Page 1: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATIONINSULATIONCOORDINATIONCOORDINATION

AC HIGH VOLTAGEAC HIGH VOLTAGECIRCUIT BREAKERSCIRCUIT BREAKERS

STEPHEN R. LAMBERTSTEPHEN R. LAMBERTSHAWNEE POWER CONSULTING, LLCSHAWNEE POWER CONSULTING, LLC

Page 2: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1. Preinsertion Resistor

2. Grading Capacitor

3. Interrupter

4. Support Column

Page 3: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATION PATHSINSULATION PATHS

PHASE TO GROUND

ACROSS THE OPEN BREAKER

PHASE TO PHASE

Page 4: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1. Preinsertion Resistor

2. Grading Capacitor

3. Interrupter

4. Support Column

Page 5: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

VOLTAGE STRESSESVOLTAGE STRESSES

60 Hz

SWITCHING SURGES

LIGHTNING SURGES

Page 6: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

60 Hz Overvoltages60 Hz Overvoltages

UNGROUNDED SYSTEMS – 1.73 PUWITH FAULTS

ACROSS OPEN BREAKER – 2.2 PU

Page 7: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SWITCHING SURGE SWITCHING SURGE OVERVOLTAGESOVERVOLTAGES

NO SURGE CONTROLENERGIZING – 3.0 PURECLOSING (trapped charge) – 4.0 PU

WITH PREINSERTION RESISTORS – 2.2 PU

SURGE ARRESTERS LIMITING – 1.9 PU

Page 8: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

2.90 PU Phase to Ground Switching Surge345 kV System

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 9: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

Application of 276 kV Surge Arrester1.83 PU

-600

-400

-200

0

200

400

600

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 10: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Application of 276 kV Surge Arrester1.83 PU

Page 11: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNINGLIGHTNINGFLASHFLASH

CHARACTERISTICSCHARACTERISTICS

Page 12: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

+++++++++ ++++++++++++++++ +++++++

++---------------------- -------------------- ++

-- ++-- ++

Neg Flash Pos Flash

Page 13: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

FLASH STATISTICSFLASH STATISTICS55% OF FLASHES HAVE MORE THAN ONE STROKE

90% OF FLASHES HAVE LESS THAN NINE STROKES

MEAN NUMBER OF STROKES/FLASH -THREE

80-90% OF STROKES ARE NEGATIVE

Page 14: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNINGLIGHTNING

CHARACTERIZED BY

CURRENT MAGNITUDE

STROKE RISE TIME

KERAUNIC LEVEL OR FLASHES/km2

Page 15: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

STROKE MAGNITUDESSTROKE MAGNITUDES

0.01

0.1

1

10

100

0 50 100 150 200 250

Stroke Current kA

Prob

. of E

xcee

ding

Abs

ciss

a First Stroke

Page 16: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

STROKE MAGNITUDESSTROKE MAGNITUDES

0.01

0.1

1

10

100

0 50 100 150 200 250

Stroke Current kA

Prob

. of E

xcee

ding

Abs

ciss

a

First StrokeSubsequent Strokes

Page 17: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TYPICAL FIRST STROKETYPICAL FIRST STROKE

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Page 18: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SUBSEQUENT STROKESSUBSEQUENT STROKES

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Subsequent Strokes

Page 19: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1.2 x 50 IMPULSE SHAPE1.2 x 50 IMPULSE SHAPE

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Subsequent Strokes

1.2 x 50 wave

Page 20: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

GROUND FLASH DENSITYGROUND FLASH DENSITY

Page 21: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

GROUND FLASH DENSITYGROUND FLASH DENSITY

Page 22: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

HOW DOES LIGHTNING GET HOW DOES LIGHTNING GET INTO THE SYSTEM?INTO THE SYSTEM?

SHIELDING FAILURES

BACKFLASHOVERS

INDUCED

Page 23: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

BACK FLASHOVERBACK FLASHOVER

`

Zsw

Zsw

Is

Ztwr

Ztfr

Vph

Vtwr

Page 24: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREZph 400 Ω

Is = 10 kA

Vph = ? `

Zsw

Zsw

Is

Ztwr

Vph

Vtwr

`

Zph

`

Zph

Page 25: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREZph 400 Ω

Is = 10 kA

Vph = 2 MV`

Zsw

Zsw

Is

Ztwr

Vph

Vtwr

`

Zph

`

Zph

Page 26: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

EXAMPLEEXAMPLE

TLine TLine

Page 27: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREPHASE TO GROUND SURGEPHASE TO GROUND SURGE

@ OPEN BREAKER@ OPEN BREAKER

-1000

-500

0

500

1000

1500

2000

2500

3000

3500

5 7 9 11 13 15 17 19

Time (μs)

kV

Page 28: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATION CAPABILITYINSULATION CAPABILITY& TESTING& TESTING

EARLY 1900’s

60 Hz TESTING ONLY

TEST LEVEL:2.25 x RATED VOLTAGE + 2000 V

1 MINUTE DRY – 10 SECONDS WET

Page 29: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

POWER FREQUENCY TEST POWER FREQUENCY TEST LEVELSLEVELS

-960800

-860550

-555362

350425245

315365170

275310145

230260123

14016072.5

758038

506025.8

455015.5

10 Second Wet(kV, rms)

1 Minute Dry(kV, rms)

Rated MaximumVoltage (kV, rms)

Power Frequency Test

Page 30: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CONTACTS OPENCONTACTS OPEN

Page 31: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CONTACTS CLOSEDCONTACTS CLOSED

Page 32: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO TEST VOLTGE TO RATEDRATIO TEST VOLTGE TO RATEDMAXIMUM VOLTAGEMAXIMUM VOLTAGE

2.08960800

2.71860550

2.66555362

3.00425245

3.72365170

3.70310145

3.66260123

3.8216072.5

3.658038

4.036025.8

5.595015.5

In pu of Rated L-G Voltage

1 Minute Dry

(kV, rms)

Rated Maximum

Voltage (kV, rms)

Power Frequency Test

Page 33: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

MINIMUM CREEPAGE DIST.MINIMUM CREEPAGE DIST.CONTAMINATION ISSUES

LIGHT CONTAMINATION

MINIMUM CREEP AT 27.7 mm/kVrms, p-g

SALT FOG, INDUSTRIAL CONTAMINATION MAY NEED MORE CREEP

Page 34: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CREEPAGE REQUIREMENTSCREEPAGE REQUIREMENTS

12900800

8890550

5850362

3960245

2750170

2340145

1990123

117072.5

61038

42025.8

25015.5

Minimum Creepage to Ground,(mm)

Rated Maximum Voltage (kV, rms)

Page 35: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPULSE TESTLIGHTNING IMPULSE TESTINTRODUCED IN 1930’s

TEST LEVEL – 2 x LF TEST + 40 kV

1.5 x 40 μs WAVE SHAPE

NOW – 1.2 x 50 μs

FULL WAVE & 2 μs CHOPPED WAVE

10 % PROB. OF FLASHOVER OR LESS

Page 36: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPUSE LIGHTNING IMPUSE WAVESHAPEWAVESHAPE

0

0.2

0.4

0.6

0.8

1

1.2

0 10 20 30 40 50 60

Time μs

V

Page 37: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPUSE TEST LEVELSLIGHTNING IMPUSE TEST LEVELS

26402050800

23201800550

16801300362

1160900245

968750170

838650145

710550123

45235072.5

25820038

19415025.8

14211015.5

Chopped Wave (2μs)Full WaveRated MaximumVoltage (kV, rms)

Lightning Impulse

Page 38: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST PROCEEDURETEST PROCEEDURECONTACTS OPEN – ALL OTHER TERMINALS GROUNDED

CONTACTS CLOSED – ALL OTHER PHASES GROUNDED

APPLY THREE IMPULSES (NEG AND POS)

IF ZERO FLASHOVERS – PASS

IF ONE FLASHOVER IN FIRST THREE, THEN 9 MORE TESTS WITH NO FLASHOVERS

Page 39: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO OF FULL WAVE IMPULSE RATIO OF FULL WAVE IMPULSE TO RATED MAXIMUM VOLTAGETO RATED MAXIMUM VOLTAGE

3.1420508004.0118005504.4013003624.509002455.407501705.496501455.485501235.9135072.56.45200387.1215025.88.6911015.5

In pu of Rated L-G Crest Voltage

Full WaveRated MaximumVoltage (kV, rms)

Lightning Impulse

Page 40: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SWITCHING IMPULSE TESTINGSWITCHING IMPULSE TESTING

INCREASE IN SYSTEM VOLTAGE TO EHV LEVELS - 345 AND 500 kV

BEGUN IN EARLY 1960’S

TEST WAVESHAPE - 250 x 2500 μs

Page 41: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST PROCEDURETEST PROCEDUREPOSITIVE AND NEGATIVE POLARITIES

SAME 3 – 9 TEST SERIES

WET AND DRY TESTS REQUIRED

OPEN AND CLOSED TEST VALUES DIFFERENT

10 % PFO OR LESS

Page 42: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST LEVELSTEST LEVELS

15001425800

13001175550

900825362--245--170--145--123--72.5--38--25.8--15.5

Breaker Open(kV, cr)

Breaker Closed(kV, cr)

Rated MaximumVoltage (kV, rms)

Switching Impulse Terminal toTerminal

Page 43: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO OF TEST LEVELS TO RATIO OF TEST LEVELS TO RATED MAXIMUM VOLTAGERATED MAXIMUM VOLTAGE

2.181425800

2.621175550

2.79825362

In pu of Rated L-G Crest Voltage

Breaker Closed(kV, cr)

Rated MaximumVoltage (kV, rms)

Switching Impulse Terminal toTerminal

Page 44: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

2.90 PU Phase to Ground Switching Surge345 kV System

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 45: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

Application of 276 kV Surge Arrester1.83 PU

-600

-400

-200

0

200

400

600

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 46: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING SURGE PROTECTIONLIGHTNING SURGE PROTECTIONUSE OF GAPUSE OF GAP

TLine TLine

Page 47: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGNTINING SURGE LIGNTINING SURGE PROTECTION PROTECTION -- GAPSGAPS

-4000

-3000

-2000

-1000

0

1000

2000

5 7 9 11 13 15 17 19

Time (μs)

kV

2 m Rod Gap

No Protection

Page 48: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERSEPARATION DISTANCESEPARATION DISTANCE

TLine TLine

Page 49: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERPHASE TO GROUND AT OPEN BREAKERPHASE TO GROUND AT OPEN BREAKER

-500

0

500

1000

1500

2000

5 7 9 11 13 15 17 19

Time μs

kV

80 m separation40 m0 m

Page 50: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERACROSS OPEN BREAKERACROSS OPEN BREAKER

0

500

1000

1500

2000

2500

5 7 9 11 13 15 17 19

Time μs

kV

80 m separation40 m0 m

Page 51: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

EFFECT OF ALTITUDEEFFECT OF ALTITUDE

TESTED AT NTP (normal temperature and pressure)

REDUCTION IN EXTERNAL INSULATION WITH INCREASING ALTITUDE

Page 52: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

ALTITUDE CORRECTION ALTITUDE CORRECTION FACTORFACTOR

H – ALTITUDE IN METERS

m – GAP FACTOR1 FOR POWER FREQUENCY, LIGHTNING AND PHASE TO PHASE SWITCHING SURGES0.9 FOR INSULATION ACROSS OPEN GAP0.75 FOR PHASE TO GROUND SWITCHING SURGES

)8150

( Hm

d ek−

=

Page 53: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

ALTITUDE CORRECTIONALTITUDE CORRECTION

0.6

0.65

0.7

0.75

0.8

0.85

0.9

0.95

1

1.05

0 500 1000 1500 2000 2500 3000 3500 4000

Alltitude Above Sea Level, m

Alti

tude

Den

sity

Cor

rect

ion

Fact

or

Switching Surge to GroundLightning

Page 54: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …
Page 55: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

-3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1

Deviation in Strength in Number of Sigmas

Prob

abili

ty o

f Pas

sing

Tes

t

3+33+915x2