CEEP MILESTONE 5 REPORT
Community
Energy
Efficiency
Program
Community
Energy
Efficiency
Program
CEEP – Fifth Milestone Requirements
In accordance with The Community Energy Efficiency Program (CEEP) Milestone Agreement, The City
of Canada Bay Council is submitting a report to address the following deliverables:
Milestone Description and Deliverables Milestone Date DCCEE Funding
(GST Exclusive)
5. Fifth Milestone
Submission of a Milestone Report for acceptance by the
Department in accordance with clause 8.4 indicating the
level of Other Contributions made in relation to and
completion in accordance with approved project plan in
Milestone 2 of the activities described in:
a. 1.2 from Table 1 including evidence of
completed works and testing;
b. 2.2 from Table 2 including evidence of
completed works and testing;
c. 3.2 from Table 3 including evidence of
completed works and testing;
d. 4.2 from Table 4 including evidence of
completed works and testing
e. 5.3.2 and 5.3.3 from Table 5 including a copy
of all fact sheets developed, in Attachment A
to Schedule 2.
Submission of a Final Report in accordance with Schedule 4
for approval by the Department in accordance with clause 8.4
of the Agreement including submitting evidence to the
Department of all expenses incurred by the Recipient in
relation to contingencies forming part of the Budget identified
in Item 2 of this Schedule 2
f. Submission of a Financial Report for
acceptance by the Department in accordance
with clause 8.2 and 8.4 of the Agreement.
Wednesday
30th October
2013
$70,808
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 3 of 77 Last Revised: 12/02/2014
PART A: Five Dock Leisure Centre, Crn Queens and William Street, Five Dock NSW 2046
PART Activity
Expected
completion
date
Estimated
cost
A.1
A.2
Lighting,
metering and
HVAC works
1.2.1 Completion of lighting works,
(including testing lighting Lux levels and
taking spot readings), and correct disposal
of lights in accordance with applicable
Local, State, Territory and Commonwealth
legislation including codes and policies.
30th October
2013
$20,000
A.3 Lighting,
metering and
HVAC works
1.2.2 Completion of HVAC works
Schedule and complete installation,
including airflow testing to ensure air
volumes and quality levels meet all
applicable standards.
30th October
2013
$20,000
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 4 of 77 Last Revised: 12/02/2014
PART A.1– Completion of lighting works, (including testing lighting Lux levels and taking spot readings). Please refer to appendix C.1 – Envirolite Community Energy Efficiency-Lighting Upgrade Handover Report – Five Dock Leisure Centre, Section 6 for the Lux Levels recorded after installation. (Section 6 of the Handover Report details the measurement procedure, lux meter and positioning guide, lux meter specifications and pre and post lux readings.)
Page Removed for Publication
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 6 of 77 Last Revised: 12/02/2014
Below are some images of the completed lighting upgrades a Five Dock Leisure Centre for your review:
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 7 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 8 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 9 of 77 Last Revised: 12/02/2014
PART A.2 – Disposal of lights.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 10 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 11 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 12 of 77 Last Revised: 12/02/2014
PART A.3 – Schedule and complete installation, including airflow testing to ensure air volumes and quality levels meet all applicable standards.
Below are some images of the completed HVAC upgrades a Five Dock Leisure Centre for your review:
Please refer to Folder – HVAC Technical Specs for further information
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 13 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 14 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 15 of 77 Last Revised: 12/02/2014
PART B: City of Canada Bay Council Depot, 15-17 Regatta Road, Five Dock NSW 2046
PART Activity Expected
completion
date
Estimated
Cost
B.1
B.2
Lighting,
metering
and HVAC
works
2.2.1 Completion of lighting works, (including
testing lighting Lux levels and taking spot
readings), and correct disposal of lights in
accordance with applicable Local, State,
Territory and Commonwealth legislation
including codes and policies.
30th October
2013
$20,000
B.3
Lighting,
metering
and HVAC
works
2.2.2 Completion of HVAC works.
Schedule and complete installation, including
airflow testing to ensure air volumes and
quality levels meet all applicable standards.
30th October
2013
$20,000
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 16 of 77 Last Revised: 12/02/2014
PART B.1 – Completion of lighting works, (including testing lighting Lux levels and taking spot readings),
Please refer to Appendix C.2 - Envirolite Community Energy Efficiency-Lighting Upgrade Handover Report – CCBC Depot, section 6 for the Lux Levels recorded after installation. (Section 6 of the Handover Report details the measurement procedure, lux meter and positioning guide, lux meter specifications and pre and post lux readings.)
Page Removed for Publication
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 18 of 77 Last Revised: 12/02/2014
Below are some images of the completed lighting upgrades to the Council Depot for your review:
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 19 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 20 of 77 Last Revised: 12/02/2014
PART B.2 –Disposal of lights in accordance with applicable Local, State, Territory and Commonwealth legislation including codes and policies.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 21 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 22 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 23 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 24 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 25 of 77 Last Revised: 12/02/2014
PART B.3 – Schedule and complete installation, including airflow testing to ensure air volumes and quality levels meet all applicable standards.
Below are some images of the completed HVAC upgrades to the Council Depot for your review:
Please refer to folder – HVAC Technical Specs for more information
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 26 of 77 Last Revised: 12/02/2014
PART C: City of Canada Bay Council Civic Centre, 1a Marlborough Street, Drummoyne NSW 2047
PART Activity Expected
completion
date
Estimated
cost
C.1
C.2
Lighting,
metering and
HVAC works
3.2.1 Completion of lighting works,
(including testing lighting Lux levels
and taking spot readings), and correct
disposal of lights in accordance with
applicable Local, State, Territory and
Commonwealth legislation including
codes and policies.
30th October
2013
$50,000
C.3
Lighting,
metering and
HVAC works
3.2.2 Completion of HVAC works.
Schedule and complete installation,
including airflow testing to ensure air
volumes and quality levels meet all
applicable standards.
30th October
2013
$80,000
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 27 of 77 Last Revised: 12/02/2014
PART C.1 – Completion of lighting works, (including testing lighting Lux levels and taking spot readings),
Please refer to Appendix C.3 - Envirolite Community Energy Efficiency-Lighting Upgrade Handover Report –CCBC Civic Centre, Section 6 for the Lux Levels recorded after installation. (Section 6 of the Handover Report details the measurement procedure, lux meter and positioning guide, lux meter specifications and pre and post lux readings.)
Page Removed for Publication
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 29 of 77 Last Revised: 12/02/2014
Below are some images of the completed lighting upgrades to the Council Civic Centre for your
review:
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 30 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 31 of 77 Last Revised: 12/02/2014
PART C.2 –Disposal of lights in accordance with applicable Local, State, Territory and Commonwealth legislation including codes and policies.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 32 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 33 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 34 of 77 Last Revised: 12/02/2014
PART C.3 – Schedule and complete installation, including airflow testing to ensure air volumes and quality levels meet all applicable standards.
Below are some images of the completed HVAC upgrades to the Council Civic Centre for your
review:
Please refer to folder – HVAC Technical Specs for further information
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 35 of 77 Last Revised: 12/02/2014
PART D: Concord Oval, Cnr Loftus and Gipps Street, Concord NSW 2137
PART Activity Expected
completion
date
Estimated
Cost
D.1
D.2
Lighting,
metering
and HVAC
works
4.2.1 Completion of lighting works, (including
testing lighting lux levels and taking spot
readings), and correct disposal of lights in
accordance with applicable Local, State,
Territory and Commonwealth legislation
including codes and policies.
30th October
2013
$20,000
D.3
Lighting,
metering
and HVAC
works
4.2.2 Completion of HVAC works,
Schedule and complete installation, including
airflow testing to ensure air volumes and
quality levels meet all applicable standards.
30th October
2013
$20,000
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 36 of 77 Last Revised: 12/02/2014
PART D.1 – Completion of lighting works, (including testing lighting Lux levels and taking spot readings),
Please refer to Appendix C.4 - Envirolite Community Energy Efficiency-Lighting Upgrade Handover Report – Concord Oval, Section 6 for the Lux Levels recorded after installation. (Section 6 of the Handover Report details the measurement procedure, lux meter and positioning guide, lux meter specifications and pre and post lux readings.)
Page Removed for Publication
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 38 of 77 Last Revised: 12/02/2014
Below are some images of the completed lighting upgrades to the Concord Oval for your review:
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 39 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 40 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 41 of 77 Last Revised: 12/02/2014
PART D.2 –Disposal of lights in accordance with applicable Local, State, Territory and Commonwealth legislation including codes and policies.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 42 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 43 of 77 Last Revised: 12/02/2014
PART D.3 – Schedule and complete installation, including airflow testing to ensure air volumes and quality levels meet all applicable standards.
Below are some images of the completed HVAC upgrades to the Concord Oval for your review:
Please refer to Folder – HVAC Technical Specs for further information required.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 44 of 77 Last Revised: 12/02/2014
PART E: Administration and communication activities
PART Activity Expected
completion
date
Estimated
Cost
E.1
E.2
Communica
tions
activities
5.3.2 Communication activities completed,
including:
- published Activity-related articles in
‘Bayside Brief’ and ‘The Enzine’ newsletter
- on-site communication – staggered for each
site as completion of each part of the Activity;
12th June
2013
$4,000
E.3
E.4
E.5
Communica
tions
activities
5.3.3 Fact sheets developed and distributed
with rates notices to all ratepayers in the
Recipient’s area post-Activity completion
(35,000 copies)
- case Studies for each Activity site written
and posted on Recipient’s web site; and
- case Studies presented to Local
Government Association of NSW (LGA) and
the Shires Association of NSW (SA)
30th October
2013
$5,000
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 45 of 77 Last Revised: 12/02/2014
PART E.1 – Activity-related articles in ‘Bayside Brief’ and ‘The Enzine’ newsletter.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 46 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 47 of 77 Last Revised: 12/02/2014
PART E.2 – On-site communication – staggered for each site as completion of each part of the Activity.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 48 of 77 Last Revised: 12/02/2014
PART E.3 – Fact sheets developed and distributed with rates notices to all ratepayers in the Recipient’s area post-Activity completion (35,000 copies).
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 49 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 50 of 77 Last Revised: 12/02/2014
PART E.4 – Case Studies for each Activity site written and posted on Recipient’s web site.
The City of Canada Bay Council has developed a series of case study video clips for the sites that were upgraded under the CEEP Program, which may be viewed by clicking on the following links:
CEEP Project - Five Dock Leisure Centre: http://youtu.be/XcrkwYiwl5I
CEEP Project – City of Canada Bay Council Works Depot: http://youtu.be/bvb6-FVreO8
CEEP Project – Concord Oval: http://youtu.be/tpFbMEDzZsg
CEEP Project – City of Canada Bay Civic Centre: http://youtu.be/Z85AOKVRlyY
CEEP Program- Project Overview: http://youtu.be/c3VkYr7HwOM
Following the Department’s review and acceptance, these case study videos will be showcased on The City of Canada Bay Council’s website for access by the general public.
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 51 of 77 Last Revised: 12/02/2014
PART E.5 – Case Studies presented to Local Government Association of NSW (LGA) and the Shires Association of NSW (SA).
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 52 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 53 of 77 Last Revised: 12/02/2014
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 54 of 77 Last Revised: 12/02/2014
APPENDICIES
Supporting Information for Milestone 5:
Appendix A – Invoices for works completed during this milestone period.
A.1 – Lighting
A.2 – HVAC
A.3 – Sub Metering
A.4 – Building Renewals
A.5 – Consultancy and Project Management
Appendix B – Financial Report
Appendix C – Envirolight Handover Reports
C.1 – Handover Report – Five Dock Leisure Centre
C.2 – Handover Report – CCBC Depot
C.3 – Handover Report – CCBC Civic Centre
C.4 – Handover Report – Concord Oval
Appendix Removed for Publication
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 75 of 77 Last Revised: 12/02/2014
Appendix B: Financial Report
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 76 of 77 Last Revised: 12/02/2014
Appendix C: Lighting Handover Reports
The City of Canada Bay – Community Energy Efficiency Program (CEEP) - Milestone 5 Report
Owner: Andrew Dimitriadis Page 77 of 77 Last Revised: 12/02/2014
1a Marlborough Street, Drummoyne NSW 2047
Tel 9911 6555 Fax 9911 6550 www.canadabay.nsw.gov.au
Community Energy Efficiency-Lighting Upgrade
Contract No. 2013/TS50
Handover Report-CCBC Civic Centre
1A Marlborough St,Drummoyne.NSW.2047.
Lighting Upgrade By
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 2 -
Introduction This report has been prepared by Envirolite Pty Ltd and details the results achieved from the recent lighting upgrade
work completed at CCBC Civic Centre 1A Marlborough St, Drummoyne as part of the City of Canada Bay Council
CEEP-Lighting Upgrade Project.
Envirolite Pty Ltd, a one hundred percent Australian Owned Company, is proud to have been selected to provide the
lighting solution for this project. Energy reductions and improvements to the working environment have been achieved
via the installation of E1 light fittings which is an Australian developed world leading lighting innovation.
A summary of the benefits achieved from the installation of the new lighting is as follows:
Direct power usage by the lighting has been reduced from 266.9 amps to 105.9 amps a reduction of 60.3%
(This excludes additional savings achieved from the installation of daylight harvesting and motion sensors and in air
conditioning where it is installed due to a reduction in the lighting heat load).
The number of fittings installed on site has reduced from 879 to 816 fittings (7.17%)
The number of lamps in operation has been reduced from 1369 to 912, a reduction of 50.1%.
The number of ballasts in operation has been reduced from 1354 to 822, a reduction of 64.7%.
Lighting levels have been maintained in accordance with the requirements of Australian Lighting Standards.
Note: During the course of the installation, 23 ballasts containing carcinogenic PCB was found, removed and disposed
of according to NSW OH & S and Workcover Regulations.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 3 -
Table of Contents 1 PROJECT DATES 5
2 LIGHT FITTING COUNTS 6
2.1 PRE-EXISTING LIGHT FITTINGS 6 2.1.1 Summary 6 2.1.2 By Location 8
2.2 AS INSTALLED LIGHT FITTINGS 14 2.2.1 Summary 14 2.2.2 By Location 15
3 EXIT LIGHTS 21
3.1.1 Details 21 3.1.2 Summary 21 3.1.3 Location 21
4 SENSORS 22
4.1 SENSOR DETAILS 22 4.2 SENSOR SUMMARY 23 4.3 SENSOR LOCATIONS 23 4.4 SENSOR ID & PROGRAMMING 23
5 FITTING COMPONENTS 27
5.1 COMPARISON OF LAMP AND BALLAST NUMBERS PRE AND POST INSTALLATION 27 5.1.1 Summary 27 5.1.2 Pre-existing 27 5.1.3 As Installed 28
5.2 INSTALLED FITTING COMPONENTS 30 5.2.1 Component Legend 30 5.2.2 Component Breakdown by Fitting 31
AMP READINGS 32
5.3 SUMMARY 32 5.4 AREA BY AREA READINGS 32
6 LUX LEVELS 35
6.1 RECOMMENDED ILLUMINANCE 35 6.2 MEASUREMENT PROCEDURE 36
6.2.1 Lux Meter Positioning Guide 37 6.2.2 Small Room / Area Positioning 37 6.2.3 Medium Room / Area Positioning 38 6.2.4 Large Room / Area Positioning 38
6.3 LUX METER SPECIFICATIONS 39 6.4 PRE AND POST LUX READINGS 40
7 RECYCLING RECONCILIATION 53
7.1 METAL RECYCLING 54 7.2 LAMP RECYCLING 56
8 GENERAL FITTING GUIDELINES 57
8.1 HANDLING E1 LIGHT FITTINGS 57 8.2 CLEANING E1 LIGHT FITTINGS 57 8.3 INSTALLATION OF E1 LIGHTING 57
9 ENVIROLITE PTY LTD WARRANTY 58
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 4 -
10 ENVIROLITE PTY LTD CONTACT DETAILS 60
10.1 OPERATIONS ENQUIRIES 60
APPENDICES 61
APPENDIX A – ELECTRICAL CERTIFICATE 61 APPENDIX B – SENSOR COMMISSIONING CHECKLIST 65 APPENDIX C – SENSOR SPECIFICATIONS 68 APPENDIX D – EXIT LIGHT SPECIFICATIONS 121 APPENDIX E –AS BUILT LIGHTING LAYOUTS 130
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 5 -
1 Project Dates Work commenced on 21st August 2013 and completed on 5th September 2013.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 6 -
2 Light Fitting Counts 2.1 Pre-existing Light Fittings
2.1.1 Summary Fitting Description Subtotal
2x18W BATTEN SM 11
1x18W BATTEN 29
2x18W BATTEN EMG 5
2x18W PLASTER TROF 2
2x18W TROFFER (300MMX600MM) 10
2x36W PLASTER TROFFER 4
1x36W PLASTER TROFFER 2
2x36W TROFFER (300MMX1200MM) 198
2x36W BATTEN WG 33
2x36W BATTEN EMG 17
2x36W BATTEN SUSPENDED 18
1x36W BATTEN 9
2x36W BATTEN PD 46
2x36W WALL LIGHT 7
1x50W DICHROIC DL 271
1x50W DICHROIC 120 DIA 10
1x36W BATTEN EMG 1
2x18W DL 175-230DIA 61
EXIT LIGHTS 47
1X40W OYSTER LIGHT HALOGEN 4
1X40W WALL LIGHT HALOGEN 6
1x60W INCANDESCANT 11
1x400W High Bay 4
1x100W Flood Light 5
2x18W BATTEN PENDANT 27
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 7 -
Fitting Description Subtotal
1x18W CFL Pendant Light 39
1X250W FLOOD LIGHT 2
Total 879
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 8 -
2.1.2 By Location
Lower Ground
Fitting Description STAFF
LU
NCH
STAFF
AM
MEN
HALL
LARG
E S
TORE &
STO
RE
CARPA
RK A
ND
STO
RAG
E
KIT
CH
EN
CO
RP
PRIN
TIN
G
OPE
N O
FFIC
E
OFF
ICE 1
OFF
ICE 2
OFF
ICE 3
OFF
ICE 4
STAIR
1
STAIR
2
STAIR
3
Tota
l Lo
wer
Gro
und
2x18W BATTEN SM 11 11
1x18W BATTEN 8 8 2x18W BATTEN EMG 1 1 2 4 2x18W PLASTER TROF 2 2 2x18W TROFFER (300MMX600MM) 0 2x36W PLASTER TROFFER 0 1x36W PLASTER TROFFER 0 2x36W TROFFER (300MMX1200MM) 4 4
2x36W BATTEN WG 20
13 33
2x36W BATTEN EMG 1 4 2 2 9
2x36W BATTEN SUSPENDED 18 18
1x36W BATTEN 1 1 2 2x36W BATTEN PD 0 2x36W WALL LIGHT 4 2 1 7 1x50W DICHROIC DL 2 3 5 1x50W DICHROIC 120 DIA 0 1x36W BATTEN EMG 1 1 2x18W DL 175-230DIA 4 6 2 4 6 2 24 EXIT LIGHTS 1 3 2 2 2 1 11 1X40W OYSTER LIGHT HALOGEN 0 1X40W WALL LIGHT HALOGEN 0 1x60W INCANDESCANT 0 1x400W High Bay 0 1x100W Flood Light 0 2x18W BATTEN PENDANT 0 1x18W CFL Pendant Light 0 1X250W FLOOD LIGHT 0
Total Lower Ground 13 10 8 23 20 4 4 24 6 4 5 6 7 3 2 139
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 9 -
Fitting Description2x
18W
BA
TTE
N S
M
1x18
W B
ATT
EN
2x18
W B
ATT
EN
EM
G
2x18
W P
LAS
TER
TR
OF
2x18
W T
RO
FFE
R (3
00M
MX
600M
M)
2x36
W P
LAS
TER
TR
OFF
ER
1x36
W P
LAS
TER
TR
OFF
ER
2x36
W T
RO
FFE
R (3
00M
MX
1200
MM
)
2x36
W B
ATT
EN
WG
2x36
W B
ATT
EN
EM
G
2x36
W B
ATT
EN
SU
SP
EN
DE
D
1x36
W B
ATT
EN
2x36
W B
ATT
EN
PD
2x36
W W
ALL
LIG
HT
1x50
W D
ICH
RO
IC D
L
1x50
W D
ICH
RO
IC 1
20 D
IA
1x36
W B
ATT
EN
EM
G
2x18
W D
L 17
5-23
0DIA
EX
IT L
IGH
TS
1X40
W O
YS
TER
LIG
HT
HA
LOG
EN
1X40
W W
ALL
LIG
HT
HA
LOG
EN
1x60
W IN
CA
ND
ES
CA
NT
1x40
0W H
igh
Bay
1x10
0W F
lood
Lig
ht
2x18
W B
ATT
EN
PE
ND
AN
T
1x18
W C
FL P
enda
nt L
ight
1X25
0W F
LOO
D L
IGH
T
Tota
l Gro
und
RECORDS UNIT 8 5 13LIBRARY 8 8
LIBRARY OFFICE 3 3RECORDS OFFICE CORRIDOR 4 2 6
STAIR 5 1 5 6MALE 4 4
FEMALE 5 5MANAGER CIT SERVIC 2 2PA DIRECTOR OFFICE 8 8DIRECTOR INFO SER 1 2 3
CORRIDOR 1 4 6 3 13CITIZEN SERV UNIT 8 8
CITIZEN AUX. 1 1RECEPTION CUST SERV 46 2 48
STAIR 3 2 2KITCHEN 2 2
ENVIRO OFFICE 5 5TRAFFIC PROPERTY 1 11 12
MANAGER ASSET INFRASTRUCTURE 1 3 4HALL1 1 9 4 14
IT STORE 2 2TOILETS 2 1 2 5
DB 1 1 1HALL2 12 1 1 14
MEETING ROOM 2 2 4STAIR 4 2 2
COMP ROOM 3 3STAIR 2 2 2
IT MANAGER 3 3IT OFFICE 6 6
IT HALL 4 4OPEN OFFICE 01 4 18 22
STAIR 1 4 4OFFICE 1 2 2 4OFFICE 2 2 2 4OFFICE 3 3 3 6OFFICE 4 2 2 4OFFICE 5 3 3 6
OPEN AREA 20 10 12 42OUTSIDE 13 13
Total Ground 0 11 0 0 10 0 2 123 0 4 0 1 6 0 102 10 0 37 12 0 0 0 0 0 0 0 0 318
Gro
und
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 10 -
Fitting Description
2x18
W B
ATT
EN
SM
1x18
W B
ATT
EN
2x18
W B
ATT
EN
EM
G
2x18
W P
LAS
TER
TR
OF
2x18
W T
RO
FFE
R (3
00M
MX
600M
M)
2x36
W P
LAS
TER
TR
OFF
ER
1x36
W P
LAS
TER
TR
OFF
ER
2x36
W T
RO
FFE
R (3
00M
MX
1200
MM
)
2x36
W B
ATT
EN
WG
2x36
W B
ATT
EN
EM
G
2x36
W B
ATT
EN
SU
SP
EN
DE
D
1x36
W B
ATT
EN
2x36
W B
ATT
EN
PD
2x36
W W
ALL
LIG
HT
1x50
W D
ICH
RO
IC D
L
1x50
W D
ICH
RO
IC 1
20 D
IA
1x36
W B
ATT
EN
EM
G
2x18
W D
L 17
5-23
0DIA
EX
IT L
IGH
TS
1X40
W O
YSTE
R L
IGH
T H
ALO
GEN
1X40
W W
ALL
LIG
HT
HA
LOG
EN
1x60
W IN
CA
ND
ES
CA
NT
1x40
0W H
igh
Bay
1x10
0W F
lood
Lig
ht
2x18
W B
ATTE
N P
END
ANT
1x18
W C
FL P
enda
nt L
ight
1X25
0W F
LOO
D L
IGH
T
Tota
l Lev
el 1
ROOM 1 4 4ROOM 2 2 2ROOM 3 3 3ROOM 4 38 3 41
ROOM 5 MALE 4 4ROOM 5A FEMALE 4 4
STAIRS 1 5 5ROOM 6 4 4ROOM 7 2 2ROOM 8 4 4STAIRS 2 1 1ROOM 10 3 3ROOM 11 8 8
HALL 1 1ROOM 12 2 2ROOM 13 5 5ROOM 14 6 6ROOM 15 17 1 18ROOM 16 42 1 43ROOM 17 2 2ROOM 18 3 3
DB2 1 1KITCHEN 4 4ROOM 20 2 2
HALL 7 2 9ROOM 23 25 1 6 32ROOM 24 24 1 25
Total Level 1 0 8 0 0 0 4 0 71 0 4 0 3 0 0 130 0 0 0 9 3 6 0 0 0 0 0 0 238
Leve
l 1
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 11 -
Rangers Cottage
Fitting Description
KIT
CH
EN
HA
LL
RO
OM
1
RO
OM
2
RO
OM
3
RO
OM
4
RO
OM
5
RO
OM
6
RO
OM
7
RO
OM
8
RO
OM
9
RO
OM
10
RO
OM
11
Toile
t
tota
l Ran
gers
cot
tage
2x18W BATTEN SM 0 1x18W BATTEN 0 2x18W BATTEN EMG 0 2x18W PLASTER TROF 0 2x18W TROFFER (300MMX600MM) 0 2x36W PLASTER TROFFER 0 1x36W PLASTER TROFFER 0 2x36W TROFFER (300MMX1200MM) 0 2x36W BATTEN WG 0 2x36W BATTEN EMG 0 2x36W BATTEN SUSPENDED 0 1x36W BATTEN 1 1 2 2x36W BATTEN PD 1 2 3 1 2 2 11 2x36W WALL LIGHT 0 1x50W DICHROIC DL 2 3 4 9 1x50W DICHROIC 120 DIA 0 1x36W BATTEN EMG 0 2x18W DL 175-230DIA 0 EXIT LIGHTS 0 1X40W OYSTER LIGHT HALOGEN 0 1X40W WALL LIGHT HALOGEN 0 1x60W INCANDESCANT 5 1 1 1 1 1 1 11 1x400W High Bay 0 1x100W Flood Light 0 2x18W BATTEN PENDANT 0 1x18W CFL Pendant Light 0 1X250W FLOOD LIGHT 0
Total Rangers Cottage 4 8 6 3 1 3 2 1 1 1 1 1 0 1 33
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 12 -
Civic Hall
Fitting Description
EN
TRY
MA
LE
FEM
ALE
KIT
CH
EN
MA
IN H
ALL
STA
GE
TOIL
ET
LOW
ER
LEV
EL
OU
TSID
E
Tota
l Civ
ic H
all
2x18W BATTEN SM 0 1x18W BATTEN 1 1 2 2x18W BATTEN EMG 1 1 2x18W PLASTER TROF 0 2x18W TROFFER (300MMX600MM) 0 2x36W PLASTER TROFFER 0 1x36W PLASTER TROFFER 0 2x36W TROFFER (300MMX1200MM) 0 2x36W BATTEN WG 0 2x36W BATTEN EMG 0 2x36W BATTEN SUSPENDED 0 1x36W BATTEN 1 1 2x36W BATTEN PD 3 2 2 4 8 10 29 2x36W WALL LIGHT 0 1x50W DICHROIC DL 21 4 25 1x50W DICHROIC 120 DIA 0 1x36W BATTEN EMG 0 2x18W DL 175-230DIA 0 EXIT LIGHTS 2 1 1 2 6 3 15 1X40W OYSTER LIGHT HALOGEN 1 1 1X40W WALL LIGHT HALOGEN 0 1x60W INCANDESCANT 0 1x400W High Bay 4 4 1x100W Flood Light 5 5 2x18W BATTEN PENDANT 20 2 5 27 1x18W CFL Pendant Light 9 30 39 1X250W FLOOD LIGHT 2 2
Total Civic Hall 35 3 8 6 60 15 3 19 2 151
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 13 -
Total Sites
Fitting Description
Tota
l Low
er G
roun
d
Tota
l Gro
und
Tota
l Lev
el 1
tota
l Ran
gers
cot
tage
Tota
l Civ
ic H
all
Tota
l All
site
s
2x18W BATTEN SM 11 0 0 0 0 11 1x18W BATTEN 8 11 8 0 2 29 2x18W BATTEN EMG 4 0 0 0 1 5 2x18W PLASTER TROF 2 0 0 0 0 2 2x18W TROFFER (300MMX600MM) 0 10 0 0 0 10 2x36W PLASTER TROFFER 0 0 4 0 0 4 1x36W PLASTER TROFFER 0 2 0 0 0 2 2x36W TROFFER (300MMX1200MM) 4 123 71 0 0 198 2x36W BATTEN WG 33 0 0 0 0 33 2x36W BATTEN EMG 9 4 4 0 0 17 2x36W BATTEN SUSPENDED 18 0 0 0 0 18 1x36W BATTEN 2 1 3 2 1 9 2x36W BATTEN PD 0 6 0 11 29 46 2x36W WALL LIGHT 7 0 0 0 0 7 1x50W DICHROIC DL 5 102 130 9 25 271 1x50W DICHROIC 120 DIA 0 10 0 0 0 10 1x36W BATTEN EMG 1 0 0 0 0 1 2x18W DL 175-230DIA 24 37 0 0 0 61 EXIT LIGHTS 11 12 9 0 15 47 1X40W OYSTER LIGHT HALOGEN 0 0 3 0 1 4 1X40W WALL LIGHT HALOGEN 0 0 6 0 0 6 1x60W INCANDESCANT 0 0 0 11 0 11 1x400W High Bay 0 0 0 0 4 4 1x100W Flood Light 0 0 0 0 5 5 2x18W BATTEN PENDANT 0 0 0 0 27 27 1x18W CFL Pendant Light 0 0 0 0 39 39 1X250W FLOOD LIGHT 0 0 0 0 2 2
Total All Sites 139 318 238 33 151 879
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 14 -
2.2 As Installed Light Fittings 2.2.1 Summary Fitting Description Subtotal
1X14W TROFFER SURFACE MOUNTED 2
2X14W TROFFER SURFACE MOUNTED 4
2x26W BATTEN 10
1x14W BATTEN 35
1x14W BATTEN EMG 5
1x14W TROFFER DIM 10
1x26W PLASTER DIM 6
1x26W TROFFER DIM 169
2x26W TROFFER DIM 24
1x26W BATTEN PD 59
1x26W BATTEN EMG 14
2X26W TROFFER SUSPENDED 18
2X26W TROFFER WALL FITTING 6
1x10.5W DR700 LED DOWNLIGHT 185
1X14W TROFFER PLASTER 2
1X36W BATTEN EMG 4
1x16W D1000 LED DOWNLIGHT 112
EXIT LIGHTS 47
1X32W LED OYSTER LAMP 5
1X7W OSRAM LED RELAMP 13
5x36W HIGH BAY 6
1X40W MAT INDUCTION 5
2X30W BATTEN 10
1x12W OSRAM PARATHOM LED RELAMP 18
1X36W BATTEN WEATHERPROOF 17
1X120W MAT FLOOD 2
1X14W WALL LIGHT 6
1X26W WALL LIGHT 1
1X16W D900 LED DOWNLIGHT 21
816
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 15 -
2.2.2 By Location
Lower Ground
Fitting Description
STAFF
LU
NCH
STAFF
AM
MEN
HALL
LARG
E S
TORE &
STO
RE
CARPA
RK A
ND
STO
RAG
E
KIT
CH
EN
CO
RP
PRIN
TIN
G
OPE
N O
FFIC
E
OFF
ICE 1
OFF
ICE 2
OFF
ICE 3
OFF
ICE 4
STAIR
1
STAIR
2
STAIR
3
Tota
l Lo
wer
Gro
und
1X14W TROFFER SURFACE MOUNTED 2 2 2X14W TROFFER SURFACE MOUNTED 4 4 2x26W BATTEN 0 1x14W BATTEN 8 8 1x14W BATTEN EMG 1 1 2 4 1x14W TROFFER DIM 0 1x26W PLASTER DIM 0 1x26W TROFFER DIM 4 4 2x26W TROFFER DIM 0 1x26W BATTEN PD 1 18 19 1x26W BATTEN EMG 2 2 2 6 2X26W TROFFER SUSPENDED 18 18 2X26W TROFFER WALL FITTING 4 1 1 6 1x10.5W DR700 LED DOWNLIGHT 0 1X14W TROFFER PLASTER 2 2 1X36W BATTEN EMG 4 4 1x16W D1000 LED DOWNLIGHT 2 4 6 2 4 8 5 31 EXIT LIGHTS 1 3 2 2 2 1 11 1X32W LED OYSTER LAMP 0 1X7W OSRAM LED RELAMP 0 5x36W HIGH BAY 0 1X40W MAT INDUCTION 0 2X30W BATTEN 0 1x12W OSRAM PARATHOM LED RELAMP 0 1X36W BATTEN WEATHERPROOF 3 14 17 1X120W MAT FLOOD 0 1X14W WALL LIGHT 0 1X26W WALL LIGHT 1 1 1X16W D900 LED DOWNLIGHT 0
Total Lower Ground 9 10 8 23 20 4 4 24 6 4 5 8 7 3 2 137
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 16 -
Fitti
ng D
escr
iptio
n
1X14
W T
RO
FFE
R S
UR
FAC
E M
OU
NTE
D
2X14
W T
RO
FFE
R S
UR
FAC
E M
OU
NTE
D
2x26
W B
ATT
EN
1x14
W B
ATT
EN
1x14
W B
ATT
EN
EM
G
1x14
W T
RO
FFE
R D
IM
1x26
W P
LAS
TER
DIM
1x26
W T
RO
FFE
R D
IM
2x26
W T
RO
FFE
R D
IM
1x26
W B
ATT
EN
PD
1x26
W B
ATT
EN
EM
G
2X26
W T
RO
FFE
R S
US
PE
ND
ED
2X26
W T
RO
FFE
R W
ALL
FIT
TIN
G
1x10
.5W
DR
700
LED
DO
WN
LIG
HT
1X14
W T
RO
FFE
R P
LAS
TER
1X36
W B
ATT
EN
EM
G
1x16
W D
1000
LE
D D
OW
NLI
GH
T
EX
IT L
IGH
TS
1X32
W L
ED
OY
STE
R L
AM
P
1X7W
OS
RA
M L
ED
RE
LAM
P
5x36
W H
IGH
BA
Y
1X40
W M
AT
IND
UC
TIO
N
2X30
W B
ATT
EN
1x12
W O
SR
AM
PA
RA
THO
M L
ED
RE
LAM
P
1X36
W B
ATT
EN
WE
ATH
ER
PR
OO
F
1X12
0W M
AT
FLO
OD
1X14
W W
ALL
LIG
HT
1X26
W W
ALL
LIG
HT
1X16
W D
900
LED
DO
WN
LIG
HT
Tota
l Gro
und
RECORDS UNIT 12 12LIBRARY 7 1 8
LIBRARY OFFICE 3 3RECORDS OFFICE CORRIDOR 4 2 6
STAIR 5 1 5 6MALE 4 4
FEMALE 5 5MANAGER CIT SERVIC 2 2PA DIRECTOR OFFICE 7 7DIRECTOR INFO SER 2 2
CORRIDOR 1 5 4 3 12CITIZEN SERV UNIT 8 8
CITIZEN AUX. 1 1RECEPTION CUST SERV 46 2 48
STAIR 3 2 2KITCHEN 2 2
ENVIRO OFFICE 4 4TRAFFIC PROPERTY 11 11
MANAGER ASSET INFRA 3 3HALL1 8 2 4 14
IT STORE 2 2TOILETS 2 1 2 5
DB 1 1 1HALL2 11 1 12
MEETING ROOM 4 4STAIR 4 2 2
COMP ROOM 3 3STAIR 2 2 2
IT MANAGER 3 3IT OFFICE 6 6
IT HALL 7 7OPEN OFFICE 01 22 22
STAIR 1 4 4OFFICE 1 2 2OFFICE 2 2 2OFFICE 3 3 3OFFICE 4 2 2OFFICE 5 3 3
OPEN AREA 20 22 42OUTSIDE 2 11 13
Total Ground 0 0 0 11 0 7 2 106 16 2 4 0 0 65 0 0 62 12 0 13 0 0 0 0 0 0 0 0 0 300
Gro
und
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 17 -
Fitti
ng D
escr
iptio
n
1X14
W T
RO
FFE
R S
UR
FAC
E M
OU
NTE
D
2X14
W T
RO
FFE
R S
UR
FAC
E M
OU
NTE
D
2x26
W B
ATT
EN
1x14
W B
ATT
EN
1x14
W B
ATT
EN
EM
G
1x14
W T
RO
FFE
R D
IM
1x26
W P
LAS
TER
DIM
1x26
W T
RO
FFE
R D
IM
2x26
W T
RO
FFE
R D
IM
1x26
W B
ATT
EN
PD
1x26
W B
ATT
EN
EM
G
2X26
W T
RO
FFER
SU
SPEN
DED
2X26
W T
RO
FFE
R W
ALL
FIT
TIN
G
1x10
.5W
DR
700
LED
DO
WN
LIG
HT
1X14
W T
RO
FFE
R P
LAS
TER
1X36
W B
ATT
EN
EM
G
1x16
W D
1000
LE
D D
OW
NLI
GH
T
EX
IT L
IGH
TS
1X32
W L
ED
OY
STE
R L
AM
P
1X7W
OS
RA
M L
ED
RE
LAM
P
5x36
W H
IGH
BA
Y
1X40
W M
AT IN
DU
CTI
ON
2X30
W B
ATT
EN
1x12
W O
SR
AM
PA
RA
THO
M L
ED
RE
LAM
P
1X36
W B
ATTE
N W
EATH
ERPR
OO
F
1X12
0W M
AT
FLO
OD
1X14
W W
ALL
LIG
HT
1X26
W W
ALL
LIG
HT
1X16
W D
900
LED
DO
WN
LIG
HT
Tota
l Lev
el 1
ROOM 1 3 3ROOM 2 2 2ROOM 3 3 3ROOM 4 3 35 3 41ROOM 5
MALE 4 4ROOM 5A FEMALE 4 4STAIRS 1 5 5ROOM 6 4 4ROOM 7 2 2ROOM 8 4 4STAIRS 2 1 1ROOM 10 3 3ROOM 11 4 4
HALL 1 1ROOM 12 2 2ROOM 13 5 5ROOM 14 6 6ROOM 15 17 1 18ROOM 16 42 1 43ROOM 17 2 2ROOM 18 3 3
DB2 1 1KITCHEN 4 4ROOM 20 2 2
HALL 7 2 9ROOM 23 25 1 6 32ROOM 24 24 1 25
Total Level 1 0 0 0 8 0 3 4 59 8 3 4 0 0 116 0 0 10 9 3 0 0 0 0 0 0 0 6 0 0 233
Leve
l 1
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 18 -
Rangers Cottage
Fitting Description
KIT
CH
EN
HA
LL
RO
OM
1
RO
OM
2
RO
OM
3
RO
OM
4
RO
OM
5
RO
OM
6
RO
OM
7
RO
OM
8
RO
OM
9
RO
OM
10
RO
OM
11
Toile
t
tota
l Ran
gers
cot
tage
1X14W TROFFER SURFACE MOUNTED 0 2X14W TROFFER SURFACE MOUNTED 0 2x26W BATTEN 3 1 3 2 9 1x14W BATTEN 0 1x14W BATTEN EMG 0 1x14W TROFFER DIM 0 1x26W PLASTER DIM 0 1x26W TROFFER DIM 0 2x26W TROFFER DIM 0 1x26W BATTEN PD 2 2 1 1 6 1x26W BATTEN EMG 0 2X26W TROFFER SUSPENDED 0 2X26W TROFFER WALL FITTING 0 1x10.5W DR700 LED DOWNLIGHT 0 1X14W TROFFER PLASTER 0 1X36W BATTEN EMG 0 1x16W D1000 LED DOWNLIGHT 2 3 4 9 EXIT LIGHTS 0 1X32W LED OYSTER LAMP 1 1 1X7W OSRAM LED RELAMP 0 5x36W HIGH BAY 0 1X40W MAT INDUCTION 0 2X30W BATTEN 0 1x12W OSRAM PARATHOM LED RELAMP 5 1 1 1 1 9 1X36W BATTEN WEATHERPROOF 0 1X120W MAT FLOOD 0 1X14W WALL LIGHT 0 1X26W WALL LIGHT 0 1X16W D900 LED DOWNLIGHT 0
Total Rangers Cottage 4 8 6 3 1 3 2 1 1 1 1 1 1 1 34
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 19 -
Civic Hall
Fitting Description
EN
TRY
MA
LE
FEM
ALE
KIT
CH
EN
MA
IN H
ALL
STA
GE
TOIL
ET
LOW
ER
LEV
EL
OU
TSID
E
Tota
l civ
ic H
all
1X14W TROFFER SURFACE MOUNTED 0 2X14W TROFFER SURFACE MOUNTED 0 2x26W BATTEN 1 1 1x14W BATTEN 2 6 8 1x14W BATTEN EMG 1 1 1x14W TROFFER DIM 0 1x26W PLASTER DIM 0 1x26W TROFFER DIM 0 2x26W TROFFER DIM 0 1x26W BATTEN PD 2 2 2 4 9 10 29 1x26W BATTEN EMG 0 2X26W TROFFER SUSPENDED 0 2X26W TROFFER WALL FITTING 0 1x10.5W DR700 LED DOWNLIGHT 4 4 1X14W TROFFER PLASTER 0 1X36W BATTEN EMG 0 1x16W D1000 LED DOWNLIGHT 0 EXIT LIGHTS 2 1 1 2 6 3 15 1X32W LED OYSTER LAMP 1 1 1X7W OSRAM LED RELAMP 0 5x36W HIGH BAY 6 6 1X40W MAT INDUCTION 5 5 2X30W BATTEN 10 10 1x12W OSRAM PARATHOM LED RELAMP 9 9 1X36W BATTEN WEATHERPROOF 0 1X120W MAT FLOOD 2 2 1X14W WALL LIGHT 0 1X26W WALL LIGHT 0 1X16W D900 LED DOWNLIGHT 21 21
Total Civic Hall 35 3 8 6 22 14 3 19 2 112
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 20 -
Total Sites
Fitting Description
Tota
l Low
er G
roun
d
Tota
l Gro
und
Tota
l Lev
el 1
tota
l Ran
gers
cot
tage
Tota
l Civ
ic H
all
Tota
l All
site
s
1X14W TROFFER SURFACE MOUNTED 2 0 0 0 0 2 2X14W TROFFER SURFACE MOUNTED 4 0 0 0 0 4 2x26W BATTEN 0 0 0 9 1 10 1x14W BATTEN 8 11 8 0 8 35 1x14W BATTEN EMG 4 0 0 0 1 5 1x14W TROFFER DIM 0 7 3 0 0 10 1x26W PLASTER DIM 0 2 4 0 0 6 1x26W TROFFER DIM 4 106 59 0 0 169 2x26W TROFFER DIM 0 16 8 0 0 24 1x26W BATTEN PD 19 2 3 6 29 59 1x26W BATTEN EMG 6 4 4 0 0 14 2X26W TROFFER SUSPENDED 18 0 0 0 0 18 2X26W TROFFER WALL FITTING 6 0 0 0 0 6 1x10.5W DR700 LED DOWNLIGHT 0 65 116 0 4 185 1X14W TROFFER PLASTER 2 0 0 0 0 2 1X36W BATTEN EMG 4 0 0 0 0 4 1x16W D1000 LED DOWNLIGHT 31 62 10 9 0 112 EXIT LIGHTS 11 12 9 0 15 47 1X32W LED OYSTER LAMP 0 0 3 1 1 5 1X7W OSRAM LED RELAMP 0 13 0 0 0 13 5x36W HIGH BAY 0 0 0 0 6 6 1X40W MAT INDUCTION 0 0 0 0 5 5 2X30W BATTEN 0 0 0 0 10 10 1x12W OSRAM PARATHOM LED RELAMP 0 0 0 9 9 18 1X36W BATTEN WEATHERPROOF 17 0 0 0 0 17 1X120W MAT FLOOD 0 0 0 0 2 2 1X14W WALL LIGHT 0 0 6 0 0 6 1X26W WALL LIGHT 1 0 0 0 0 1 1X16W D900 LED DOWNLIGHT 0 0 0 0 21 21
Total All Sites 137 300 233 34 112 816
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 21 -
3 Exit Lights 3.1.1 Details
Product Code Description Category Number
LSC102 LE GRANDE SLIDE CONNECT G2 686200-686210 For specifications of installed exit lights refer Appendix D
3.1.2 Summary
Level G2 Slide Connect Subtotal
Lower Ground 10 10
Ground 13 13
Level 1 9 9
Hall 15 15
Total 47 47 3.1.3 Location Exit Light locations are shown on the as built lighting layouts. Refer Appendix E
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 22 -
4 Sensors Time out Function. Active in all sensors. Time out settings Settings vary depending on the function and occupancy of the space. See table for time outs.
Description Time Out Meeting Rooms, Board Rooms, 20 minsSmall Office 30 minsOpen Office 20 minsAmenities 30 minsAll other areas 20 minsMeeting Rooms, Board Rooms, 20 mins
Commissioning Notes
Sensor functions have been tailored to suit the client’s needs. There are many factors in an office environment that influence the function of sensors e.g. Wall, carpet and furniture colour, partition height, ambient light and occupancy to name a few. With these factors in mind the above settings were developed in consultation with the City of Canada Bay Council to provide lighting that is compliant with Australian Standards whilst at the same time providing maximum functionality and energy savings. Note: Refer below and relevant drawings for sensor settings and locations. 4.1 Sensor Details
Sensor Type Description Subtotal
ME CP Electronics Passive Infrared Motion Sensor 42
MEDD CP Electronics Passive Infrared Motion Sensor with Dimming 27
M5DD CP Electronics Microwave Motion Detector with Dimming 18
M6 CP Electronics Microwave Motion Detector 4
M6DD CP Electronics Microwave Motion Detector with Dimming 2
Total 93
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 23 -
4.2 Sensor Summary
Level ME MEDD M5DD M6 M6DD Subtotal
LG 14 1 4 19
G 11 19 8 2 40
1 5 7 10 22
Ranger 9 9
Hall 3 3
Total 42 27 18 4 2 93 4.3 Sensor Locations Sensor location and type are shown on the as built lighting layouts. Refer Appendix E 4.4 Sensor ID & Programming
Level Location *Sensor ID Type Time Out
(mins) Dimming
Lower Ground Staff Lunch 80 M6 20
Lower Ground Staff Amenities 81 ME 30
Lower Ground Staff Amenities 82 ME 30
Lower Ground Hall 83 ME 20
Lower Ground Carpark 84 M6 20
Lower Ground Carpark 85 M6 20
Lower Ground Carpark 86 M6 20
Lower Ground Corp. Printing 89 MEDD 20
Lower Ground Kitchen 90 ME 20
Lower Ground Office 1 91 ME 30
Lower Ground Office 2 92 ME 30
Lower Ground Office 3 93 ME 30
Lower Ground Office 4 94 ME 30
Lower Ground Open Office 95 ME 20
Lower Ground Open Office 96 ME 20
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 24 -
Level Location *Sensor ID Type Time Out
(mins) Dimming
Lower Ground Open Office 97 ME 20
Lower Ground Open Office 98 ME 20
Lower Ground Open Office 99 ME 20
Lower Ground Open Office 100 ME 20
GROUND Office 5 1 MEDD 30
GROUND Office 4 2 MEDD 30 90
GROUND Office 3 3 MEDD 30
GROUND Office 2 4 MEDD 30 90
GROUND Office 1 5 MEDD 30 90
GROUND Open Area 6 M6DD 20
GROUND Open Area 7 M6DD 20
GROUND Open Area 8 ME 20
GROUND Open Area 9 ME 20
GROUND Meeting Room 10 ME 20
GROUND Open Office 11 ME 20
GROUND Open Office 12 ME 20
GROUND It Office 13 M5DD 20
GROUND It Manager 14 MEDD 30
GROUND It Hall 15 ME 20
GROUND It Store 16 MEDD 20
GROUND Computer Room 17 MEDD 30
GROUND Hall 1 18 MEDD 20
GROUND Mgr. Assets 19 MEDD 30
GROUND Traffic Property 20 M5DD 20
GROUND Toilets 21 MEDD 30
GROUND It Hall 22 ME 20
GROUND Open Office 23 ME 20
GROUND Open Office 24 ME 20
GROUND Traffic Property 25 M5DD 20
GROUND Hall 1 26 MEDD 20
GROUND Enviro. Office 27 M5DD 30
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 25 -
Level Location *Sensor ID Type Time Out
(mins) Dimming
GROUND Kitchen 28 MEDD 20
GROUND Corridor 29 MEDD 20
GROUND Dir. Info Services 30 MEDD 30
GROUND Citizen Services Unit 32 M5DD 20
GROUND P.A. Director Office 33 M5DD 20
GROUND Corridor 35 MEDD 20
GROUND Mgr. Cit. Services 36 MEDD 30
GROUND Records Office Corridor 37 MEDD 20
GROUND Female 39 ME 30
GROUND Male 40 ME 30
GROUND Records Unit 41 M5DD 20
GROUND Library 42 M5DD 20
GROUND Library Office 43 MEDD 30
Level 1 Room 1 50 MEDD 30 90
Level 1 Room 2 51 MEDD 30
Level 1 Room 3 52 MEDD 30 90
Level 1 Male 55 ME 30
Level 1 Female 56 ME 30
Level 1 Room 4 57 M5DD 20
Level 1 Room 4 58 M5DD 20
Level 1 Room 4 59 M5DD 20
Level 1 Room 4 60 M5DD 20
Level 1 Room 10 61 MEDD 30
Level 1 Room 6 62 MEDD 30
Level 1 Room 7 63 MEDD 30
Level 1 Room 8 64 M5DD 30
Level 1 Room 11 66 ME 30
Level 1 Room 13 67 M5DD 40
Level 1 Room 14 68 M5DD 40
Level 1 Room 15 69 M5DD 40
Level 1 Room 16 70 M5DD 20
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 26 -
Level Location *Sensor ID Type Time Out
(mins) Dimming
Level 1 Room 16 71 M5DD 20
Level 1 Kitchen 72 MEDD 20
Level 1 Room 18 73 ME 30
Level 1 Room 17 74 ME 30
Ranger Room 1 106 ME 20
Ranger Hall 107 ME 20
Ranger Hall 108 ME 20
Ranger Hall 109 ME 20
Ranger Room 5 110 ME 20
Ranger Room 3 111 ME 20
Ranger Room 2 112 ME 20
Ranger Kitchen 113 ME 20
Hall Kitchen 114 ME 20
Hall Female 115 ME 30
Hall Male 116 ME 30
* Sensor ID as shown on Plans (see attachments)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 27 -
5 Fitting Components Apart from reducing energy consumption the installation of e1 fittings also provides a reduction in the number of lamps and ballasts in operation and consequently reduces ongoing lighting maintenance costs. Further cost savings are provided by the extended life cycle of the e1 fitting components. 5.1 Comparison of Lamp and Ballast Numbers Pre and Post Installation 5.1.1 Summary
Description Lamps Ballasts
Pre-existing 1369 1354
As Installed 912 822
% Change -50.11% -64.72% 5.1.2 Pre-existing Fitting Description Lamps Ballasts
2x18W BATTEN SM 22 22
1x18W BATTEN 29 29
2x18W BATTEN EMG 10 10
2x18W PLASTER TROF 4 4
2x18W TROFFER (300MMX600MM) 20 20
2x36W PLASTER TROFFER 8 8
1x36W PLASTER TROFFER 2 2
2x36W TROFFER (300MMX1200MM) 396 396
2x36W BATTEN WG 66 66
2x36W BATTEN EMG 34 34
2x36W BATTEN SUSPENDED 36 36
1x36W BATTEN 9 9
2x36W BATTEN PD 92 92
2x36W WALL LIGHT 14 14
1x50W DICHROIC DL 271 271
1x50W DICHROIC 120 DIA 10 10
1x36W BATTEN EMG 1 1
2x18W DL 175-230DIA 122 122
EXIT LIGHTS 94 94
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 28 -
Fitting Description Lamps Ballasts
1X40W OYSTER LIGHT HALOGEN 8 4
1X40W WALL LIGHT HALOGEN 6 6
1x60W INCANDESCANT 11 0
1x400W High Bay 4 4
1x100W Flood Light 5 5
2x18W BATTEN PENDANT 54 54
1x18W CFL Pendant Light 39 39
1X250W FLOOD LIGHT 2 2
Total 1369 1354
5.1.3 As Installed
Fitting Description Lamps Ballasts
1X14W TROFFER SURFACE MOUNTED 2 2
2X14W TROFFER SURFACE MOUNTED 8 4
2x26W BATTEN 20 10
1x14W BATTEN 35 35
1x14W BATTEN EMG 5 5
1x14W TROFFER DIM 10 10
1x26W PLASTER DIM 6 6
1x26W TROFFER DIM 169 169
2x26W TROFFER DIM 48 24
1x26W BATTEN PD 59 59
1x26W BATTEN EMG 14 14
2X26W TROFFER SUSPENDED 36 18
2X26W TROFFER WALL FITTING 12 6
1x10.5W DR700 LED DOWNLIGHT 185 185
1X14W TROFFER PLASTER 2 2
1X36W BATTEN EMG 4 4
1x16W D1000 LED DOWNLIGHT 112 112
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 29 -
Fitting Description Lamps Ballasts
EXIT LIGHTS 47 47
1X32W LED OYSTER LAMP 5 5
1X7W OSRAM LED RELAMP 13 13
5x36W HIGH BAY 30 12
1X40W MAT INDUCTION 5 5
2X30W BATTEN 20 10
1x12W OSRAM PARATHOM LED RELAMP 18 18
1X36W BATTEN WEATHERPROOF 17 17
1X120W MAT FLOOD 2 2
1X14W WALL LIGHT 6 6
1X26W WALL LIGHT 1 1
1X16W D900 LED DOWNLIGHT 21 21
Total 912 822
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 30 -
5.2 Installed Fitting Components 5.2.1 Component Legend
Component Type No. Description
Tube 1 Osram 36w XXT 840
2 Brightgreen 16w D900
3 40w Matsushima Induction Lamp
4 120w Matsushima Induction Lamp
5 GE 26w T5
6 14w Lumos
7 Brightgreen 10.5w DR700 LED Downlight
8 Brightgreen D1000 16w
9 Maxibright 32w Oyster Light
10 Osram 12w Parathom LED Replacement
11 Osram 7w LED Replacement
12 Osram 30W
13 Osram 30w XXT
Ballast 1 Osram QTP8 1x36w
2 Osram QTP8 2x36w
3 Osram Redback
4 Matsushima Ballast 40w 220
5 Matsushima Ballast 120w 220
6 Tridonic PCA T5 1x28 lp
7 Tridonic PCA T5 2x28 lp
8 Tridonic PCA T5 1x14lp
9 Osram QTP5 2x14w
10 Osram QTP5 2x24-39
11 Osram QTP5 26w
12 Osram QTP5 2x26w
13 Osram QTP5 14w
Diffuser 1 Curved Y5 2 Weatherproof Osram Neptune 3 4mm Toughened Tempered Diffuser 4 Flat Y5 5 Rectangle Acrylic
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 31 -
5.2.2 Component Breakdown by Fitting
Fitting Description Tube Type Ballast Type
Diffuser Type
1X14W TROFFER SURFACE MOUNTED 6 13 1
2X14W TROFFER SURFACE MOUNTED 6 9 1
2x26W BATTEN 5 12 5
1x14W BATTEN 6 13 5
1x14W BATTEN EMG 6 13 5
1x14W TROFFER DIM 6 8 1
1x26W PLASTER DIM 5 6 4
1x26W TROFFER DIM 5 6 1
2x26W TROFFER DIM 5 7 1
1x26W BATTEN PD 5 11 5
1x26W BATTEN EMG 5 11 5
2X26W TROFFER SUSPENDED 5 12 1
2X26W TROFFER WALL FITTING 5 12 1
1x10.5W DR700 LED DOWNLIGHT 7 3 N/A
1X14W TROFFER PLASTER 6 13 4
1X36W BATTEN EMG 1 1 5
1x16W D1000 LED DOWNLIGHT 8 3 N/A
EXIT LIGHTS N/A N/A N/A
1X32W LED OYSTER LAMP 9 3 N/A
1X7W OSRAM LED RELAMP 11 3 N/A
5x36W HIGH BAY 1 1 & 2 4
1X40W MAT INDUCTION 3 4 3
2X30W BATTEN 13 10 5
1x12W OSRAM PARATHOM LED RELAMP 10 3 N/A
1X36W BATTEN WEATHERPROOF 1 1 2
1X120W MAT FLOOD 4 5 3
1X14W WALL LIGHT 6 13 1
1X26W WALL LIGHT 5 11 3
1X16W D900 LED DOWNLIGHT 2 3 N/A
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 32 -
Amp Readings The areas powered by each lighting circuit were identified and at the time of each reading Envirolite Staff were
positioned accordingly to ensure all light fittings were active. Communication during this period was achieved via
Walkie Talkie.
5.3 Summary
5.4 Area by Area Readings
Level Location Circuit Pre (Amps)
Post (Amps) % Change
Lower Ground DB Lower Ground 33 3.1 1.1 -64.5%
37 9.2 2.4 -73.9%
26 4.5 4.5 0.0%
DB5 1 5.1 2.3 -54.9%
3 3.8 1.7 -55.3%
5 5.0 1.3 -74.0%
7 2.8 1.7 -39.3%
9 8.0 2.5 -68.8%
2 4.6 3.0 -34.8%
4 4.3 1.7 -60.5%
6 5.8 2.4 -58.6%
8 5.1 1.7 -66.7%
33 4.0 1.1 -72.5% 33
35 5.7 1.0 -82.5% 35
38 9.1 8.4 -7.7% 38
Location Pre Installation (Amps)
Post Installation (Amps) % Change
Lower Ground 94.6 44.0 -53.49%
Ground 71.8 21.4 -70.19%
Level 1 58.9 18.5 -68.59%
Ranger 8.3 4.3 -48.19%
Hall 33.3 17.7 -46.85%
Total 266.9 105.9 -60.3%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 33 -
Level Location Circuit Pre (Amps)
Post (Amps) % Change
40 5.7 2.4 -57.9% 40
42 4.3 0.4 -90.7% 42
44 4.5 4.4 -2.2% 44
Ground Floor DB1 7 4.5 2.4 -46.7%
9 12.8 3.3 -74.2%
11 1.5 0.2 -86.7%
13 4.7 1.2 -74.5%
15 5.0 1.7 -66.0%
17 8.5 2.1 -75.3%
19 8.7 2.8 -67.8%
21 2.2 0.3 -86.4%
6 1.0 0.2 -80.0%
8 1.0 0.0 -100.0%
10 0.6 0.0 -100.0%
14 3.0 0.3 -90.0%
DB2 1 6.3 1.7 -73.0%
2 4.9 2.2 -55.1%
4 4.7 2.6 -44.7%
6 0.3 0.0 -100.0%
7 0.2 0.2 0.0%
8 1.0 0.2 -80.0%
9 0.5 0.0 -100.0%
10 0.4 0.0 -100.0%
Level 1 DB4 13 9.2 3.2 -65.2%
15 10.0 3.8 -62.0%
41 9.0 3.3 -63.3%
2 4.8 0.4 -91.7%
12 2.3 0.7 -69.6%
28 2.1 0.7 -66.7%
32 6.3 1.9 -69.8%
34 5.3 1.5 -71.7%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 34 -
Level Location Circuit Pre (Amps)
Post (Amps) % Change
42a 0.9 0.4 -55.6%
42b 9.0 2.6 -71.1%
Ranger DB Outside 4 4.8 2.4 -50.0%
Hall DB3 33 4.0 1.1 -72.5%
35 5.7 1.0 -82.5%
38 9.1 8.4 -7.7%
40 5.7 2.4 -57.9%
42 4.3 0.4 -90.7%
44 4.5 4.4 -2.2%
266.9 105.9 -60.3%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 35 -
6 Lux Levels A requirement of the project was that the new lighting installation must comply with Australian Standards
AS/NZS1680, in particular with regards to minimum lux levels.
6.1 Recommended Illuminance
AS/NZS Type of Interior or Activity Maintenance Illuminance
(lx)
1680.2.1
Entrances
Entrance Halls, Lobbies, Foyers 160*
Waiting Rooms 160*
Enquiry Desks 320
Circulation Areas Corridors, Passageways, Ramps 40*
Stairs (internal) 80
Kitchens General 160
Food Preparation, Cooking, Washing Up 240
First Aid Centres Rest Room 40
Treatment Room 320
Toilets 80
Plant Rooms General 80
1680.2.2
General General Tasks Involving Typing, Reading, Writing 320
Computer Rooms Equipment Rooms 320
Meeting Rooms
Meeting Rooms 320
Training Rooms, Seminar Rooms 240
Conference Rooms, Boardrooms 240 * Illuminance applies at floor level
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 36 -
6.2 Measurement Procedure Measurements are to be in accord with the requirements of AS/NZS 1680.1 Appendix B.
1. Measurements in theory should be taken at night or if this is not possible with blinds drawn (no daylight
component) and in an area empty of all furniture such that the light level at a point is the sum of ALL light sources
in the room with no masking from desk partitions, cabinets, people etc. This is obviously not usually possible so
all care should be taken to ensure we minimise shadowing or shrouding and omit or discount readings that do
not comply with this requirement.
2. Lux readings are not always at a height of 700-720 mm (see table over page).
3. Measurements should not be taken closer than 1000mm from room perimeter.
4. If in a room a low reading is recorded in isolation when all other readings are consistent careful consideration
should be given to the validity of this reading.
5. The accuracy of the light meter should also be considered and routinely checked against a recently calibrated
unit, or if such a unit is not immediately to hand, a number of meters can be checked with the same light source
for consistency.
6. The particulars of the meter should be included in the report i.e. specifications, model, type
7. If practical, new lamps should be burnt in for 100 hours before measurement. It is noted that seasoning of new
lamps allows for the burning off of particulates and the even distribution of mercury within the tube. This
stabilization process ensures optimal lamp performance and in general light measurements taken after aging or
seasoning will be higher than those taken earlier.
There are other influences on the 100 hour burn in which would make this requirement impractical. These include
the interaction of sensors and daylight harvesting; the potential waiting periods, especially at some locations, is
financially unviable; and, adjusting lights to remain on 24 hours per day for the four to five days needed is not
environmentally responsible.
8. The environment in which measurement is to be recorded should be allowed to stabilize, the lamps should be on
for 1 hour prior to measurement and air conditioning / ventilation operating normally. If measurements are taken
at night, this may not be possible and readings will generally be lower than otherwise expected.
9. For typically required light levels refer 6.1 Recommended Illuminance.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 37 -
10. The layout of the measurement grid can be a square array of points or if the luminaires are in a regular
rectangular array. Refer 6.2.1 Lux Meter Positioning Guide
11. Number of points and areas of measurement grid.
Area > 25m2 - Measured area 9m2 minimum and must include at least 4 luminaires.
Area < 25m2 - Entire area to be checked. Minimum of 9 points.
As an indication of the number of points the following can be used as a guide for a roughly square area.
Size of space No. of points
5m x 5m 9
7m x 7m 16
10m x 10m and above 25
6.2.1 Lux Meter Positioning Guide Position under light fittings: Meter shall be placed directly under the centre of the light fitting at a height of 700mm.
Positions between light fittings: Meter shall be placed as close as practical to the mid way points between light fittings
at a height of 700mm.
6.2.2 Small Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 2
Position 5
Position 8
Position 3 Light
Position 6
Position 9 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 38 -
6.2.3 Medium Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 10
Position 13 Light
Position 2
Position 5
Position 8
Position 11
Position 14
Position 3 Light
Position 5
Position 9 Light
Position 12
Position 15 Light
6.2.4 Large Room / Area Positioning
Position 1 Light
Position 6
Position 11 Light
Position 16
Position 21 Light
Position 2
Position 7
Position 12
Position 17
Position 22
Position 3 Light
Position 8
Position 13 Light
Position 18
Position 23 Light
Position 4
Position 9
Position 14
Position 19
Position 24
Position 5 Light
Position 10
Position 15 Light
Position 20
Position 25 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 39 -
6.3 Lux Meter SpecificationsTesto 540
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 40 -
6.4 Pre and Post Lux Readings The following sample lux levels were taken across the upgraded areas to confirm that actual lux levels corresponded
to computer modelling generated lux levels.
Level Area Position Pre Post
G Kitchen 1 193 312
2 246 353
3 232 310
4 260 296
5 268 348
6 270 317
Average 245 323
Hall 1 1 232 495
2 83 456
3 108 472
4 67 601
Average 123 506
Room 1 1 306 335
2 242 378
3 147 405
4 170 410
5 301 362
6 334 389
7 297 401
8 228 423
9 158 390
Average 243 388
G Board Room 1 612 655
2 673 800
3 615 810
4 574 698
5 483 678
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 41 -
Level Area Position Pre Post
6 516 576
7 412 668
8 556 794
9 603 852
10 690 946
1 601 866
12 450 679
565.4 751.8
G Office 3 1 406 396
2 563 423
3 421 418
4 472 422
5 755 420
6 540 410
7 280 390
8 431 391
9 382 379
Average 472 405
Office 4 1 198 375
2 416 422
3 305 387
4 437 444
5 432 437
6 275 447
7 217 368
8 311 387
9 294 378
Average 321 405
G Office 2 1 348 381
2 424 383
3 358 426
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 42 -
Level Area Position Pre Post
4 462 436
5 600 386
6 497 401
7 352 397
8 413 387
9 296 447
Average 417 405
Reception 1 166 207
2 166 211
3 133 226
4 123 197
5 94 178
6 138 199
7 132 207
8 127 213
9 108 211
Average 132 205
Reception Desk 1 277 318
2 305 307
3 414 380
4 437 322
Average 358 332
G Traffic Property 1 506 407
2 436 403
3 515 389
4 482 401
5 575 417
6 635 422
7 594 398
8 568 397
9 565 394
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 43 -
Level Area Position Pre Post
10 598 401
Average 547 402
Managed Assets 1 432 394
2 542 397
3 509 401
4 352 411
5 284 474
6 492 390
Average 435 411
Computer Room 1 320 522
2 310 541
3 196 471
4 160 421
5 161 385
6 132 319
Average 213 443
G Office 5 1 494 386
2 476 428
3 374 366
4 424 418
5 644 400
6 626 498
7 298 361
8 483 343
9 344 412
Average 463 401
Environment Office 1 146 397
2 200 399
3 297 385
4 437 411
5 428 413
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 44 -
Level Area Position Pre Post
6 237 407
Average 291 402
Office 1 1 477 437
2 428 434
3 403 401
4 399 396
5 279 395
6 330 380
Average 386 407
Records unit 1 596 420
2 646 401
3 764 410
4 760 378
5 683 423
6 620 379
Average 678 402
Cit. Services Unit 1 431 400
2 475 394
3 564 356
4 446 418
5 498 411
6 511 433
Average 488 402
G Library 1 185 410
2 228 396
3 225 403
4 257 399
5 405 407
6 422 395
7 433 399
Average 308 401
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 45 -
Level Area Position Pre Post
Library Office 1 420 466
2 396 457
3 222 399
4 319 411
Average 339 433
LG Large Store 01 1 232 142
2 212 120
3 168 143
4 204 116
5 248 259
6 206 226
Average 212 168
Office 2 1 260 398
2 205 379
3 234 416
4 214 422
5 210 432
6 243 449
Average 228 416
Corp Printing 1 640 467
2 886 507
3 444 426
4 404 444
5 471 427
6 338 449
Average 531 453
Kitchen 1 146 439
2 178 440
3 242 427
4 120 460
Average 172 442
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 46 -
Level Area Position Pre Post
LG Office 1 1 268 454
2 383 384
3 244 505
4 296 435
5 188 476
6 126 513
Average 251 461
Office 4 1 290 390
2 257 420
3 299 440
4 330 433
5 327 360
6 290 364
Average 299 401
Staff Lunch 1 132 182
2 157 240
3 132 164
4 106 186
5 105 210
6 82 186
Average 119 195
Female Toilets 1 674 316
2 95 69
3 168 57
4 89 61
5 141 186
6 125 365
Average 215 176
LG Open Office 1 187 401
2 129 388
3 436 423
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 47 -
Level Area Position Pre Post
4 351 405
5 212 398
6 367 423
7 438 388
8 464 389
9 310 411
10 356 397
11 220 410
12 261 413
Average 311 404
Office 3 1 330 428
2 190 391
3 257 378
4 402 451
5 187 393
6 307 376
Average 279 403
Stair 3 1 360 415
2 279 339
3 268 372
4 134 358
Average 260 371
LG Amenities 1 95 69
2 168 57
3 89 61
4 141 186
5 125 365
6 137 153
7 92 160
8 163 126
Average 126 147
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 48 -
Level Area Position Pre Post
1 Mayor Office 1 240 368
2 202 401
3 165 415
4 210 397
5 178 388
6 167 432
Average 194 400
General Manager Office 1 403 416
2 341 411
3 395 398
4 384 432
Average 381 414
Room 07 1 498 394
2 464 403
3 511 411
4 532 467
5 460 417
6 402 326
Average 478 403
Room 06 1 399 407
2 416 401
3 456 394
4 432 411
5 450 396
6 399 402
Average 425 402
1 Room 10 1 560 440
2 523 408
3 490 424
4 497 437
5 380 378
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 49 -
Level Area Position Pre Post
6 405 347
Average 476 406
Room 8 & 9 1 501 435
2 487 382
3 516 413
4 490 418
5 420 314
6 463 326
Average 480 381
Room 11 1 408 386
2 339 363
3 386 394
4 411 401
Average 386 386
Room 14 1 436 411
2 316 399
3 378 401
4 441 415
5 468 387
6 351 405
Average 398 403
1 Room 3 1 411 496
2 425 446
3 405 402
4 378 391
5 430 402
6 359 460
Average 401 433
Open Office 1 415 430
2 386 403
3 399 397
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 50 -
Level Area Position Pre Post
4 395 373
5 425 422
6 416 431
7 396 436
8 389 453
9 344 427
10 322 388
11 447 395
12 380 375
13 365 390
Average 391 409
Room 01 1 433 446
2 411 396
3 398 310
4 419 452
5 419 425
6 356 400
Average 406 405
1 Room 02 1 445 461
2 346 375
3 441 390
4 424 413
5 438 432
6 386 450
Average 413 420
Ranger Room 2 1 305 462
2 310 435
3 216 404
4 181 413
5 341 410
6 301 500
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 51 -
Level Area Position Pre Post
7 296 419
8 362 430
Average 289 434
Hall 1 52 78
2 57 93
3 72 106
4 105 128
Average 72 101
Room 5 1 418 521
2 426 547
3 390 471
4 303 410
5 358 453
6 306 501
Average 367 484
CP Car Park Storeroom 1 145 208
2 132 211
3 122 222
4 108 199
5 129 186
6 114 197
7 184 211
8 124 221
9 115 216
10 137 188
11 127 175
12 119 160
Average 130 200
Hall Main Hall 1 310 497
2 286 485
3 236 462
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 52 -
Level Area Position Pre Post
4 218 499
5 301 384
6 277 415
7 290 432
8 283 417
9 260 439
Average 273 448
Kitchen 1 319 169
2 332 180
3 261 221
4 240 242
5 168 203
Average 264 203
Male Toilet 1 87 134
2 88 149
3 106 143
4 97 118
Average 95 136
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 53 -
7 Recycling Reconciliation The light fittings removed from site have been recycled. The components of the lights fittings are recycled as follows:
- Aluminium & brass: The metal ends from tubes are separated and subsequently recycled into cast products
such as ingots used in foundry application.
- Glass from the tubes is separated and recycled into various glass based applications
- Mercury is distilled from the separated powders and then used in the manufacture of dental amalgam
- Phosphor powder from fluorescent tubes is consolidated for future use in the manufacture of land applications
- Metal is recycled into foundry applications
The following reconciliation is based on the weights of the old individual fitting types replaced and the total weights of
materials recycled by Envirolite’s recycling partners.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 54 -
7.1 Metal Recycling
Fitting Description Qty Unit Fitting Weight (kg)
Total Fitting Weight (kg)
2x18W BATTEN SM 11 2.50 27.50
1x18W BATTEN 29 2.50 72.50
2x18W BATTEN EMG 5 2.50 12.50
2x18W PLASTER TROF 2 2.50 5.00
2x18W TROFFER (300MMX600MM) 10 2.50 25.00
2x36W PLASTER TROFFER 4 5.75 23.00
1x36W PLASTER TROFFER 2 5.75 11.50
2x36W TROFFER (300MMX1200MM) 198 5.75 1138.50
2x36W BATTEN WG 33 5.75 189.75
2x36W BATTEN EMG 17 5.75 97.75
2x36W BATTEN SUSPENDED 18 5.75 103.50
1x36W BATTEN 9 5.75 51.75
2x36W BATTEN PD 46 5.75 264.50
2x36W WALL LIGHT 7 5.75 40.25
1x50W DICHROIC DL 271 0.75 203.25
1x50W DICHROIC 120 DIA 10 0.75 7.50
1x36W BATTEN EMG 1 5.75 5.75
2x18W DL 175-230DIA 61 2.50 152.50
EXIT LIGHTS 47 0.50 23.50
1X40W OYSTER LIGHT HALOGEN 4 3.00 12.00
1X40W WALL LIGHT HALOGEN 6 3.00 18.00
1x60W INCANDESCANT 2 0.50 5.50
1x400W High Bay 4 12.00 48.00
1x100W Flood Light 5 6.00 30.00
2x18W BATTEN PENDANT 27 2.50 67.50
1x18W CFL Pendant Light 30 2.20 85.80
1X250W FLOOD LIGHT 2 8.00 16.00
TOTAL 879 2738.30
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 55 -
Weight Recycled: 2734.8kg (As provided by recycling partners) Variance: -3.5kg (-0.13%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 56 -
7.2 Lamp Recycling
2x18W BATTEN SM Total Lamps Unit Lamp Weight (g)
Total Lamp Weight (kg)
1x18W BATTEN 22 68.9 1.52
2x18W BATTEN EMG 29 68.9 2.00
2x18W PLASTER TROF 10 68.9 0.69
2x18W TROFFER (300MMX600MM) 4 68.9 0.28
2x36W PLASTER TROFFER 20 68.9 1.38
1x36W PLASTER TROFFER 8 138.9 1.11
2x36W TROFFER (300MMX1200MM) 2 138.9 0.28
2x36W BATTEN WG 396 138.9 55.00
2x36W BATTEN EMG 66 138.9 9.17
2x36W BATTEN SUSPENDED 34 138.9 4.72
1x36W BATTEN 36 138.9 5.00
2x36W BATTEN PD 9 138.9 1.25
2x36W WALL LIGHT 92 138.9 12.78
1x50W DICHROIC DL 14 138.9 1.94
1x50W DICHROIC 120 DIA 271 31.0 8.40
1x36W BATTEN EMG 10 31.0 0.31
2x18W DL 175-230DIA 1 138.9 0.14
EXIT LIGHTS 122 59.0 7.20
1X40W OYSTER LIGHT HALOGEN 47 10.0 0.47
1X40W WALL LIGHT HALOGEN 4 60.0 0.24
1x60W INCANDESCANT 6 60.0 0.36
1x400W High Bay 2 31.0 0.06
1x100W Flood Light 4 300.0 1.20
2x18W BATTEN PENDANT 5 200.0 1.00
1x18W CFL Pendant Light 54 68.9 3.72
1X250W FLOOD LIGHT 39 59.0 2.30
TOTAL 1369 - 124.06 Weight Recycled: 125.5 kg (As provided by recycling partners) Variance: 1.44 (1.16%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 57 -
8 General Fitting Guidelines 8.1 Handling E1 Light Fittings
All e1 light fittings contain a matte white High Performance e1 Reflector. It is recommended that light cotton
gloves be worn when handling E1 light fittings so as not to mark or damage the reflector and air conditioning
slots.
If using a cutting implement to remove packaging be careful not to scratch or damage the light fitting.
If a blue protective film is present on the High Performance e1 Reflector, this should be removed prior to
installation.
When lifting the fitting, ensure it is properly supported so as not to bend of crease air conditioning slots.
Plug fitting into a designated surface socket.
Remove fluorescent lamp.
With one hand touching the light fitting, peel off remainder of blue film and discard. Note: Failure to touch fitting
when peeling off film will result in the build up of a static charge, which will release when you next earth yourself.
Replace lamp.
8.2 Cleaning E1 Light Fittings
Ensure all fittings and diffusers are clean and free of any contaminates. Wipe with a clean, lint free, cloth if
necessary.
If the High Performance e1 Reflector becomes marked or soiled it should be gently cleaned, using a circular
motion, with a lint free cloth dipped in methylated spirits.
DO NOT use any abrasive or caustic materials on e1 Lighting products.
8.3 Installation of E1 Lighting
Installation of all e1 Lighting products should be carried out by suitably qualified personnel only
Prior to installation electrical safety of the general area should be assessed by suitably qualified personnel.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 58 -
9 Envirolite Pty Ltd Warranty
The Envirolite Warranty Covers Replacement of:
1. Any component (including the lamps) in the E1 Lighting fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of five (5) years from the date of practical completion.
2. Any component (including the lamps) in LED fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of three (3) years from the date of practical completion.
3. Any component in any sensor installed by Envirolite Pty Ltd that fails in the normal course of operation for a
period of three (3) years from the date of practical completion.
The Warranty Does Not Cover the Replacement of:
1. Any component in the light fittings or sensors installed by Envirolite Pty Ltd that have failed other than in the course of normal operation. This includes but is not limited to failures caused by fire, water damage, earthquakes, power surges, vandalism or other willful or accidental acts that cause damage to the fittings or their components.
2. Failure or damage to any light fitting or sensor component caused by a third party carrying out other works in the building. This includes but is not limited to (a) electrical works that adversely affect the lighting circuits or sensor cables etc and (b) works on the air-conditioning or ceiling grid.
Service calls for the replacement of fitting or sensor components (other than lamps) covered by this warranty will be provided free of cost.
However if the failure of a fitting or sensor component is due to other than normal operation (as covered in Paragraphs 2A and 2B above) then a service call out fee of $100.00 (ex GST) will be charged plus the costs for the supply of replacement components and any associated installation labour. Lamp Failures
A small reserve stock of replacement lamps will be provided to the Building Manager as part of the Scope of Works to allow for the immediate in house replacement of any failures. The Building Manager will be required to keep all failed lamps in the cartons provided and contact Envirolite when 50% of the reserve stock has been used. Envirolite will then replenish the reserve stock to its original numbers and take away the old lamps for recycling. The cost of hire of any man lifting equipment necessary to replace lamps is excluded from this warranty. Failed Sensors and/or Electrical Components in Luminaries.
Envirolite will within a maximum of two (2) workings days following the day of receipt of a service call send one of its service staff to investigate and rectify the failure.
All service calls for replacement of failed components under this warranty should be directed to [email protected]
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 59 -
Listing of Envirolite Warranty Reserve Stock
Stock given to Dino Finucci and held at CCBC Civic Centre for all sites.
Item Description Quantity
Lamp Osram XXT 36w (box of 40) 1
Lamp GE 26w (box of 25) 1
LED D1000 2
LED D900 2
LED DR700 6
Transformer ET-REDBACK 60VA/230-240 6
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 60 -
10 Envirolite Pty Ltd Contact Details
OFFICE: Unit 4A, 2 Resolution Drive,
CARINGBAH. NSW. 2229
POSTAL ADDRESS: PO Box 220
MIRANDA. NSW. 2228.
PHONE: +61 2 9540 3302
FAX: +61 2 9540 3306
EMAIL: [email protected]
10.1 Operations Enquiries
NAME: Mr. Kerry Powell
MOBILE: 0412 858 303
EMAIL: [email protected]
Appendix A, B, C, D & E removed for publication
Community Energy Efficiency-Lighting Upgrade
Contract No. 2013/TS50
Handover Report-Concord Oval
Loftus St, Concord.NSW.2137.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 2 -
Introduction
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 3 -
Table of Contents
1 PROJECT DATES 5
2 LIGHT FITTING COUNTS 6
2.1 PRE-EXISTING LIGHT FITTINGS 6 2.1.1 Summary 6 2.1.2 By Location 7
2.2 AS INSTALLED LIGHT FITTINGS 9 2.2.1 Summary 9 2.2.2 By Location 10 2.2.3 Details 12 2.2.4 Summary 12 2.2.5 Location 12
3 SENSORS 13
3.1 SENSOR DETAILS 13 3.2 SENSOR LOCATIONS 13 3.3 SENSOR ID & PROGRAMMING 14
4 FITTING COMPONENTS 16
4.1 COMPARISON OF LAMP AND BALLAST NUMBERS PRE AND POST INSTALLATION 16 4.1.1 Summary 16 4.1.2 Pre-existing 16 4.1.3 As Installed 17
4.2 INSTALLED FITTING COMPONENTS 18 4.2.1 Component Legend 18 4.2.2 Component Breakdown by Fitting 19
5 AMP READINGS 20
5.1 SUMMARY 20 5.2 AREA BY AREA READINGS 20
6 LUX LEVELS 22
6.1 RECOMMENDED ILLUMINANCE 22 6.2 MEASUREMENT PROCEDURE 23
6.2.1 Lux Meter Positioning Guide 24 6.2.2 Small Room / Area Positioning 24 6.2.3 Medium Room / Area Positioning 25 6.2.4 Large Room / Area Positioning 25
6.3 LUX METER SPECIFICATIONS 26 6.4 PRE AND POST LUX READINGS 27
7 RECYCLING RECONCILIATION 34
7.1 METAL RECYCLING 35 7.2 LAMP RECYCLING 36
8 GENERAL FITTING GUIDELINES 37
8.1 HANDLING E1 LIGHT FITTINGS 37 8.2 CLEANING E1 LIGHT FITTINGS 37 8.3 INSTALLATION OF E1 LIGHTING 37
9 ENVIROLITE PTY LTD WARRANTY 38
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 4 -
10 ENVIROLITE PTY LTD CONTACT DETAILS 40
10.1 OPERATIONS ENQUIRIES 40
APPENDICES 41
APPENDIX A – ELECTRICAL CERTIFICATE 41 APPENDIX B – SENSOR COMMISSIONING CHECKLIST 45 APPENDIX C – SENSOR SPECIFICATIONS 48 APPENDIX D – EXIT LIGHT SPECIFICATIONS 65 APPENDIX E –AS BUILT LIGHTING LAYOUTS 74
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 5 -
1 Project Dates
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 6 -
2 Light Fitting Counts
2.1 Pre-existing Light Fittings
2.1.1 Summary
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 7 -
2.1.2 By Location
1 1
5 4 2
16 3 1 1 1 2 1 2 3 6 6 1 1 3 3 21
6 6 3
1 5 4
11 18
1 2 2 1 1 1 2 1
1 1 6
31Total 553 3 1 1 1 2 2 2 3 6 7 4 12 2 1 9 8 3 1 4 4 1 6 6 21 1 24
GROUND
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 8 -
Tota
l Com
plex
1 1 1 5
1 12
2 2 7 82
3 18
9 19
29
1 1 2 15
1 17 5 25 56
2 1 1 4 2 3 2 2 5 3 25
4 6 4 14
2 2
6 6
3 3 6
6 3 40 11 7 10 3 10 7 2 99
31Total 66 3 40 4 1 11 7 10 4 1 4 1 17 2 8 6 25 4 2 1 1 14 7 2 5 2 2 5 3 0 10 3 20 419
LEVEL 1 GRANDSTAND AND OTHER
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 9 -
2.2 As Installed Light Fittings
2.2.1 Summary
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 10 -
2.2.2 By Location
GYM
SPI
N R
OO
M
OFF
ICE 1
OFF
ICE 2
OFF
ICE 3
OFF
ICE 4
OFF
ICE 5
OFF
ICE 6
OFF
ICE 7
CAN
TEEN
STO
RE 1
LAU
ND
RY 7
EN
CLO
SED
WALK
WAY
CLE
AN
ER
STAIR
FO
YER
CH
AN
GE R
OO
M 2
CH
AN
GE R
OO
M 1
REFS
DIS
ABLE
D
FEM
ALE
MALE
STAIR
FO
YER 2
CH
AN
GE R
OO
M 3
CH
AN
GE R
OO
M 4
UN
ION
AREA
PUM
P RO
OM
MID
DLE
WALK
WAY
1 1
7 2 1 1 1 9
1 1 1 2 1 2 3 6 12
21 11 3 3 3 18
6 6 5 4
3
2 2 1 2 1
1 1 1
1 6
1 4 1 2 1 1 2 1 4
Total 23 3 1 1 1 2 2 2 3 6 7 4 16 2 2 11 9 3 1 4 4 2 8 7 21 1 28
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 11 -
5
24
33
59
21
12
10
5
19
7
25
18
3
6
6
100
31
5
18
12
Total 6 3 42 4 2 11 8 12 4 1 4 1 18 2 9 10 25 5 2 1 1 14 7 2 5 2 2 5 3 0 11 3 20 419
Green designates area with sensor.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 12 -
2.2.3 Details
Appendix D
2.2.4 Summary
2.2.5 Location
Appendix E
14
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 13 -
3 Sensors
Description Time Outs
Commissioning Notes
Refer below and relevant drawings for sensor settings and locations.
3.1 Sensor Details
3.2 Sensor Locations Appendix E
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 14 -
3.3 Sensor ID & Programming
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 15 -
* Sensor ID as shown on Plans (see attachments)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 16 -
4
4.1 Comparison of Lamp and Ballast Numbers Pre and Post Installation
4.1.1 Summary
4.1.2 Pre-existing
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 17 -
4.1.3 As Installed
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 18 -
4.2 Installed Fitting Components
4.2.1 Component Legend
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 19 -
4.2.2 Component Breakdown by Fitting
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 20 -
Amp Readings
5.1 Summary
5.2 Area by Area Readings
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 21 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 22 -
6 Lux Levels
6.1 Recommended Illuminance
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 23 -
6.2 Measurement Procedure
6.1 Recommended Illuminance
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 24 -
6.2.1 Lux Meter Positioning Guide
6.2.1 Lux Meter Positioning Guide
6.2.2 Small Room / Area Positioning
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 25 -
6.2.3 Medium Room / Area Positioning
6.2.4 Large Room / Area Positioning
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 26 -
6.3 Lux Meter Specifications
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 27 -
6.4 Pre and Post Lux Readings
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 28 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 29 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 30 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 31 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 32 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 33 -
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 34 -
7 Recycling Reconciliation
-
-
-
-
-
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 35 -
7.1 Metal Recycling
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 36 -
7.2 Lamp Recycling
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 37 -
8 General Fitting Guidelines
8.1 Handling E1 Light Fittings
8.2 Cleaning E1 Light Fittings
8.3 Installation of E1 Lighting
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 38 -
9 Envirolite Pty Ltd Warranty
The Envirolite Warranty Covers Replacement of:
The Warranty Does Not Cover the Replacement of:
Lamp Failures
Failed Sensors and/or Electrical Components in Luminaries.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 39 -
Stock given to Dino Finucci and held at CCBC Civic Centre for all sites.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 40 -
10 Envirolite Pty Ltd Contact Details
10.1 Operations Enquiries
Appendix A, B, C, D & E removed for publication
Community Energy Efficiency-Lighting Upgrade
Contract No. 2013/TS50
Handover Report-Five Dock Leisure Centre
William St, Five Dock.NSW.2046.
Lighting Upgrade By
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 2 -
Introduction This report has been prepared by Envirolite Pty Ltd and details the results achieved from the recent lighting upgrade work
completed at Five Dock Leisure Centre William St, Five Dock as part of the City of Canada Bay Council CEEP-Lighting
Upgrade Project.
Envirolite Pty Ltd, a one hundred percent Australian Owned Company, is proud to have been selected to provide the
lighting solution for this project. Energy reductions and improvements to the working environment have been achieved via
the installation of E1 light fittings which is an Australian developed world leading lighting innovation.
A summary of the benefits achieved from the installation of the new lighting is as follows:
Direct power usage by the lighting has been reduced from 95.8 amps to 25.1 amps, a reduction of 69.6%.
(This excludes additional savings achieved from the installation of daylight harvesting and motion sensors and in air
conditioning where it is installed due to a reduction in the lighting heat load).
The number of fittings installed on site has remained constant at 297 fittings.
The number of lamps in operation has been reduced from 525 to 306, a reduction of 71.6%.
The number of ballasts in operation has been reduced from 511 to 300, a reduction of 70.3%.
Lighting levels have been maintained in accordance with the requirements of Australian Lighting Standards.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 3 -
Table of Contents
1 PROJECT DATES 5
2 LIGHT FITTING COUNTS 6
2.1 PRE-EXISTING LIGHT FITTINGS 6 2.1.1 Summary 6 2.1.2 By Location 7
2.2 AS INSTALLED LIGHT FITTINGS 8 2.2.1 Summary 8 2.2.2 By Location 9
2.3 EXIT LIGHTS 10 2.3.1 Details 10 2.3.2 Summary 10 2.3.3 Location 10
3 SENSORS 11
3.1 SENSOR DETAILS 11 3.2 SENSOR LOCATIONS 12 3.3 SENSOR ID & PROGRAMMING 12
4 FITTING COMPONENTS 14
4.1 COMPARISON OF LAMP AND BALLAST NUMBERS PRE AND POST INSTALLATION 14 4.1.1 Summary 14 4.1.2 Pre-existing 14 4.1.3 As Installed 15
4.2 INSTALLED FITTING COMPONENTS 16 4.2.1 Component Legend 16 4.2.2 Component Breakdown by Fitting 17
5 AMP READINGS 18
5.1 SUMMARY 18 5.2 FLOOR BY FLOOR READINGS 18
6 LUX LEVELS 19
6.1 RECOMMENDED ILLUMINANCE 19 6.2 MEASUREMENT PROCEDURE 20
6.2.1 Lux Meter Positioning Guide 21 6.2.2 Small Room / Area Positioning 21 6.2.3 Medium Room / Area Positioning 22 6.2.4 Large Room / Area Positioning 22
6.3 LUX METER SPECIFICATIONS 23 6.4 PRE AND POST LUX READINGS 24
7 RECYCLING RECONCILIATION 28
7.1 METAL RECYCLING 29 7.2 LAMP RECYCLING 30
8 GENERAL FITTING GUIDELINES 31
8.1 HANDLING E1 LIGHT FITTINGS 31 8.2 CLEANING E1 LIGHT FITTINGS 31 8.3 INSTALLATION OF E1 LIGHTING 31
9 ENVIROLITE PTY LTD WARRANTY 32
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 4 -
10 ENVIROLITE PTY LTD CONTACT DETAILS 34
10.1 OPERATIONS ENQUIRIES 34
APPENDICES 35
APPENDIX A – ELECTRICAL CERTIFICATE 35 APPENDIX B – SENSOR COMMISSIONING CHECKLIST 39 APPENDIX C – SENSOR SPECIFICATIONS 43 APPENDIX D – EXIT LIGHT SPECIFICATIONS 64 APPENDIX E – AS BUILT LIGHTING LAYOUTS 73
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 5 -
1 Project Dates
Work commenced on 31
st July 2013 and the work was completed on 6
th August 2013.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 6 -
2 Light Fitting Counts
2.1 Pre-existing Light Fittings
2.1.1 Summary
Fitting Description Subtotal
2x18W BATTEN 3
1x18W BATTEN 2
1x36W BATTEN 9
2x36W BATTEN 114
1x36W BATTEN WP 6
2x36W BATTEN WP 10
2x36W PLASTER TROFFER 2
2x58W BATTEN 8
1X50W DICHROIC SUSPENDED 20
1x50W DICHROIC 7
1x16W DL 130DIA LED 3
2x26W DL 200DIA 11
2x36W TROFFER 69
EXIT LIGHTS 17
2x18W BATTEN WP 8
1x400W FLOOD LIGHT (Outside) 2
1x100W SPOT LIGHTS (Outside) 3
2X28W TROFFER 3
Total 297
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 7 -
2.1.2 By Location
Fittin
g D
escrip
tion
Gym
Hall
Sports
Hall
Sports
Offic
e
Gym
Offic
e
Hall 1
Entry
Hall 2
Receptio
n
Offic
e 1
Offic
e 2
Offic
e 3
Offic
e 4
Cle
aners
Cupboard
Dis
Toile
t &
Show
er
Sto
re
Male
Toile
ts
Fem
ale
Toile
ts
Kitc
hen
Physio
Health
Clu
b
Health
Clu
b 2
Health
Clu
b 3
Health
Clu
b 5
Health
Clu
b 6
Health
Clu
b 7
Activ
ities R
oom
Activ
ites T
oile
ts
Carp
ark
Entry
Aw
nin
g
Tota
l
2x18W BATTEN 2 1 3
1x18W BATTEN 2 2
1x36W BATTEN 7 1 1 9
2x36W BATTEN 2 1 1 3 2 1 1 1 7 7 42 28 15 1 1 1 114
1x36W BATTEN WP 3 3 6
2x36W BATTEN WP 5 4 1 10
2x36W PLASTER TROFFER 2 2
2x58W BATTEN 8 8
1X50W DICHROIC
SUSPENDED20 20
1x50W DICHROIC 7 7
1x16W DL 130DIA LED 3 3
2x26W DL 200DIA 4 1 6 11
2x36W TROFFER 41 2 2 2 7 15 69
EXIT LIGHTS 3 6 1 2 2 1 1 1 17
2x18W BATTEN WP 8 8
1x400W FLOOD LIGHT
(Outside)2 2
1x100W SPOT LIGHTS
(Outside)3 3
2X28W TROFFER 3 3
Total 5 6 1 1 7 29 55 7 2 2 2 2 1 2 1 15 14 9 8 44 31 16 1 1 1 17 4 10 3 297
2.2 As Installed Light Fittings
2.2.1 Summary
Fitting Description Subtotal
1x18W BATTEN SENSOR 2
1x18W BATTEN 3
1x36W BATTEN 0
1x36W BATTEN 13
1X36W BATTEN SENSOR 102
1x36W BATTEN WP SENSOR 31
1x36W BATTEN WP 2
1x36W PLASTER 2
1x36W BATTEN 0
1x7W LED REPLACEMENT (OSRAM) 20
1x12W DR700 LED 7
1x16W BRIGHT GREEN LED D900 3
1x16W BRIGHT GREEN LED w\ shroud D900 10
1X36W TROFFER SENSOR 63
2x36W TROFFER DIMMABLE 6
2x36W BATTEN CURVED SUSP. 0
EXIT LIGHTS 17
1x18W BATTEN WP 8
1x250W INDUCTION FLOOD LIGHT (outside) 2
1x40W INDUCTION FLOODLIGHT 3
2X28W TROFFER RELAMP 3
297
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 9 -
2.2.2 By Location
Fit
tin
g D
escri
pti
on
Gym
Hall
Sport
s H
all
Sport
s O
ffic
e
Gym
Offic
e
Ha
ll 1
Entr
y
Ha
ll 2
Re
ception
Offic
e 1
Offic
e 2
Offic
e 3
Offic
e 4
Cle
aners
Cupboard
Dis
Toile
t &
Show
er
Sto
re
Male
Toile
ts
Fem
ale
Toile
ts
Kitchen
Physio
He
alth C
lub
He
alth C
lub 2
He
alth C
lub 3
He
alth C
lub 5
He
alth C
lub 6
He
alth C
lub 7
Activitie
s R
oom
Activites T
oile
ts
Ca
rpark
Entr
y A
wn
ing
To
tal
1x18W BATTEN
SENSOR2 2
1x18W BATTEN 3 3
1x36W BATTEN 0
1x36W BATTEN 7 3 1 1 1 13
1X36W BATTEN
SENSOR2 1 1 8 2 42 28 15 1 1 1 102
1x36W BATTEN WP
SENSOR2 15 14 31
1x36W BATTEN
WP1 1 2
1x36W PLASTER 2 2
1x36W BATTEN 0
1x7W LED
REPLACEMENT
(OSRAM)
20 20
1x12W DR700 LED 7 7
1x16W BRIGHT
GREEN LED D9003 3
1x16W BRIGHT
GREEN LED w\
shroud D900
4 6 10
1X36W TROFFER
SENSOR41 7 15 63
2x36W TROFFER
DIMMABLE2 2 2 6
2x36W BATTEN
CURVED SUSP.0
EXIT LIGHTS 3 6 1 2 2 1 1 1 17
1x18W BATTEN WP 8 8
1x250W INDUCTION
FLOOD LIGHT
(outside)
2 2
1x40W INDUCTION
FLOODLIGHT3 3
2X28W TROFFER
RELAMP3 3
Total 5 6 1 1 7 29 55 7 2 2 2 2 1 2 1 15 14 9 8 44 31 16 1 1 1 17 4 10 3 297
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 10 -
2.3 Exit Lights
2.3.1 Details
Product Code Description Category Number
LSC102 LE GRANDE SLIDE CONNECT G2 686200-686210
For specifications of installed exit lights refer Appendix D
2.3.2 Summary
Level G2 Slide Connect Subtotal
G 17 17
Total 17 17
2.3.3 Location Exit Light locations are shown on the as built lighting layouts. Refer Appendix E
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 11 -
3 Sensors
Time out settings Settings vary depending on the function and occupancy of the space. See table for time outs.
Description Time Outs Meeting Rooms, Board Rooms, 20 mins
Small Office 10 mins
Open Office 20 mins
Amenities 30 mins
Disabled Amenities 10 mins
Hallways 20 mins
Health Club 1-3 20 mins
Health Club 4-6 10 mins
Note: Refer below and relevant drawings for sensor settings and locations.
3.1 Sensor Details
Sensor Type Description Subtotal
ME CP Electronics Passive Infrared Motion Sensor 20
M6 CP Electronics Microwave Motion Detector 5
M1 CP Electronics Microwave Motion Detector Long range 5
Total 30
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 12 -
3.2 Sensor Locations Sensor location and type are shown on the as built lighting layouts. Refer Appendix E
3.3 Sensor ID & Programming
Level Zone No. *Sensor ID Type Time Out
(mins) Dimming
Sports Office 1 1 ME 10
Hall 1 1 2 ME 10
Gym Office 1 3 ME 10
Entry 1 4 M6 20
Hall 2 1 7 M6 20
Hall 2 1 8 M6 20
Hall 2 1 10 ME 20
Hall 2 1 15 ME 20
Hall 2 1 17 ME 20
Office 1 1 12 ME 10
Office 2 1 11 ME 10 92
Office 3 1 14 ME 10 92
Office 4 1 13 ME 10 92
Disabled Toilet 1 30 ME 10
Disabled Shower 1 31 ME 10
Male Toilets 1 18 ME 30
Male Toilets 1 19 ME 30
Female Toilets 1 20 ME 30
Female Toilets 1 21 ME 30
Physio 1 9 ME 20
Health Club 6 1 22 ME 10
Health Club 5 1 23 ME 10
Health Club 4 1 24 ME 10
Health Club 3 1 25 M1 20
Health Club 1 26 M1 20
Health Club 1 27 M1 20
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 13 -
Level Zone No. *Sensor ID Type Time Out
(mins) Dimming
Health Club 2 1 28 M1 20
Health Club 2 1 29 M1 20
Activities Room 1 5 M6 20
Activities Room 1 6 M6 20
* Sensor ID as shown on Plans (see attachments)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 14 -
4 Fitting Components Apart from reducing energy consumption the installation of e1 fittings also provides a reduction in the number of lamps and ballasts in operation and consequently reduces ongoing lighting maintenance costs. Further cost savings are provided by the extended life cycle of the e1 fitting components.
4.1 Comparison of Lamp and Ballast Numbers Pre and Post Installation
4.1.1 Summary
Description Lamps Ballasts
Pre-existing 525 511
As Installed 306 300
% Change -71.57% -70.33%
4.1.2 Pre-existing
Fitting Description Lamps Ballasts
2x18W BATTEN 6 6
1x18W BATTEN 2 2
1x36W BATTEN 9 9
2x36W BATTEN 228 228
1x36W BATTEN WP 6 6
2x36W BATTEN WP 20 20
2x36W PLASTER TROFFER 4 4
2x58W BATTEN 16 16
1X50W DICHROIC SUSPENDED 20 20
1x50W DICHROIC 7 7
1x16W DL 130DIA LED 3 3
2x26W DL 200DIA 22 22
2x36W TROFFER 138 138
EXIT LIGHTS 17 17
2x18W BATTEN WP 16 8
1x400W FLOOD LIGHT (Outside) 2 2
1x100W SPOT LIGHTS (Outside) 3 3
2X28W TROFFER 6 6
Total 525 511
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 15 -
4.1.3 As Installed
Fitting Description Lamps Ballasts
1x18W BATTEN SENSOR 2 2
1x18W BATTEN 3 3
1x36W BATTEN 0 0
1x36W BATTEN 13 13
1X36W BATTEN SENSOR 102 102
1x36W BATTEN WP SENSOR 31 31
1x36W BATTEN WP 2 2
1x36W PLASTER 2 2
1x36W BATTEN 0 0
1x7W LED REPLACEMENT (OSRAM) 20 20
1x12W DR700 LED 7 7
1x16W BRIGHT GREEN LED D900 3 3
1x16W BRIGHT GREEN LED w\ shroud D900 10 10
1X36W TROFFER SENSOR 63 63
2x36W TROFFER DIMMABLE 12 6
2x36W BATTEN CURVED SUSP. 0 0
EXIT LIGHTS 17 17
1x18W BATTEN WP 8 8
1x250W INDUCTION FLOOD LIGHT (outside) 2 2
1x40W INDUCTION FLOODLIGHT 3 3
2X28W TROFFER RELAMP 6 6
Total 306 300
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 16 -
4.2 Installed Fitting Components
4.2.1 Component Legend
Component Type No. Description
Tube 1 Osram 18w XXT 840
2 Osram 36w XXT 840
3 Osram 7w LED Replacement
4 Brightgreen 12w DR700
5 Brightgreen 16w D900
6 250w Matsushima Induction Lamp
7 40w Matsushima Induction Lamp
8 GE 28w T5
Ballast 1 Osram QTP8 1x18w
2 Osram QTP8 1x36w
3 Osram QTP8 2x36w
4 Osram Redback
5 Matsushima Ballast 250w 220
6 Matsushima Ballast 40w 220
7 Tridonic Atco PCA 2/36w ECO Dimmable
Diffuser 1 Curved Y5
2 Weatherproof Osram Neptune
3 4mm Toughened Tempered Diffuser
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 17 -
4.2.2 Component Breakdown by Fitting
Fitting Description Tube Type Ballast Type
Diffuser Type
1x18W BATTEN SENSOR 1 1 1
1x18W BATTEN 1 1 1
1x36W BATTEN 2 2 1
1x36W BATTEN 2 2 1
1X36W BATTEN SENSOR 2 2 1
1x36W BATTEN WP SENSOR 2 2 2
1x36W BATTEN WP 2 2 2
1x36W PLASTER 2 2 1
1x36W BATTEN 2 2 1
1x7W LED REPLACEMENT (OSRAM) 3 4 N/A
1x12W DR700 LED 4 4 N/A
1x16W BRIGHT GREEN LED D900 5 4 N/A
1x16W BRIGHT GREEN LED w\ shroud D900 5 4 N/A
1X36W TROFFER SENSOR 2 2 1
2x36W TROFFER DIMMABLE 2 7 1
2x36W BATTEN CURVED SUSP. 2 3 1
EXIT LIGHTS N/A N/A N/A
1x18W BATTEN WP 1 2
1x250W INDUCTION FLOOD LIGHT (outside) 6 5 3
1x40W INDUCTION FLOODLIGHT 7 6 3
2X28W TROFFER RELAMP 8 N/A N/A
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 18 -
5 Amp Readings The areas powered by each lighting circuit were identified and at the time of each reading Envirolite Staff were
positioned accordingly to ensure all light fittings were active. Communication during this period was achieved via
Walkie Talkie.
5.1 Summary
5.2 Floor by Floor Readings
Level Location Circuit Pre
(Amps) Post
(Amps) % Change
Foyer Main Switchboard 1 1.00 0.00 -100.0%
3 8.20 3.40 -58.5%
5 16.90 2.40 -85.8%
7 15.20 4.80 -68.4%
9 10.50 2.40 -77.1%
11 11.50 2.70 -76.5%
13 0.20 0.00 -100.0%
15 0.00 0.50
17 0.20 0.70 250.0%
35 0.70 0.30 -57.1%
37 0.00 0.10
39 0.20 0.00 -100.0%
Health Club Distribution Board B 2 9.5 3.7 -61.1%
4 8.9 3.4 -61.8%
6 6.5 2.3 -64.6%
10 0.8 0.2 -75.0%
24 5.5 2.2 -60.0%
Total 95.8 29.1 -69.6%
Location Pre Installation
(Amps) Post Installation
(Amps) % Change
Foyer 64.6 17.3 -73.22%
Health Club 31.2 11.8 -62.18%
Total 95.8 29.1 -69.6%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 19 -
6 Lux Levels A requirement of the project was that the new lighting installation must comply with Australian Standards
AS/NZS1680, in particular with regards to minimum lux levels.
6.1 Recommended Illuminance
AS/NZS Type of Interior or Activity Maintenance Illuminance
(lx)
1680.2.1
Entrances
Entrance Halls, Lobbies, Foyers 160*
Waiting Rooms 160*
Enquiry Desks 320
Circulation Areas Corridors, Passageways, Ramps 40*
Stairs (internal) 80
Kitchens General 160
Food Preparation, Cooking, Washing Up 240
First Aid Centres Rest Room 40
Treatment Room 320
Toilets 80
Plant Rooms General 80
1680.2.2
General General Tasks Involving Typing, Reading, Writing 320
Computer Rooms Equipment Rooms 320
Meeting Rooms
Meeting Rooms 320
Training Rooms, Seminar Rooms 240
Conference Rooms, Boardrooms 240
* Illuminance applies at floor level
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 20 -
6.2 Measurement Procedure Measurements are to be in accord with the requirements of AS/NZS 1680.1 Appendix B.
1. Measurements in theory should be taken at night or if this is not possible with blinds drawn (no daylight
component) and in an area empty of all furniture such that the light level at a point is the sum of ALL light sources
in the room with no masking from desk partitions, cabinets, people etc. This is obviously not usually possible so
all care should be taken to ensure we minimise shadowing or shrouding and omit or discount readings that do
not comply with this requirement.
2. Lux readings are not always at a height of 700-720 mm (see table over page).
3. Measurements should not be taken closer than 1000mm from room perimeter.
4. If in a room a low reading is recorded in isolation when all other readings are consistent careful consideration
should be given to the validity of this reading.
5. The accuracy of the light meter should also be considered and routinely checked against a recently calibrated
unit, or if such a unit is not immediately to hand, a number of meters can be checked with the same light source
for consistency.
6. The particulars of the meter should be included in the report i.e. specifications, model, type
7. If practical, new lamps should be burnt in for 100 hours before measurement. It is noted that seasoning of new
lamps allows for the burning off of particulates and the even distribution of mercury within the tube. This
stabilization process ensures optimal lamp performance and in general light measurements taken after aging or
seasoning will be higher than those taken earlier.
There are other influences on the 100 hour burn in which would make this requirement impractical. These include
the interaction of sensors and daylight harvesting; the potential waiting periods, especially at some locations, is
financially unviable; and, adjusting lights to remain on 24 hours per day for the four to five days needed is not
environmentally responsible.
8. The environment in which measurement is to be recorded should be allowed to stabilize, the lamps should be on
for 1 hour prior to measurement and air conditioning / ventilation operating normally. If measurements are taken
at night, this may not be possible and readings will generally be lower than otherwise expected.
9. For typically required light levels refer 6.1 Recommended Illuminance.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 21 -
10. The layout of the measurement grid can be a square array of points or if the luminaires are in a regular
rectangular array. Refer 6.2.1 Lux Meter Positioning Guide
11. Number of points and areas of measurement grid.
Area > 25m2 - Measured area 9m
2 minimum and must include at least 4 luminaires.
Area < 25m2 - Entire area to be checked. Minimum of 9 points.
As an indication of the number of points the following can be used as a guide for a roughly square area.
Size of space No. of points
5m x 5m 9
7m x 7m 16
10m x 10m and above 25
6.2.1 Lux Meter Positioning Guide
Position under light fittings: Meter shall be placed directly under the centre of the light fitting at a height of 700mm.
Positions between light fittings: Meter shall be placed as close as practical to the mid way points between light fittings
at a height of 700mm.
6.2.2 Small Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 2
Position 5
Position 8
Position 3 Light
Position 6
Position 9 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 22 -
6.2.3 Medium Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 10
Position 13 Light
Position 2
Position 5
Position 8
Position 11
Position 14
Position 3 Light
Position 5
Position 9 Light
Position 12
Position 15 Light
6.2.4 Large Room / Area Positioning
Position 1 Light
Position 6
Position 11 Light
Position 16
Position 21 Light
Position 2
Position 7
Position 12
Position 17
Position 22
Position 3 Light
Position 8
Position 13 Light
Position 18
Position 23 Light
Position 4
Position 9
Position 14
Position 19
Position 24
Position 5 Light
Position 10
Position 15 Light
Position 20
Position 25 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 23 -
6.3 Lux Meter Specifications Testo 540
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 24 -
6.4 Pre and Post Lux Readings The following sample lux levels were taken across the upgraded areas to confirm that actual lux levels corresponded
to computer modelling generated lux levels.
Level Area Position Pre Post
G Amenities Room 1 186 385
2 162 375
3 239 363
4 158 391
5 91 379
6 93 410
7 79 417
8 146 391
Average 144.3 388.9
G Office 1 1 231 556
2 146 511
3 296 517
4 227 535
5 195 586
6 203 542
Average 216.3 541.2
G Office 3 1 173 407
2 258 435
3 106 418
4 249 451
5 118 407
6 156 445
Average 176.7 427.2
G Office 4 1 202 497
2 193 505
3 131 515
4 87 485
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 25 -
Level Area Position Pre Post
5 63 586
6 111 575
Average 131.2 527.2
Foyer Entrance 1 205 233
2 110 195
3 115 242
4 163 278
5 229 387
6 228 452
7 266 423
8 229 380
9 287 367
10 157 335
11 149 346
12 70 317
13 61 331
14 86 307
15 103 317
16 84 298
17 70 301
18 104 316
19 147 327
20 163 301
21 169 319
22 164 331
23 188 307
Average 154.2 322.2
Foyer Male 01 toilets 1 263 285
2 271 300
3 176 278
4 293 301
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 26 -
Level Area Position Pre Post
5 226 288
6 315 308
7 226 297
8 256 301
9 303 319
10 311 296
11 275 321
12 336 340
Average 270.9 302.8
G Disabled Toilet 1 56 207
2 70 222
3 63 217
Average 63.0 215.3
G Disabled Shower 1 11 201
2 11 195
3 13 207
Average 11.7 201.0
Health Club Middle 1 109 235
2 98 248
3 119 213
4 108 205
5 122 232
6 101 207
7 86 188
8 100 217
9 116 205
Average 106.6 216.7
Health Club Left Hand Side 1 64 220
2 72 231
3 50 217
4 63 235
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 27 -
Level Area Position Pre Post
5 97 209
6 47 217
7 72 232
8 90 207
9 58 213
Average 68.1 220.1
Health Club Right Hand Side 1 38 246
2 29 233
3 46 251
4 49 248
5 37 222
6 30 212
7 41 225
8 36 218
9 60 232
Average 40.7 231.9
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 28 -
7 Recycling Reconciliation The light fittings removed from site have been recycled. The components of the lights fittings are recycled as follows:
- Aluminium & brass: The metal ends from tubes are separated and subsequently recycled into cast products
such as ingots used in foundry application.
- Glass from the tubes is separated and recycled into various glass based applications
- Mercury is distilled from the separated powders and then used in the manufacture of dental amalgam
- Phosphor powder from fluorescent tubes is consolidated for future use in the manufacture of land applications
- Metal is recycled into foundry applications
The following reconciliation is based on the weights of the old individual fitting types replaced and the total weights of
materials recycled by Envirolite’s recycling partners.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 29 -
7.1 Metal Recycling
Fitting Description Qty Unit Fitting Weight (kg)
Total Fitting Weight (kg)
2x18W BATTEN 3 2.50 7.5
1x18W BATTEN 2 2.50 5.0
1x36W BATTEN 9 5.75 51.75
2x36W BATTEN 114 5.75 655.5
1x36W BATTEN WP 6 5.75 34.5
2x36W BATTEN WP 10 5.75 57.5
2x36W PLASTER TROFFER 2 5.75 11.5
2x58W BATTEN 8 7.00 56.0
1X50W DICHROIC SUSPENDED 20 0.80 16.0
1x50W DICHROIC 7 0.75 5.25
1x16W DL 130DIA LED 3 0.90 2.7
2x26W DL 200DIA 11 0.90 9.9
2x36W TROFFER 69 5.75 396.75
EXIT LIGHTS 17 0.50 8.5
2x18W BATTEN WP 8 2.50 20.0
1x400W FLOOD LIGHT (Outside) 2 12.00 24.0
1x100W SPOT LIGHTS (Outside) 3 6.00 18.0
TOTAL 294 1338.35
Weight Recycled: 1303.00kg (As provided by recorded by recycling partners) Variance: -35.5kg (-2.64%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 30 -
7.2 Lamp Recycling
Fitting Description Total Lamps Unit Lamp Weight (g)
Total Lamp Weight (kg)
2x18W BATTEN 6 68.90 0.41
1x18W BATTEN 2 68.90 0.14
1x36W BATTEN 9 138.40 1.25
2x36W BATTEN 228 138.40 31.56
1x36W BATTEN WP 6 138.40 0.83
2x36W BATTEN WP 20 138.40 2.77
2x36W PLASTER TROFFER 4 138.40 0.55
2x58W BATTEN 16 199.60 3.19
1X50W DICHROIC SUSPENDED 20 31.00 0.62
1x50W DICHROIC 7 31.00 0.22
1x16W DL 130DIA LED 3 59.00 0.18
2x26W DL 200DIA 22 66.00 1.45
2x36W TROFFER 138 138.40 19.10
EXIT LIGHTS 17 10.00 0.17
2x18W BATTEN WP 16 68.90 1.10
1x400W FLOOD LIGHT (Outside) 2 300.00 0.60
1x100W SPOT LIGHTS (Outside) 3 280.00 0.84
2X28W TROFFER RELAMP 6 96.60 0.58
TOTAL 525 63.54
Weight Recycled: 64.0kg (As provided by recorded by recycling partners) Variance: 0.46 kg (0.73%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 31 -
8 General Fitting Guidelines
8.1 Handling E1 Light Fittings
All e1 light fittings contain a matte white High Performance e1 Reflector. It is recommended that light cotton
gloves be worn when handling E1 light fittings so as not to mark or damage the reflector and air conditioning
slots.
If using a cutting implement to remove packaging be careful not to scratch or damage the light fitting.
If a blue protective film is present on the High Performance e1 Reflector, this should be removed prior to
installation.
When lifting the fitting, ensure it is properly supported so as not to bend of crease air conditioning slots.
Plug fitting into a designated surface socket.
Remove fluorescent lamp.
With one hand touching the light fitting, peel off remainder of blue film and discard. Note: Failure to touch fitting
when peeling off film will result in the build up of a static charge, which will release when you next earth yourself.
Replace lamp.
8.2 Cleaning E1 Light Fittings
Ensure all fittings and diffusers are clean and free of any contaminates. Wipe with a clean, lint free, cloth if
necessary.
If the High Performance e1 Reflector becomes marked or soiled it should be gently cleaned, using a circular
motion, with a lint free cloth dipped in methylated spirits.
DO NOT use any abrasive or caustic materials on e1 Lighting products.
8.3 Installation of E1 Lighting
Installation of all e1 Lighting products should be carried out by suitably qualified personnel only
Prior to installation electrical safety of the general area should be assessed by suitably qualified personnel.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 32 -
9 Envirolite Pty Ltd Warranty
The Envirolite Warranty Covers Replacement of:
1. Any component (including the lamps) in the E1 Lighting fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of five (5) years from the date of practical completion.
2. Any component (including the lamps) in LED fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of three (3) years from the date of practical completion.
3. Any component in any sensor installed by Envirolite Pty Ltd that fails in the normal course of operation for a
period of three (3) years from the date of practical completion.
The Warranty Does Not Cover the Replacement of:
1. Any component in the light fittings or sensors installed by Envirolite Pty Ltd that have failed other than in the
course of normal operation. This includes but is not limited to failures caused by fire, water damage, earthquakes, power surges, vandalism or other willful or accidental acts that cause damage to the fittings or their components.
2. Failure or damage to any light fitting or sensor component caused by a third party carrying out other works in the building. This includes but is not limited to (a) electrical works that adversely affect the lighting circuits or sensor cables etc and (b) works on the air-conditioning or ceiling grid.
Service calls for the replacement of fitting or sensor components (other than lamps) covered by this warranty will be provided free of cost.
However if the failure of a fitting or sensor component is due to other than normal operation (as covered in Paragraphs 2A and 2B above) then a service call out fee of $100.00 (ex GST) will be charged plus the costs for the supply of replacement components and any associated installation labour.
Lamp Failures
A small reserve stock of replacement lamps will be provided to the Building Manager as part of the Scope of Works to allow for the immediate in house replacement of any failures. The Building Manager will be required to keep all failed lamps in the cartons provided and contact Envirolite when 50% of the reserve stock has been used. Envirolite will then replenish the reserve stock to its original numbers and take away the old lamps for recycling. The cost of hire of any man lifting equipment necessary to replace lamps is excluded from this warranty. Failed Sensors and/or Electrical Components in Luminaries.
Envirolite will within a maximum of two (2) workings days following the day of receipt of a service call send one of its service staff to investigate and rectify the failure.
All service calls for replacement of failed components under this warranty should be directed to [email protected]
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 33 -
Listing of Envirolite Warranty Reserve Stock
Stock given to Dino Finucci and held at CCBC Civic Centre for all sites.
Item Description Quantity
Lamp Osram XXT 36w (box of 40) 1
Lamp GE 26w (box of 25) 1
LED D1000 2
LED D900 2
LED DR700 6
Transformer ET-REDBACK 60VA/230-240 6
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 34 -
10 Envirolite Pty Ltd Contact Details
OFFICE: Unit 4A, 2 Resolution Drive,
CARINGBAH. NSW. 2229
POSTAL ADDRESS: PO Box 220
MIRANDA. NSW. 2228.
PHONE: +61 2 9540 3302
FAX: +61 2 9540 3306
EMAIL: [email protected]
10.1 Operations Enquiries
NAME: Mr. Kerry Powell
MOBILE: 0412 858 303
EMAIL: [email protected]
Appendix A, B, C & D removed for publication
Community Energy Efficiency-Lighting Upgrade
Contract No. 2013/TS50
Handover Report-CCBC Depot
Regatta Rd,Five Dock.NSW.2046.
Lighting Upgrade By
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 2 -
Introduction This report has been prepared by Envirolite Pty Ltd and details the results achieved from the recent lighting upgrade
work completed at CCBC Regatta Rd Depot, Five Dock as part of the City of Canada Bay Council CEEP-Lighting
Upgrade Project.
Envirolite Pty Ltd, a one hundred percent Australian Owned Company, is proud to have been selected to provide the
lighting solution for this project. Energy reductions and improvements to the working environment have been achieved
via the installation of E1 light fittings which is an Australian developed world leading lighting innovation.
A summary of the benefits achieved from the installation of the new lighting is as follows:
Direct power usage by the lighting has been reduced from 122.0 amps to 51.4 amps a reduction of 57.9%.
(This excludes additional savings achieved from the installation of daylight harvesting and motion sensors and in air
conditioning where it is installed due to a reduction in the lighting heat load).
The number of fittings installed on site has reduced from 295 to 292 fittings (-1.02%)
The number of lamps in operation has been reduced from 517 to 393, a reduction of 31.6%.
The number of ballasts in operation has been reduced from 517 to 312, a reduction of 65.7%.
Lighting levels have been maintained in accordance with the requirements of Australian Lighting Standards.
Note: During the course of the installation,1 ballast containing carcinogenic PCB was found, removed and disposed of
according to NSW OH & S and Workcover Regulations.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 3 -
Table of Contents
1 PROJECT DATES 5
2 LIGHT FITTING COUNTS 6
2.1 PRE-EXISTING LIGHT FITTINGS 6 2.1.1 Summary 6 2.1.2 By Location 7
2.2 AS INSTALLED LIGHT FITTINGS 8 2.2.1 Summary 8 2.2.2 By Location 9 2.2.3 Details 10 2.2.4 Summary 10 2.2.5 Location 10
3 SENSORS 11
3.1 SENSOR DETAILS 11 3.2 SENSOR SUMMARY 12 3.3 SENSOR LOCATIONS 12 3.4 SENSOR ID & PROGRAMMING 12
4 FITTING COMPONENTS 15
4.1 COMPARISON OF LAMP AND BALLAST NUMBERS PRE AND POST INSTALLATION 15 4.1.1 Summary 15 4.1.2 Pre-existing 15 4.1.3 As Installed 16
4.2 INSTALLED FITTING COMPONENTS 17 4.2.1 Component Legend 17 4.2.2 Component Breakdown by Fitting 18
5 AMP READINGS 19
5.1 SUMMARY 19 5.2 AREA BY AREA READINGS 19
6 LUX LEVELS 21
6.1 RECOMMENDED ILLUMINANCE 21 6.2 MEASUREMENT PROCEDURE 22
6.2.1 Lux Meter Positioning Guide 23 6.2.2 Small Room / Area Positioning 23 6.2.3 Medium Room / Area Positioning 24 6.2.4 Large Room / Area Positioning 24
6.3 LUX METER SPECIFICATIONS 25 6.4 PRE AND POST LUX READINGS 26
7 RECYCLING RECONCILIATION 32
7.1 METAL RECYCLING 33 7.2 LAMP RECYCLING 34
8 GENERAL FITTING GUIDELINES 35
8.1 HANDLING E1 LIGHT FITTINGS 35 8.2 CLEANING E1 LIGHT FITTINGS 35 8.3 INSTALLATION OF E1 LIGHTING 35
9 ENVIROLITE PTY LTD WARRANTY 36
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 4 -
10 ENVIROLITE PTY LTD CONTACT DETAILS 38
10.1 OPERATIONS ENQUIRIES 38
APPENDICES 39
APPENDIX A – ELECTRICAL CERTIFICATE 39 APPENDIX B – SENSOR COMMISSIONING CHECKLIST 43 APPENDIX C – SENSOR SPECIFICATIONS 46 APPENDIX D – EXIT LIGHT SPECIFICATIONS 107 APPENDIX E – AS BUILT LIGHTING LAYOUTS 116
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 5 -
1 Project Dates
Work commenced on 9
th August 2013 and completed on 23
rd August 2013.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 6 -
2 Light Fitting Counts
2.1 Pre-existing Light Fittings
2.1.1 Summary
Fitting Description Subtotal
2x36W Aris Surface Mounted 43
2x36W Troffer 1200x300 40
2x36W Batten PD 68
1x18W Batten PD 10
Exit Lights 11
1x36W Batten 16
1x400W High Bay 17
2x58W Batten 19
2x65W Batten 16
2x18W Batten WP 18
2x36W Batten WP 18
1x400W Flood Light 6
1x150W Spot Light 5
1x15W CFL 2
1x60W Incandescent 2
1x40W Wall Light 4
Total 295
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 7 -
2.1.2 By Location
Fittin
g D
escrip
tion
Dep
ot
Ad
min
Fro
nt
Bu
ildin
g
Dep
ot
Ad
min
Ba
ck
Bu
ildin
g
SE
S R
oo
m &
Tra
inin
g
SE
S O
uts
ide
Depot
Outs
ide
Mechanic
Work
shop
Mechanic
s O
ffic
e &
Sto
rage
Sto
rage B
uildin
g 1
& 2
Tra
des W
ork
shop
Wash B
ay
Am
enties &
Kitchen &
Toilets
Exis
ting S
tora
ge S
hed
Tim
ber
Sto
rage &
Dog
Are
a
Genera
l Yard
To
tal
2x36W Aris Surface
Mounted43 43
2x36W Troffer
1200x30019 21 40
2x36W Batten PD 3 13 8 9 3 32 68
1x18W Batten PD 2 1 1 6 10
Exit Lights 5 6 11
1x36W Batten 3 8 2 3 16
1x400W High Bay 12 3 2 17
2x58W Batten 5 14 19
2x65W Batten 16 16
2x18W Batten WP 8 10 18
2x36W Batten WP 5 4 9 18
1x400W Flood Light 3 3 6
1x150W Spot Light 1 1 2 1 5
1x15W CFL 2 2
1x60W Incandescent 2 2
1x40W Wall Light 4 4
Total 84 44 9 17 0 17 9 16 20 7 42 4 13 13 295
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 8 -
2.2 As Installed Light Fittings
2.2.1 Summary
Fitting Description Subtotal
2x26W Aris Surface Mounted 43
1x26W Troffer 1200x300 40
1x26W Batten PD 11
1x14W Batten PD 5
2x26W Batten PD 16
Exit Lights 11
1x36W Batten PD 44
1x18W Batten WP 23
3x36W High Bay 18
1x36W Batten WP 60
4x36W High Bay WP 2
1x250W Induction Flood Light 3
1x40W Induction Floodlight 7
1x16 W D1000 D\L 4
1x14.5W E27 Relamp 4
1x120W Induction Floodlight 1
292
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 9 -
2.2.2 By Location
Fittin
g D
escrip
tio
n
Depot
Adm
in F
ront
Build
ing
Depot
Adm
in B
ack B
uild
ing
SE
S R
oom
& T
rain
ing
SE
S O
uts
ide
Depot
Outs
ide
Me
chanic
Work
shop
Me
chanic
s O
ffic
e &
Sto
rage
Sto
rage B
uild
ing 1
& 2
Tra
des W
ork
shop
Wash B
ay
Am
entie
s &
Kitchen &
To
ilets
Exis
tin
g S
tora
ge S
hed
Tim
ber
Sto
rage &
Dog A
rea
Genera
l Y
ard
To
tal
2x26W Aris Surface Mounted 43 43
1x26W Troffer 1200x300 19 21 40
1x26W Batten PD 6 5 11
1x14W Batten PD 4 1 5
2x26W Batten PD 8 8 16
Exit Lights 5 6 11
1x36W Batten PD 9 16 7 8 4 44
1x18W Batten WP 6 1 6 10 23
3x36W High Bay 12 6 18
1x36W Batten WP 4 8 5 5 26 12 60
4x36W High Bay WP 2 2
1x250W Induction Flood Light 3 3
1x40W Induction Floodlight 1 1 2 2 1 7
1x16 W D1000 D\L 4 4
1x14.5W E27 Relamp 4 4
1x120W Induction Floodlight 1 1
Total 88 46 9 15 0 17 9 16 13 7 42 4 13 13 292
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 10 -
Exit Lights
2.2.3 Details
Product Code Description Category Number
LSC102 LE GRANDE SLIDE CONNECT G2 686200-686210
For specifications of installed exit lights refer Appendix D
2.2.4 Summary
Level G2 Slide Connect Subtotal
G 11 11
Total 11 11
2.2.5 Location Exit Light locations are shown on the as built lighting layouts. Refer Appendix E
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 11 -
3 Sensors Time out Function. Active in all sensors. Time out settings Settings vary depending on the function and occupancy of the space. See table for proposed time outs.
Description Time Outs
Meeting Rooms, Board Rooms, 20 mins
Office 20 mins
Amenities 30 mins
Disabled Amenities 10 mins
Storage 20 mins
Machinery Workshops 30 mins
Trade Workshops/Wash Bay/Yard 20 mins
Commissioning Notes Sensor functions have been tailored to suit the client’s needs. There are many factors in an office environment that influence the function of sensors e.g. Wall, carpet and furniture colour, partition height, ambient light and occupancy to name a few. With these factors in mind the above settings were developed in consultation with the City of Canada Bay Council to provide lighting that is compliant with Australian Standards whilst at the same time providing maximum functionality and energy savings.
Note: Refer below and relevant drawings for sensor settings and locations.
3.1 Sensor Details
Sensor Type Description Subtotal
ME CP Electronics Passive Infrared Motion Sensor 21
MEDD CP Electronics Infrared Motion Sensor with Dimming 22
M6 CP Electronics Microwave Motion Detector 5
M1 CP Electronics Microwave Motion Detector Long range 5
M5 CP Electronics Microwave Motion Detector 2
C Clipsal Infrascan Outdoor 2
Total 57
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 12 -
3.2 Sensor Summary
Level ME MEDD M1 M5 M6 C Subtotal
Offices 10 22 5 1 38
Yard 11 5 2 1 19
Total 21 22 5 5 2 2 57
3.3 Sensor Locations Sensor location and type are shown on the as built lighting layouts. Refer Appendix E
3.4 Sensor ID & Programming
Level Location *Sensor
ID Type
Time Out (mins)
Dimming
Offices SES HQ 1 ME 20
Offices SES Office 2 ME 20
Offices Office 15 3 ME 20
Offices Hall 3 4 ME 20
Offices Training Room 5 ME 20
Offices WC 6 ME 20
Offices Dis. WC 7 ME 20
Offices Kitchen 8 ME 20
Offices Hall 3 9 ME 20
Offices Open Office 2 11 M5 20
Offices Open Office 2 12 M5 20
Offices Hall 2 13 MEDD 20
Offices Office 14 14 MEDD 20
Offices Office 13 15 MEDD 20
Offices Open Office 16 M5 20
Offices Open Office 17 M5 20
Offices Office 12 18 MEDD 20
Offices Office 10 19 MEDD 20
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 13 -
Level Location *Sensor
ID Type
Time Out (mins)
Dimming
Offices Office 9 20 MEDD 20
Offices Hall 21 MEDD 20
Offices Office 11 22 MEDD 20
Offices Office 8 23 MEDD 20
Offices Admin Support 24 MEDD 20
Offices Male Toilets 25 ME 30
Offices Hall 26 MEDD 20
Offices Reception 27 MEDD 20
Offices Hall 28 MEDD 20
Offices Office 4 29 MEDD 20
Offices Office 7 30 MEDD 20
Offices Female Toilets 31 MEDD 30
Offices Office 6 32 MEDD 20
Offices Hall 33 MEDD 20
Offices Office 3 34 MEDD 20
Offices Office 2 35 MEDD 20
Offices Office 5 36 MEDD 20
Offices Office 1 37 MEDD 20
Offices Female Toilets 39 ME 30
Yard Mechanics Workshop 40 M1 30
Yard Mechanics Workshop 41 M1 30
Yard Mechanics Office 42 ME 20
Yard Mechanics Storage 43 ME 20
Yard Storage Building 44 M1 30
Yard Storage Building 45 M1 30
Yard Trades Workshop 46 M6 20
Yard Trades Workshop 47 ME 20
Yard Trades Workshop 48 ME 20
Yard Wash Bay 49 M1 20
Yard Kitchen 50 M6 30
Yard Toilets Amenities 51 ME 30
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 14 -
Level Location *Sensor
ID Type
Time Out (mins)
Dimming
Yard Toilets 52 ME 30
Yard Amenities Building 53 ME 30
Yard Amenities Building 54 ME 30
Yard Amenities Building 55 ME 30
Yard Amenities Building 56 ME 30
Yard Amenities Building 57 ME 30
Yard Dog Area 58 C 20
Offices SES Outside 59 C 20
* Sensor ID as shown on Plans (see attachments)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 15 -
4 Fitting Components Apart from reducing energy consumption the installation of e1 fittings also provides a reduction in the number of lamps and ballasts in operation and consequently reduces ongoing lighting maintenance costs. Further cost savings are provided by the extended life cycle of the e1 fitting components.
4.1 Comparison of Lamp and Ballast Numbers Pre and Post Installation
4.1.1 Summary
Description Lamps Ballasts
Pre-existing 517 517
As Installed 393 312
% Change -31.55% -65.71%
4.1.2 Pre-existing
Fitting Description Lamps Ballasts
2x36W Aris Surface Mounted 86 86
2x36W Troffer 1200x300 80 80
2x36W Batten PD 136 136
1x18W Batten PD 10 10
Exit Lights 11 11
1x36W Batten 16 16
1x400W High Bay 17 17
2x58W Batten 38 38
2x65W Batten 32 32
2x18W Batten WP 36 36
2x36W Batten WP 36 36
1x400W Flood Light 6 6
1x150W Spot Light 5 5
1x15W CFL 2 2
1x60W Incandescent 2 2
1x40W Wall Light 4 4
Total 517 517
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 16 -
4.1.3 As Installed
Fitting Description Lamps Ballasts
2x26W Aris Surface Mounted 86 43
1x26W Troffer 1200x300 40 40
1x26W Batten PD 11 11
1x14W Batten PD 5 5
2x26W Batten PD 32 16
Exit Lights 11 11
1x36W Batten PD 44 44
1x18W Batten WP 23 23
3x36W High Bay 54 36
1x36W Batten WP 60 60
4x36W High Bay WP 8 4
1x250W Induction Flood Light 3 3
1x40W Induction Floodlight 7 7
1x16 W D1000 D\L 4 4
1x14.5W E27 Relamp 4 4
1x120W Induction Floodlight 1 1
Total 393 312
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 17 -
4.2 Installed Fitting Components
4.2.1 Component Legend
Component Type No. Description
Tube 1 Osram 18w XXT 840
2 Osram 36w XXT 840
3 Osram Parathom 14.5w E27 LED
4 Brightgreen 16w D1000
5 250w Matsushima Induction Lamp
6 40w Matsushima Induction Lamp
7 GE 26w T5
8 14w Lumos
9 120w Matsushima Induction Lamp
Ballast 1 Osram QTP8 1x18w
2 Osram QTP8 1x36w
3 Osram QTP8 2x36w
4 Osram Redback
5 Matsushima Ballast 250w 220
6 Matsushima Ballast 40w 220
7 Matsushima Ballast 120w 220
8 Osram QTP5 26w
9 Osram QTP5 2x26w
10 Osram QTP5 14w
Diffuser 1 Curved Y5
2 Weatherproof Osram Neptune
3 4mm Toughened Tempered Diffuser
4 Boxed Aristolite Diffuser
5 Flat Y5
6 Rectangle Acrylic
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 18 -
4.2.2 Component Breakdown by Fitting
Fitting Description Tube Type Ballast Type
Diffuser Type
2x26W Aris Surface Mounted 7 9 4
1x26W Troffer 1200x300 7 8 5
1x26W Batten PD 7 8 6
1x14W Batten PD 8 10 6
2x26W Batten PD 7 9 6
Exit Lights N/A N/A N/A
1x36W Batten PD 2 2 6
1x18W Batten WP 1 1 2
3x36W High Bay 2 2 & 3 5
1x36W Batten WP 2 2 2
4x36W High Bay WP 2 2 2
1x250W Induction Flood Light 5 5 3
1x40W Induction Floodlight 6 6 3
1x16 W D1000 D\L 4 4 N/A
1x14.5W E27 Relamp 3 N/A N/A
1x120W Induction Floodlight 9 7 3
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 19 -
5 Amp Readings The areas powered by each lighting circuit were identified and at the time of each reading Envirolite Staff were
positioned accordingly to ensure all light fittings were active. Communication during this period was achieved via
Walkie Talkie.
5.1 Summary
5.2 Area by Area Readings
Level Location Circuit Pre
(Amps) Post
(Amps) % Change
Workshops DB2 Boilermaker 2 5.2 1.9 -63.5%
DB2 Boilermaker 4 7.9 1.9 -75.9%
DB2 Boilermaker 1 8.9 2.5 -71.9%
DB2 Boilermaker 3 1.5 1.4 -6.7%
DB2 Boilermaker 5 0 0
DB2 Boilermaker 7 0 0
DB Middle Shed 3 0.8 0.6 -25.0%
DB 1 Mechanical Workshop 27 2.8 1.1 -60.7%
DB 1 Mechanical Workshop 29 4.7 4.4 -6.4%
DB 1 Mechanical Workshop 31 1.6 0 -100.0%
DB 1 Mechanical Workshop 35 0 0
DB 1 Mechanical Workshop 26 0 0
DB 1 Mechanical Workshop 28 0 0
DB 1 Mechanical Workshop 30 3.4 0.1 -97.1%
DB 1 Mechanical Workshop 32 4.4 1.3 -70.5%
DB 1 Mechanical Workshop 34 2.5 0 -100.0%
Location Pre Installation
(Amps) Post Installation
(Amps) % Change
Workshops 74.0 27.5 -62.84%
Office 40.6 19.1 -52.96%
SES 2.0 1.7 -15.00%
Other 5.4 3.1 -42.59%
Total 122.0 51.4 -57.9%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 20 -
Level Location Circuit Pre
(Amps) Post
(Amps) % Change
DB2 Carpenters Workshop 31 0.2 0.6 200.0%
33 0.5 0.2 -60.0%
37 8.4 0 -100.0%
26 4.4 3.7 -15.9%
28 4.2 2 -52.4%
DB3 Amenities Block 9 5.4 2.2 -59.3%
11 4.3 2.5 -41.9%
2 1.7 0.9 -47.1%
4 1.2 0.2 -83.3%
Office Main Office 6 4.2 1.4 -66.7%
Main Office 8 3.7 1.9 -48.6%
Main Office 10 4.2 2.3 -45.2%
Main Office 12 4.7 2.8 -40.4%
Main Office 14 5.8 2.9 -50.0%
Main Office 16 3.4 2.5 -26.5%
Main Office 18 2.9 1.9 -34.5%
Main Office 20 1 0 -100.0%
Main Office 22 0.2 0 -100.0%
Main Office 24 10.5 3.4 -67.6%
SES SES 4 2 1.7 -15.0%
Other DB3 1 5.4 3.1 -42.6%
122.0 51.4 -57.9%
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 21 -
6 Lux Levels A requirement of the project was that the new lighting installation must comply with Australian Standards
AS/NZS1680, in particular with regards to minimum lux levels.
6.1 Recommended Illuminance
AS/NZS Type of Interior or Activity Maintenance Illuminance
(lx)
1680.2.1
Entrances
Entrance Halls, Lobbies, Foyers 160*
Waiting Rooms 160*
Enquiry Desks 320
Circulation Areas Corridors, Passageways, Ramps 40*
Stairs (internal) 80
Kitchens General 160
Food Preparation, Cooking, Washing Up 240
First Aid Centres Rest Room 40
Treatment Room 320
Toilets 80
Plant Rooms General 80
1680.2.2
General General Tasks Involving Typing, Reading, Writing 320
Computer Rooms Equipment Rooms 320
Meeting Rooms
Meeting Rooms 320
Training Rooms, Seminar Rooms 240
Conference Rooms, Boardrooms 240
* Illuminance applies at floor level
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 22 -
6.2 Measurement Procedure Measurements are to be in accord with the requirements of AS/NZS 1680.1 Appendix B.
1. Measurements in theory should be taken at night or if this is not possible with blinds drawn (no daylight
component) and in an area empty of all furniture such that the light level at a point is the sum of ALL light sources
in the room with no masking from desk partitions, cabinets, people etc. This is obviously not usually possible so
all care should be taken to ensure we minimise shadowing or shrouding and omit or discount readings that do
not comply with this requirement.
2. Lux readings are not always at a height of 700-720 mm (see table over page).
3. Measurements should not be taken closer than 1000mm from room perimeter.
4. If in a room a low reading is recorded in isolation when all other readings are consistent careful consideration
should be given to the validity of this reading.
5. The accuracy of the light meter should also be considered and routinely checked against a recently calibrated
unit, or if such a unit is not immediately to hand, a number of meters can be checked with the same light source
for consistency.
6. The particulars of the meter should be included in the report i.e. specifications, model, type
7. If practical, new lamps should be burnt in for 100 hours before measurement. It is noted that seasoning of new
lamps allows for the burning off of particulates and the even distribution of mercury within the tube. This
stabilization process ensures optimal lamp performance and in general light measurements taken after aging or
seasoning will be higher than those taken earlier.
There are other influences on the 100 hour burn in which would make this requirement impractical. These include
the interaction of sensors and daylight harvesting; the potential waiting periods, especially at some locations, is
financially unviable; and, adjusting lights to remain on 24 hours per day for the four to five days needed is not
environmentally responsible.
8. The environment in which measurement is to be recorded should be allowed to stabilize, the lamps should be on
for 1 hour prior to measurement and air conditioning / ventilation operating normally. If measurements are taken
at night, this may not be possible and readings will generally be lower than otherwise expected.
9. For typically required light levels refer 6.1 Recommended Illuminance.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 23 -
10. The layout of the measurement grid can be a square array of points or if the luminaires are in a regular
rectangular array. Refer 6.2.1 Lux Meter Positioning Guide
11. Number of points and areas of measurement grid.
Area > 25m2 - Measured area 9m
2 minimum and must include at least 4 luminaires.
Area < 25m2 - Entire area to be checked. Minimum of 9 points.
As an indication of the number of points the following can be used as a guide for a roughly square area.
Size of space No. of points
5m x 5m 9
7m x 7m 16
10m x 10m and above 25
6.2.1 Lux Meter Positioning Guide
Position under light fittings: Meter shall be placed directly under the centre of the light fitting at a height of 700mm.
Positions between light fittings: Meter shall be placed as close as practical to the mid way points between light fittings
at a height of 700mm.
6.2.2 Small Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 2
Position 5
Position 8
Position 3 Light
Position 6
Position 9 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 24 -
6.2.3 Medium Room / Area Positioning
Position 1 Light
Position 4
Position 7 Light
Position 10
Position 13 Light
Position 2
Position 5
Position 8
Position 11
Position 14
Position 3 Light
Position 5
Position 9 Light
Position 12
Position 15 Light
6.2.4 Large Room / Area Positioning
Position 1 Light
Position 6
Position 11 Light
Position 16
Position 21 Light
Position 2
Position 7
Position 12
Position 17
Position 22
Position 3 Light
Position 8
Position 13 Light
Position 18
Position 23 Light
Position 4
Position 9
Position 14
Position 19
Position 24
Position 5 Light
Position 10
Position 15 Light
Position 20
Position 25 Light
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 25 -
6.3 Lux Meter Specifications Testo 540
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 26 -
6.4 Pre and Post Lux Readings The following sample lux levels were taken across the upgraded areas to confirm that actual lux levels corresponded
to computer modelling generated lux levels.
Level Area Position Pre Post
Admin Office 11 1 336 431
2 381 460
3 370 458
4 391 489
Average 369.5 459.5
Admin Office 12 1 391 438
2 397 450
3 411 486
4 425 501
Average 406.0 468.8
Admin Office 13 1 360 438
2 386 460
3 396 466
4 403 490
Average 386.3 463.5
Admin Admin Support 1 410 490
2 417 510
3 431 523
4 458 531
5 411 487
6 431 501
Average 426.3 507.0
Admin Office 9 /Safe 1 407 543
2 400 515
3 426 560
Average 411.0 539.3
Admin Office 11 1 336 431
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 27 -
Level Area Position Pre Post
2 381 460
3 370 458
4 391 489
Average 369.5 459.5
Admin Office 12 1 391 438
2 397 450
3 411 486
4 425 501
Average 406.0 468.8
Admin Office 13 1 360 438
2 386 460
3 396 466
4 403 490
Average 386.3 463.5
Admin Admin Support 1 410 490
2 417 510
3 431 523
4 458 531
5 411 487
6 431 501
Average 426.3 507.0
Admin Office 9 /Safe 1 407 543
2 400 515
3 426 560
Average 411.0 539.3
Admin Office 10 1 486 503
2 477 515
3 501 523
4 492 499
Average 489.0 510.0
Admin Office 6 1 383 460
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 28 -
Level Area Position Pre Post
2 397 467
3 401 501
4 423 517
Average 401.0 486.3
Admin Office 7 1 401 515
2 414 501
3 399 483
4 413 497
Average 406.8 499.0
Admin Office 8 1 385 444
2 391 459
3 414 501
4 381 497
Average 392.8 475.3
Admin Office 4 1 481 507
2 408 487
3 469 501
4 435 479
Average 448.3 493.5
Admin Office 10 1 486 503
2 477 515
3 501 523
4 492 499
Average 489.0 510.0
Admin Office 6 1 383 460
2 397 467
3 401 501
4 423 517
Average 401.0 486.3
Admin Office 7 1 401 515
2 414 501
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 29 -
Level Area Position Pre Post
3 399 483
4 413 497
Average 406.8 499.0
Admin Office 8 1 385 444
2 391 459
3 414 501
4 381 497
Average 392.8 475.3
Admin Office 4 1 481 507
2 408 487
3 469 501
4 435 479
Average 448.3 493.5
Admin Female Toilet 1 335 395
2 297 407
3 286 413
4 301 388
Average 304.8 400.8
Admin Office 5 1 444 481
2 413 477
3 426 496
4 439 503
Average 430.5 489.3
Admin Office 1 1 414 467
2 403 483
3 437 507
4 423 469
Average 419.3 481.5
Admin Office 2 1 401 413
2 413 455
3 399 422
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 30 -
Level Area Position Pre Post
4 387 407
Average 400.0 424.3
Admin Office 3 1 423 462
2 431 414
3 427 422
4 433 451
Average 428.5 437.3
Male Change Room 1 256 316
2 240 314
3 242 323
4 238 329
5 251 334
6 287 310
Average 252.3 321.0
Lunchroom 1 347 369
2 380 353
3 353 374
4 398 377
5 307 352
6 300 348
Average 347.5 362.2
Storage Bldg 2 1 275 407
2 318 397
3 312 403
4 327 382
5 268 353
6 272 399
Average 295.3 390.2
Mechanics Storage 1 298 435
2 265 404
3 315 394
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 31 -
Level Area Position Pre Post
4 305 435
5 268 442
6 215 428
Average 277.7 423.0
Male Change Room 1 256 316
2 240 314
3 242 323
4 238 329
5 251 334
6 287 310
Average 252.3 321.0
Mechanics Office 1 461 487
2 438 445
3 397 505
4 401 475
5 415 518
6 397 467
Average 418.2 482.8
Storage Bldg 1 1 318 414
2 298 397
3 257 365
4 397 438
5 362 417
6 385 423
Average 336.2 409.0
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 32 -
7 Recycling Reconciliation
The light fittings removed from site have been recycled. The components of the lights fittings are recycled as follows:
- Aluminium & brass: The metal ends from tubes are separated and subsequently recycled into cast products
such as ingots used in foundry application.
- Glass from the tubes is separated and recycled into various glass based applications
- Mercury is distilled from the separated powders and then used in the manufacture of dental amalgam
- Phosphor powder from fluorescent tubes is consolidated for future use in the manufacture of land applications
- Metal is recycled into foundry applications
The following reconciliation is based on the weights of the old individual fitting types replaced and the total weights of
materials recycled by Envirolite’s recycling partners.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 33 -
7.1 Metal Recycling
Fitting Description Qty Unit Fitting Weight (kg)
Total Fitting Weight (kg)
2x36W Aris Surface Mounted 43 5.75 247.25
2x36W Troffer 1200x300 40 5.75 230.00
2x36W Batten PD 68 5.75 391.00
1x18W Batten PD 10 2.75 27.50
Exit Lights 11 0.50 5.50
1x36W Batten 16 5.75 92.00
1x400W High Bay 17 12.00 204.00
2x58W Batten 19 7.00 133.00
2x65W Batten 16 7.50 120.00
2x18W Batten WP 18 2.75 49.50
2x36W Batten WP 18 5.75 103.50
1x400W Flood Light 6 12.00 72.00
1x150W Spot Light 5 3.50 17.50
1x15W CFL 2 2.50 5.00
1x60W Incandescent 2 0.50 1.00
1x40W Wall Light 4 3.00 12.00
TOTAL 291 - 1710.75
Weight Recycled: 1778.0kg (As provided by recycling partners) Variance: 67.25kg (3.93%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 34 -
7.2 Lamp Recycling
Fitting Description Total Lamps Unit Lamp Weight (g)
Total Lamp Weight (kg)
2x36W Aris Surface Mounted 86 138.40 11.90
2x36W Troffer 1200x300 80 138.40 11.07
2x36W Batten PD 136 138.40 18.82
1x18W Batten PD 10 68.90 0.69
Exit Lights 11 0.10 0.00
1x36W Batten 16 138.40 2.21
1x400W High Bay 17 300.00 5.10
2x58W Batten 38 160.00 6.08
2x65W Batten 32 180.00 5.76
2x18W Batten WP 36 68.90 2.48
2x36W Batten WP 36 138.40 4.98
1x400W Flood Light 6 300.00 1.80
1x150W Spot Light 5 150.00 0.75
1x15W CFL 2 42.00 0.08
1x60W Incandescent 2 55.00 0.11
1x40W Wall Light 4 59.00 0.24
TOTAL 517 72.08
Weight Recycled: 76.0kg (As provided by recycling partners) Variance: 3.92kg (5.44%)
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 35 -
8 General Fitting Guidelines
8.1 Handling E1 Light Fittings
All e1 light fittings contain a matte white High Performance e1 Reflector. It is recommended that light cotton
gloves be worn when handling E1 light fittings so as not to mark or damage the reflector and air conditioning
slots.
If using a cutting implement to remove packaging be careful not to scratch or damage the light fitting.
If a blue protective film is present on the High Performance e1 Reflector, this should be removed prior to
installation.
When lifting the fitting, ensure it is properly supported so as not to bend of crease air conditioning slots.
Plug fitting into a designated surface socket.
Remove fluorescent lamp.
With one hand touching the light fitting, peel off remainder of blue film and discard. Note: Failure to touch fitting
when peeling off film will result in the build up of a static charge, which will release when you next earth yourself.
Replace lamp.
8.2 Cleaning E1 Light Fittings
Ensure all fittings and diffusers are clean and free of any contaminates. Wipe with a clean, lint free, cloth if
necessary.
If the High Performance e1 Reflector becomes marked or soiled it should be gently cleaned, using a circular
motion, with a lint free cloth dipped in methylated spirits.
DO NOT use any abrasive or caustic materials on e1 Lighting products.
8.3 Installation of E1 Lighting
Installation of all e1 Lighting products should be carried out by suitably qualified personnel only
Prior to installation electrical safety of the general area should be assessed by suitably qualified personnel.
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 36 -
9 Envirolite Pty Ltd Warranty
The Envirolite Warranty Covers Replacement of:
1. Any component (including the lamps) in the E1 Lighting fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of five (5) years from the date of practical completion.
2. Any component (including the lamps) in LED fittings installed by Envirolite Pty Ltd that fails in the normal course of operation for a period of three (3) years from the date of practical completion.
3. Any component in any sensor installed by Envirolite Pty Ltd that fails in the normal course of operation for a
period of three (3) years from the date of practical completion.
The Warranty Does Not Cover the Replacement of:
1. Any component in the light fittings or sensors installed by Envirolite Pty Ltd that have failed other than in the
course of normal operation. This includes but is not limited to failures caused by fire, water damage, earthquakes, power surges, vandalism or other willful or accidental acts that cause damage to the fittings or their components.
2. Failure or damage to any light fitting or sensor component caused by a third party carrying out other works in the building. This includes but is not limited to (a) electrical works that adversely affect the lighting circuits or sensor cables etc and (b) works on the air-conditioning or ceiling grid.
Service calls for the replacement of fitting or sensor components (other than lamps) covered by this warranty will be provided free of cost.
However if the failure of a fitting or sensor component is due to other than normal operation (as covered in Paragraphs 2A and 2B above) then a service call out fee of $100.00 (ex GST) will be charged plus the costs for the supply of replacement components and any associated installation labour.
Lamp Failures
A small reserve stock of replacement lamps will be provided to the Building Manager as part of the Scope of Works to allow for the immediate in house replacement of any failures. The Building Manager will be required to keep all failed lamps in the cartons provided and contact Envirolite when 50% of the reserve stock has been used. Envirolite will then replenish the reserve stock to its original numbers and take away the old lamps for recycling. The cost of hire of any man lifting equipment necessary to replace lamps is excluded from this warranty. Failed Sensors and/or Electrical Components in Luminaries.
Envirolite will within a maximum of two (2) workings days following the day of receipt of a service call send one of its service staff to investigate and rectify the failure.
All service calls for replacement of failed components under this warranty should be directed to [email protected]
Envirolite Pty Limited – ABN 83 116 943 947 PO Box 220 Miranda NSW 2228. Unit 4A, 2 Resolution Drive, Caringbah.NSW.2229. Phone +61 2 9540 3302; Fax +61 2 9540 3306
Helping you make a world of difference
- 37 -
Listing of Envirolite Warranty Reserve Stock
Stock given to Dino Finucci and held at CCBC Civic Centre for all sites.
Item Description Quantity
Lamp Osram XXT 36w (box of 40) 1
Lamp GE 26w (box of 25) 1
LED D1000 2
LED D900 2
LED DR700 6
Transformer ET-REDBACK 60VA/230-240 6
Page Removed for Publication