DSE7110/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
DSEGenset
®
1ph2ph3phN
1ph2ph3ph
1ph2ph3phN
4 4
PC
VOLTS
3
+
DEUTZISUZUPERKINSCATERPILLARMTUVOLVOCUMMINSSCANIA
D +W/L
GENERATOR SENSING
VOLTSCURRENT
USBPORT
CONFIGURABLEINPUTS
DC OUTPUTS ANALOGUESENDERS
EMERGENCY STOP
DC POWER SUPPLY 8-35V
ELECTRONICENGINES ORMAGNETIC PICK-UP
FUEL & CRANKOUTPUTS(Flexible with CAN)
CHARGEALTERNATOR
MAINS (UTILITY) SENSINGDSE7120 ONLY
ISSUE 2
+
1 1
N/C VOLT FREEOUTPUT
N/O VOLT FREEOUTPUT
COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS
7
OTHER
DSE7110/20
The DSE7110 is an Auto StartControl Module and the DSE7120is an Auto Mains (Utility) FailureControl Module suitable for a widevariety of single, diesel or gas, gen-set applications.
Monitoring speed, frequency,voltage, current, oil pressure,coolant temperature and fuel level,the modules will display warnings,shutdown and engine statusinformation on the back-lit LCDscreen and illuminated LEDs.
Both modules offer electronic(CAN) and non-electronic (magneticpick-up/alternator sensing) engineversions and offer an extensivenumber of flexible inputs, outputsand advanced engine protectionsso the system can be easilyadapted to suit a wide range ofapplication demands.
Enhanced features include a 4-lineicon display.
The modules can be easilyconfigured using the DSEConfiguration Suite PC software.Front panel editing is also available.
FEATURES
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment
OPERATING TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC
VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours
SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS
DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.
PENDING
DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com
055-081/10/11 (4)
KEY FEATURES• Back-lit icon LCD display• Five key menu navigation• Front panel editing• LED and LCD alarm indication• Power Save mode• 4 Digital inputs• 3 Analogue inputs (2 fixed, 1flexible)
• 6 configurable outputs• Configurable timers and alarms• Alternative configuration• Event Log (5)• CAN and Magnetic Pick up /Alt. sensing
• 3 Phase generator monitoring• Current monitoring andprotection
• 3 Phase Mains (Utility)monitoring (DSE7120 only)
• Test button (DSE7120 only)• Automatic load transfer(DSE7120 only)
• Battery voltage monitoring• Engine pre-heat• Hours counter• Comprehensive shutdown orwarning on fault condition
• Fully configurable via DSEConfiguration Suite PC software
• USB connectivity• Remote SCADA monitoring viaDSE Configuration Suite PCsoftware
KEY BENEFITS• Automatically transfers betweenmains (utility) and generatorpower (DSE7120 only)
• Hours counter provides accurate
information for monitoring andmaintenance periods
• User-friendly set-up and buttonlayout
• Multiple engine parameters aremonitored simultaneously
• Module can be configured tosuit individual applications
• Compatible with a wide rangeof CAN engines
• Uses DSE Configuration SuitePC software for simplifiedconfiguration
• IP65 rating (with suppliedgasket) offers increasedresistance to water ingress
• Licence-free software
RELATED MATERIALSTITLE PART NO’SDSE7110 Installation Instructions 053-080DSE7120 Installation Instructions 053-081DSE7100 Operator Manual 057-113DSE7100 Configuration Suite PC Manual 057-117
DSE7110/20AUTO START & AUTO MAINS FAILURECONTROL MODULES
®
DSEGenset
DSE7110
DSE7120
FEATURES
Registered in England & Wales No.01319649VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.
SPECIFICATION
DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT290 mA at 12 V, 140 mA at 24 V
MAXIMUM STANDBY CURRENT75 mA at 12 V, 40 mA at 24 V
CHARGE FAIL/EXCITATION RANGE0 V to 35 V
MAINS (UTILITY) DSE7120 ONLYVOLTAGE RANGE15 V to 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
OUTPUTSOUTPUT A (FUEL)15 A DC at supply voltage
OUTPUT B (START)15 A DC at supply voltage
OUTPUTS C & D8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E, F, G & H2 A DC at supply voltage
GENERATORVOLTAGE RANGE 15 V to 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
MAGNETIC PICK UPVOLTAGE RANGE+/- 0.5 V to 70 V
FREQUENCY RANGE10,000 Hz (max)
DIMENSIONSOVERALL240 mm x 181 mm x 42 mm 9.4” x 7.1” x 1.6”
PANEL CUT-OUT220 mm x 160 mm8.7” x 6.3”
MAXIMUM PANEL THICKNESS8 mm0.3”
STORAGE TEMPERATURE RANGE-40 oC to +85 oC
OPERATING TEMPERATURE RANGE-30°C TO +70°C