L.T. Doulos, PhD, MSc, [email protected]
Lighting Design, Hellenic Open University
Photometry Laboratory, National Technical University of Athens
Efficient Indoor Lighting Design
Miramare Hotel, Limassol, Thursday 4 May 2017
1st International Conference “Energy in Buildings”, Cyprus
Who we are…
• Luminaires
• Lamps
• Photometric, Electrical, Color, Spectral measurements
http://lighting.ece.ntua.gr/
What we do…
• Measuring LED pilot installations in municipalities and national roads
• Tunnel lighting (new installations, energy savings etc)
• Maintenance http://lighting.ece.ntua.gr/
Lighting design is changing…
• Standards
• More available information
• Optical comfort
• More and more efficient equipment, new technologies
• Lighting control, sensors, dimmers
• Energy savings and low maintenance costs
• Smart buildings
• Office
• Commercial buildings
• Hotel
• Industry – Warehouses
• Hospital
• Entertainment (wine bars, coffee shops)
• Households
Efficient lighting design is more and more necessary
Lighting design and standards
• ΕΝ 12464-1, 2011. Light and lighting - Lighting of work places, Part 1: Indoor work places
Tip: Lighting simulation tools (RELUX, Dialux) have tables with the limits
Be careful: Don’t place more luminaires than enough , for 500lux don’t calculate 650lux For Greece: Κ.Υ.Α. Δ6/Β/14826 17/6/2008
Light design using ΕΝ 12464-1, 2011
Licht.de Guide to DIN EN 12464-1
An example
Glare index UGR
Color rendering index Ra
Color quality matters
Ra or CRI;
Using the LED spectrum and standard test strips, it is examined how the LED renders each standard colour
Color temperature and emotional response
Viitanen J., J. Lehtovaara, E. Tetri, L. Halonen. User Preferences in Office Lighting: A Case Study Comparing LED and T5 Lighting, Leukos, 9, 4, (2013) 261-290
Users noted as the most pleasant color temperature 4100Κ for 500lx Users noted that eitherΤ5 fluorescent lamps or LED have the same emotional response
Kruithof, 1941
Photo biological hazards
Blue light hazard: increase distance from the source, no direct contact
Circadian disorder: Avoid “cold” color temperature after dusk
ΦΕΚ 145, 1/9/2010, Π.Δ. 82, 3075-3094 - Lighting Europe, February 2013
Photobiological hazards
Blue light hazard
ΙR Infra Red hazard
UV Ultra Violet hazard
Circadian rhythm disorder
Special halogen lamps
LED, MH with clear tube
MH without filters
?
Can we use 12000K lamps?
Viitanen J., J. Lehtovaara, E. Tetri, L. Halonen. User Preferences in Office Lighting: A Case Study Comparing LED and T5 Lighting, Leukos, 9, 4, (2013) 261-290
Users reported as most pleasant color temperature close to 4100Κ and no difference between T5 lamps and LEDs (Office use, 500lux)
Luminous efficacy and T5 lamps (lm/W)
75,9 lm/W*
82,4 lm/W*
* Without taken account ballast
6.500Κ
2.700Κ
Luminous efficacy and LED (lm/W)
111,5 lm/W
6.500Κ
3.000Κ
101,6 lm/W
Luminous efficacy for luminaires (lm/W)
minimum value for Greece → 55 lm/W
luminous flux of lamps
luminaire efficiency
luminous flux of
luminaire
Power of lamp
Power of Ballast or driver
Power of luminaire
An example
8.900lm X 75,34%
2 X 54W + ballast
6.705lm 56,44 lm/W
118,8W*
82,4 lm/W**
** only lamp
* 20%-25% for electromagnetic ballast, 5%-10% for electronic ballast
More standards
Technical guidelines:
• Illuminance levels
• W/m2 (Greece: 16 W/m2 for lighting levels 500lx)
• Daylight zones
• Users schedules
• ΕΝ 12464-1:2011 Light and lighting — Lighting of work places Part 1 Indoor work places
• EN 15193:2007 Energy performance of buildings. Energy requirements for lighting.
With a LED retrofit the installation will be lower than 16W/m2. Is it enough? (EN15193: Energy performance of buildings — Energy requirements for lighting)
W/m2, maybe it is time for a stricter limit?
Typical luminous efficacies of lamps and luminaires lm/W
Lamp type Luminous efficacy of
lamps (lm/W) LOR
Luminous efficacy of luminaire (lm/W)
Fluorescent Τ5 90 70% 63
Fluorescent Τ8 80 70% 56
LED 160 70% 112
ΗPS 140 70% 98
HPM 60 70% 42
MH 120 70% 84
CFL 60 60% 36
Less energy efficient lamps are banned
• “COMMISSION REGULATION (EC) No 245/2009 of 18 March 2009*” from April 2015 High Intensity Discharge lamps with low luminous efficacy (lm/W) are banned
• ΗPM lamps have banned
54,4 – 60lm/W
HPM lamp
* EC Regulations are mandatory in Ε.U. countries
Can we just replace HPS lamps from 400W to 250W or 150W;
Luminaire HPS 250W Lamp 250W Lamp 150W
288,9W 265,5W 100% Στο 92%
Luminaire HPS 400W Lamp 400W Lamp 250W
429,0W 428,1W 100% Στο 99,8%
Replacement;
Life time;
Photometric results;
?
Dimming profiles of ballasts and drivers
Doulos T. L. et al. Quantifying energy savings in daylight responsive systems : The role of dimming electronic ballasts, Energy and Buildings 40 (2008) 36–50
238 lux
227 lux
214 lux
Light economics
15 luminaires 2Χ36W T8
Installed power 1,3kW
Power reduction 56% Reduced maintenance costs
The feasibility study will result in the selection with the fewest luminaires
Scenario Α, retrofit 1 to 1 15 luminaires 38W LED Installed power 0,57kW
Scenario Β, retrofit with fewer luminaires 10 luminaires 57W LED Installed power 0,57kW
LED can be dimmed to the proper lighting levels
Target illuminance: 300lx
356 lx, Uo 0,72, 7,32W/m2 , 63,7 lm/W
The same luminaire LED increasing current (and heat sink) can be used
for target illuminance 500lx
Malpractice with LED driver
With proper driver
Max 79,1 oC
Malpractice
Max 151,3 oC
Fast ageing
Using LED luminaire or Τ8 LED tubes?
What is happening with CE;
LED Luminaires: more expensive but more efficient and according standards
Selecting the proper luminaire
• Lighting Output Ratio, luminous efficacy • Type of the lamps • Optical equipment (Lens, anti glare etc) • Placement and volume of luminaire • IP protection
The selection of the light distribution
Finally… the specifications
• Photometric calculations according ΕΝ12464-1
• Energy national rules
• High LOR, Luminous Efficacy >90lm/W
• Power Factor >0,9
• Color Temperature 3000Κ-4000Κ, CRI not only Ra8 > 80 but also Ra15 > 80
• Replaceable LED modules
• Heat sink and check with thermophotography
More specifications
• Life time with high LLMF factor
• Declaration of Conformity CE, Photobiological safety, Restriction of the use of certain Hazardous Substances in electrical and electronic equipment Directive ROHS, ISO κλπ
• Proper light distribution
• Photometric files *.ldt ή *.ies
• Warranty
The placement of the luminaires isn’t lighting design
Relux a free lighting simulation tool
Sensor placement
Emergency lighting according EN 1838
Energy calculations according EN 15193 and
DIN 18599
Interior lighting according EN 12464 -1
Exterior lighting according EN 12464 -2
Road lighting according EN 13201 and Tunnel lighting
www.relux.biz
Thank you
Lighting Standards
• For luminaires
• For lighting design
Φωτιστικά σώματα και πρότυπα
• Declaration of Conformity from manufacturer CE
• Electromagnetic compatibility Directive (EMC)
• Low Voltage Directive (LVD)
• EN 62031 ( Ασφάλεια των LED στον γενικό φωτισμό)
• ΕΝ 62471 ( Πρότυπο για τη κατηγοριοποίηση των δομικών μονάδων LED ως προς την φωτοβιολογική καταλληλότητα / ασφάλεια)
• Πιστοποιητικά ISO 9001:2008 και ISO 14001:2004 για το εργοστάσιο κατασκευής από αναγνωρισμένο φορέα πιστοποίησης
• Restriction of the use of certain Hazardous Substances in electrical and electronic equipment Directive (RoHS)
Is ENEC necessary;
Private logo
• CE
• Φωτοβιολογική καταλληλότητα
• ROHS
• ISO
…, however….
• Υποχρεωτική είναι η σήμανση CE*
• Δεν είναι υποχρεωτική η πιστοποίηση ΕΝΕC
CE - EMC
Πρότυπο Περιγραφή μέτρησης Θύρα Τάξη
EN 55015 Αγόμενες διαταραχές
9kHz έως 30MHz AC τροφοδοσία B
EN 55015 Εκπεμπόμενες διαταραχές
9kHz έως 30MHz Περίβλημα B
EN 55015 Εκπεμπόμενες διαταραχές 30MHz έως 300MHz Περίβλημα B
ΕΝ 61000-3-2 Διαταραχές αρμονικών ρεύματος AC τροφοδοσία C
EN 61000-3-3 Διακυμάνσεις τάσης AC τροφοδοσία -
Πρότυπο Περιγραφή μέτρησης Θύρα Επίπεδο Κριτήριο
EN 61000-4-2 Ηλεκτροστατικές εκφορτίσεις Περίβλημα ±8kV αέρος
±4kV επαφής
B
Β
EN 61000-4-3 RF εκπεμπόμενο ΗΜ πεδίο Περίβλημα 3V/m A
EN 61000-4-4 Ριπές παλμών AC τροφοδοσία ±1kV B
EN 61000-4-4 Ριπές παλμών Signal and telecom. ±1kV B
EN 61000-4-5 Υπερτάσεις - Υπερεντάσεις AC τροφοδοσία L PE ±2kV
Lines ±1kV C
EN 61000-4-5 Υπερτάσεις - Υπερεντάσεις Signal and telecom. B
EN 61000-4-6 RF αγόμενο ΗΜ πεδίο AC τροφοδοσία 3V A
EN 61000-4-6 RF αγόμενο ΗΜ πεδίο Signal and telecom. 3V A
EN 61000-4-8 Μαγνητικό πεδίο βιομηχανικής
συχνότητας Περίβλημα 3A/m A
EN 61000-4-11 Βυθίσεις και διακοπές τάσεις AC τροφοδοσία 0,5 κύκλος
10 κύκλοι
B
C
• Μετρήσεις διαταραχών
• Δοκιμές ατρωσίας
CE - LVD
• Δοκιμές ασφάλειας
Δοκίμιο Υπηρεσία Πρότυπο
Φωτιστικό Σώμα LED Δρόμου Δοκιμές τύπου EN 60598-1
EN 60598-2-3
Φωτιστικό Σώμα LED Εσωτερικού Χώρου Δοκιμές τύπου EN 60598-1
EN 60598-2-1
Φωτιστικό Σώμα LED Χωνευτό Δοκιμές τύπου EN 60598-1
EN 60598-2-2
Αξιολόγηση εξοπλισμού φωτισμού σχετικού με την
ανθρώπινη έκθεση σε ηλεκτρομαγνητι-κά πεδία (αν έχουν
γίνει οι δοκιμές EMC)
Δοκιμές τύπου EN 62493
Αξιολόγηση εξοπλισμού φωτισμού σχετικού με την
ανθρώπινη έκθεση σε ηλεκτρομαγνητι-κά πεδία (αν δεν
έχουν γίνει οι δοκιμές EMC)
Δοκιμές τύπου EN 62493
Φωτιστικό Σώμα LED Έλεγχος Τεκμηρίωσης για
Συμμόρφωση με ROHS -