It’s Getting Hot In Here New solutions for data center cooling
November 2014
The Advancing Trend Moving From Air to Liquid
• Many industry experts and vendors recognise liquid cooling is the future for data centres
• Liquids Carry 1000’s of times more heat per volume
• At ISC this year, 21 different liquid cooling solutions were exhibited
• This presentation highlights the trend and offers Iceotope’s perspective, as well as giving an insight into Iceotope’s patented technology.
• Liquid cooling is being adopted for a variety of reasons: • Efficiency • Density • Total Cost • Hostile or Complex Environments
From Air To Liquid
Cooling
Liquid Cooling
Direct Liquid Cooling
Total Liquid Cooling
• Air is passed through servers and then through a rear door or in row air-water heat exchanger.
• Liquid is taken direct to some components • Fans are still needed.
• All components are cooled directly by liquid. Air side losses are minimised.
• Inside the DC, the system has no fans and breathes no air.
The Benefits of Advancing Liquid Cooling Technolgies
Cooling
Liquid Cooling
Direct Liquid Cooling
Total Liquid Cooling
• Offers Better Density • Offers Better Efficiency.
• Offers better Density • Offers better Efficiency.
• Eliminates/Massively Reduces air based infrastructure. (Fridge Argument)
• Offers better efficiency still. • Density is high, especially overall.
Cooling With Liquids
0 10 20 30 40 50 60 70 80 90 100
Co
st (
TCO
)
% Maximum Heat Captured Direct to Liquid
Total Cost Vs % Heat Max Captured to Liquid
Zon
e O
f To
tal L
iqu
id C
oo
ling
TCO Reduces Because of Increasing Efficiency
Step Change in TCO Because of
CapEx Reduction
Not to Scale, general trend illustrated, situations may vary results
ASHRAE Water Cooling
Hotter Coolants Reduce Total Cost
15 20 25 30 35 40 45 50 55 60
Co
st (
TCO
)
Temperature (C)
Cost Vs Maximum Coolant Input Temperature
Zone Of Full Time Free Cooling
Reducing TCO With
Increasing Efficiency
Step Change Due to
Removal of Chillers
Not to Scale, general trend illustrated, situations may vary results
Reducing TCO as waste heat is
more valuable
The Cost Reduction Oasis
Who Are Iceotope?
• British Startup company based in Sheffield, UK • Backed By:
• Schneider Electric • Solvay Specialist Plastics
• Additional partnerships with: • Intel • 3M
• ASHRAE W4 & Total Liquid Cooling
Our Ethos: The Elimination Of Waste
1. Waste infrastructure required to support servers 2. Waste power consumed in supporting the
electronics – and running the same electronics with greater speed and efficiency
3. Waste product – producing a viable waste product in the form of hot water
Air Conditioners
IT Cabinets AKA “Racks” Each contains 10-20 Servers
Raised Floor
Back Up Batteries AKA “UPS” Generators
x4
External Coolers
x8
Power Distribution
1. TLC needs no A/C
3.TLC servers have no fans – use less power
2. No Airflow, no raised floor
4. No A/C, average and peak power consumption reduced
x10
x4
x8
x78
x3
x0
5. At least 2x as many servers per Cabinet
x2
x2
x8 x4
x39 72
The Iceotope Revolution
The Iceotope Blade, developed in partnership with Intel, is sealed electronics are immersed
Exotic Coolant
High Thermal Expansivity
Electrical Insulator
Certified non-flammable
Non Ozone depleting
Clean & Safe
Cooler Servers Run Faster & More Efficiently
• Cooler servers better leverage Turbo modes • Dual E5 2699 v3 processors supported • Up to 60kW (72 Blades per cabinet) • Up to 14kW/sqm • Up to 45C (113F) input coolant
Real World Results
• Cooling Overhead (internal): as low as 0.33%
• Cooling Overhead (external): 1.7% - 4% (pPUE 1.017-1.04 @30KW/cab) • Poznan National Supercomputing Centre indicated 1.7% (2% overall) average • Romonet indicated 4% cooling overhead in 2N model in Houston Texas
• IT Energy Reduction vs Fan Cooled: 8% • Based on measurements at Leeds University (Chi et Al 2013)
• Overall performance per watt benefit vs equivalent servers in a high density, close coupled cooling environment: 40.8% • Based on studies at Leeds University (Chi et Al 2013)
Questions?
• Please Follow Us On Twitter • @Iceotope
• And our Chief Visionary Officer • @PeteHopton
• Plus, Visit our Stand to see: • A Total Liquid Cooled Cluster Running Flat Out • Silent • PUE <1.01