Page 1: Performance maintenance of large PV installations€¦ · History of generator-correction factor k G (April-September) Periode 1 Periode 2 Periode 3 Periode 4 Longer snow coverings

Daniel Gfeller

Jlcoweg 1 | 3400 Burgdorf | Switzerland

www.pvtest.ch | iem.bfh.ch/photovoltaik | [email protected]

▶ Engineering and Information Technology

▶ Photovoltaic Laboratory

Performance maintenance of

large PV installations

14. Nationale Photovoltaik-Tagung, 22. - 23. Februar 2016, Bern

Manuel Lanz, Prof. Urs Muntwyler

Partners:

Monitoring of large PV installations

can be very labour intensive. A

thermal imaging drone system can

significantly increase the monitoring

efficiency.

A new system and unmanned aerial

drone vehicle, developed and built at

the Photovoltaic Laboratory (PV LAB)

of Bern University of Applied Sciences

BFH, provides evidence for efficiency

advantages in the search for soiling

effects on large PV installations.

Unmanned aerial vehicle UAV

The PV LAB drone system carries both (i)

an infrared camera that records a

thermal imaging video and (ii) a digital

camera for comparison shots. Using this

combination, PV module surfaces can

quickly be monitored and defects easily

determined and located. Fig. 1 shows

the UAV ready to take-off.

Quality control of PV installations

Screening of PV installations in the

monitoring network operated by the PV

LAB at BFH shows that the UAV is able to

detect power losses of about 5 Wp.

Fig. 2 displays a IR video capture and a

close-up thermal image of a defective

Siemens M55 module.

Another example is the “Stade de

Suisse”, a PV installation with a total

capacity of 1347 kWp. Cleaning effects

were determined in summer 2015. The

soiling effects were examined before

and after cleaning the installation with

the PV LAB thermal imaging drone.

Again, the extra energy yield gained

from cleaning the PV modules was

determined by the difference in KG-

values (Table 1).

The degradation of the “Stade the

Suisse” PV installation is displayed in Fig.

5. Cleaning the PV modules in 2015 (i.e.,

after 5 years of operation) increased the

energy yield up to 4-5% (module

inclination of 7 degrees). Cleaning the

PV modules after 8 years of operation

(also in 2015), increased the energy

yield up to 6-9% (module inclination of

20.5).

In conclusion, regular inspection with

thermal imaging drones offers a real

efficiency advantage when monitoring

the improved energy yield production

from PV due to cleaning.

This PV LAB research is sponsored by:

Fig. 3 illustrates the power loss (of

about 20%) of the module in Fig. 2.

Soiling effects on PV installations

As evidenced by PV LAB studies (e.g.,

examination of the PV plant on the

“Stade de Suisse”), regular cleaning of PV

modules increases the electric energy

production. As an example, the Siemens

M55 PV module surface, a 50 kWp

installation on the roof of the PV LAB

building at BFH in Burgdorf, is cleaned

every four years. This results in a yield

increase of 5-8% (Fig. 4).

The values in Fig. 4 are determined with

the "generator correction factor" kG,

which is formed by dividing the "array

yield" YA with the "temperature-corrected

radiation yield" YT (Formula 1) and thus

represents the ratio of the actual yield to

the theoretical yield.

Fig. 1: PV LAB IR-multicopter drone; the take-off

weight is about 7.5 kg.

Fig 2: IR video capture, magnified (left) and close-

up of marked module (right).

Table 1: Increase of energy yield at “Stade de

Suisse” after cleaning the PV modules.

65

70

75

80

85

90

95

100

05.0

6.20

10

05.0

9.20

10

05.1

2.20

10

05.0

3.20

11

05.0

6.20

11

05.0

9.20

11

05.1

2.20

11

05.0

3.20

12

05.0

6.20

12

05.0

9.20

12

05.1

2.20

12

05.0

3.20

13

05.0

6.20

13

05.0

9.20

13

05.1

2.20

13

05.0

3.20

14

05.0

6.20

14

kG

valu

e [%

]

Date [DD.MM.YYYY]

Degradation of kG values over time

DI1

DI2

BI1

BI2

CI1

CI2

CI3

Fig. 5: Degradation of kG values (2010-14) of the

“Stade de Suisse” PV installation.

Subsystems Increase in % Notes/year

BI1 4.0 ~4 2nd cleaning 10/15

BI2 6.4 ~6 2nd cleaning 10/15

CI1 5.7 ~6 2nd cleaning 10/15

CI2 4.3 ~4 2nd cleaning 10/15

CI3 4.3 ~4 2nd cleaning 10/15

DI1 5.6 ~6 2nd cleaning 10/15

DI2 6.4 ~6 2nd cleaning 10/15

E1 (AA1) 6.4 ~6 1st cleaning 07/15

E2 (AA2) 8.5 ~9 1st cleaning 07/15

F1 (DA1) 7.8 ~8 1st cleaning 07/15

F2 (DA2) 7.5 ~8 1st cleaning 07/15

Total 6.2 ~6

Fig. 3: Characteristics of the defective module

(marked Siemens M55 module, Fig. 2)

0

5

10

15

20

25

30

0

0.5

1

1.5

2

2.5

3

0 5 10 15 20 25

Po

wer [W

]

Cu

rren

t [A

]

Voltage [V]

Siemens M55 Referenzmodul defektes M55 Modul

Siemens M55 Referenzmodul (Leistung) defektes M55 Modul (Leistung)

Fig. 4: Energy yield increase (1994-2007) of the PV

installation at BFH Burgdorf due to cleaning.

0.70

0.75

0.80

0.85

0.90

0.95

1.00

1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007

Ge

ne

rato

r-c

orr

ec

tio

n f

ac

tor

kG =

Ya / Y

T

Year

PV installation Tiergarten West, BFH-TI, Burgdorf: History of generator-correction factor kG (April-September)

Periode 1

Periode 2

Periode 3

Periode 4

Longer snow coverings (> 7 days)

1st cleaning

2nd cleaning

Irradiation measured with Pyranometer

3rd cleaning

Formula 1: Calculation of formula kG