APPROVED FOR PUBLICATION
Washington State Department of Transportation
STATE DESIGN ENGINEER
1
KEY
2
3 PHOTOCELL BREAKER ~ SPST 15 AMP - 120/240 VOLT
4
5
6 BRANCH BREAKER ~ SEE BREAKER SCHEDULE
7 SIGNAL BREAKER ~ SEE BREAKER SCHEDULE
8
9 RECEPTACLE BREAKER ~ SPST 20 AMP - 120/240 VOLT
10 RECEPTACLE (GROUNDED) ~ GFCI 20 AMP - 125 VOLT
11
12
13
POLISHED WIRE GLASS WINDOW
HINGED FRONT FACING DOOR WITH 4" (IN) x 4" (IN) MINIMUM
14
15
16 SPARE BRANCH BREAKER ~ DPST 20 AMP - 120/240 VOLT
17 METAL WIRING DIAGRAM HOLDER
18 1/4" (IN) DIAMETER DRAIN HOLE ~ DRILL BEFORE GALVANIZING
19 MOUNTING HOLE ~ SEE SERVICE CABINET MOUNTING DETAILS
20
MAIN BREAKER
18-CIRCUIT PANEL BOARD ~ MINIMUM SIZE WITH SEPARATE
21 LABEL CABINET WITH BUSSWORK RATING
15 AMP - 120/277 VOLT - "T" RATED
TEST SWITCH ~ SPDT SNAP ACTION - POSITIVE CLOSE
PHOTOCELL MOUNTING DETAIL
MESH MAY BE USED AS ALTERNATIVE MATERIAL ~ SEE
5/8" (IN) OPENINGS EQUIVALENT TO 5/8" (IN) EXPANDED STEEL
FABRICATION ~ TYPE 5052 - H32 ALUMINUM WITH 5/8" (IN) x
AND MOUNTING FLANGES ~ HOT-DIP GALVANIZED AFTER
FROM 5/8" (IN) EXPANDED STEEL MESH WITH WELDED SEAMS
PHOTOCELL ENCLOSURE ~ ENCLOSURE TO BE FABRICATED
SERVICE CABINET DETAIL
LEFT SIDE
21
17
PHOTOELECTRIC CONTROL ~ SEE
SPECIFICATION 9-29.11(2)
STANDARD
ISOLATED NEUTRAL BUSS ~ 14 LUG COPPER
MAIN BREAKER ~ DPST ~ SIZE PER BREAKER SCHEDULE
JUMPER ASSEMBLY DETAIL
BE 14 LUG TINNED COPPER ~ SEE CABINET MAIN BONDING
CABINET MAIN BONDING JUMPER ASSEMBLY ~ BUSS SHALL
SHEET 1 OF 5 SHEETS
120/240 SINGLE PHASE)
MODIFIED (0 - 200 AMP TYPE
SERVICE CABINET TYPE B
STANDARD PLAN J-10.20-01
DR
AW
N B
Y:
CO
LB
Y F
LE
TC
HE
R
EXTEND INTO VERTICAL LIMITS OF THE BREAKER ARRAY(S)
SLIDE LATCHES ~ DEAD FRONT PANEL BOLTS SHALL NOT
HINGED DEAD FRONT WITH 1/4 TURN FASTENERS OR
SECTION
DOOR HINGE DETAIL
DOOR HINGE DETAIL
NEOPRENE GASKET
CLOSED CELL
1/4" (IN) x 1 1/4" (IN)
CABINETDOOR
DOOR
BARREL
OPEN ~ 3/8"
HIGH x 2" (IN)
HINGE ~ 2" (IN)
CABINET
LAP WELD
1/8
PIANO HINGE
PANEL WALL
CABINET OR
1/8PANEL DOOR
A
A
CABINET
ALTERNATE TYPE B MODIFIED
(SEE NOTE 15)
TYP.
SIDESTHREE
NEOPRENE GASKET
1/4" (IN) x 5/8" (IN)
PHOTOCELL ENCLOSURE MOUNTING DETAIL
NUT
FLANGE
ENCLOSURE
PHOTOCELL
METAL WASHERS
NUT
CABINET
SERVICE
PRIOR TO INSTALLATION
SIDES OF RUBBER WASHER
SILICONE SEALER TO BOTH
RUBBER WASHER ~ APPLY
MACHINE BOLT
1/4" (IN) x 1" (IN)
4
1
32
15
TEST ON
PHOTOCELL BYPASS
W
5
B R
120/240 VAC
{
7
SIGNAL CKT
{
ILL CKT A
86
{
16
SPARE CKT
AUTOMATIC
TEST OFF -
PHOTOCELL
{
ILL CKT B
6 8
9
10
11
WIRING DIAGRAM
SIZE PER NEC ~ MINIMUM SIZE #2
CABINET BONDING JUMPER ~
VENTS
6"
3’ - 4"
1’ - 7"
18
HINGE DETAIL
SEE DOOR
12
5
NOTE 6)
(SEE
1
18
VENTS
5
12
HINGE DETAIL
SEE DOOR
RIGHT SIDE
14
FRONT
3’ - 4"
1’ - 10"
4
WARNING
Hazard
Arc Flash
Potential
LABEL "A"
PHOTOCELL
TEST
OFF/AUTOMATIC
PHOTOCELL
BYPASS
TEST ON
13
6"
12
5
19 19
19 19
19
10"
2"
MIN.
19
18
18
11"
1
PHOTOCELL
TEST
OFF-AUTOMATIC
PHOTOCELL
BYPASS
TEST ON
(SEE NOTE 6)
STAINLESS STEEL
BASE ENCLOSURE SHALL BE FABRICATED FROM TYPE 304
ON THE SIDE OR BACK OF THE SERVICE CABINET, THE METER
WHEN THE UTILITY REQUIRES METER BASE TO BE MOUNTED
~ EUSERC DRAWING 305MEETS THE REQUIREMENTS OF
WITH FACTORY-INSTALLED TEST BYPASS FACILITY THAT
MINIMUM, THE METER BASE SHALL BE SAFETY SOCKET BOX
METER BASE PER SERVING UTILITY REQUIREMENTS ~ AS A
LABEL "A"
BARRIER
CONTACTOR (BEHIND DEAD FRONT) ~ SEE BREAKER SCHEDULE
WARNING
Hazard
Arc Flash
Potential
3
7
2
9
10
6 6
16
20
15
14
8
PHOTOCELL
TEST
OFF-AUTOMATIC
PHOTOCELL
BYPASS
TEST ON
MOUNTING PANEL
REMOVABLE
LABEL "A"
8
SLIDE LATCH (TYP.)
11
(TYP.)
1/4 TURN FASTENER
OR
RIGHT HALF SERVICE CABINET DETAIL
CABINET DETAIL
SEE RIGHT HALF SERVICE
STAT
EOFWASHINGTON
REGISTERED
PROFESSIONAL ENGI
NEER
39820
YELI
AB
HPESOJ ERODOE
HT
APPROVED FOR PUBLICATION
Washington State Department of Transportation
STATE DESIGN ENGINEER
SHEET 2 OF 5 SHEETS
LEFT SIDE - SAFETY SOCKET BOX MOUNTING DETAIL
10 1/2"
6"
10 1/2"
6"
6"
1’ - 7"
5" MIN.
11" MAX.
(TYP.) ~ SEE DETAIL
MOUNTING BLOCK
OF DOOR
INSIDE FACE
(TYP.)
90° +/- 1°
1 1/2" (TYP.)
SAFETY SOCKET BOX
FRONT SURFACE OF
WASHER ~ EACH SIDE OF PANEL
CUT OFF AFTER ADJUSTMENT
ALL-THREAD ~ 6 PLACES (TYP.) ~
1/2" (IN) UNC S.S. x 8" (IN) LONG
(SEE NOTE 16)
THREE 1/2" (IN) S.S. NUTS (TYP.)
DIMENSION
STAND-OFF
(SEE NOTE 16)
TOP AND BOTTOM ~ SPACED EVENLY
MACHINE SCREWS, WASHERS, AND NUTS ~
FOUR 1/4-20 S.S. PANHEAD PHILLIPS
1/2" (IN) RETURN ~ WELD AT CORNERS
12-GAGE REMOVABLE PANEL
MOUNTING BLOCK DETAIL
FRONT VIEW SIDE VIEW
FOUR PLACES
TACK WELD BOLT TO NUT ~
SAME AS CABINET MATERIAL
12-GAGE ~ MATERIAL SHALL BE THE
1’ - 6 1/2"
3/32 3/32 OF MOUNTING BLOCK
WELD TO EACH END
PLATE (TYP.)
2" (IN) x 3" (IN) END
3/8"
1 1/2"
1 1/2"
3"
PLATE BEFORE WELDING
PLACE NUT AGAINST END
2"TYP.
3/32 TYP.
SIDE WALL
CABINET
120/240 SINGLE PHASE)
MODIFIED (0 - 200 AMP TYPE
SERVICE CABINET TYPE B
STANDARD PLAN J-10.20-01ELEVATION VIEW
CABINET MAIN BONDING JUMPER ASSEMBLY DETAIL
SIDE VIEW BSECTION
2 1/1
6"
(TY
P.)
1/2" MIN. (TYP.) BUSS
2" (IN) x 7 5/8" (IN) ANGLE
3/16" (IN) x 2" (IN) x
B
1/8SIDE
OTHER
TYP.
2 1/16PLACES
FOUR
TYP.
1/8
SIDE WALL
CABINET
STAINLESS STEEL ALLEN HEAD (TYP.)
CABINET SIDE WALL
PAST THE FACE OF THE NUTS
MORE THAN 3 FULL THREADS EXTEND
BOLT SO THAT NO LESS THAN 2 AND NO
ANTI-OXIDANT COMPOUND ~ CUT OFF
LIBERALLY COAT ASSEMBLY WITH
WITH TWO STAINLESS STEEL NUTS ~
1/4" (IN) x 2" (IN) STAINLESS STEEL BOLT
FLAT WASHER
STAINLESS STEEL
(TYP.)
FILLET WELD
STEEL SPRING WASHER
BELLEVILLE STAINLESS
Hinges shall have stainless steel or brass pins.
rain-tight vents.
Cabinets shall be rated NEMA 3R and shall include two
TEST OFF-AUTOMATIC". See Service Cabinet Detail.
"PHOTOCELL BYPASS TEST ON" and "PHOTOCELL
Key Number 4 name plate shall read:
Key Numbers 2, 3, 4, 6, 7, 8, 9, & 16
plate attached with screws or rivets:
shall have an appropriately engraved phenolic name
The following equipment within the service enclosure
accommodate the various sizes of equipment installed.
Dimensions shown are minimum and shall be adjusted to
equipment as shown in the breaker schedule.
allowed. Busswork shall accommodate all future
onto the busswork. Jumpering of breakers shall not be
or exceed the main breaker rating. All breakers shall bolt
All busswork shall be high-grade copper and shall equal
the photocell enclosure.
photocell without removal of the photocell unit or
enclosure to permit 360 degree rotation of the
The photocell unit shall be centered in the photocell
shall be used.
Approved PVC or polyolefin wire marking sleeves
letters and/or numbers shown on the schedules.
"TO - FROM" coded tags labeled with the code
All internal wire runs shall be identified with
photocell enclosure shall be stainless steel.
All nuts, bolts, and washers used for mounting the
A 1% tolerance is allowed for all dimensions.
stainless steel.
clamps shall be hot-dipped galvanized steel or
components shall be stainless steel. Conduit
Slotted steel channel and mounting hardware
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
NOTES (200 AMP TYPE 120/240 1ł SERVICE CABINET)
requirements.EUSERC Drawing 309
designed to meet metering portion of
The meter base portion of this service was
Standard Specification 9-29.24 (Service Cabinets).See
of the service equipment.
Utility’s requirements prior to fabrication and installation
Mounting Detail. The Contractor shall verify the serving
11" (in) shown in the Left Side - Safety Socket Box
and the front of the safety socket box to be less than the
The Utility may require the dimension between the door
enclosure, on the side, or on the back of the enclosure.
The Utility may require meter base mounting in the
Metering arrangements vary with different serving Utilities.
Core on right side door. See Door Hinge Detail.
door shall be gasketed. Install Best CX Construction
Metering equipment door shall be pad-lockable. Each
17.
more than three full threads extend past the face of the nuts.
adjustment, cut off all-thread bolts so that no less than two and no
panel to the measurement provided by the Utility Company. After
Verify the service utility stand-off dimension. Adjust the removable
with brass pin and solder in place.
prior to hot-dip galvanizing. After galvanizing, replace pin
Remove hinge pin prior to welding hinge to cabinet and
When using alternate door hinge:
used. Three pairs required.
back to back continuous slotted steel channel may be
steel channel or factory welded 1 5/8" (in) x 1 5/8" (in) 12-gage
supports, 1 5/8" (in) x 3 1/4" (in) 12-gage continuous slotted
As an alternate to the bolted or field welded strut mount
DRAWN BY: COLBY FLETCHER
PANEL
REMOVABLE
STAT
EOFWASHINGTON
REGISTERED
PROFESSIONAL ENGI
NEER
39820
YELI
AB
HPESOJ ERODOE
HT
APPROVED FOR PUBLICATION
Washington State Department of Transportation
STATE DESIGN ENGINEER
SHEET 3 OF 5 SHEETS
CABINET BRACKET MOUNTING DETAIL
SERVICE CABINET
SPRING NUT
POST
TIMBER
CHANNEL BRACKET
SLOTTED STEEL
TO UTILITY
FRONT OF SERVICE CABINET
POST MOUNT STRAP DETAIL
GALVANIZED STRAP
2" (IN) x 1/8" (IN) HOT-DIPPED
RIGHT SIDE OF SERVICE CABINET
5’ - 0"
MINIM
UM
6’ - 0"
MA
XIM
UM
LOCK WASHER, AND NUT (TYP.)
3/8" (IN) DIAM. x 1" (IN) BOLT,
OR SERVED DEVICES
TO LUMINAIRES
CONDUIT SUPPORT DETAIL
TIMBER POST
TREATED
6" (IN) x 8" (IN)
SIZE TO LENGTH
ALL-THREAD ROD (TYP.) ~
3/8" (IN) HOT-DIP GALVANIZED
SIZE TO LENGTH
RIGID METAL CONDUIT ~
1 1/4" (IN) DIAM.
STANDARD PLAN J-10.20-01
120/240 SINGLE PHASE)
MODIFIED (0 - 200 AMP TYPE
SERVICE CABINET TYPE B
STEEL CHANNEL
12-GAGE SLOTTED
1 5/8" (IN) x 1 5/8" (IN)
FRONT OF SERVICE CABINET
SINGLE POST MOUNTTWO POST MOUNT
4
CABINET
TO CONTROLLER
TO UTILITY
TIMBER POST
TREATED
6" (IN) x 8" (IN)
CONDUIT SUPPORT DETAIL
1"
(TYP.)
AND NUT (TYP.)
PLATE WASHER
HOT-DIP GALVANIZED
AND NUT (TYP.)
PLATE WASHER
HOT-DIP GALVANIZED
FLAT WASHER AND NUT (TYP.)
3/8" (IN) HOT-DIP GALVANIZED CLAMP WITH BOLT (TYP.)
TWO-PIECE CONDUIT
PLATE WASHER (TYP.)
HOT-DIP GALVANIZED
PLATE WASHER (TYP.)
HOT-DIP GALVANIZED
DR
AW
N B
Y:
CO
LB
Y F
LE
TC
HE
R
WITH BOLT (TYP.)
CONDUIT CLAMP
TWO-PIECE
FLAT WASHER AND NUT (TYP.)
3/8" (IN) HOT-DIP GALVANIZED
(SINGLE POST MOUNT ONLY) (TWO POST MOUNT ONLY)
POST MOUNTS)
(FOR SINGLE POST AND TWO
POST MOUNTS)
(FOR SINGLE POST AND TWO
(SINGLE POST MOUNT ONLY)
SIZE TO LENGTH
ALL-THREAD ROD (TYP.) ~
3/8" (IN) HOT-DIP GALVANIZED
TO LENGTH (TYP.)
METAL CONDUIT ~ SIZE
1 1/4" (IN) DIAM. RIGID
STEEL CHANNEL
12-GAGE SLOTTED
1 5/8" (IN) x 1 5/8" (IN)
TO CONTROLLER CABINET
10’ (FT) LONG
6 x 8 TREATED TIMBER POST ~
SUPPORT DETAIL
THREADS ~ SEE CONDUIT
ASSEMBLY ~ PEEN BOLT
CONDUIT SUPPORT
AND POST MOUNT STRAP DETAIL
CABINET MOUNTING DETAILS
BRACKET ~ SEE SERVICE
TO SLOTTED STEEL CHANNEL
SERVICE CABINET BOLTED
STRAP DETAIL
SEE POST MOUNT
BEVEL 1/2"
POST MOUNT ONLY)
STRAP DETAIL (SINGLE
DETAILS AND POST MOUNT
CABINET MOUNTING
THREADS ~ SEE SERVICE
CHANNEL ~ PEEN BOLT
AND NUTS FOR EACH
3/8" (IN) BOLTS, WASHERS,
TO POST ~ USE TWO
BRACKETS BOLTED
STEEL CHANNEL
12-GAGE SLOTTED
1 5/8" (IN) x 1 5/8" (IN)
+/- 1°
CONDUIT
PLUMB
SERVED DEVICES
TO LUMINAIRES OR
POST ~ 10’ (FT) LONG (TYP.)
6 x 8 TREATED TIMBER
2’ - 0"2’ - 0"
2’ - 0"
PLAN VIEW
POST MOUNTS)
MAINTENANCE PAD (FOR SINGLE POST AND TWO
9"
MAINTENANCE PAD
FOR STRUT MOUNT
~ NOT REQUIRED
FOR EACH CHANNEL)
3/8" (IN) BOLT (TWO
(THREE FOR EACH CHANNEL)
LOCK WASHER AND SPRING NUT
STEEL CHANNEL BRACKET WITH
BOLT SIZED FOR SLOTTED
STEEL CHANNEL
SLOTTED
SERVICE CABINET
1
(SEE NOTE 6)
4
SPEC. 9-07.7
STD. OF PAD ~ SEE
PLACED IN CENTER
4 x 4 ~ W4.0 x W4.0 ~
WELDED WIRE FABRIC
5’ - 0"
MINIM
UM
1
(SEE NOTE 6)
6’ - 0"
MA
XIM
UM
5 (TYP.)55 5 (TYP.)
STAT
EOFWASHINGTON
REGISTERED
PROFESSIONAL ENGI
NEER
39820
YELI
AB
HPESOJ ERODOE
HT
APPROVED FOR PUBLICATION
Washington State Department of Transportation
STATE DESIGN ENGINEER
DR
AW
N B
Y:
CO
LB
Y F
LE
TC
HE
R
FRONT OF SERVICE CABINET
1
2
3
RIGHT SIDE OF SERVICE CABINET
4
(SEE NOTE 6)
5’ - 0"
MINIM
UM
6’ - 0"
MA
XIM
UM
#4 HOOPS
BOLT (TYP.)
ANCHOR
EACH CORNER
#4 BARS
3"
TO CONTROLLER CABINET
4TO UTILITY
2
9"
CABINET
CONTROLLER
FRONT OF
2’ - 0"
POLICE PANEL
WITH APPROVED COVER (TYP.)
13" (IN) DIAM. DRAIN TILE
3
2’ - 0"
5
LOCATE DRAIN AWAY FROM ACCESS DOORS
SLOPE TO DRAIN OUTSIDE FOUNDATION ~
POLYETHYLENE OR COPPER DRAIN PIPE ~
FOUNDATION TOWARD SUMP ~ 3/8" (IN) DIAM.
4" (IN) DIAM. x 1/2" (IN) DEEP SUMP. SLOPE
TO SERVICE GROUND ~ PER
PLAN J-60.05
STANDARD
9"
OF PAD ~ SEE
PLACED IN CENTER
4 x 4 ~ W4.0 x W4.0 ~
WELDED WIRE FABRIC
SPEC. 9-07.7
STD.
OF PAD ~ SEE
PLACED IN CENTER
4 x 4 ~ W4.0 x W4.0 ~
WELDED WIRE FABRIC
SPEC. 9-07.7
STD.
ROD (TYP.)
GROUND
(TYP.)
2’ - 0"
MIN.
(TY
P.)
3"
(TYP.)
PLUMB CONDUIT +/- 1°
CONDUITS AS REQUIRED ~
5
OR SERVED DEVICES
TO LUMINAIRES
TO THE CABINET GROUNDING BUSS
GROUNDING END BUSHING AND BONDED
CABINET SHALL BE TERMINATED WITH
ALL RMC CONDUITS PENETRATING
1
D
SECTION C
C
D
12"
MA
X.
(TY
P.)
1"
1/8 @ 12
1/8 @ 12
END
FROM EACH
1" (IN) MIN.
(SEE NOTE 17)
PLAN VIEW OF SERVICE CABINET
CABINET
CONTROLLER
CABINET
SERVICE
DO
OR
3
2’ - 0"2’ - 0" CABINET BASE
1" 1"
TWO #4 HOOPS
1"
2’ - 0"
CA
BIN
ET
BA
SE
1"
1’ - 7"
2’ - 0"
1#4 BAR EACH CORNER
"X"
"X"
"X"CABINET TYPE
332 OR 334 TYPE CABINET
333SD TYPE CABINET
332D OR 334D TYPE CABINET
NEMA P44 TYPE CABINET
26"
24"
26"
46 1/2"
STD. PLAN J-10.10
PLUS 2 INCHES
"X" = WIDTH OF DOOR OPEN TO 180°
:IS NOT LISTED ON
FOR A SPECIAL DESIGN CABINET THAT
SPACING TABLETABLE)
SPACING
(SEE
TA
BLE)
SP
ACIN
G
(SE
E
STRUT MOUNT SUPPORT DETAILS
BRACKETS (TWO REQUIRED)
SLOTTED STEEL CHANNEL
1 5/8" (IN) x 1 5/8" (IN) 12-GAGE
SUPPORT DETAILS
IN FOUNDATION ~ SEE STRUT MOUNT
SLOTTED STEEL CHANNEL ~ EMBED 12" (IN) MIN.
1 5/8" (IN) x 3 1/4" (IN) 12-GAGE CONTINUOUS
STEEL CHANNEL (THREE PAIRS REQUIRED) OR
BACK-TO-BACK CONTINUOUS SLOTTED
TWO 1 5/8" (IN) x 1 5/8" (IN) 12-GAGE
(SEE NOTE 17)
(FIELD WELDED OR BOLTED)
ELEVATION VIEW
STEEL CHANNEL
CONTINUOUS SLOTTED
12-GAGE BACK TO BACK
TWO 1 5/8" (IN) x 1 5/8" (IN)
SECTION
(WELDED CONNECTION)
SHALL NOT BE GLUED TO THE COUPLING
CONDUIT STUB AND END BELL BUSHING
IF PVC CONDUITS ARE SPECIFIED,THE
SHALL BE FLUSH WITH TOP OF CONCRETE ~
CONDUITS ~ TOP OF CONDUIT COUPLINGS
INSTALL CONDUIT COUPLINGS ON ALL
ON
BETWEEN GROUND RODS AS DETAILED
MAINTAIN A 6’ (FT) MINIMUM CLEARANCE
ACHIEVE FULL GROUND PENETRATION ~
TILE(S) WITH COVER(S) AS REQUIRED TO
CONCRETE ~ MOVE ROD(S) AND DRAIN
DRIVE GROUND RODS BEFORE PLACING
STANDARD PLAN J-60.05
SHEET 4 OF 5 SHEETS
STANDARD PLAN J-10.20-01
120/240 SINGLE PHASE)
MODIFIED (0 - 200 AMP TYPE
SERVICE CABINET TYPE B
12" (IN) MAX. CENTERS
NUT ~ SPACED AT
WASHERS AND LOCK
LONG BOLT WITH TWO
3/8" (IN) DIAM. x 1 1/4" (IN)
(BOLTED CONNECTION)
DOOR
DOOR
5
(TYP.)
CONDUIT COUPLING
APPLICABLE
AS SECTION D
OR SECTION C
BOLT POINT ~ SEE
FIELD WELD OR
GROUND ROD (TYP.)
1’ - 8"
1’ - 11"
DRAINAGE WELL18" (IN) x 18" (IN) x 18" (IN)
TIE-DOWN UNITGENERATOR ANTI-THEFT
6" MIN.
6"
MIN.
(TYP.)
(TY
P.)
DO
OR
TABLE AND DETAILS NOT SHOWN
FOR CABINET DIMENSIONPLAN J-10.10
STANDARDFOUNDATION DETAILS ON
SEE CONTROLLER CABINET
STD. PLAN J-10.10SEE
REQUIRED AT EACH CORNER ~
ANCHOR BOLT (TYP.) ~ ONE
(2 PLACES)30" (IN) LEGS
#4 ~ 90° WITH
STAT
EOFWASHINGTON
REGISTERED
PROFESSIONAL ENGI
NEER
39820
YELI
AB
HPESOJ ERODOE
HT
APPROVED FOR PUBLICATION
Washington State Department of Transportation
STATE DESIGN ENGINEER
DR
AW
N B
Y:
CO
LB
Y F
LE
TC
HE
R
SHEET 5 OF 5 SHEETS
STANDARD PLAN J-10.20-01
120/240 SINGLE PHASE)
MODIFIED (0 - 200 AMP TYPE
SERVICE CABINET TYPE B
BDETAIL
CONDUIT
STRANDED
# 6 INSULATED
CLAMP (TYP.)
BRONZE GROUND
WASHERS AND SET SCREWS
WITH BRONZE U-BOLT,
BRONZE GROUND CLAMP ~
TINNED BRAIDED COPPER
# 8 AWG MIN. × 1 FT OF
PLAN VIEW
STANDARD PLAN L-20.10SEE
END OR CORNER POST (TYP.) ~
STANDARD PLAN L-20.10SEE
TYPE 3 CHAIN LINK FENCE (TYP.) ~
MAINTENANCE PAD
3’ - 6"
24"
PLAN VIEW
SEE
END OR CORNER POST (TYP.) ~
STANDARD PLAN L-20.10
SEE
TYPE 3 CHAIN LINK FENCE (TYP.) ~
STANDARD PLAN L-20.10
3’ - 6"
SEE
6’ CHAIN LINK GATE ~
PLAN L-30.10
STANDARD
24"
ELEVATION VIEW
OMITTED FOR CLARITY, SEE SHEET 4 FOR ADDITIONAL DETAILS.
FOR CONDUITS NOT SHOWN, DRAIN TILE FOR GROUNDING, DRAIN TUBES, REINFORCING STEEL, ETC.
STANDARD PLAN L-20.10SEE
TYPE 3 CHAIN LINK FENCE (TYP.) ~
STANDARD PLAN L-30.10SEE
6’ CHAIN LINK GATE ~
POST MOUNTED SERVICE CABINET WITHIN RIGHT-OF-WAY FENCE
SERVICE CABINET
SIDE VIEW
MAINTENANCE PAD
SERVICE CABINET
CONTROLLER CABINET
TIE-DOWN UNIT
GENERATOR ANTI-THEFT
ELEVATION VIEW
PAD MOUNTED SERVICE CABINET WITHIN RIGHT-OF-WAY FENCE
OMITTED FOR CLARITY, SEE SHEET 4 FOR ADDITIONAL DETAILS.
FOR CONDUITS NOT SHOWN, DRAIN TILE FOR GROUNDING, DRAIN TUBES, REINFORCING STEEL, ETC.
DISCONNECT SWITCH
SERVICE METER BASE OR
SIDE VIEW
ADETAIL
CONDUIT
STRANDED
# 6 INSULATED
WASHERS AND SET SCREWS
WITH BRONZE U-BOLT,
BRONZE GROUND CLAMP ~
3’ - 6" MIN.
(TYP.)
SERVICE CABINET
STANDARD PLAN L-20.10SEE
TYPE 3 CHAIN LINK FENCE (TYP.) ~
STANDARD PLAN L-30.10SEE
6’ (FT) CHAIN LINK GATE ~
A B
SERVICE CABINET
SERVICE CABINET
SLOPE BREAK
GROUND LINE
3’ - 6"
MIN.
A B
CONTROLLER CABINET
3’ - 6"
MIN.
PAD
MAINTENANCE
CABINET
SERVICE
FENCE
PLAN VIEW SIDE VIEW
FENCE IS PRESENT)
3’ - 6" MIN. (WHEN
SIDES WITH DOORS1’ - 6" MIN. ON ALL CABINET
SWITCH
DISCONNECT
BASE OR
SERVICE METER
SLOPE
THAN 2H : 1V
NOT STEEPER
SERVICE CABINET IN VICINITY OF CHAIN LINK FENCE
PAD MOUNTED SERVICE CABINET SIMILAR
POST MOUNTED SERVICE CABINET SHOWN,
SWITCH
OR DISCONNECT
SERVICE METER BASE
L-30.10
STANDARD PLANSEE
6’ CHAIN LINK GATE ~
STAT
EOFWASHINGTON
REGISTERED
PROFESSIONAL ENGI
NEER
39820
YELI
AB
HPESOJ ERODOE
HT