1
2
INTRODUCTION
VanPacker refractory lined chimneys have been inuse since 1944. Our Model HT product, which was ULListed as a Medium Heat Appliance Chimney in 1957,uses a similar refractory mix to our earliest refractorylined chimneys. Underwriters Laboratory tested thecorrosion resistance of this product to pH2 in sulfur acidsand pH37 in mixed acids.
The Model HT product was originally designed toresist the corrosive atmospheres of appliances burningcoal and heavy fuel oils. But, as the shift to gas andlighter oil continued, appliances have become moreefficient and flue gas temperatures have become lowerwith many operating below acid dew points forconsiderable periods making refractory lining anexcellent choice for today’s appliances.
Since 1944 VanPacker chimneys have beendesigned to provide superior quality and maximum costeffectiveness. Our Model HT chimney has serviced boilerinstallations through those many years with provenperformance. We give a 1year warranty and offer anextended 15year warranty. For a long lasting,competitive price and easily installed chimney let VanPacker assist you with System Design, CorrosionAnalysis and Thermal Analysis.
3
GENERAL
VanPacker standard components are cylindrical, factorybuilt products made of acid resistant refractory encased insteel jackets. The wall thickness ranges from 2” to 6” depending on the diameter. The refractory material iscentrifugally cast in various lengths. Standard jacket materials are 26ga Aluminized steel and 11ga Galvanizedsteel. Other jacket materials are available on special order.
UL and ULC LISTING Medium Heat Appliance Chimney, Model HT: VanPacker Model HT is “Listed” by ULunder file number MH 7475 and by ULC under file number CMH 866 as “Medium Heat Appliance Chimneys” forcontinuous use at 1800ºF (983ºC) and for intermittent use at 2000ºF (1093ºC).
Enclosures: VanPacker Model HT chimneys are listed for enclosure within 1 to 2 hour fire rated walls (ratingdepends on local codes).
Acid Resistance: Model HT chimneys are made of a proprietary acid resistant refractory mixture. Undercomparable conditions, a VanPacker Model HT chimney will outlast an uninsulated carbon steel or stainless steelstack many times over.
Low Cost: VanPacker Model HT systems are slightly more expensive initially than unlined, uninsulated carbonsteel stacks; but will last many times longer. Prices are comparable with doublewall stainless steel chimneys.
Ease of Installation: VanPacker chimney sections are simple to install using internal lifters, joint sealant and asingle drawband. Only one simple butt joint required every four feet.
Factory Welded Units: VanPacker components with 11ga jackets are available in combination as factory weldedunits, reducing field installation time. Breechings, freestanding or other complicated units may be joined together atthe factory in sizes and weights acceptable for shipping and handling.
Codes & Standards: NFPA 211 & UL 959.
SIMPLE INSTALLATION
Individual sections are loweredinto place by means of a winch,crane, etc., and a sectionliftingdevice, which grips the chimneysection when liftingaction isapplied. Contact your VanPacker Representative forinformation on the sectionliftingdevice.
Sections are installed one atopanother using VanPacker jointsealant to provide a leakproof,acidproof seal. Silicone sealantis used when flue gastemperatures will remain below600ºF. Hightemp sealant isused when flue gastemperatures will exceed 600ºF.
VanPacker 8” wide 26gaaluminized steel drawbandsare installed and bolted tightlyto secure the joint. For heavygauge jackets, 11gagalvanized steel drawbandsare available or the joint maybe welded.
4
LINING SELECTION
VanPacker offers a wide range of refractory linings to meet specific applications. All are similar in construction tothe Model HT in that the refractory liner is encased in a steel shell. In most cases the sizes available are the sameas for the Model HT. In some cases, the thermal and corrosion analysis may require a greater wall thickness oradditional insulation thickness. In other cases, a membrane lining or other specialty coating is required.
The following is a listing of VanPacker Company’s standard linings, which have been developed for specialapplications.
MODEL HT is the standard UL and ULC listed product. It consists of a lightweight refractory aggregate bonded withcalcium aluminate cement. It is resistant to flue acids, as found in fuel oils and coal, and is for incineration at1800ºF where plastics content is low. When plastics content is above 3%, flue gas temperatures must remain below1600ºF to avoid disruption by alkalies. Flue temperatures must be kept above 500ºF to avoid corrosion due tocondensed flue gases, particularly hydrochloric acid.
MODEL HTplus is available in sizes from 10”ID to 60”ID. One inch of the standard HT refractory is replaced withinsulating board. Btu loss is reduced in heat recovery applications and surface temperatures are lowered wheresafety and building heat gain are concerns.
MODEL VHT is available in the same standard sizes as our Model HT. Model VHT consists of a highdensityaggregate bonded with high purity calcium aluminate cement. It is resistant to 1/50N sulfuric acid, but is notintended for use with incinerator effluents below acid dew points. It resists alkali attacks and may be operated up to2400ºF continuous or 3000ºF intermittent. Model VHT is used for incinerator chimneys operating between 500ºFand 2400ºF or as a breeching to heat recovery or scrubbing units.
MODEL AR2 utilizes a highdensity aggregate cobonded with high purity calcium aluminate cement andpotassium silicate binders. It resists 5% solutions of both hydrochloric and sulfuric acids and is suitable forintermittent operations where flue surfaces fall below acid dew points. Model AR2 is used for chimney systemswith intermittent exposure to condensed flue acids as well as high temperature. These conditions exist when a heatrecovery system normally in use is bypassed for service.
MODEL ARH is a 60% Alumina, high strength, high density, high abrasion resistant, low shrink mix with 3100ºFservice temperature. It resists chloride and halogen vapors as well as alkali and is therefore suitable for chimneysservicing hazardous waste incinerators. Model ARH provides a superior chimney for high temperature operationwith aggressive flue gases.
MODEL ART is an amorphous, vitreous silica, high density, and high abrasion resistant refractory. It has excellentacid resistance coupled with an ability to withstand extreme thermal shock. Model ART has characteristics allowingit to handle not only the chimney system environment down stream of scrubbers with temperatures in the 140ºrange and water saturated acid flue gases, but also under bypass temperatures not exceeding 2000ºF.
Technical Data Sheets are available from VanPacker for the above products.
In some cases, a combination of lining materials, increased insulation thickness or increased wall thickness isdesirable. VanPacker can provide components with standard inside diameters having larger standard outsidediameters. For example, a 10”ID section could be provided with a 16”OD (the OD of our 12”ID material).
VANPACKER is also able to custom apply linings, such as premixed refractories and membranes. This providesthe flexibility of an engineered lining with the quality control of factory fabrication. VanPacker Company can helpyou select the right product for your chimney and breeching system.
5
SERVICES
MANUFACTURING: VanPacker Company has continuously produced Underwriters Laboratories listed chimneyssince 1944 at the same location in Buda, Illinois. During that time the company has increased its manufacturingfloor space under roof to 81,136 sq. ft. Current management assumed leadership of the company in 1956. Thecompany has gained wide experience in the technology of chimney and allied product technology problems.ENGINEERING: VanPacker has developed the first indepth Thermal and Corrosion Analysis Program to handleall chimney types and exhaust systems. Our Technical Service Department with their timeproven experience willbe pleased to assist you with Sizing, System Design, Corrosion Analysis, Thermal Analysis, Structural Analysis,Design of Freestanding Stacks and Field Inspection & Repair.TECHNICAL CREDENTIALS: VanPacker can provide the expertise of CHEMICAL, CORROSION, MECHANICALand STRUCTURAL ENGINEERS to service your entire chimney needs. We have been involved in, NFPA, ASTM,NACE, CICIND, AHR (ASHRAE), AICHE and ACI. VanPacker personnel have also been active in thedevelopment of the ASME STEEL STACK STANDARD.UNDERWRITERS LABORATORIES LISTINGS: It is VanPacker’s policy to acquire UL & ULC listings for thestandard items it produces. Consequently all VanPacker products adhere to UL’s rigid standards and safetyfactors. This assures a high degree of quality control and aids in achieving listings for new units as they becomestandard.COMPLETE SYSTEM DESIGN: VanPacker will examine the operating conditions and other requirements of aproject. We will then suggest the type of system that is best suited, both technically and economically, toaccommodate these conditions. VanPacker is capable of providing a wide range of chimney and breechingproducts that cover a wide range of applications and operating conditions.SYSTEM SIZING: VanPacker has been a leader in developing sizing procedures. A member of our staff coauthored the sizing procedures in the ASHRAE HANDBOOK. Our computerized sizing will size your system fromthe appliance outlet to chimney top, selecting the proper diameters for both the stack and breeching. Computerprintouts will be provided verifying the diameter selections.BUDGET PRICING AND PRELIMINARY DESIGN DATA: Through its representatives, VanPacker will providebudget pricing and preliminary design data for all chimney and breeching systems within our range of capabilities.This enables you to have accurate figures on the cost of the chimney for both materials and installation, as well aspreliminary design data for foundations. This information is very useful in the early stages of a project.SPECIFICATION WRITING: VanPacker and its representatives will provide full product information and will assistengineers to achieve optimum, cost effective specifications. We will also review existing specifications and makesuggestions for changes and revisions. Specifications for all VanPacker products are available on computer diskfor use with your word processor, contact VanPacker for a free copy.CORROSION ANALYSIS: VanPacker’s corrosion engineers will examine the operating conditions of a system anddetermine what corrosive affect these conditions will have on the system. We will then provide engineers with theinformation necessary to make the proper selection.THERMAL ANALYSIS: The VanPacker computerized Thermal Analysis Program examines the entire chimneyand breeching system from a temperature standpoint. Given the proper input temperature, readings are calculatedfor any point in the system; midflue, hot face, and any point through the lining and cold face. This enables you tocalculate the heat loss in a system and determine its affects on the system.REPRESENTATIVES: VanPacker representatives are located in the United States, Canada, Puerto Rico, HongKong and the Pacific Islands, providing World Wide service.PRODUCTS: VanPacker provides a full line of field tested, high quality chimney and exhaust systems, factoryfabricated in sizes from 4”ID to 60”ID. We provide lengths compatible with handling and shipping requirements,designed for easy installation to suit your specific needs, and backed by the latest technology at competitive prices.
6
INSTALLATION DETAILS
High Temperature Chimneys: VanPacker hightemperature chimneys are listed for enclosure withinfire rated walls. This will range from 1 to 2 hoursdepending on local codes.
Factory Welded Units: Standard VanPackercomponents are available in combination as factorywelded units that ease field installation. Breechings,freestanding units or other complicated units may bejoined together at the factory in size and weightsacceptable for shipping.
Installation EquipmentScaffolding: The height of scaffolding should beabout twenty feet higher than the chimney to beerected.FloortoFloor Installation: Highrise constructionlends itself to installation where the hoistingequipment may be secured by the existing floors.Helicopters: Helicopters have been successfullyused to install in unusual areas.
FOUNDATIONS
The VanPacker smokestack foundation is based onwind load exposure on the entire stack, with properguy wire support. Foundations for VanPackersmokestacks are typically designed and furnished byothers. A suggested minimum foundation size isshown below, however, the actual size is dependentupon stack base reactions and the existing soilconditions. Your Engineer may determine that theseminimum dimensions are too conservative.
X = OD of stackA = X + 12” (min.) round or square
B = X + 24” (min.) square
Footing depth to be determined by depth of frost linein area.
OUTDOOR INSTALLATIONConcrete foundation and footing with VanPacker
cleanout section.
7
PREENGINEERED SYSTEMSThe heights in the following charts includecombinations of 26ga and 11ga jacketed sections toprovide the maximum allowable heights inaccordance with good engineering practice onstandard 11ga tees, cleanouts and straight sections.Engineered sections can be used when heightsexceed those allowed on standard sections. Thesedesigns exceed UL limitations. Note: 26ga availableup to 36”ID only.
STRAIGHT SECTIONSMaximum Combined Height (Feet)
Chimney Safe "A" "B" "C" "D"ID Working 26 GA. 11 GA. Ultimate Maximum
Load Height HeightPounds C=A+B 11 GA.only
10 22108 180 175 355 31412 25420 180 166 346 31115 34371 180 169 349 31418 44342 165 181 346 32021 55080 150 181 331 30424 66583 140 200 340 31927 78538 135 196 331 30830 91059 135 181 316 29933 104266 135 181 316 30136 117494 135 171 306 28939 130889 27642 144348 27045 157756 26348 171417 26851 193859 26754 217737 27257 243282 26960 270584 271
CLEANOUT SECTIONSMaximum Combined Height (Feet)
Chimney Safe "A" "B" "C" "D"ID Working 26 GA. 11 GA. Ultimate Maximum
Load Height HeightPounds C=A+B 11 GA.only
10 17412 180 108 288 24712 20021 180 100 280 24515 27071 180 102 282 24818 34923 165 113 278 25221 43381 150 116 266 23924 52441 140 132 272 25127 61856 135 131 266 24330 71718 135 118 253 23533 82120 135 117 252 23736 92539 135 110 245 22839 103088 21842 113688 21245 124248 20748 135007 21151 152683 21154 171490 21457 191608 21260 213112 213
ENGINEERED TEEVanPacker has developed tee sections capable ofsupporting the maximum heights allowable on preengineered straight sections in guyed situations asshown in chart for straight sections. We can alsodesign complete systems both guyed andfreestanding. VanPacker will assist you with yourchimney design problems.
TEE SECTIONSMaximum Combined Height (Feet)
Chimney Safe "A" "B" "C" "D"ID Working 26 GA. 11 GA. Ultimate Maximum
Load Height HeightPounds C=A+B 11 GA only
10 17088 180 103 283 24212 18344 180 79 259 22415 22108 180 57 237 20218 24756 165 40 205 17921 29647 150 41 191 16424 34956 140 48 188 16727 40691 135 48 183 15930 46750 135 35 170 15333 49987 135 24 159 14436 52338 135 11 146 12939 55427 11742 58205 10945 62576 10448 66158 10451 66367 9254 64811 8157 62627 6960 58260 58
8
ENGINEERING DATA
Model HT Surface (Cold Face) Temperatures Based on 70ºF ambient temperature
EQUILIBRIUM CONDITIONS FLUE GAS VELOCITY 17fpsNO AIR MOVEMENT AIR VELOCITY AROUND STACK 15mph (22fps)
CHIMNEY Flue Surface (Hot Face) Temperature ºF CHIMNEY Flue Surface (Mid Flue) Temperature ºFID 350 500 1000 1500 2000 ID 350 500 1000 1500 200010 170 210 330 442 540 10 108 129 201 283 36512 170 210 330 442 540 12 108 129 201 283 36515 160 202 324 418 530 15 106 126 195 278 34518 154 197 320 407 525 18 103 122 186 255 32621 151 193 308 390 502 21 101 118 179 238 31124 150 186 300 384 483 24 99 115 172 221 29727 148 182 282 371 471 27 97 113 166 217 28430 147 181 278 353 465 30 95 111 161 214 27233 143 162 268 336 456 33 94 109 156 207 26236 135 160 254 334 452 36 93 107 151 200 25239 132 158 248 320 418 39 92 105 148 194 24342 130 156 243 312 413 42 91 103 145 188 23445 128 153 241 303 405 45 90 102 141 184 22848 123 151 232 299 391 48 90 100 138 179 22251 122 150 230 286 376 51 89 99 135 175 21854 121 145 228 285 360 54 88 98 133 170 21357 120 143 220 280 357 57 87 96 130 165 20760 118 140 214 273 354 60 87 94 128 160 202
THERMAL CONDUCTIVITY (k) MODEL HTk = BTU/sq ft/Hr/ºF/Inch of Thickness
ºF k ºF k350 2.35 1000 2.62500 2.41 1500 2.83750 2.51 2000 3.05
LINEAR THERMAL EXPANSION MODEL HTUse Cold Face Temperature To Calculate Thermal Expansion70ºF1800ºF… … .… .… .0.0000057 inches/inch/ºF
MODEL HT DATAUnit Weight Dried 99.9 lbs/cu ftUnit Weight Fired 78.6 lbs/cu ftMaximum Service Temperature 2000ºF
CLEARANCE MODEL HT: An unenclosed chimney may be placed adjacent to walls of combustible material at theclearances shown in the table below. By protecting the combustibles with a radiation shield, clearances may bereduced as per NFPA 211. Clearance to walls of noncombustible construction shall be at least 2” for sizes through18”ID and 4” for sizes over 18”ID. Clearance in a noncombustible interior chase shall be as necessary forinstallation or access. When the chimney is used with low heat appliances (producing flue gas temperatures not inexcess of 1000ºF), the clearance to walls of combustible construction may be 6” for all sizes. Consult local codes orbuilding authorities for requirements in their areas.
2000ºF Clearance ChartID 415 1821 24 27 3036 45 45 48 51 54 57 60CL 16" 18" 20” 21" 22" 25" 26" 27" 28" 29" 30" 31"
9
RELATIONSHIP OF HOT AND COLD FACE TEMPERATURES AT VARIOUS APPLIANCE OUTLETTEMPERATURES, FLUE AND WIND VELOCITIES AT 100 FEET FROM APPLIANCE OUTLET FOR A 24”ID
MODEL HT CHIMNEY. 70ºF AMBIENT.Zero Wind Velocity Around Chimney
MID FLUETemperature @ Stack
Exit
Interior FlueSurface Temperature
ºF (Hot Face)
Exterior SkinSurface
Flue Velocity fps Flue Velocity fps Flue Velocity fps
Temp. @Stack
Entrance15 25 35 15 25 35 15 25 35
200ºF 191 195 196 180 186 189 92 93 94300ºF 282 289 292 261 273 278 106 107 108400ºF 370 382 387 342 358 367 118 120 122500ºF 456 473 480 421 444 455 129 133 134
15 MPH Wind Velocity Around ChimneyMID FLUE
Temperature @ StackExit
Interior FlueSurface Temperature
ºF (Hot Face)
Exterior SkinSurface
Flue Velocity fps Flue Velocity fps Flue Velocity fps
Temp. @Stack
Entrance15 25 35 15 25 35 15 25 35
200ºF 190 194 195 177 184 187 78 79 79300ºF 280 288 291 257 269 276 84 85 85400ºF 367 380 385 336 354 363 90 91 92500ºF 452 470 478 414 438 450 95 97 98
UNLINED, UNINSULATED SINGLE WALL STEEL CHIMNEYS AND UL LISTED DOUBLE WALL STEELCHIMNEYS WILL HAVE LOWER INTERIOR FLUE SURFACE TEMPERATURES AND HIGHER EXTERIOR SKIN
TEMPERATURES THAN MODEL HT SHOWN ABOVE.ACID DEW POINTS AND CORROSION POTENTIAL
(Ask for Thermal and Corrosion Analysis of Chimney Systems.)No. 2 Fuel Oil with 0.6% sulfur will produce Sulfur Trioxide in the flue gas, which will condense as 77% Sulfuric Acidat about 275ºF. This will cause corrosion. Note that appliance outlet temperatures below 400ºF in the abovetabulations can cause corrosion problems.
VANPACKER TECHNICAL DEPARTMENT WILL ASSIST YOU WITH YOURDESIGNTHERMALCORROSION PROBLEMS
MECHANICAL SPECIFICATIONSMODEL HT UL LISTED LIMITATIONS
MAXIMUM HEIGHT ABOVE (Feet)26 Gage Jacket Aluminized Steel 11 Gage Jacket Galvanized Steel
ChimneyID
(Inches) STRAIGHT TEE CLEANOUT STRAIGHT TEE CLEANOUTFLOOR
SUPPORT4 180 120 136 235 120 185 326 180 120 136 235 120 185 328 180 120 136 235 120 185 3210 180 120 136 235 182 185 3212 180 90 106 233 168 185 3215 180 90 106 236 152 186 3218 165 80 96 242 134 189 3221 150 80 96 228 123 180 3224 140 70 86 239 126 188 3227 135 N/A 71 231 120 182 3230 135 N/A 56 229 115 177 3233 135 N/A 49 226 107 178 3236 135 N/A 41 217 97 171 3239 N/A N/A N/A 207 88 163 3242 N/A N/A N/A 202 82 159 3245 N/A N/A N/A 197 78 155 3248 N/A N/A N/A 201 78 159 2851 N/A N/A N/A 201 69 158 2654 N/A N/A N/A 204 61 161 2357 N/A N/A N/A 202 52 159 2160 N/A N/A N/A 203 44 160 20
10
SECTION DATAINSIDE OUTSIDE WALL FLUE BEARING AVERAGE WEIGHT PER FOOT (Pounds)
DIAMETER DIAMETER THICKNESS AREA SURFACE MODEL HT MODEL VHT
(Inches) (Inches) (Inches) (sq in) (sq in)26ga
Aluminized11ga
Galvanized1/4" Prime
Painted12ga
Aluminized1/4" Prime
Painted4 8 2 12.56 37.69 27.9 36.25 N/A 39.35 N/A6 10 2 28.27 50.26 37.4 45 N/A 51.8 N/A8 12 2 50.26 62.83 43.9 58.75 N/A 64.3 N/A10 14 2 78.53 75.39 54.4 70.5 81.61 76.8 90.612 16 2 113.09 87.96 65.9 81.75 94.6 89.3 10515 19 1/2 2 1/4 176.71 121.93 88.3 109.3 125.63 121.14 140.518 23 2 1/2 254.46 161 116.6 138.5 160.21 157.22 18021 26 1/2 2 3/4 346.36 205.18 148.2 181.25 198.34 197.6 223.924 30 3 452.38 254.46 178.1 208.75 240 242.17 272.127 33 1/2 3 1/4 572.55 304.85 210.8 255 285.23 291 324.530 37 3 1/2 706.85 368.35 265.4 304.75 334 344.12 381.1333 40 1/2 3 3/4 855.29 432.95 307.8 346.75 386.3 401.5 44236 44 4 1017.87 502.65 355.8 406 442.15 463.1 507.1839 47 1/2 4 1/4 1194.59 577.46 N/A 473.63 501.54 528.97 576.642 51 4 1/2 1386.44 657.37 N/A 535.25 564.48 599 650.2545 54 1/2 4 3/4 1590.43 742.39 N/A 599.75 631 673.47 728.1648 58 5 1809.55 832.52 N/A 638.63 701 752.1 810.3351 61 1/2 5 1/4 2042.82 927.75 N/A 725 774.6 835 896.7554 65 5 1/2 2290.22 1028.08 N/A 799.63 851.7 922.13 987.4357 68 1/2 5 3/4 2551.75 1133.52 N/A 904.75 932.37 1013.5 1082.3660 72 6 2827.43 1244.07 N/A 999.5 1016.6 1109.17 1181.55
WARRANTY: VanPacker makes no representation regarding the specifications appearing herein or their suitabilityfor particular installations. VanPacker warrants that the standard products described herein are of merchantablequality, BUT DOES NOT WARRANT THEIR FITNESS FOR ANY PARTICULAR USE OR MAKE ANY OTHERWARRANTY, EXPRESSED OR IMPLIED. This warranty may not be enlarged or extended by salesrepresentatives, written sales information or drawings. Liability of VanPacker under the warranty is limited toreplacement of its products found to be defective or, at its option, a refund of the purchase price. All advice givenand structural specifications supplied by VanPacker representatives shall be used at the sole risk of thosereceiving the same, and VanPacker assumes no responsibility for the design or construction of any structure inwhich its products are used. Any review or inspection of plans, buildings or product applications by VanPackerrepresentatives is not to be construed as approval thereof by VanPacker.
Paints and/or coatings, other products or parts or accessories manufactured by others are warranted only to theextent of the original manufacturers warranty. VanPacker’s obligation under this warranty is limited to thereplacement or refund of the cost of the paint, coating or products or the repair or replacement of parts andaccessories as it shall be determined by its sole discretion upon examination by qualified personnel as approved byVanPacker and only to that material produced or fabricated at the Buda Factory.
The erection, installation, field fabrication or welding by installing contractors or VanPacker representatives arewarranted only by and to the extent of the installing contractors or representatives.
The Warranties made herein by VanPacker Co. are in lieu of any and all other warranties, stated or inferred andVanPacker assumes no liability for loss of use or any direct, indirect or consequential damage of any kind inrespect to the use or operation of VanPacker products, or any equipment or accessories used in connectiontherewith.
INSPECTION… . All Products: Chimneys, vents and exhaust systems of all construction types are by their verynature the highest points in their given area. They are subject to lightning, high winds, earth movement, to unusualcorrosion and combustion processes which can deteriorate linings or create excessive soot, temperatures andother conditions which may sometimes be above the design criteria or the addition or modification of appliancesmay overload an installation.
Listed prefabricated chimneys are subject to severe testing and controls that minimize many of the problemsassociated with other construction types: however, it is good practice with all chimneys, vents and exhaust systemsto inspect them annually to insure that no unusual conditions exist.
11
GENERALJACKET MATERIALStandard sections are availablewith 26ga Aluminized Steeljackets in sizes 4”36”ID, with11ga Galvanized Steel jacketsfor sizes 4”60”ID and 1/4” primepainted steel jackets in sizes10”60”ID. Other jackets areavailable on special order.SECTION JOINTSDrawbands are provided with26ga sections and are optionalon 11ga and 1/4” sections.Joints between sections with 11ga or 1/4” jackets may bebanded, welded or flanged.SECTION LENGTHSThe chart below shows thestandard lengths for Straight,Cleanout, Floor Support andCompanion Sections. For TeeSection lengths, see theindividual component drawing.
ID JACKET LENGTH4"8" 26ga 36"
10"36" 26ga 48"4"8" 11ga 36"
10"60" 11ga 48"10"60" 1/4" 72"
Shorter sections (12” min.) areavailable on special order.PART NUMBERSEach part is assigned a partnumber based on the followingcode:H 06 STR 26
MODEL CODEHT HVHT VJACKET CODE26ga Aluminized Steel 2611ga Galvanized Steel 111/4” Steel, Prime Painted 25For special and custom parts,engineered chimneys and oddlength sections, a part numberwill be assigned at the factory.
CLEANOUT SECTIONPart C/OUsed at the base of the chimneyfor access to and inspection ofthe chimney interior. A drainshould be provided in theconcrete pad.
4”ID – 8”ID Cleanout Sectionshave a drawband type closure.10”ID – 60”ID Cleanout Sectionshave a bolted door.
CLEANOUT SECTION WITHDRAINPart CODThis section provides accessand a drain at the base of thechimney.
4”ID – 8”ID Cleanout SectionsWith Drain have a drawbandtype closure. 10”ID – 60”IDCleanout Sections With Drainhave a bolted door.
Cleanout Opening SizeID HEIGHT WIDTH4" 4” 4”6” 6” 6”8” 8” 8”
10"15" 7 ¾” 7 3/4”18"24" 11 7/8” 11 7/8”27"36" 11 7/8” 15 3/439"60" 17 7/8” 17 7/8”
CUSTOM ITEMSVanPacker can provide a widerange of custom tees, elbowsand other sections to meet yourspecial needs. Let VanPackerCompany’s Tech Service designthe right part for your project.
12
ANCHOR LUGSPart LUGUsed at the base of guyed orbraced chimneys. The AnchorLug is bolted to the concretepad; it is not welded to thechimney. Anchor Lugs are madeof cast iron and are coated withblack primer paint.
Anchor LugsSECTION ID NO. OF LUGS
6"12” 315”21” 4
24” 527”30” 633”36” 839”48” 1051”60” 12
Note: Anchor lugs are not usedon 4”ID sections. A 1 ½” x 1 ½” x1/4” angle ring is used instead.
STRAIGHT SECTIONPart STRUsed for straight runs betweencomponents. The StraightSection may be used as avertical riser or in horizontalbreechings.
DRAWBANDPart DRWUsed between two sections tosecure the joints. Drawbands areavailable in 26ga AluminizedSteel and 11ga GalvanizedSteel.
LIFTING DEVICEPart L/DUsed for lifting components inthe vertical position. Can berented or purchased. Availablefor sizes 6”ID – 36”ID.
BAROMETRIC DAMPERPart BMDUsed to regulate excess draft.Attaches to a tee projection orsection end with a factoryinstalled adapter.
INCREASERPart INCUsed for diameter changes inmanifold breechings. 11gaGalvanized Steel jacket isstandard. Increaser must bewelded to adjacent sections.
The chart below shows lengthsof increasers “X” whenincreasing from one standardinside diameter, “ID 1”, to thenext, “ID 2”.
Increaser Data“ID 1” HEIGHT4"10” 3 3/4”12”57” 5 5/8”
When “ID 2” is more than onestandard diameter larger than“ID 1”, add the lengths together.Example: The length of a 12” to18” increaser would be 11 1/4”.
13
SPARK SCREEN Part SCREENThe Spark Screen or spark arrestor is used primarily on incinerator chimneys. Its function is to catch large particlesof ash. Meets the requirements of NFPA 82. Standard material is type 316 Stainless Steel.
RAIN CAP Part DCRThe Double Cone Rain Cap is made of type 304 Stainless Steel. See “Rain Cap Discussion” when considering theuse of a Rain Cap. The Double Cone Rain Cap is also available with a bird screen, Part RCS.
SPARK SCREEN / ARRESTOR DOUBLE CONE RAIN CAP RAIN CAP WITH BIRD SCREENPart SCREEN Part DCR Part RCS
SPARK SCREEN & RAIN CAP DIMENSIONS (Inches)Section ID “A” “B” “C” “D” “E”
4 8 9 16 6 2 11/166 10 11 20 7 1/2 3 11/328 12 13 24 9 410 14 15 20 7 1/2 3 11/3212 16 17 24 9 415 19 1/2 21 1/2 30 11 1/4 518 23 25 1/2 36 13 1/2 621 26 1/2 29 1/2 42 15 3/4 724 30 33 1/2 48 18 827 33 1/2 37 54 20 1/4 930 37 41 60 22 1/2 1033 40 1/2 45 66 24 3/4 1136 44 49 72 27 1239 47 1/2 56 78 29 1/4 1342 51 60 84 31 1/2 1445 54 1/2 64 90 33 3/4 1548 58 68 96 36 1651 61 1/2 72 102 38 1/4 1754 65 76 108 40 1/2 1857 68 1/2 80 114 42 3/4 1960 72 84 120 45 20
RAIN CAP DISCUSSIONRain caps are not recommended for general use. They are ineffective in keeping rain out, reduce effective draft, aresubject to corrosion, and divert effluent back to the building where it can create problems for both equipment andpersonnel. Rain caps are also expensive and present a large area to catch wind, thereby increasing loads in thefoundation and bracing.
Condensation occurs in chimney systems at some point in the operating cycle. Therefore it is always recommendedthat a drain be provided at the base of the chimney. With a drain in the chimney, a rain cap is not required.
VanPacker recommends that the chimney top be left open and a drain be provided at the chimney base.
14
VanPacker provides a widerange of standard, custom andengineered chimney’s andrelated products. While ourstandard components will fitmost job conditions, VanPackercan produce components withcustom lengths, diameters andconfigurations. We have theproducts you need to get the jobdone. Let VanPacker knowyour special requirements.
90º TEE SECTIONPart TEEUsed to connect vertical andhorizontal sections in chimneyand breeching systems.Reference page 15.
TEE WITH RECTANGULAROPENINGPart TROThis section has a rectangularopening and may be providedwith or without a projection.Reference page 15.
PRE ENGINEERED TEES
In sizes 39”60”ID only. Used toattain greater heights thanpossible on a tee section with11ga jackets. Reference page15.
45º TEE SECTIONPart 45TUsed to connect vertical andhorizontal sections in chimneyand breeching systems.Reference page 15.
TEST PORTSTest ports can be added tovirtually any component. Providethe diameter and length of portand it will be topped off with acap or plug. Flange connectionsare available also. Pleaseprovide flange OD, bolt holediameter and bolt circle alongwith test port diameter.
15
TEE SECTION DIMENSIONS (Inches)ID OD “A” “B” “C” “D” “E” “F” “G” “H”4 8 36 12 13 5/8 22 36 N/A 4 3 27/326 10 36 12 16 1/16 23 36 N/A 6 4 1/48 12 36 12 18 1/2 24 36 N/A 8 5 5/810 14 48 18 20 7/8 31 48 N/A 10 7 1/1612 16 48 18 23 5/16 32 48 N/A 12 8 1/215 19 1/2 48 18 27 9/16 33 3/4 48 N/A 15 10 5/818 23 48 18 31 3/4 35 1/2 48 N/A 18 12 3/421 26 1/2 48 18 36 37 1/4 48 N/A 21 14 7/824 30 48 24 40 1/4 51 72 N/A 24 1727 33 1/2 48 24 44 3/8 52 3/4 72 N/A 27 1930 37 48 24 48 5/8 54 1/2 72 N/A 30 21 1/433 40 1/2 72 36 57 7/8 56 1/4 72 N/A 33 23 5/836 44 72 36 57 1/8 70 96 N/A 36 25 1/239 47 1/2 72 36 61 3/8 71 3/4 96 72 39 27 5/842 51 72 36 65 5/8 73 1/2 96 72 42 29 3/445 54 1/2 72 36 69 7/8 75 1/4 96 72 45 31 7/848 58 72 36 74 1/16 77 96 72 48 3451 61 1/2 96 48 78 5/16 90 3/4 120 96 51 3654 65 96 48 82 3/8 92 1/2 120 96 54 38 1/457 68 1/2 96 48 86 5/8 94 1/4 120 96 57 40 1/460 72 96 48 90 7/8 96 120 96 60 42 3/8
MAXIMUM UNSUPPORTED BREECHING SPANUsing Ground Supported Concrete Saddles (By Others)
VanPacker will also engineer for greater free spans and for other breeching support systems.
MODEL HT, 11 GA JACKETED BREECHING, WELDED JOINTSStiffener Band Size
Section ID NumberStiffener 8”x1/4” 8”x3/8” 8”x1/2” 10”x1/2” 10”x5/8” 10”x3/4” 12”x3/4”
10 15* 24 24 24 24 24 24 2412 15 24 24 24 24 24 24 2415 9 24 24 24 24 24 24 2418 6 24 24 24 24 24 24 2421 6 24 24 24 24 24 24 2424 6 24 24 24 24 24 24 2427 6 18 24 24 24 24 24 2430 6 13 24 24 24 24 24 2433 6 11 22 24 24 24 24 2436 6 9 20 24 24 24 24 2439 6 6 16 22 22 22 22 2242 6 6 13 22 22 22 22 2245 6 6 11 19 22 22 22 2248 6 6 9 17 21 22 22 2251 6 6 6 14 17 22 22 2254 6 6 6 12 15 22 22 2257 6 6 6 10 12 18 21 2160 6 6 6 9 12 18 21 21
* All span dimensions in feet.
16
VanPacker Companyis a full service company.
We do not bend your needs toour products.
We provide productsto suit your needs.
GUY BANDPart GUYUsed for attachment of guy wiresand rigid braces to give lateralsupport to chimneys. Guy Bandsfor 4”–36”ID sections are madefrom 8ga Galvanized Steel.Guy Bands for 39”60”IDsections are made from 1/4”thick steel coated with ColdGalvanizing Compound.
The Guy Band may also be usedto support horizontal or diagonalbreechings.
SUGGESTED GUYINGMATERIALSGuying Cable shall begalvanized or copper clad indiameters as shown in thefollowing table:
SECTION ID(Inches) MINIMUM CABLE Ø (inches)
415 5/161824 3/8
27 & 30 7/1633 & 36 1/23948 9/165160 5/8
Standard pipe bracing ispreferable to cable guys where itis practical because only twopoints of attachment arerequired instead of the threeneeded for cables. Minimalmaintenance is required withpipe bracing, whereas cableguys must be regularly checkedand the turnbuckles must beadjusted for tension. 11/2”standard galvanized pipe withplain ends will handle mostrequirements.
Steel Angle, 2”x2”x1/4”, inrequired lengths will handle mostbracing needs.
Miscellaneous Guying andBracing Materials: 115/16”IDsteel tubing fits snugly over 11/2” pipe for making connectorsand telescoping adjusters. 1”diameter black iron pipe may beused to connect bracing pipe toroof anchors. Galvanized bolts inthe following sizes should beused:
SECTION ID(Inches) MINIMUM BOLT Ø (Inches)
415 1/21824 5/82736 3/43960 1
Exterior chimneys must beguyed or braced at a point nomore than 10’ below the top,with no more than 30’ betweenguys or braces. Others shallsupply guying and bracingmaterial.
Interior chimneys should bebraced as shown in theinstallation instructions. Specialconsideration should be givenfor installations in seismic zones.
17
BREECHING SUPPORTHANGER BANDPart HGRUsed for support of horizontalbreeching runs. The partincludes the band and therequired 2”x2”x1/4” flat washer,but does not include support rodor nuts. Hanger Bands for 4”36”ID are made of 11ga steel,require a 1/2” diameter rod andwill support a maximum of 1840pounds. Hanger Bands for 39”60”ID are made of 1/4” steel,require a 3/4” rod and willsupport a maximum of 4500pounds.
END CAPPart CAPUsed to close off unused teeopenings and the ends ofhorizontal runs. Provides ameans of access for inspectionand cleaning. The End Capflange matches the StandardBolt Flange shown at right. TheEnd Cap can also be suppliedwith a drain for vertical runs.Part C/D. Caps include matchingbolt flange (field welded tosection being capped), nuts &bolts.
BOLT FLANGEPart FLGBolt flanges are welded tochimney sections to provide aflanged connection betweensections. Bolt Flanges arefabricated in donut style or anglering. Not for use on unguyedchimneys.
DIMENSIONS (Inches)Section ID Section OD “A” “B” “C” “D” “E” “F”
4 8 6 2 8 3/8 9 1/2 1 1/4 x 1 1/4 x 1/86 10 7 3/16 2 8 3/8 11 1/2 1 1/4 x 1 1/4 x 1/88 12 8 13/16 2 12 7/16 13 13/16 1 1/2 x 1 1/2 x 1/810 14 10 1/2 2 12 7/16 15 13/16 1 1/2 x 1 1/2 x 3/1612 16 12 2 16 7/16 18 1/8 1 3/4 x 1 3/4 x 3/1615 19 1/2 14 5/8 2 1/4 18 7/16 21 5/8 1 3/4 x 1 3/4 x 3/1618 23 17 1/4 2 1/2 20 7/16 25 1/8 1 3/4 x 1 3/4 x 3/1621 26 1/2 19 7/8 2 3/4 24 9/16 29 2 x 2 x 3/1624 30 22 1/2 3 28 9/16 32 1/2 2 x 2 x 3/1627 33 1/2 25 1/8 3 1/4 30 9/16 36 2 x 2 x 3/1630 37 27 3/4 3 1/2 34 9/16 39 1/2 2 x 2 x 3/1633 40 1/2 30 3/8 3 3/4 36 9/16 43 2 x 2 x 3/1636 44 33 4 40 9/16 46 1/2 2 x 2 x 3/1639 47 1/2 35 5/8 4 1/4 42 9/16 50 2 x 2 x 1/442 51 38 1/4 4 1/2 46 9/16 53 1/2 2 x 2 x 1/445 54 1/2 40 7/8 4 3/4 48 9/16 57 2 x 2 x 1/448 58 43 1/2 5 52 9/16 60 1/2 2 x 2 x 1/451 61 1/2 46 1/8 5 1/4 54 9/16 64 2 x 2 x 1/454 65 48 3/4 5 1/2 58 9/16 67 1/2 2 x 2 x 1/457 68 1/2 51 3/8 5 3/4 60 9/16 71 2 x 2 x 1/460 72 54 6 64 9/16 74 1/2 2 x 2 x 1/4
18
90º ELBOWPart 90EThis part is used to changedirection by 90 degrees. Offsetsare nonload bearing. Madefrom two 45º Elbows. Referencepage 19.
60º ELBOWPart 60EThis part is used to changedirection by 60 degrees. Offsetsare nonload bearing. Made fromtwo 30º Elbows.
45º ELBOWPart 45EThis part is used to changedirection by 45 degrees. Offsetsare nonload bearing.
45º OFFSETOffset is nonload bearing andmade from two 45º Elbows.Reference page 19.
30º ELBOWPart 30EThis part is used to changedirection by 30 degrees. Offsetsare nonload bearing.
30º OFFSETOffset is nonload bearing andmade from two 30º Elbows.Reference page 19.
19
LONG SWEEP 90ºELBOWPart 9LSOffset is nonload bearing andmade from three 30º Elbows.
NONSTANDARD 45ºOFFSETOffset is nonload bearing andmade from two 45º Elbows witha section of length “T” between.
G1= Desired offset in inchesT = Length of section
needed to obtain offsetG1
2C1= G1 x 1.414T = 2C1 – 2CF1= G1 + 2C
NONSTANDARD 30ºOFFSETOffset is nonload bearing andmade from two 30º Elbows witha section of length “T” between.
I1= Desired offset in inchesT = Length of section
needed to obtain offsetI1
2D1= I1 x 2T = 2D1 – 2DH1= 2D + (I1 X 1.732)
ELBOW DIMENSIONS IN (Inches)ID OD “A” “B” “C” “D” “E” “F”4 8 13 5/8 8 19 5/16 5 1/16 18 7/8 18 61/646 10 14 5/8 8 9/16 20 11/16 5 11/32 19 15/16 19 15/168 12 15 5/8 9 3/16 22 3/16 5 5/8 21 2110 14 16 5/8 9 3/4 23 1/2 5 7/8 21 15/16 21 15/1612 16 17 5/8 10 11/32 24 31/32 6 1/8 22 13/16 22 7/815 19 1/2 19 3/8 11 11/32 27 13/32 6 5/8 24 11/16 24 23/3218 23 21 1/8 12 3/8 29 7/8 7 3/32 26 7/16 26 15/3221 26 1/2 22 7/8 13 7/16 32 7/16 7 9/16 28 3/16 28 1/424 30 24 5/8 14 7/16 34 7/8 8 29 7/8 29 7/827 33 1/2 26 3/8 15 15/32 37 11/32 8 1/2 31 11/16 31 23/3230 37 28 1/8 16 1/2 39 13/16 8 31/32 33 7/16 33 15/3233 40 1/2 29 7/8 17 1/2 42 1/4 9 7/16 35 3/16 35 7/3236 44 31 5/8 18 9/16 44 13/16 9 29/32 36 15/16 36 31/3239 47 1/2 33 3/8 19 9/16 47 3/16 10 3/8 38 11/16 38 23/3242 51 35 1/8 20 9/16 49 11/16 10 13/16 40 3/8 40 3/845 54 1/2 36 7/8 21 5/8 52 1/4 11 5/16 42 3/16 42 7/3248 58 38 5/8 22 5/8 54 5/8 11 3/4 43 7/8 43 27/3251 61 1/2 40 3/8 23 11/16 57 3/16 12 1/4 45 11/16 45 23/3254 65 42 1/8 24 11/16 59 9/16 12 11/16 47 3/8 47 11/3257 68 1/2 43 7/8 25 3/4 62 1/8 13 3/16 49 5/16 49 7/3260 72 45 5/8 26 3/4 64 5/8 13 5/8 50 7/8 50 27/32
20
ROOF FLASHINGPart FLSProvides a weather seal on a flatroof. Sizes 4”60”ID are madefrom 24ga Aluminized Steel.
COUNTER FLASHINGPart CFLUsed with the Roof Flashing(FLS) to provide weatherprotection. Sizes 4”18”ID aremade from 24ga AluminizedSteel. Sizes 21”60”ID are madefrom 22ga Aluminized Steel.
INSULATED ROOF THIMBLEPart THMRequired where a chimneypasses through a combustibleroof structure.
Flashing, Counter Flashing & Thimble Dimensions (Inches)ID OD “A” “B” “C” “D” “E” “F”4 8 28 16 8 1/4 19 7/8 9 1/4 15 1/46 10 30 18 10 1/4 21 7/8 11 1/4 17 1/48 12 32 20 12 1/4 23 7/8 13 1/4 19 1/4
10 14 34 22 14 1/4 25 7/8 15 1/4 21 1/412 16 36 24 16 1/4 27 7/8 17 1/4 23 1/415 19 1/2 39 1/2 27 1/2 19 3/4 31 3/8 20 3/4 26 3/418 23 43 31 23 1/4 34 7/8 24 1/4 30 1/421 26 1/2 46 1/2 34 1/2 26 3/4 38 3/8 27 3/4 33 3/424 30 50 38 30 1/4 41 7/8 31 1/4 37 1/427 33 1/2 53 3/4 41 3/4 33 3/4 45 3/8 35 4130 37 57 1/2 45 1/2 37 1/4 48 7/8 38 3/4 44 3/433 40 1/2 61 1/2 49 1/4 40 3/4 52 3/8 42 1/2 48 1/236 44 65 53 44 1/4 55 7/8 46 5239 47 1/2 68 1/2 56 1/2 47 3/4 59 3/8 49 1/2 55 1/242 51 72 60 51 1/4 62 7/8 53 5945 54 1/2 75 1/2 63 1/2 54 3/4 66 3/8 56 1/2 62 1/248 58 79 67 58 1/4 69 7/8 60 6651 61 1/2 82 1/2 70 1/2 61 3/4 73 3/8 63 1/2 69 1/254 65 86 74 65 1/4 76 7/8 67 7357 68 1/2 89 1/2 77 1/2 68 3/4 80 3/8 70 1/2 76 1/260 72 93 81 72 1/4 83 7/8 74 80
FLASHING AND INSULATED THIMBLECrosssection diagram of components in place.
Insulated thimble may be installed with zero inchesclearance to combustibles at roof openings. Requiredfor UL Listed installation of Model HT stack through acombustible roof. The Thimble has 3” thick wall. Roofopening diameter should be 1/2inch greater thanthimble OD.
21
2 PIECE EXPANSION JOINT BANDPart 2PCUsed in vertical and/or horizontal runs of a chimneysystem requiring expansion. One joint allows for a1/2” of expansion. The 2 Piece Expansion Joint Bandrequires a Floor Support Section installed in thevertical or a Straight Section w/a Male End installedin the horizontal along with one Straight Sectionhaving a female end/or known as a companionsection. The 2 Piece Expansion Joint is not smoketight and should be used in applications requiring anegative or neutral draft.
Parts include:12 Piece BandSealing Compound
STEP 1.Apply “Sealing Compound” to joining surfaces, thenposition sections as shown making sure the 1/2” gapis maintained. Care should be used so that the“sealing compound” is not scraped off the joint. Thiscompound is furnished in the dry form and should bemixed with clean water to a convenient spreadingconsistency. (Approximately 3 parts water to 1 partcompound by weight.)
STEP 2.Place 6” wide 11ga, 2piece band over the section.Secure by means of a comealong or chain ratchet.Place a continuous weld around the cover band onthe section with male end. Buttweld seams of band.
STRAIGHT SECTION W/A MALE ENDPart H__STR__MUsed in horizontal runs of a system requiringexpansion. Jacket fabricated in 11ga Galvanized oroptional materials.
STRAIGHT SECTION W/A FEMALE ENDPart H__STR__FAlso known as a Companion Section and is usedbelow a Floor Support Section to provide forexpansion in a floor supported chimney installation.In conjunction with a Straight Section having a maleend, provides for expansion in horizontal breechingruns. Jacket fabricated in 26ga Aluminized, 11gaGalvanized or optional materials.
FLOOR SUPPORT SECTIONPart FSUsed in vertical chimney runs of a system requiringexpansion. Jacket fabricated in 11ga Galvanized oroptional materials.
22
SMOKETIGHT EXPANSION JOINTPart 4PCUsed in vertical and or horizontal runs of a chimneysystem requiring expansion. One joint allows for a1/2” of expansion. The 4 Piece Smoke TightExpansion Joint requires a Floor Support Sectioninstalled in the vertical or a Straight Section w/a MaleEnd installed in the horizontal along with one StraightSection having a female end/or known as acompanion section. The 4 Piece Smoke TightExpansion Joint is an excellent choice for allapplications.
Parts include:12 Piece Spacer Band12 Piece Cover BandCeramic Fiber BlanketSealing Compound
STEP 1.Apply “Sealing Compound” to joining surfaces, thenposition sections as shown making sure the 1/2” gapis maintained. Care should be used so the “sealingcompound” is not scraped off the joint. Thiscompound is furnished in the dry form and should bemixed with clean water to a convenient spreadingconsistency. (Approximately 3 parts water to 1 partby weight.)
STEP 2.Secure 3” x 1/2” Ceramic Fiber Blanket to sectionwith female end using joint cement or any convenientadhesive. Fit Ceramic Fiber Blanket ends snuglytogether with a beveled joint.
STEP 3.Weld 2” wide 11ga, 2piece spacer band to sectionwith male end.
STEP 4.Place 6” wide 11ga, 2piece cover band over theCeramic Fiber Blanket and spacer band. Secure tosection by means of a comealong or chain ratchet.Place a continuous weld around the cover band onthe section with male end. Buttweld the seams of theband to obtain a gas tight seal. This procedurecompresses the 1/2” Ceramic Fiber Blanket to 11gathickness insuring a smoke tight joint while leavingthe female section free to move, due to expansionand contraction.
23
FLOOR SUPPORT BRACKETSPart FSBAnchor bolt requirements are based on pull strength of the “Drilled In Type” & include Standard Engineering SafetyFactors. When chimney is supported on structural steel, brackets may be welded to structural members using 1/4”Fillet Welds.
BRACKET SET REQUIREMENTSSECTION ID (Inches) NO. BRACKETS NO. CLIPS BOLT Ø (Inches)
621 2 Single 2 5/82433 2 Double 2 3/43645 4 Double 3/44860 4 Special Dbl. 3/4
24
INSTALLATION DETAILSA qualified structural engineer should use the support details shown below only after appropriate structural reviewof the building. VanPacker assumes no responsibility for the design and/or modification of buildings.INTERMITTENT SUPPORTSAll materials except stack sections, anchor lugs and draw bands furnished by others. Use of these supports, atproperly determined intervals, permits the vertical alignment of any number of stack sections under maximumheight conditions to form a stack of the desired height through building interiors. Sufficient airspace should beprovided around the support to allow air circulation in the enclosure.
When “A”Equals
“B”Equals
When “C”Equals
“D”Equals
“E”Equals
25’ 8” 25’ 2” 3”50’ 12” 50’ 3” 4”75’ 16” 75’ 5” 5”
FLOOR SUPPORT AND COMPANION SECTIONNote: When casting support in 2 segments, a grout using calcium aluminate cement, should be used to insure100% bearing between both segments. To prevent lateral movement for stability, both segments of reinforcingjacket should be welded or fastened together with clips.
25
26
A FULL SERVICE COMPANYWe do not bend your needs to our productsWe provide products to suit your needs
OTHER VANPACKER PRODUCTSDouble Wall 1400ºF Chimneys and Kitchen Exhaust UL ListedVanPacker Model DW 1400ºF and Building Heating Appliance Chimneys include a range of component parts,including straight sections, elbows, tees, cleanouts, supports and increasers. All sections are double wall steel.Diameters range from 6”ID to 48”ID. Our catalog contains mechanical specifications, component drawings andinstallation details.
AfterburnersAfterburners are recommended for use in VOC, odor, and opacity (smoke) abatement applications, custom designavailable per application.
Steel Stacks – Engineered ChimneysThese stacks can be fabricated from the UL listed refractory lined units, or lined with any of a wide variety of acidand corrosion resistant refractories, polymers, rubbers, organics or borosilicate block as required by the designconditions. VanPacker engineers will provide system design, sizing, structural and corrosion engineering, andthermal analysis.
PosidraftTM Draft InducersOur refractory lined PosidraftTM has no moving parts in the air stream. The refractory is corrosion resistant and issuitable for continuous operation at 1800ºF. See our catalog for operation characteristics and mounting instructions.
Single Wall Fume Hoods, Particle Containment, Breeching SystemsA single wall Stainless Steel exhaust system for venting caustic air, fume hoods, particle containment, breeching forboilers and heating appliances. Diameters 6”36” are fabricated in 20ga Type 304 or 316 stainless steel.Diameters 38”48” are fabricated in 18ga Type 304 or 316 stainless steel.
ES Positive Pressure Exhaust SystemsOneinch refractory lined positive pressure system for venting boilers, kilns, emergency generators, caustic air,fumes, scrubber, and heat recovery (inlet sides). The refractory is corrosion resistant and is suitable for continuousoperation at 1400ºF. The Stainless Steel jacket is flanged and the product comes with joint sealant and vee bandsto ensure product integrity is maintained.