK 250 350 400
250 500 kcmil(2) 3/0 250 kcmil or (1) 3/0 500 kcmil
KD,HKD, KDC,CKD, CHKD
225 350 400
(1) #3 350 kcmil(1) 250 500 kcmil(2) 3/0 250 kcmil or(1) 3/0 500 kcmil
LGE, LGH 250 400 500 600
(1) #2 500 kcmil(2) #2 500 kcmil
LD,HLD, LDC,CLD, CHLD
300 500
600
(2) 250 350 kcmil
(2) 400 500 kcmil
MDL, HMDL,CMDL,CHMDL
400 600 700 800
(2) #1 500 kcmil(3) 3/0 400 kcmil
ND, HND,CND, CHNDNDC, CNDC
800 10001200
(3) 3/0 400 kcmil(4) 4/0 500 kcmil
LCL 125 225 250 400
(1) #6 350 kcmil(1) #4 250 kcmil and (1) 3/0 600 kcmil
FB-P 15 100 #14 1/0
LA-P 70 225 250 400
#6 350 kcmil(1) #4 250 kcmil and (1) 3/0 600 kcmil
NB-P 300 700 800
(2) #1 500 kcmil(3) 3/0 400 kcmil
Table 14-4. FDPW Switch Terminals
AmpereRating
WireRange
30 60 100
#14 1/0#14 1/0#14 1/0
200 #4 300 kcmil
400 250 750 kcmil or(2) 3/0 250 kcmil
600 (2) #4 600 kcmil or(4) 3/0 250 kcmil
800 (3)250 750 kcmil or(6) 3/0 250 kcmil
1200 (4) 250 750 kcmil or(8) 3/0 250 kcmil
7/13/2019 Tb 01400001 e
11/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Selection Guide (Continued)Table 14-5. Molded Case Circuit Breaker RatingsNote: Circuit breakers equal or exceed Federal Specification W-C-375b requirements for the particular class associated with each circuit breaker type.
dc ratings apply to substantially non-inductive circuits. 15 and 20 amperes 1-pole switching duty rated for fluorescent applications. 1-, 2- and 3-pole HACR rated. dc rated 1-pole, 15 70 amperes only. 2- and 3-pole HACR rated. 100% rated circuit breaker. dc rating not available with electronic trip. Available with integral ground fault protection. 100k based on NEMA test procedure.
BreakerType
ContinuousAmpereRating
Numberof Poles
Voltsac
UL Listed Interrupting Ratings kA Symmetrical Amperes
ac Rating Volts dc Rating Volts
120/240 240 277 480 600 125 250
BAB, HQP 15 70 15 100 15 100
122, 3
120120/240240
1010
10
BABRP, BABRSP 15 30 15 30
12
120120/240
1010
QBGF, QBGFEP,QPGF, QPGFEPQBAF, QBAG
15 40 15 50 15 20 15 20
1212
120120/240120120/240
10101010
QBHW, QPHW 15 70 15 100 15 100
122, 3
120120/240240
2222
22
QBHGF, QBHGFEP,QPHGF, QPHGFEP
15 30 15 30
12
120120/240
2222
GQ, GHQ
GHB 15 20 15 100
15 100
112, 3
277277480Y/277
6565
65
1414
14
14
14
HGHB
GHBGFEP 15 30 15 60
11
277277
65
2514
GHBS 15 30 15 30
12
277480Y/277
65
65
14
14
EHD 15 100 15 100
12, 3
277480
18
14
14
10
10
FDB
FD 15 150 15 150 15 225
2, 312, 3
600277600
18 65
35
14 35
14 18
10
1010
HFD 15 150 15 225
12, 3
277600
100
65
65
25
10
22
FDC
FCL 15 225 15 100
2, 32, 3
600480
200200
100150
35
22
EDB
EDS
ED
EDH
EDC
100 225100 225100 225100 225100 225
2, 32, 32, 32, 32, 3
240240240240240
224265100200
1010101010
JD
HJD
JDC
70 250 70 250 70 250
2, 32, 32, 3
600600600
65100200
35 65100
18 25 35
102222
DKKD, CKD
HKD, CHKD
250 400100 400100 400
2, 32, 32, 3
240600600
65 65100
35 65
25 35
1010
22
KDCLCL
LGELD, CLD
100 400125 400250 600300 600
2, 32, 332, 3
600600600600
200200 65 65
100200 35 35
65100 18 25
22
2222
LGHHLD, CHLD
LDC, CLDC
MDL, CMDL
250 600300 600300 600400 800
32, 32, 32, 3
600600600600
100100200 65
65 65100 50
35 35 50 25
2225
25
22
HMDL, CHMDL
ND, CND
HND, CHND
NDC, CNDC
400 800600 1200600 1200600 1200
2, 32, 32, 32, 3
600600600600
100 65100200
65 50 65100
35 25 35 65
25
Integrally Fused, Current Limiting Circuit BreakersFB-PLA-PNB-P
15 100 70 400300 800
2, 32, 32, 3
600600600
200200200
200200200
200200200
7/13/2019 Tb 01400001 e
12/89
February 2007
4-12
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Series Rated CombinationsUnderwriters Laboratories permitspanelboards to be labeled with a shortcircuit rating of up to 200,000 amperes(symmetrical) where UL listed combi-nations of main and branch circuit
breakers are used.
These combinations consist of mainbreakers or fusible devices connectedahead of, and in series with approvedconventional breakers used as branchdevices.
Two arrangements are acceptable andcomply with UL standards for panel-boards. The main circuit breaker orfusible switch may be installed in thepanel as a main device, or it may bemounted remote, (directly upstream)from the panel.In either case, theapproved main and branch combina-tions must be followed. These
arrangements are acceptable andare UL listed having been tested inaccordance with UL 67 standards.
From the tables that follow, specificcombinations of main devices(upstream) and branch devices(downstream), series connected andelectrically adjacent in the system,may be selected to qualify theassembled panelboard for the shortcircuit ratings shown.
Applying Series Ratings
The following is provided to use theseries rating tables on the followingpages.
1. Determine the available systemvoltage and fault current.
2. Select the appropriate table usingthe system voltage.
3. Use the appropriate SeriesEquipment Rating column equalto, or greater than, the availablefault current, to determine theallowable UL recognized combina-tions of main (upstream) andbranch (downstream) overcurrentdevices. Main devices are shownin bold/shaded areas. Respectivebranch breakers are showndirectly below their associatedmain device. If a rating is not
initially found in a column, firstlook to the columns to the rightfor higher Series EquipmentRatings within the same table.If still not found, use ratings fromtable of a higher system voltage(higher numbered table(s).
Table 14-6 on Page 14-13
120/240 Volts ac Breaker/Breaker
Table 14-7 on Page 14-14
240 Volts ac Breaker/Breaker
Table 14-8 on Page 14-16
277 Volts ac Breaker/Breaker
Table 14-9 on Page 14-16
480Y/277 Volts ac Breaker/Breaker
Table 14-10 on Page 14-17
480 Volts ac Breaker/Breaker
Table 14-11 on Page 14-18
600 Volts ac Breaker/Breaker
Table 14-12 on Page 14-18
120/240 Volts ac Fuse/Breaker
Table 14-13 on Page 14-19
240 Volts ac Fuse/Breaker
Table 14-14 on Page 14-19
277 Volts ac Fuse/Breaker
Table 14-15 on Page 14-20
480Y/277 Volts ac Fuse/Breaker
Table 14-16 on Page 14-20
480 Volts ac Fuse/Breaker
Table 14-17 on Page 14-20
600 Volts ac Fuse/Breaker
Table 14-18 on Page 14-20
Triple Series Ratings
7/13/2019 Tb 01400001 e
13/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Series Rating Tables
Table 14-6. 120/240 Volts ac Breaker/Breaker Series RatingsMain devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
18 22 42 65 100 200
100 EHD QBHW GB, GHB FB-P FCL
BA, BABBABRPBABRSPHQPQBGFQBAFQBAG
QPHW BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHW
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHWEHDFD
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHWGB, GHBGHQEHDFDHFD
BA, BABHQPQBGFQPGFQBAFQBAG
150 FDB
BA, BABHQPQBGFQBAFQBAG
200 LA-P
BA, BABHQPQBHWQPHWEHDFD
225 EDB EDS ED, FD EDH, EDC HFD FDC FDC
BA, BABBABRPBABRSPHQPQBGFQPGFQBHGFQPHGFQBHWQPHWQBAFQBAG
BA, BABBABRPBABRSPHQPQBGFQPGFQBHGFQPHGFQBHWQPHWQBAFQBAG
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQBHGF
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAG
BA, BABHQPQBGFQBAFQBAGQBHWQPHWQBHGFGB, GHBGHQ, GHQRSPEHDFD
BA, BABHQPQBHWQPHW
GB, GHBGHQGHQRSPEHDFDHFD
250 JD, JDB HJD JDC HJD JDC JDC
BA (15 70 A)BAB (15 70 A)HQP (15 70 A)QBHWQPHWEHD
BA, BABHQPQBHWQPHW
QBGFQPGFQBAFQBAG
GB, GHBEHDFD
BA, BABHQPQBHWQPHW
GB, GHBEHDFDHFD
400 DK, KD DK, KD HKD, CHKD DK, KD KDC HKD KDC KDC LCLKDB KDB, CKD BA (15 70 A)
BAB (15 70 A)BABRPBABRSP
HQP (15 70 A)QBHWQPHW
KDB BA (15 70 A)BAB (15 70 A)HQP (15 70 A)
CHKD QBHWQPHW
GB, GHBEHDFDHFD
BA, BABHQPQBGFQPGF
QBAFQBAGQBHWQPHWGB, GHBEHDFDHFD
BA, BABBABRPBABRSP
HQPQBGFQPGFQBAFQBAG
BA (15 70 A)BAB (15 70 A)BABRP
BABRSPHQP (15 70 A)QBHWQPHW
CKD GB, GHBEHDFD
EHD
600 CHLD, HLD
EHD
800 HMDL
EHD
1200 HND
EHD
7/13/2019 Tb 01400001 e
14/89
February 2007
4-14
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Table 14-7. 240 Volts ac Breaker/Breaker Series RatingsFor 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-6.Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
18 22 42 65 100 200
100 EHD QBHW_H GB, GHB FB-P FCL
BAB_HHQP_H
QPHW_H BAB_HHQP_HQBHW_HQPHW_H
BAB_HHQP_HEHDFDBFD
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFDFDBHFD
BAB_HHQP_H
150 FDB
BAB_HHQP_H
200 LA-P
BAB_HHQP_H
QBHW_HQPHW_HEHDFDBFDJD, JDB
225 EDB EDS ED FD EDH, EDC HFD FDC FDC
HQP_HBAB_HQBHWQPHW
HQP_HBAB_HQBHWQPHW
BAB_HHQP_HQBHW_H
BAB_HHQP_HQBHW_HQPHW_HEHD (15 70 A)FDB
BAB_HHQP_H
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFDBFD
BAB_HHQP_HQBHW_HQPHW_H
GB, GHBEHDFDBFDHFD
250 JD, JDB HJD HJD JDC JDC
BAB_H (15 70 A)HQP_H (15 70 A)
QBHW_HQPHW_HEHDFDB
BAB_H (15 70 A)HQP_H (15 70 A)
QBHW_HQPHW_H
GB, GHBEHD
FDFDBEDJD, JDB
BAB_HHQP_H
QBHW_HQPHW_H
GB, GHBEHD
FDFDBHFD, EDB, EDSEDEDHJD, JDBHJD
7/13/2019 Tb 01400001 e
15/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Table 14-7. (Continued) 240 Volts ac Breaker/Breaker Series RatingsFor 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-6.Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
Valid on 2- and 3-pole breakers only. Not valid for 1-pole.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
65 100 200
400 DK, KD, KDB HKD, CHKD KDC KDC LCLCKD QBHW_H
QPHW_H
GB, GHBEHDFDBFD, EDB, EDSEDJD, JDBDK, KD, KDB
QBHW_HQPHW_H
GB, GHBEHDFDBFDHFD, EDB, EDSEDEDHJD, JDBHJDDK, KD, KDBHKD
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFDBFD, HFD, EDB, EDSEDEDHJD, JDBHJDDK, KD, KDBHKD
BAB_HHQP_HQBHW_HQPHW_HEHDFDB
500 NB-P
JD, JDB
KD, KDB, DKCKD
600 HLD, HLDB, CHLD LDC
GB , GHB
FD, EDB, EDSED, EHDJD, JDBKD, KDB, DK, CKDLD, LDB
EDB, EDS, EDEDH
800 NB-P HMDL
KD, KDB, DK EHDFD
1200 HND, CHND NDC
EDB, EDS, EDEHD
EDB, EDS, EDEDH
2500 RD RDC
EDB, EDS, ED EDB, EDS, EDEDH
7/13/2019 Tb 01400001 e
16/89
February 2007
4-16
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Table 14-8. 277 Volts ac Breaker/Breaker Series RatingsMain devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, see other tables.
Table 14-9. 480Y/277 Volts ac Breaker/Breaker Series RatingsMain devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to 2- and 3-pole branch breakers only. For single-pole branch breakers, see Table 14-8.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
22 25 35 65 100 150
100 FCL
GHBGHQ, GHQRSPEHDFDHFD
225 FD HFD FDC
GHBGHQGHQRSP
GHB, GHQRSPGHQEHDFD
GHBEHDFDHFD
250 JD, JDB JD, JDB HJD LCL JDC
GHB GHB (15 50 A) GHB (15 50 A)EHDFD
GHBS GHBEHDFDHFD
400 KD, KDB HKD KD, KDB HKD, CHKD KDC LCLCKD CHKD CKD GHB (15 50 A)
EHDFD
GHB (15 50 A)EHDFDHFD
GHBEHDFDHFD
GHB GHB GHB (15 50 A)EHDFD
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
22 25 35 65 100 150
100 FCL
GHB, GHQRSP
225 FD HFD FDC
GHB, GHQRSP GHB, GHQRSP GHB
250 JD, JDB JD, JDB HJD JDC
GHB GHB (15 50 A) GHB (15 50 A) GHB
400 KD, KDB HKD, CHKD KD, KDB HKD, CHKD KDC LCLCKD GHB CKD GHB (15 50 A) GHB (15 50 A) GHB
GHB GHB (15 50 A)
7/13/2019 Tb 01400001 e
17/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Table 14-10. 480 Volts ac Breaker/Breaker Series RatingsMain devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for 1-pole branch breakers.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
25 35 65 100 150
100 FB-P FCL
EHDFDBFDHFD
EHDFDBFDHFD
200 LA-P
EHDFDBFDHFDJD, JDBHJD
225 FD HFD FDC
EHDFDB
EHDFDBFD
EHDFDBFD
HFD250 JD, JDB HJD JDC
EHDFDB
EHDFDBFDJD, JDB
EHDFDBFDHFDJD, JDBHJD
400 KD, KDB HKD KDC LA-P LCL
EHDFDB
EHDFDBFDJD, JDBKD, KDB
EHDFDBFDHFDJD, JDBHJDKD, KDBHKD
JD, JDBHJDKD, KDBHKD
EHDFDBFDHFDFDCJD, JDBHJDKD, KDBHKD
500 NB-P
JD, JDBHJDKD, KDBHKD
600 LD, LDB HLD, HLDBCLD CHLD
JD, JDB FDJD, JDBKD, KDBLD, LDB
7/13/2019 Tb 01400001 e
18/89
February 2007
4-18
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Table 14-11. 600 Volts ac Breaker/Breaker Series RatingsMain fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for 1-pole branch breakers.
Table 14-12. 120/240 Volts ac Fuse/Breaker Series RatingsMain fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
MainBreakerMaximumAmperes
Series Equipment Rating kA Symmetrical
18 25 35 42 50 100
225 FD HFD FDC
FDB FDBFD
FDBFDHFD
250 JD, JDB HJD JDC
FDB FDBFDJD, JDB
FDBFDHFDJD, JDBHJD
400 KD, KDB HKD, CHKD KDC KDC LCLCKD FDB
FDHFDJD, JDBHJD
FDBFDHFD
JD, JDBHJDKD, KDBHKD
FDBFDHFDFDCJD, JDB
HJDJDCKD, KDBHKDKDC
FDBFDJD, JDB
600 LD, LDB HLD, HLDBCLD CHLD
FDJD, JDB
KD, KDBLD, LDB
MainFuseMaximumAmperes
Series Equipment Rating kA Symmetrical
100 200
100 R
BA, BABHQPQBHWQPHWGBGHB
200 R J T
GBGHB
BA, BABHQPQBHWQPHW
BA, BABHQPQBHWQPHW
400 J T J T
BA, BABHQPQBHWQPHW
BA, BABHQPQBHWQPHW
GBGHB
GBGHB
7/13/2019 Tb 01400001 e
19/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
Technical Data and Specifications
Table 14-13. 240 Volts ac Fuse/Breaker Series RatingsFor 1- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 14-12.Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
Valid on 2- and 3-pole breakers only. Not valid for 1-pole.
Table 14-14. 277 Volts ac Fuse/Breaker Series RatingsMain fuse class are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, consult other tables.
MainFuseMaximumAmperes
Series Equipment Rating kA Symmetrical
100 200
100 R
BAB_HHQP_HQBHW_HQPHW_HGBGHB
200 R J T R
GBGHB
BAB_HHQP_HQBHW_HQPHW_H
BAB_HHQP_HQBHW_HQPHW_H
GB
GHB
400 J T J T
BAB_HHQP_HQBHW_H
QPHW_H
BAB_HHQP_HQBHW_H
QPHW_H
GBGHB
GBGHB
600 L
EHDFDBFDEDJD, JDBDK, KD, KDB
MainFuseMaximumAmperes
Series Equipment Rating kA Symmetrical
65 100 200
100 J T R
GHBSGHQGHQRSP
GHBSGHQGHQRSP
GHB
200 J T J T R
GHBSGHQGHQRSP
GHBSGHQGHQRSP
EHDFDHFD
EHDFDHFD
GHB
400 J T
GHB GHB
7/13/2019 Tb 01400001 e
20/89
February 2007
4-20
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
Technical Data and Specifications
Table 14-15. 480Y/277 Volts ac Fuse/Breaker Series RatingsMain fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.For single-pole branch breakers, see Table 14-14.
Table 14-16. 480 Volts ac Fuse/Breaker Series RatingsMain fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.Not valid for single-pole branch breakers.
Table 14-17. 600 Volts ac Fuse/Breaker Series RatingsMain fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.Not valid for single-pole branch breakers.
Table 14-18. Triple Series Ratings
Valid on 2- and 3-pole breakers only. Not valid for single-pole.
Main
FuseMaximumAmperes
Series Equipment Rating kA Symmetrical
65 100 200
100 J T R
GHBS GHBS GHB
200 J T R
GHBS GHBS GHB
400 J T
GHB GHB
600 J T
EHDFDHFDFDC
GHBEHDFDHFDFDCJD
HJDJDC
MainFuseMaximumAmperes
Series Equipment Rating kA Symmetrical
100 200
100 R
EHD
200 J T
EHD
FDHFDFDC
EHD
FDHFDFDC
Main
FuseMaximumAmperes
Series Equipment Rating kA Symmetrical
100 200
100 R
FDHFDFDC
200 J T R
FDHFDFDC
FDHFDFDC
JDHJDJDC
400 J T R
JDHJDJDC
JDHJDJDC
KDHKDKDC
600 J T
KDHKDKDC
KDHKDKDC
Main FuseClass andMaximumAmperes
Tenant MainType
BranchType
SystemVoltage
ShortCircuitSeriesRating(kA, Sym.)
L-6000 DK, KD, KDB GB, GHB, EHD 240 100
L-6000 DK, KD, KDB GB, GHB 120/240 100
L-6000 DK, KD, KDB FD , FDB 240 100
L-6000 DK, KD, KDB JD, JDB 240 100
L-6000 JD, JDB GB, GHB 240 100
L-6000 JD, JDB GB, GHB 120/240 100
L-6000 FD GB, GHB 240 100
L-6000 FD GB, GHB 120/240 100
L-6000 FD, FDB BAB_H, HQP_HQBHW_H, QPHW_H
240 100
L-6000 FD, FDB BA, BABHQP (15 70A)
120/240 100
L-6000 EHD BAB_H, HQP_H 240 100
L-6000 EHD BA, BAB, HQP 120/240 100
7/13/2019 Tb 01400001 e
21/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL1a
Product Description
240 Vac maximum.
3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
400 ampere maximum mains.
100 ampere maximum branchbreakers.
Bolt-on or plug-on branch breakers.
Factory assembled.
Refer to Page 14-5for additionalinformation.
Type PRL1a
Application Description Lighting and appliance branch
panelboard.
Fully rated or series rated.
Interrupting ratings up to 200 kAsymmetrical.
Suitable for use as Service EntranceEquipment, when specified onthe order.
See Pages 14-5through14-18foradditional information.
Standards and Certifications
UL 67, UL 50. Federal Specification W-P-115c.
Refer to Page 14-5for additionalinformation.
Options and Accessories
Refer to Page 14-46.
Layout and Sizing Refer to Page 14-22.
Product Selection
Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $
Table 14-19. Base Prices PRL1a
Table 14-20. Branch Circuit Breakers PRL1a
1-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a
midpoint delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker.
AmpereRating
InterruptingRating (kA Sym.)
240 Vac
BreakerType
Price U.S. $
3-Phase
4-Wire
1-Phase 3-Wire,
1-Phase 2-Wire
3-Phase
3-Wire
Main Lug Only
100225400
Main Breaker
100100100100100100100100100
10 18 22 22 42 65 65100100
BABEHDQBHWEDBEDSEDFDEDHHFD
225225
225225
22 42
65100
EDBEDS
EDEDH
250250250
65100200
JDHJDJDC
400400400400
65 65100200
DKKDHKDKDC
Bolt-on = BAB, QBHW, QBGF, QBHGF, QBGFEP, QBHGFEP, QBAF, QBAG, QBHAF, QBHAGPlug-on = HQP, QPHW, QPGF, QPHGF, QPGFEP, QPHGFEP
AmpereRating
InterruptingRating (kA Sym.)240 Vac
BreakerType
Price U.S. $
1-Pole120 V
2-Pole120/240 V
2-Pole240 V
3-Pole240 V
15 607080 10015 50
15 50
15 2015 20
10101010101010
BAB, HQPBAB, HQPBAB, HQPQBGF, QPGF
QBGFEP, QPGFEP
QBAF
QBAG
15 6015 3015 3015 30
10101010
BAB-D, HQP-D
BAB-C, HQP-B
BABRP
BABRSP
15 607080 10015 3015 3015 2015 20
22222222222222
QBHW, QPHWQBHW, QPHWQBHW, QPHWQBHGF, QPHGF
QBHGFEP, QPHGFEP
QBHAF
QBHAG
Provision
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
22/89
February 2007
4-22
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL1a
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size and box and trim catalognumbers for all standard panelboardtypes are found in Table 14-21.
Instructions1. Using description of the required
panelboard, select the rating andtype of main required.
2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere ratingsection from Table 14-21.
4. Select panelboard type from firstcolumn, main breaker frame, ifapplicable, from second column,and sub-feed breaker frame, ifapplicable, from the third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trimcatalog numbers across columnsto the right. Specify surface orflush mounting on the order.
CabinetsFronts are code-gauge steel, ANSI-61light gray painted finish.
Boxes are code-gauge galvanized steel
without knockouts. Standard depth is5-3/4 inches (146.1 mm). Standardwidth is 20 inches (508.0 mm). Anoptional 28-inch (711.2 mm) widebox is available.
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Table 14-21. PRL1a Panelboard Sizing
Metric box dimensions:
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
PanelboardTypes
Main Breaker Types& Mounting Position(H) = Horiz.(V) = Vert.
Sub-Feed Breaker Types& Mounting Position(H) = Horiz.(V) = Vert.
Maximum No. ofBranch CircuitsIncludingProvisions
Box DimensionsInches
YS BoxCatalogNumber
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumber
H W D
100 Ampere Maximum
Main Breaker BAB, QBHW(H)
15273942
36.0048.0048.0060.00
20.0020.0020.0020.00
5.755.755.755.75
YS2036YS2048YS2048YS2060
LT2036S or FLT2048S or FLT2048S or FLT2060S or F
EZB2036REZB2048REZB2048REZB2060R
EZT2036S or FEZT2048S or FEZT2048S or FEZT2060S or F
Main Lugs orMain Breaker
EHDFD, HFD(V)
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
Main Lugs or MainBreaker with 100 AThru-Feed Lugs orSub- Feed Breaker
EHDFDHFD(V)
EHDFDHFD(V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
225 Ampere Maximum
Main Lugs orMain Breaker
EDB, EDS, ED,EDH, FD, HFD(V)
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
JD, HJDJDC(V)
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs orMain Breaker with225 A Thru-FeedLugs or Sub-FeedBreaker
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
JD, HJDJDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
400 Ampere Maximum
Main Lugs orMain Breaker
DK, KD, HKD,KDC(V)
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs orMain Breaker with225 A Thru-FeedLugs or Sub- FeedBreaker
DK, KD, HKD,KDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
Main Lugs orMain Breaker with400 A Thru-FeedLugs or Sub- FeedBreaker
DK, KD, HKD,KDC(V)
JD, HJD, JDC,DK, KD,HKD, KDC(V)
183042
72.0090.0090.00
20.0020.0020.00
5.755.755.75
YS2072YS2090YS2090
LT2072S or FLT2090S or FLT2090S or F
EZB2072REZB2090REZB2090R
EZT2072S or FEZT2090S or FEZT2090S or F
Catalog Number Dimensions in mm
YS Box EZ Box Height Width Depth
YS2036YS2048YS2060YS2072YS2090
EZB2036REZB2048REZB2060REZB2072REZB2090R
914.41219.21524.01828.82286.0
508.0508.0508.0508.0508.0
146.1146.1146.1146.1146.1
7/13/2019 Tb 01400001 e
23/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL2a
Product Description
480Y/277 Vac maximum (125 Vdc).
3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
400 ampere maximum mains.
100 ampere maximum branchbreakers.
Bolt-on branch breakers.
Factory assembled.
Refer to Page 14-5for additionalInformation.
Type PRL2a
Application Description
Lighting and appliance branchpanelboard.
Fully rated or series rated.
Interrupting ratings up to 200 kAsymmetrical.
Suitable for use as Service EntranceEquipment, when specified onthe order.
See Pages 14-5 through14-18foradditional information.
Standards and Certifications
UL 67, UL 50.
Federal Specification W-P-115c.
Refer to Page 14-5for additionalinformation.
Options and Accessories
Refer to Page 14-46.
Layout and Sizing Refer to Page 14-24.
Product Selection
Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $
Table 14-22. Base Prices PRL2a
These system voltages apply only to 240 volts.
Table 14-23. Branch Circuit Breakers PRL2a
Interrupting ratings in this column are applicable to 120 Vac for 1-pole breakers. At 480 volts, must be used on 480Y/277 volts grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires 2-pole spaces. 277 Vac only. HID (High Intensity Discharge) rated breaker.
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
Price U.S. $
240 Vac 480Y/277 Vac 125/250 Vdc 3-Phase4-Wire
1-Phase 3-Wire,1-Phase 2-Wire
3-Phase3-Wire
Main Lug Only
100225400
Main Breaker
100100
65 18
14 14
1410
GHBEHD
100100100
65100200
35 65100
102222
FDHFDFDC
225225225225
65 65100200
35 65100
102222
EDFDHFDFDC
250250250
65100200
35 65100
102222
JDHJDJDC
400400400
65100200
35 65100
102222
KDHKDKDC
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
Price U.S. $
240 Vac 480Y/277 Vac 125/250 Vdc 1-Pole 2-Pole 3-Pole
15 2015 2025 6070 100
15 3015 2015 30
65656565
656565
14141414
251414
141414
GHQ
GHB
GHB
GHB
HGHB
GHQRSP
GHBS
15 6015 20
1414
GHBGFEP
GHBHID
Provision
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
24/89
February 2007
4-24
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL2a
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size and box and trim catalognumbers for all standard panelboardtypes are found in Table 14-24.
Instructions1. Using description of the required
panelboard, select the rating andtype of main required.
2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere ratingsection from Table 14-24.
4. Select panelboard type from firstcolumn, main breaker frame, ifapplicable, from second column,and sub-feed breaker frame, ifapplicable, from the third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trimcatalog numbers across columnsto the right. Specify surface orflush mounting on the order.
Cabinets
Fronts are code-gauge steel, ANSI-61light gray painted finish.
Boxes are code-gauge galvanized steel
without knockouts. Standard depth is5-3/4 inches (146.1 mm). Standardwidth is 20 inches (508.0 mm). Anoptional 28-inch (711.2 mm) widebox is available.
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Table 14-24. PRL2a Panelboard Sizing
Metric box dimensions:
Smaller panelboard box sizes are available if required. Contact Eaton for application information.
PanelboardTypes
Main Breaker Types& Mounting Position(H) = Horiz.
(V) = Vert.
Sub-Feed Breaker Types& Mounting Position(H) = Horiz.
(V) = Vert.
Maximum No. ofBranch CircuitsIncluding
Provisions
Box DimensionsInches YS BoxCatalog
Number
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumberH W D
100 Ampere Maximum
Main Breaker BAB, QBHW(H)
15273942
36.0048.0048.0060.00
20.0020.0020.0020.00
5.755.755.755.75
YS2036YS2048YS2048YS2060
LT2036S or FLT2048S or FLT2048S or FLT2060S or F
EZB2036REZB2048REZB2048REZB2060R
EZT2036S or FEZT2048S or FEZT2048S or FEZT2060S or F
Main Lugs orMain Breaker
EHDFD, HFD(V)
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
Main Lugs or MainBreaker with 100 AThru-Feed Lugs orSub- Feed Breaker
EHDFDHFD(V)
EHDFDHFD(V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
225 Ampere Maximum
Main Lugs orMain Breaker
EDB, EDS, ED,EDH, FD, HFD(V)
183042
36.0048.0048.00
20.0020.0020.00
5.755.755.75
YS2036YS2048YS2048
LT2036S or FLT2048S or FLT2048S or F
EZB2036REZB2048REZB2048R
EZT2036S or FEZT2048S or FEZT2048S or F
JD, HJDJDC(V)
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or MainBreaker with 225 AThru-Feed Lugs orSub-Feed Breaker
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
48.0048.0060.00
20.0020.0020.00
5.755.755.75
YS2048YS2048YS2060
LT2048S or FLT2048S or FLT2060S or F
EZB2048REZB2048REZB2060R
EZT2048S or FEZT2048S or FEZT2060S or F
JD, HJDJDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
400 Ampere Maximum
Main Lugs orMain Breaker
DK, KD, HKD,KDC(V)
183042
60.0060.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2060YS2072
LT2060S or FLT2060S or FLT2072S or F
EZB2060REZB2060REZB2072R
EZT2060S or FEZT2060S or FEZT2072S or F
Main Lugs or MainBreaker with 225 AThru-Feed Lugs orSub- Feed Breaker
DK, KD, HKD,KDC(V)
EHD, FD, HFD,EDB, EDS, ED,EDH (V)
183042
60.0072.0072.00
20.0020.0020.00
5.755.755.75
YS2060YS2072YS2072
LT2060S or FLT2072S or FLT2072S or F
EZB2060REZB2072REZB2072R
EZT2060S or FEZT2072S or FEZT2072S or F
Main Lugs or MainBreaker with 400 AThru-Feed Lugs orSub- Feed Breaker
DK, KD, HKD,KDC(V)
JD, HJD, JDC,DK, KD,HKD, KDC(V)
183042
72.0090.0090.00
20.0020.0020.00
5.755.755.75
YS2072YS2090YS2090
LT2072S or FLT2090S or FLT2090S or F
EZB2072REZB2090REZB2090R
EZT2072S or FEZT2090S or FEZT2090S or F
Catalog Number Dimensions in mm
YS Box EZ Box Height Width Depth
YS2036YS2048YS2060YS2072YS2090
EZB2036REZB2048REZB2060REZB2072REZB2090R
914.41219.21524.01828.82286.0
508.0508.0508.0508.0508.0
146.1146.1146.1146.1146.1
7/13/2019 Tb 01400001 e
25/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL3a
Product Description
600 Vac maximum (250 Vdc).
3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
800 ampere maximum main lugs.
600 ampere maximum mainbreaker.
225 ampere maximum branchbreakers.
Bolt-on branch breakers.
Factory assembled.
Refer to Page 14-5for additionalinformation.
Type PRL3a
Application Description
Lighting and appliance branchpanelboard or power distributionpanelboard.
Fully rated or series rated.
Interrupting ratings up to 200 kAsymmetrical.
Suitable for use as Service EntranceEquipment, when specified onthe order.
See Pages 14-5 through14-18foradditional information.
Standards and Certification
UL 67, UL 50.
Federal Specification W-P-115c.
Refer to Page 14-5for additional
information.
Options and Accessories
Refer to Page 14-46.
Layout and Sizing Refer to Page 14-27.
Product Selection
Formula Pricing: Base Price + Branch Circuits + Modifications = Total Price U.S. $
Table 14-25. Base Prices PRL3a
800 ampere MLO requires 28-inch (711.2 mm) wide box. 100,000 based on NEMA test procedure. Top feed only. Requires 6-1/2-inch (165.1 mm) deep box. Not available in Type 3R, 12, 4 and 4X enclosures. 100% rated circuit breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures.
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType
Price U.S. $
240 Vac 480 Vac 600 Vac 250 Vdc 3-Phase
4-Wire
1-Phase 3-Wire,
1-Phase 2-Wire
3-Phase
3-Wire
Main Lug Only
100250400600800
Main Breaker
100100100100100100100100100
100100
18 18 22 42 65100 65100200
200200
14 14 35 65100
150200
14 18 25 35
200
10 10 10 22 22
100
EHDFDBEDBEDSEDEDHFDHFDFDC
FCLFB-P
225225225225225225225225
22 42 65100200 65100200
35 65100
18 25 35
10 22 22
EDBEDSEDEDHEDCFDHFDFDC
250250250
65100200
35 65100
18 25 35
10 22 22
JDHJDJDC
400400400400400
400
65 65100200200
200
35 65100200
200
25 35 65
200
10 10 22 22
100
DKKDHKDKDCLCL
LA-P600600600600600600600600
65100 65100200 65100200
35 65 35 65100 35 65100
18 35 25 35 50 25 35 50
22 22 22 25 25 22 25 25
LGELGHLDHLDLDCCLD
CHLD
CLDC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
26/89
February 2007
4-26
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL3a
Table 14-26. Branch Circuit Breakers PRL3a
50 ampere devices are available as 2-pole only. 1-pole breaker rated 120 Vac. 2-pole breaker rated 120/240 Vac.
Arc fault circuit breaker. Arc fault circuit breaker with GFCI. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker. 1-pole breaker rated 277 Vac. For use on 480Y/277 volt systems only. AIC rating for 2- and 3-pole breakers only. Maximum of six breakers per panel, 175 225 amperes.
AmpereRating
Interrupting Rating (kA Symmetrical ) BreakerType
Price U.S. $
240 Vac 480 Vac 600 Vac 250 Vdc Breaker Space Only Provision Only
1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole
15 60 15 60 70 70 80 100 80 100 15 50
15 50
15 20 15 20 15 60 15 30 15 30 15 30
10
10 10
10 10
10 10
10 10
10
10
10
10
10
BABBAB-HBABBAB-HBABBAB-HQBGFQBGFEPQBAF
QBAG
BAB-D
BAB-C
BABRP
BABRSP
15 60 15 60 70 70 80 100 80 100
15 30 15 30 15 20 15 20
22
22 22
22 22
22
22 22 22
22
QBHWQBHW-HQBHWQBHW-HQBHWQBHW-H
QBHGFQBHGFEPQBHAF
QBHAG
15 20 15 20 25 60 70 100 15 30 15 20 15 30 15 60 15 20
65 65 65 65 65 65 65
14
14
14
14
25
14
14
14
14
1414141414
GHQGHBGHBGHBHGHBGHQRSP
GHBS
GHBGFEPGHBHID
15 60 70 100
18
18 14
14
1010
EHDEHD
15 60 70 100110 150
18 18 18
V14 14 14
141414
101010
FDBFDBFDB
15 60 70 100110 225
65 65
65
35 35
35
181818
101010
FDFDFD
15 60 70 100110 225
100
100
100
65
65
65
252525
222222
HFDHFDHFD
15 60 70 100110 225
200200200
100100100
353535
222222
FDCFDCFDC
100 225100 225100 225100 225100 225
22 42 65100200
EDB
EDS
ED
EDH
EDC
Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
27/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL3a
Figure 14-4. PRL3a Layout GHB, HGHB and GHQ breakers cannot be
mixed on same connector as BAB, QBHW,BABRP and BABRSP.
Maximum of six breakers per panel. Horizontal mounted 15 150 ampere mainbreakers EHD, FDB, FD, HFD and FDC, willbe furnished as branch breaker construction.Branch breakers 1-, 2- or 3-pole as required,may be located opposite these main breakers.
If optional terminal kit 3TA225FDK isrequired, use 10X.
FB-P and LA-P top mounting only. LCL or LA-P main breaker requires 6-1/2-inch
(165.1 mm) deep box.
Poles BAB, QBHW,
BABRP,BABRSP
GHQ, GHB,HGHB
6 - 3X
12 - 5X
18 - 8X
24 - 10X
30 - 13X
36 - 15X
42 - 18X
1X
2X
3X
EDB, EDS, ED,EDH, EDC,EHD, FDB, FD,HFD, FDC150 A Max. PerBranch Breaker(300 A Max. PerConnector)
2X2-Pole
EDB, EDS, ED,EDH, EDCFD, HFD, FDC
3X3-Pole
Neutral
Section
5X 100 250 A
8X 400 800 A
11X 800A withThru-feed Lug
Main LugSection
2X 100 A
5X 250 A
8X 400 600 A
14X 800 A
MainBreakerSection
Hori-zontalMount-ing
2X2-Pole
EHD, FDB, FD,HFD, FDC
3X3-Pole
EDB, EDS, ED,EDH, EDC
VerticalMount-ing
7X EHD, FDB, FD,HFD, FDC, EDB,EDS, ED, EDH,EDC
9X FCL, FB-P
14X JDHJD, JDC
15X DK, KDHKD, KDC
17X LD, HLD, LDCCLD, CHLD,CLDC
18X LGE, LGH
21X LCL, LA-P
1-Pole
2-Pole
1-Pole
2-Pole
1-Pole
2-Pole
3-Pole
2- or 3-Pole
Panel Layout Instructions1. Select:
a. Required mains (lugs orbreaker).
b. Neutral where required.
c. Branch circuits as required.
2. Layout panel as shown inFigure 14-4, using appropriateX dimensions.
3. Using total X units (panel height)find box height in inches (mm)and box catalog number fromTable 14-27. (When total X unitscome out to an uneven number,use next highest number; i.e., iftotal X comes out 25X, use 31X.)
Layout Example1. Description of Panel
Type PRL3a 3-phase, 4-wire,120/208 Vac flush mounting. Panelto have short circuit rating of22,000 symmetrical amperes.
Main breaker 400 amperes, 3-pole,bottom mounting. Branch circuitsbolt-on as follows:
12 20 ampere 1-pole QBHW1 200 ampere 3-pole ED1 225 ampere 3-pole ED
2. Layout Information fromFigure 14-4:
a. 400 ampere Neutral . . . . . . = 8X
b. 12-poles of QBHW . . . . . . . = 5X
c. Two 3-pole ED breakers . . . .= 6X
d. Main breaker, 400 amperes,3-pole DK . . . . . . . . . . . . . = 15X
Total Height . . . . . . . . . . . = 34X
3. From Table 14-27:
a. 34X Height (use 40X box)
b. Box Height . . . . . . . . . 72 inches(1828.8 mm)
c. Box Catalog Number. . . . YS2072. . . . . . . . . . . . . . . . or EZB2072R
Table 14-27. Box Tabulation PRL3a
Cabinets
Fronts are code-gauge steel, ANSI-61
light gray painted finish.Boxes are code-gauge galvanized steelwithout knockouts. Standarddepth is 5-3/4 inches (146.1 mm).
Standard widths are:
20-inch (508.0 mm) 100 600 amperes.28-inch (711.2 mm) 800 amperes.
Standard Depth
5-3/4 inches (146.1 mm).
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Side Gutters
4 inches (101.6 mm) minimum.
XUnits
Box Height YS BoxCatalogNumber
LT TrimCatalogNumber
EZ BoxCatalogNumber
EZ TrimCatalogNumber
Inches mm
100 400 Amperes
14X23X31X40X53X
3648607290
914.41219.21524.01828.82286.0
YS2036YS2048YS2060YS2072YS2090
LT2036S or FLT2048S or FLT2060S or FLT2072S or FLT2090S or F
EZB2036REZB2048REZB2060REZB2072REZB2090R
EZT2036S or FEZT2048S or FEZT2060S or FEZT2072S or FEZT2090S or F
600 Amperes
23X31X40X53X
48607290
1219.21524.01828.82286.0
YS2048YS2060YS2072YS2090
LTV2048S or FLTV2060S or FLTV2072S or FLTV2090S or F
EZB2048REZB2060REZB2072REZB2090R
EZTV2048S or FEZTV2060S or FEZTV2072S or FEZTV2090S or F
800 Amperes
23X31X40X53X
48607290
1219.21524.01828.82286.0
YS2848YS2860YS2872YS2890
LTV2848S or FLTV2860S or FLTV2872S or FLTV2890S or F
7/13/2019 Tb 01400001 e
28/89
February 2007
4-28
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL4
Type PRL4
Type PRL4B Circuit Breaker Panelboard
Product Description
600 Vac maximum (250 Vdc).
3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
PRL4B circuit breaker panelboard.
PRL4F fusible switch panelboard.
1200 ampere maximum mains.
1200 ampere maximum branchdevices.
Bolt-on branch devices.
Factory assembled.
Refer to Page 14-5for additionalinformation.
Type PRL4F Fusible Panelboard
Application Description
Power distribution panelboard.
Fully rated or series rated.
Interrupting ratings up to 200 kAsymmetrical.
Suitable for use as Service EntranceEquipment, when specified onthe order.
See Pages 14-5 through14-18foradditional information.
Standards and Certifications
UL 67, UL 50.
Federal Specification W-P-115c.
Refer to Page 14-5for additionalinformation.
Options and Accessories
Refer to Page 14-46.
Layout and Sizing PRL4B Refer to Pages 14-33
through14-35.
PRL4F Refer to Pages 14-36through 14-38.
7/13/2019 Tb 01400001 e
29/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL4
Product SelectionFormula Pricing: Base Price + Branch Devices + Modifications = Total Price U.S. $
Table 14-28. Base Prices PRL4 Main Lugs and Main Breakers
For ground fault protection on main devices, see Modification 14 Applies to 310 and 310+ Trip Units or Modification 15, Page 14-48. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Requires 44-inch (1117.6 mm) wide box.
Table 14-29. Base Prices PRL4 Main Fusible Switches
For ground fault protection on main devices, see Modification 15, Page 14-48. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, add $308. per switch. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below. No dc rating on 600, 800 and 1200 ampere switches.
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType
Price U.S. $
240 Vac 480 Vac 600 Vac 250 Vdc 3-Phase4-Wire
1-Phase 3-Wire,1-Phase 2-Wire
3-Phase3-Wire
Main Lug Only
250 400 600 8001200
Main Breaker
250 250 250 250
65100200200
35 65100200
18 25 35
102222
JDHJDJDCLCL
400 400 400 400 400 400 400
400
65 65 65100100200200
200
35 35 65 65100200
200
25 25 35 35 65
200
10102222
DKKDCKD
HKDCHKD
KDCLCL
LA-P 600 600 600 600 600 600 600 600
65100 65 65100100200200
35 65 35 35 65 65100100
18 35 25 25 35 35 50 50
2222222525
LGELGHLDCLD
HLDCHLD
LDCCLDC
800 800 800 800 800
65100 65100200
50 65 50 65200
25 35 25 35200
2225
MDLHMDLCMDL
CHMDL
NB-P
800 800 800 800 800 800
65100200 65100200
50 65100 50 65100
25 35 65 25 35 65
NDHNDNDCCND
CHND
CNDC
120012001200120012001200
65100200 65100200
50 65100 50 65100
25 35 65 25 35 65
NDHNDNDCCND
CHND
CNDC
AmpereRating
Interrupting Rating (kA Symmetrical) Price U.S. $
240 Vac 480 Vac Device Type 3-Phase 4-Wire 1-Phase 3-Wire, 1-Phase 2-Wire 3-Phase 3-Wire
Main Fusible Switch 240 Vac, 250 Vdc
200
400 600
800
1200
See Table 14-32 FDPB
FDPWFDPWFDPWFDPW
Main Fusible Switch 600 Vac
200 400 600
800
1200
See Table 14-32 FDPBFDPWFDPWFDPWFDPW
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
30/89
February 2007
4-30
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL4
Table 14-30. Branch Devices PRL4
Includes provisions for breaker types BAB, BAB-H, QBGF, QBHW, QBHW-H, QBHGF, GHQ, GHB, HGHB.
50 ampere devices are available as 2-pole only. 1-pole breakers rated 120 Vac. 2-pole breakers rated 120/240 Vac. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. 1-pole breakers rated 277 Vac. At 480 volts, must be used on 480Y/277 volt grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Available in single branch mounting only.
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType
Price U.S. $ Price U.S. $ Space Only Price U.S. $3-PoleProvision
240 Vac 480 Vac 600 Vac 250 Vdc 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole
15 60 15 60
70 100 70 100 15 50
15 20 15 20
10
10
10
10 10
10
10
BABBAB-H
BABBAB-HQBGFQBAF
QBAG
15 60 15 60 70 100 70 100 15 30 15 20 15 20
22
22 22
22 22
22
22
QBHWQBHW-HQBHWQBHW-HQBHGFQBHAF
QBHAG
15 20 15 60 70 100 15 30
65
65
65
65
14
14
14
25
1414
GHQ
GHB
GHB
HGHB
15 60 70 100 15 60
70 100110 150
18
18
18
18 18
14
14
14
14 14
14
1414
101010
1010
EHDEHDFDB
FDBFDB
15 60 70 100110 225 15 60 70 100110 225
65
65
65
100
100
100
35
35
3565
65
65
181818252525
101010222222
FDFDFDHFDHFDHFD
15 60 70 100110 225 15 100
200200200200
100100100150
353535
222222
FDCFDCFDCFCL
100 225100 225100 225100 225100 225
22 42 65100200
EDBEDSEDEDHEDC
70 225250 70 225250 70 225250
65 65100100200200
35 35 65 65100100
181825253535
101022222222
JDJDHJDHJDJDCJDC
125 250 200 200 LCL
250 400100 400100 400100 400100 400100 400
65 65 65100100200
35 35 65 65100
2525353565
10102222
DKKDCKD
HKDCHKD
KDC
200 400 200 200 LCL
250 600300 600300 600
65 65 65
35 35 35
182525
2222
LGELDCLD
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
31/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL4
Table 14-30. Branch Devices PRL4 (Continued)
100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. 100% rated breaker. Requires 44-inch (1117.6 mm) wide box. 100,000 AIC based on NEMA test procedure. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, add $308. per switch (T fuse clips not available for
200/200 twin switches). When branches of a twin unit are of different ampere ratings, as a 30 60 twin unit, price and layout as a 60 60 twin unit;
when a 60 100 twin unit, price and layout as a 100 100 twin unit. No dc rating on 600, 800 and 1200 ampere switches. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts.
AmpereRating
Interrupting Rating (kA Symmetrical) DeviceType
Price U.S. $ Price U.S. $ Space Only Price U.S. $3-PoleProvision
240 Vac 480 Vac 600 Vac 250 Vac 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole
250 600 300 600
300 600 300 600 300 600
100100
100200200
65 65
65100100
3535
355050
2225
2525
LGHHLD
CHLD
LDCCLDC
400 800 400 800 400 800 400 800
65100 65100
50 65 50 65
25352535
2225
MDLHMDLCMDL
CHMDL
400 800 400 800 400 800 400 800 400 800 400 800
65100200 65100200
50 65100 50 65100
25 35 65 25 35 65
NDHNDNDCCND
CHND
CNDC
600 1200 600 1200 600 1200 600 1200 600 1200
600 1200
65100200 65100
200
50 65100 50 65
100
25 35 65 25 35
65
NDHNDNDCCND
CHND
CNDC
Integrally Fused, Current Limiting Circuit Breaker
15 100 125 225 250 400 400 600 700 800
200200200200200
200200200200200
200200200200200
FB-PLA-PLA-PNB-PNB-P
Fusible Switches 240 Vac, 250 Vdc
30/30
60/60
100/100
200/200 100 200
See Table 14-32 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPW-SingleFDPB-Single
400 600
800
1200
See Table 14-32 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single
Fusible Switches 600 Vac
30/30
60/60
100/100
200/200
100 200
See Table 14-32 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPW-SingleFDPB-Single
400 600
800
1200
See Table 14-32 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
32/89
February 2007
4-32
For more information visit: www.eaton.com CA08101001E
Panelboards
4
Pow-R-Line C Panelboards
PRL4
Table 14-31. Branch Devices Earth LeakageGround Fault Circuit Breakers PRL4(Adj. Pickup from 30 mA to 30 A)
Note: Terminals and external accessoriesare the same as standard breakers. F-Frame
breakers are twin mounted (3X). J-Frame(3X) and K-Frame (4X) are single mountedonly. 36-inch (914.4 mm) minimum box width.
Table 14-32. FDPW and FDPB Switch Ratings,240 or 600 Vac
No dc rating on 600, 800 and 1200 ampereswitches.
Class J fuse provisions are applicable to600 volt units. When required, use price anddimensions of 600 volt units for all voltages600 volts and below.
Twin 200 ampere switches are not availablewith Class R fuse clips at 600 volts.
When shunt trip is required, 400 600ampere switches used with Class R fusesare rated 100,000 AIC.
AmpereRating
kAIC (sym.) BreakerType
Price U.S. $
480 Vac 3-Pole
35 60 70 100110 150
35 35 35
ELFDELFDELFD
35 60 70 100110 150
65 65 65
ELHFDELHFDELHFD
35 60 70 100110 150
100100100
ELFDCELFDCELFDC
100 250100 250100 250
35 65100
ELJDELHJDELJDC
200 400200 400200 400
35 65100
ELKDELHKDELKDC
AmpereRating
FuseClassUsed
Short CircuitRatings(Sym. Amperes)
30 100
200 Single200 Twin400, 600
800, 1200
R, J
R, JR, J, TR, J, TL
200,000
200,000200,000200,000200,000
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
7/13/2019 Tb 01400001 e
33/89
February 2007
CA08101001E For more information visit: www.eaton.com
14PanelboardsPow-R-Line C Panelboards
PRL4
Layout and Sizing PRL4BMain Lug (MLO), Main Breaker, Neutral, Through-Feed (TFL)and Sub-Feed Lug (