Class 4141
MP Meter-Pak™ Meter Centers
MP44125
MP86200
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2General and Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Catalog 4141CT0701
2008
MP Meter-Pak™ Meter CentersProduct Description
2© 2008 Schneider Electric All Rights Reserved 03/2008
PRODUCT DESCRIPTIONSquare D® brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications:
• UL® Listed NEMA Type 3R construction
• Meets EUSERC standards
• 9-inch meter center spacing allows for more sockets per device creating lighter, more compact branch enclosures
• Meter socket jaws, constructed of tin-plated copper, are spring reinforced on MP devices
• Lever type bypass meter socket jaws are spring reinforced and equipped with jaw release
• Stainless steel cover hasps and latches meet tough coastal utility sealing requirements
• Barrel lock provisions on all ringless devices
MP Meter-Pak Meter Centers
For 2- to 6-unit apartment buildings or light commercial applications.
• Surface and semi-flush mounting
• Suitable only for use as service equipment
• Main bus ratings range from 200–800 A
• 125, 200, and 225 A (2 to 4 positions) tenant circuit breaker versions
• Four meter socket configurations available:
— Ring type four-jaw without bypass
— Ringless type with 5th jaw without bypass
— Ringless type with 5th jaw and horn bypass
— Ringless type with 5th jaw and lever bypass with jaw release
• 120/240 Vac, 1φ3W or 120/208 Vac, 1φ3W (derived from a 208Y/120 Vac, 3φ4W network)
MPH66125 with Horn Bypass
MPH33125
MP Meter-Pak™ Meter CentersProduct Description
303/2008 © 2008 Schneider Electric All Rights Reserved
Short Circuit Current Rating Selection Process
1. Review local utility requirements to ensure that metering equipment meets their standards.
2. Check with local utility to determine available fault current at the meter center.
3. Use the Short Circuit Current Ratings (SCCR) table below to:
a. Read down to select SCCR equal to or greater than desired rating.
b. Read across to select Tenant Circuit Breaker type.
4. With information obtained from Step 3, turn to the appropriate selection pages to determine catalog numbers for Meter-Pak Device and Tenant Circuit Breakers.
UL Listed Meter Center Short Circuit Current Ratings (SCCR) 10,000, 22,000, 25,000. 42,000, 65,000 and 100,000 AIR
Short Circuit Current Rating (RMS Symmetrical Amperes at 240 Vac
Maximum)1
1 Meter center short circuit current rating is equal to the lowest short circuit current rating given in the table for any circuit breaker installed in any meter panelboard in the meter center.
MP Meter-Pak Meter Centers
Tenant Circuit Breakers2
2 When slider type manual circuit closers are installed, the meter center short circuit current rating is limited to 10,000 RMS symmetrical amperes.
10,000 AIR 3
3 AIR = Amperes Interrupting Rating.
QO (125 A max., 2-pole)
QOM2-MM (200 A max., 2-pole)
QBP-TM (70–225 A max., 2-pole)
22,000 AIR 3QO-VH (125 A max., 2-pole)
QOM2-MVH (200 A max., 2-pole)
25,000 AIR 3 QDP-TM (70–225 A max., 2-pole)
42,000 AIR 3 QOH (125 A max., 2-pole)
65,000 AIR 3 QGP-TM (70–225 A max., 2-pole)
100,000 AIR 3 QJP-TM (70–225 A max, 2-pole)
MP Branch Compartments
ServiceDisconnects(6 Maximum)
Main Lugs Load Center
(Typical)
Transformer
MP Main Lugs Compartment
MP Meter-Pak™ Meter CentersTable of Contents
4© 2008 Schneider Electric All Rights Reserved 03/2008
Table of Contents
MP METER-PAK™ METER CENTERS
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5125 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6200 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6225 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Mains Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Branch Circuit Breaker Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Meter Socket Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9Utility Pull Box Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Customer/Tenant Compartment Cover . . . . . . . . . . . . . . . . . . . . . . . . . .11Mounting Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Rotating Mounting Feet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Top Endwall Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12125 A Maximum MP Meter-Pak Meter Center Top Endwalls . . . . . . . . .12200 and 225 A Maximum MP Meter-Pak Meter Center Top Endwalls . .12Semi-Flush Flange Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12MP Meter-Center Hub and Knockout Configurations . . . . . . . . . . . . . . .13Main Lugs Section Service Conductor Termination Data . . . . . . . . . . . .14Alternate Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14NEMA/EUSERC Lug Landing Kit . . . . . . . . . . . . . . . . . . . . . . . . . . .14–15Tenant Circuit Breaker Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . .16Service Grounding/Load Neutral and Equipment Grounding Termination Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Hinged Rain Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Underground Service Wireway . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17–18Catalog Number Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
MP Meter-Pak™ Meter CentersApplication Data
503/2008 © 2008 Schneider Electric All Rights Reserved
Application Data
MP22125 (shown)MPR22125, MPH22125
(Sealing Rings not shown) MP55125, MPR55125, MPH55125, MP66125, MPR66125, MPH66125 (shown)(Top Left Position Omitted on 5-Position Units)
MP33125, MPR33125, MPH33125 (shown)MP42200 (shown)
MPR42200, MPH42200
MP44125 (shown)MPR44125, MPH44125
MP43200, MPR43200MPH43200 (shown)
MP Meter-Pak™ Meter CentersApplication Data
6© 2008 Schneider Electric All Rights Reserved 03/2008
125 A Maximum MP Meter-Pak™ Meter Center Configurations
• Ring-type MP supplied with 4-jaw meter socket without bypass (5th jaw and manual slider type bypass kits can be ordered separately and field-installed).
• Ringless-type MPR supplied with 5-jaw meter socket without bypass (horn-type bypass kits can be ordered separately and field-installed).
• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.
• Both ring- and ringless-type units have provisions for mounting 2-pole, plug-on type QO®, QO-VH, or QOH circuit breakers.
200 A Maximum MP Meter-Pak Meter Center Configurations
• Ring-type MP supplied with 4-jaw meter socket without bypass (5-jaw and manual slider type bypass kits can be ordered separately and field-installed).
• Ringless-type MPR supplied with 5-jaw meter socket without bypass (horn-type bypass kits can be ordered separately and field-installed).
• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.
• Both ring- and ringless-type units have provisions for mounting 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers.
225 A Maximum MP Meter-Pak Meter Center Configurations
• Ringless-type MPL supplied with 5-jaw meter sockets with lever bypass and jaw release.
• MPL devices have provisions for mounting QBP-TM, QDP-TM, QGP-TM, or QJP-TM 2-pole bolt-on type circuit breakers.
MP64200, MPR64200, MPH64200 (shown)
MP85200, MPR85200, MPH85200, MP86200 (shown), MPR86200, MPH86200
(Top Left Position Omitted on 5-Position Units)MPL32225, MPL53225 (shown), MPL64225
MP Meter-Pak™ Meter CentersApplication Data
703/2008 © 2008 Schneider Electric All Rights Reserved
Type
• Enclosures are indoor/rainproof NEMA Type 3R
• MP, MPH and MPR available in 2-, 3-, 4-, 5-, or 6-position configurations
• MPL available in 2-, 3-, or 4-position configurations
• Suitable only for use as service entrance equipment (cannot be fed from an upstream service disconnect)
• Designed to be wall mounted only, not suitable for use as floor standing equipment
• All unmetered conductor compartments are sealable by the utility company
• Finish: ANSI gray, baked powder coat epoxy electro-deposited over cleaned phosphatized steel
• UL Listed under File E-6294
Service
• 120/240 Vac, 1φ3W
• 120/208 Vac, 1φ3W (derived from a 208Y/120 Vac, 3φ4W network)
Mains Ratings
125 A Maximum MP Meter-Pak Meter Centers
200 A (2-position), 300 A (3-position), 400 A (4-position), 500 A (5-position), and 600 A (6-position) main bus ratings.
200 A Maximum MP Meter-Pak Meter Centers
400 A (2- and 3-position), 600 A (4-position) and 800 A (5- and 6-position) main bus ratings.
225 A Maximum MP Meter-Pak Meter Centers
350 A (2-position), 500 A (3-position), 600 A (4-position) main bus ratings.
Branch Circuit Breaker Provisions
125 A Maximum MP Meter-Pak Meter Centers
Accepts 40–125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit breakers. (Order circuit breakers separately.)
UL® Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of installed tenant circuit breaker.
NOTE: For load center series ratings used downstream from metering equipment, refer to the following Data Bulletins: 4100DB0301 and 2700DB9901.
MPH66125
400 A Main Lugs
QO Plug-On Mounting Base
QO2100Plug-On Circuit
Breaker Installed
Ampere Rating10,000 AIR120/240 Vac
22,000 AIR120/240 Vac
42,000 AIR120/240 Vac
40 QO240 QO240VH QOH240
50 QO250 QO250VH QOH250
60 QO260 QO260VH QOH260
70 QO270 QO270VH QOH270
80 QO280 QO280VH QOH280
90 QO290 QO290VH QOH290
100 QO2100 QO2100VH QOH2100
125 QO2125 QO2125VH QOH2125
MP Meter-Pak™ Meter CentersApplication Data
8© 2008 Schneider Electric All Rights Reserved 03/2008
200 A Maximum MP Meter-Pak Meter Centers
Accepts 100–200 A, 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit breakers. (Order circuit breakers separately.)
UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of tenant circuit breaker installed.
NOTE: For load center series ratings used downstream from metering equipment, refer to Data Bulletins: 4100DB0301 and 2700DB9901.
225 A Maximum MP Meter-Pak Meter Centers
Accepts 70–225 A, 2-pole, bolt-on type, QBP-TM, QDP-TM, QGP-TM, or QJP-TM circuit breakers. Also accepts 40–60 A, 2-pole, plug-on type QO, QO-VH or QOH circuit breakers; but requires the use of EZM125QOA adapter kit. (Order circuit breakers and adapter kit separately).
UL Listed meter center short circuit current rating (RMS symmetrical amperes) equal to the lowest interrupting rating of tenant circuit breaker installed.
Meter Sockets
Standard Meter Socket Configurations
• Rated 200 A continuous duty.
• Front removable spring reinforced jaws equipped with line and load side blade guides.
• Thermoset polyester with fiberglass reinforced base assembly.
• 5th jaw supplied factory-installed on ringless-type MPH and MPR in the 9 o'clock position, 5th jaw can be moved to the 3 or 6 o’clock position as required.
• Ring-type MP supplied with 4-jaw meter socket without bypass.
• Ringless-type MPR supplied with 5-jaw meter socket without bypass.
• Ringless-type MPH supplied with 5-jaw meter socket with horn-type bypass.
• Ringless-type MPL supplied with 5-jaw meter socket with lever bypass and jaw release.
QDP22200TM 2-Pole, Bolt-on Type Circuit Breaker
QOM2-MM or QOM2-MVH Bolt-On Mounting Base
QOM2200MVH Bolt-On Circuit Breaker Installed
Optional 5th Jaw Kit Installed on Ring-Type Device
Ringless-Type MPHIncludes 5-Jaw Meter Socket and Horn Bypass
Ampere Rating 10,000 AIR 120/240 Vac 22,000 AIR 120/240 Vac
100 QOM2100MM QOM2100MVH
125 QOM2125MM QOM2125MVH
150 QOM2150MM QOM2150MVH
175 QOM2175MM QOM2175MVH
200 QOM2200MM QOM2200MVH
Ampere Rating
10,000 AIR 120/240 Vac
25,000 AIR 120/240 Vac
65,000 AIR 120/240 Vac
100,000 AIR 120/240 Vac
40 QO240 1
1 Requires use of EZM125QOA adapter (order separately).
QO240VH 1 2
2 QOVH tenant circuit breakers are rated 22,000 AIR at 120/240 Vac.
QOH240 1 3
3 QOH tenant circuit breakers are rated 42,000 AIR at 120/240 Vac.
—
50 QO250 1 QO250VH 1 2 QOH250 1 3 —
60 QO260 1 QO260VH 1 2 QOH260 1 3 —
70 QBP22070TM QDP22070TM QGP22070TM QJP22070TM
80 QBP22080TM QDP22080TM QGP22080TM QJP22080TM
90 QBP22090TM QDP22090TM QGP22090TM QJP22090TM
100 QBP22100TM QDP22100TM QGP22100TM QJP22100TM
110 QBP22110TM QDP22110TM QGP22110TM QJP22110TM
125 QBP22125TM QDP22125TM QGP22125TM QJP22125TM
150 QBP22150TM QDP22150TM QGP22150TM QJP22150TM
175 QBP22175TM QDP22175TM QGP22175TM QJP22175TM
200 QBP22200TM QDP22200TM QGP22200TM QJP22200TM
225 QBP22225TM QDP22225TM QGP22225TM QJP22225TM
MP Meter-Pak™ Meter CentersApplication Data
903/2008 © 2008 Schneider Electric All Rights Reserved
Optional Meter Socket
• 5th jaw kit (catalog number 5J) can be field-installed on ring-type MP at the 3, 6, or 9 o’clock position and is required for 120/208 Vac, 1φ3W, service (derived from a 208Y/120 Vac 3φ4W network). One kit required per meter socket, order separately.
• Horn-type bypass kit, catalog number MMHB, can be field-installed on ringless-type MPR. One kit required per meter socket, order separately.
• Manual slider type bypass kit, catalog number MM125MB (for top position only on 125 A, 2-position ring-type MP) or MM200MB (for 125 A and 200 A ring-type MP). One kit required per meter socket, order separately for field-installation.
NOTE: Manual slider type bypass kits limit meter center equipment short circuit current rating to 10,000 RMS symmetrical amperes.
Meter Socket Covers
Optional Meter Socket Sealing Rings for Type MP
• Stainless steel snap-type sealing ring (catalog number ARP00026). Order separately for field-installation.
• Aluminum screw-type sealing ring (catalog number 29008W). Order separately for field-installation.
Ring-Type MP4-Jaw Meter Socket without Bypass
Manual Slider-Type Bypass, Closed PositionMM125MB, MM200MB (shown)
Manual Slider-Type Bypass, Open PositionMM125MB, MM200MB (shown)
Ring-Type MP Meter Socket Cover
• Individual meter socket cover provided for each meter socket.
• Cover cannot be removed with meter installed in meter socket.
• Seal ring is required to secure base of meter ontorim provided on meter socket cover.
• Aluminum snap-type seal ring (catalog number 29209-100-01) is standard on all ring-type MP meter socket covers.
Individual Ring-Type Meter Socket Cover
Snap-Type Sealing Ring Screw-Type Sealing Ring
MP Meter-Pak™ Meter CentersApplication Data
10© 2008 Schneider Electric All Rights Reserved 03/2008
Ringless-Type MPH, MPL, and MPR Meter Socket Covers
• Individual meter socket cover provided for each meter socket.
• Base of meter is supported by brackets extending from meter socket base assembly. Meter socket cover is installed over meter to seal meter base to socket.
• Ringless meter socket covers are each supplied with a stainless steel latch and hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals.
• Ringless meter socket covers are also supplied with a 3/4-inch knockout to accommodate front-entry barrel locks.
• Barrel lock bracket located behind 3/4-inch knockout in each ringless meter socket cover.
• Barrel lock head protector kit (catalog number MMBLC) includes ferrule, lock nut, and seal cap to accommodate 1-inch long barrel lock (barrel lock not included).
Individual Ringless-Type Meter Socket Cover
Barrel Lock Installed Front Entry through Knockout in Ringless Meter Socket Cover
(Reverse View)
Barrel Lock Head Protector Kit MMBLC Installed through Knockout in Ringless Meter Socket Cover
Stainless Steel Latch and Hasp, Ringless Meter Socket Cover
Support Brackets for Base of Meter
MP Meter-Pak™ Meter CentersApplication Data
1103/2008 © 2008 Schneider Electric All Rights Reserved
Utility Pull Box Cover
• Supplied with handles on 3- through 6-position 125 A maximum,2- through 6-position 200 A maximum, and 2- through 4-position 225 A maximum Meter-Pak meter center units.
• Supplied with rotating locking hasp to accommodate utility seals including lead wire seals, barrel locks, ribbon seals, padlocks, and snap-type seals.
Customer/Tenant Compartment Cover
• Removable without interfering with meter covers.
• Supplied with rotating locking hasp to accommodate a padlock (see rotating locking hasp above).
• Supplied with vertical rainproof tenant circuit breaker covers, one per meter socket.
Tenant Circuit Breaker Covers
• Constructed of impact resistant thermoplastic
• Provisions for padlocking or sealing
• Equipped with latch
Mounting Channel
• Mounting channel supplied with 3- through 6-position 125 A maximum and all 200 A and 2- through 4-position 225 A maximum units.
• Mounting flange is formed as a part of the top endwall to permit easy installation.
• Mount the channel to the wall at proper height. Hang unit on channel from mounting flange.
Rotating Mounting Bracket
• Permanently attached to save time
• Easily moved for mounting hole drilling after marking
• Accommodates slight mounting hole misalignment
• Used for permanent mounting of device to wall
Lifting Handles for Pull Box Cover
Hasp with Cover Installed
Circuit Breaker Cover, Closed
Circuit Breaker Cover, Open
Tenant Compartment Circuit Breaker Cover
Mounting Channel
Rotating Locking Hasp
Rotating Mounting Bracket
12© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Application Data
Top Endwall Configurations
125 A Maximum MP, MPR, and MPH Meter-Pak Meter Center Top Endwalls
• 2-position unit has utility compartment provisions for mounting one type A hub for use with 1- through 2.5-inch size conduit. Closing plate (Catalog Number ACP) supplied, order hub separately.
• 3- and 4-position units have utility compartment provisions for mounting one type A-L hub for use with 2- through 4-inch size conduit. Closing plate (Catalog Number ACPL) supplied, order hub separately.
• 5- and 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduits. Two ACPL closing plates supplied, order hubs separately.
200 and 225 A Maximum MP, MPR, and MPH Meter-Pak Meter Center Top Endwalls
2- through 6-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL closing plates supplied, order hubs separately.
Semi-Flush Flange Kits
Prior to installation, semi-flush flange kits can be ordered separately for field modification. (Refer to instructions included in kits for complete directions.)
To drill enclosure top endwall and box sides to secure mounting flanges:
1. Drill 5/16-inch diameter clearance holes at center punched marks provided and secure flanges with 1/4-20 mounting hardware provided.
2. Secure mounting flanges of enclosure to stud wall on three sides (top, left, and right).
3. Cover mounting flanges with building paper and caulk to seal between enclosure and building paper.
225 A Maximum MPL Meter-Pak Meter Center Top Endwalls
2- through 4-position units have utility compartment provisions for mounting two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL closing plates supplied, order hubs separately.
Semi-Flush Flange Kit
Type A-L Hub Installed3- and 4-Position 125 A Top Endwall
Closing Plate ACP (supplied)2-Position 125 A Top Endwall
Type A Hub Installed2-Position 125 A Top Endwall
Closing Plate ACPL (supplied)3- and 4-Position 125 A Top Endwall
Two Type A-L Hubs Installed5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall2- through 4-Position 225 A Top Endwall
Two Closing Plates ACPL (supplied)5- and 6-Position 125 A Top Endwall and 2- through 6-Position 200 A Top Endwall2- through 4-Position 225 A Top Endwall
Description Catalog Number
125 A Maximum 2-Position MPSF12
125 A Maximum 3- and 4-Position MPSF14
125 A Maximum 5- and 6-Position MPSF16
200 A Maximum 2- and 3-Position MPSF23
200 A Maximum 4-Position MPSF24
200 A Maximum 5- and 6-Position MPSF26
Semi-Flush Flange KitMPSF23
MP Meter-Pak™ Meter CentersApplication Data
1303/2008 © 2008 Schneider Electric All Rights Reserved
Knockouts
SymbolConduit Size Hole Diameter
in. [mm] in. [mm]
A 0.50 13 0.88 22
B 0.75 19 1.25 29
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.19 105
J 4.00 102 4.63 117
MP Meter-Pak Meter Center Hub and Knockout Configurations
Maximum Tenant Circuit Breaker Ampere Rating and Number of
Positions
CatalogNumber
Top Endwall Pull Box Compartment Bottom EndwallBox Back Tenant Circuit Breaker Compartment
Knockouts
Closing Plate(s) Supplied
Factory-InstalledHub Provisions
Pull Box Compartment Knockout and
Hub Provisions
Tenant Circuit Breaker
Compartment Knockouts
125 A2-Position
MP22125MPH22125MPR22125
(1) ACP (1) Type A(1) Type A Hub or(1) B300 Hub or(1) D, F, G, and (1) A
(2) C, D, F and(1) A (2) C, D, F 1
1 Same knockout pattern on side of box.
125 A3-Position
MP33125MPH33125MPR33125
(1) ACPL (1) Type A–L
(2) Type A–L Hubs or(2) E, F, G, Hand (1) A, BNote: One knockout is provided with I and J rings.
(4) C, D, Fand (1) A, B (4) C, D, F
125 A4-Position
MP44125MPH44125MPR44125
125 A5-Position
MP55125MPH55125MPR55125
(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A
(3) C, D, F and (1) A, BProvided per compartment.
(3) C, D, FProvided per compartment.125 A
6-Position
MP66125MPH66125MPR66125
200 A2-Position
MP42200MPH42200MPR42200
(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A
(4) C, D, F and(1) A, B (3) C, D, F
200 A3-Position
MP43200MPH43200MPR43200
200 A4-Position
MP64200MPH64200MPR64200
(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A
(4) C, D, Fand (1) A, B (4) C, D, F
200 A5-Position
MP85200MPH85200MPR85200
(2) ACPL (2) Type A–L(2) Type A–L Hubs or(2) G, H, I, Jand (1) A, B, C
(3) C, D, Fand (1) A, BProvided per compartment.
(3) C, D, FProvided per compartment.200 A
6-Position
MP86200MPH86200MPR86200
225 A2-Position MPL32225 (2) ACPL (2) Type A–L
(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B
(3) C, D, E, F and(1) A, B (3) C, D, E, F
225 A3-Position MPL53225 (2) ACPL (2) Type A–L
(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B
(4) C, D, E, F and(1) A, B
(4) C, D, E, F
225 A4-Position MPL64225 (2) ACPL (2) Type A–L
(2) Type A–L Hubs or(2) E, F, G, H, I, J and(1) A, B
(5) C, D, E, F and(1) A, B (5) C, D, E, F
14© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Application Data
Main Lugs SectionService Conductor Termination Data• Neutral bus is bonded permanently to the enclosure
• Suitable only for use as service equipment
Alternate Lug KitsAvailable for use on 3–6 position 125 A, all 200 A, and all 225 A Meter-Pak meter center units (order separately):
NEMA/EUSERC Lug Landing Kit• Catalog numbers MMSK2 and MMSK4 (order separately).
• MMSK2 is available for use on 3- through 6-position 125 A and all 200 A Meter-Pak meter center units.
• MMSK4 is available for use ONLY on MPL53225 and MPL64225, Not required for MPL32225.
• Kits include three bus bar lug landing pads and mounting hardware to secure pads to main cross bus.
• Each lug landing pad with MMSK2 is supplied with two 1/2-13 studs; MMSK4 with four 1/2-13 studs; all on 1-3/4 inch center. Kits include lug mounting hardware.
• MMSK2 is rated 600A maximum when applied in EUSERC areas.
• Order one kit per Meter-Pak device, order lugs separately (refer to each device wiring diagram for lug catalog numbers).
Main Lugs Compartment
MMLK600
MMSK2
MMLK250
MMLK500
MMSK4
125 A Maximum MP Meter-Pak™ Meter Center Service Conductor Termination Data
Number of Meter Socket Positions
Main Bus Rating (Amperes)
Factory-Installed Main Lugs Capacity
(Amperes)
Line Phase and Neutral Lug Wire Size
Al/Cu AWG kcmil
2 200 A 200 A (1) #4-250
3 300 A 300 A(1) 1/0-600
or(2) 1/0-250
4 400 A 400 A
5 500 A 400 A Al or 500 A Cu
6 600 A 400 A Al or 500 A Cu
200 A Maximum MP Meter-Pak Meter Center Service Conductor Termination Data
2 400 A 400 A (1) 1/0-600or
(2) 1/0-2503 400 A 400 A
4 600 A 400 A Al or 500 A Cu
5 800 A 600 A Al or 750 A Cu(2) 3/0-500
6 800 A 600 A Al or 750 A Cu
225 A Maximum MP Meter-Pak Meter Center Service Conductor Termination Data
2 350 A 350 A (1) 1/0-600or
(2) 1/0-2503 500 A 400 A
4 600 A 400 A
Catalog Number Lug Type (Mechanical) Lug Wire Size Al/Cu AWG/kcmil
MMLK250 1
1 Standard lug kit supplied factory-installed on 3–6 position 125 A units, 2–4 position 200 A units, and 2–4 position 225 A units.
Double-Barrel (1) 1/0-600 or (2) 1/0-250
MMLK500 Double-Barrel (2) 3/0-500
MMLK600 2
2 Kit includes NEMA/EUSERC lug landing pads (MMSK2). Kit is rated 800 A maximum (600 A maximum in EUSERC areas).
Double-Barrel (2) #2-600
MP Meter-Pak™ Meter CentersApplication Data
1503/2008 © 2008 Schneider Electric All Rights Reserved
MMSK2
MMSK4
Lugs for Use with NEMA/EUSERC Lug Landing Kit MMSK2
Mains RatingLug
ManufacturerCatalog Number 1 Lug Type
Lug Wire Size AWG/kcmil
Crimping Tool or Torque
300 A
Anderson
VACL-500-12BN
Compression
4/0–500 Al/Cu VC-6FT
VCEL-060-12H2 400–600 Al, 400–500 Cu VC-6FT
VCEL-075-12H2 500 Cu VC-6FT
VHCL-500-12BN 4/0–500 Cu VC-6FT
VHCL-400-12BN 4/0–400 Cu VC-6FT
VHCL-350-12BN 3/0–350 Cu VC-6FT
ILSCOTA-600-2N 2
Mechanical#2-600 Al/Cu 375 lb-in. (42 N•m)
AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)
400 A
Anderson VHCL-600-12BN Compression 250–600 Cu VC-6FT
ILSCOTA-600-2N 2
Mechanical#2-600 Al/Cu 375 lb-in. (42 N•m)
AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)
500–600 AILSCO
AU-600-2NMechanical
(2) #2-600 Al/Cu 500 lb-in. (57 N•m)
800 A AU-600-2N (2) 3/0-500 Al/Cu 500 lb-in. (57 N•m)
1 Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2 Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).
Lugs for Use with NEMA Lug Landing Kit MMSK4
Catalog NumberLug
ManufacturerCatalog Number 1 Lug Type
Lug Wire Size AWG/kcmil
Crimping Tool or Torque
MPL32225 2
Anderson
L1D2-600Mechanical
#2-600 Al/Cu 550 lb-in. (62 N•m)
L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)
VCEL-050-12H2
Compression
2/0–500 Al/Cu VC-6FT
VCEL-060-12H2 400–600 Al or 400–500 Cu VC-6FT
VCEL-075-12H2 500–750 Al or 500 Cu VC-6FT
VACL-500-12BN 4/0–500 Al/Cu VC-6FT
VACL-600-12BN 350–600 Al or 350–500 Cu VC-6FT or VC8
VACL-750-12BN 500–750 Al or 500 Cu VC-6FT or VC8
VACL-1000-12BN 750–1000 Al VC8
VHCL-500-12BN 4/0–500 Cu VC-6FT or VC-7FT
VHCL-600-12BN 3/0–350 Cu VC-6FT
ILSCO
TA-600-2N 3
Mechanical
#2-600 Al/Cu 375 lb-in. (42 N•m)
TA-800-2N 300–800 Al/Cu 500 lb-in. (57 N•m)
AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)
Connector Manufacturing
Company
A1B2-600-2
Mechanical
#2-600 Al/Cu 375 lb-in. (42 N•m)
2AB2-600 (2) #2-600 Al/Cu 375 lb-in. (42 N•m)
3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)
L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)
MPL53225
Anderson
L1D2-600 Mechanical #2-600 Al/Cu 550 lb-in. (62 N•m)
VCEL-050-12H2
Compression
2/0–500 Al/Cu VC-6FT
VCEL-060-12H2 400–600 Al, 400–500 Cu VC-6FT
VACL-500-12BN 4/0–500 Al/Cu VC-6FT
VHCL-500-12BN 4/0–500 Cu VC-6FT or VC-7FT
VHCL-600-12BN 250–600 Cu VC-6FT, VC-7FT, or VC-8
ILSCO TA-600-2N 3 Mechanical #2-600 Al/Cu 375 lb-in. (42 N•m)
Connector Manufacturing
Company
A1B2-600-2Mechanical
#2-600 Al/Cu 375 lb-in. (42 N•m)
3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)
1) Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2) Lug landing kit is not required for this device.3) Available by ordering kit catalog number CMELK4 (kit includes 4 lugs). Continued on next page
MP Meter-Pak™ Meter CentersApplication Data
16© 2008 Schneider Electric All Rights Reserved 03/2008
Tenant Circuit Breaker Termination Data
MPL64225
Anderson
L1D2-600Mechanical
#2-600 Al/Cu 550 lb-in. (62 N•m)
L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)
VCEL-050-12H2
Compression
2/0–500 Al/Cu VC-6FT
VCEL-060-12H2 400–600 Al or 400–500 Cu VC-6FT
VCEL-075-12H2 500–750 Al or 500 Cu VC-6FT
VACL-500-12BN 4/0–500 Al/Cu VC-6FT
VACL-600-12BN 350–600 Al or 350–500 Cu VC6-FT or VC8
VACL-750-12BN 500–750 Al or 500 Cu VC6-FT or VC8
VHCL-500-12BN 4/0–500 Cu VC6-FT or VC7-FT
VHCL-600-12BN 250–600 Cu VC6-FT, VC7-FT or VC8
ILSCO
TA-600-2N 3
Mechanical
#2-600 Al/Cu 375 lb-in. (42 N•m)
TA-800-2N 300–800 Al/Cu 500 lb-in. (57 N•m)
AU-600-2N (2) #2-600 Al/Cu 500 lb-in. (57 N•m)
Connector Manufacturing
Company
A1B2-600-2
Mechanical
#2-600 Al/Cu 375 lb-in. (42 N•m)
2AB2-600 (2) #2-600 Al/Cu 375 lb-in. (42 N•m)
3AB2-250 (3) #6-250 Al/Cu 275 lb-in. (31 N•m)
L1D2-800 300–800 Al/Cu 550 lb-in. (62 N•m)
1 Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.2 Lug landing kit is not required for this device.3 Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).
Lugs for Use with NEMA Lug Landing Kit MMSK4
Catalog NumberLug
ManufacturerCatalog Number 1 Lug Type
Lug Wire Size AWG/kcmil
Crimping Tool or Torque
MMSK4
125 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
Type and Ampere Rating Lug Wire Size
QO, QO-VH, and QOH 2-pole, 40–70 A #8–#2 AWG Al/Cu
QO, QO-VH, and QOH 2-pole, 80–125 A #4–2/0 AWG Al/Cu
200 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
Type and Ampere Rating Lug Wire Size Wire Bending Space
QOM2-MM and QOM2-MVH2-pole, 100–200 A #4 AWG–300 kcmil Al/Cu #4 AWG–250 kcmil Al/Cu 1
1 Bottom tenant circuit breaker position has wire bending space to accommodate 300 kcmil wire, for bottom feed only.
225 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
Type and Ampere Rating Lug Wire Size Wire Bending Space
QBP-TM, QDP-TM, QGP-TM, and QJP-TM,
2-pole, 70–225 A#4 AWG–300 kcmil Al/Cu #4 AWG–300 kcmil Al/Cu
Continued from previous page
MP Meter-Pak™ Meter CentersApplication Data
1703/2008 © 2008 Schneider Electric All Rights Reserved
Service Grounding/Load Neutral and Equipment Grounding Termination Data
• Service grounding/load neutral lugs, located in the tenant compartment, are bonded to the enclosure.
• Two service grounding lugs provided per device.
• One load neutral lug and one equipment grounding lug are provided for each tenant circuit breaker position.
125 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Load neutral and service grounding lugs will accept one #14-2/0 AWG Cu or one #12-2/0 AWG Al conductor.
200 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Load neutral and service grounding lugs will accept one #6 AWG–300 kcmil Al/Cu conductor.
225 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Load neutral and service grounding lugs will accept one #4 AWG–300 kcmil Al/Cu conductor.
Hinged Rain Channel
Rain channel is hinged at bottom of tenant compartment allowing easy access to wiring gutter for pulling wires.
Underground Service Wireway
Square D brand Underground Service Wireways are a convenient solution for protecting a utility's underground service conductors that terminate in MP Meter-Pak Meter Centers.
These Underground Service Wireways are not load-bearing; they are intended for use only as a means to cover and secure service entrance cables prior to entering a wall-mounted Square D MP Meter-Pak device. The units connect easily to any MP Meter-Pak Meter Center by attaching to tapped hub provisions in the bottom endwall of the metering device.
• Cover latch accommodates up to three different types of utility seals.
• All locking provisions are made of durable, corrosion-resistant stainless steel for long-lasting security.
• Mounts easily to MP Meter-Pak device’s underground, bolt-on hub provisions using supplied hardware.
• Open bottom with ½ inch srolled edge reduces possibility of cutting conductor insulation.
• Wireway covers are secured by latching means (no screws to lose).
• Gasketed, bushed openings in top provide watertight seal between the wireway and MP Meter-Pak device.
• Constructed of 14-gauge painted galvanneal steel for superior corrosion protection in all applications.
Equipment Grounding Lugs
Service Grounds and Load Neutrals
Hinged Rain Channel
MP43X11PED Shown with Cover Off (left) and
On (above)
18© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Application Data
Underground Service Wireway Devices
Catalog Number DescriptionHeight Width
in. mm in. mm
MP43X11PED Underground Service Wireway 43 1092 11 279
MP43X8PED Underground Service Wireway 43 1092 8 203
MP35X11PED Underground Service Wireway 35 889 11 279
MP12X11PEDEXT Underground Service Wireway One-foot Extension 12 305 11 279
MP12X8PEDEXT Underground Service WirewayOne-foot Extension 12 305 8 203
Selection Chart
Wireway Catalog Number
Grade to Device Bottom
Grade to Meter
MP Meter-Pak
Device
Bottom Meter
Top Meter
in. mm in. mm
MP43X8PED 25 in. [635 mm] 42.5 1080 51.5 1308
MP22125
MPR22125
MPH22125
MP43X11PED 25 in. [635 mm]
36.0 914
54.0 1372
MP33125
MPR33125
MPH33125
63.0 1600
MP44125
MPR44125
MPH44125
54.0 1372
MP55125
MPR55125
MPH55125
MP66125
MPR66125
MPH66125
37.25 946
46.25 1175
MP42200
MPR42200
MPH42200
55.25 1403
MP43200
MPR43200
MPH43200
64.25 1632
MP64200
MPR64200
MPH64200
55.25 1403
MP85200
MPR85200
MPH85200
MP86200
MPR86200
MPH86200
MP35X11PED 16.625 in.[422 mm] 50.625 1286 64.625 1642 MPL32225
MP43X11PED 25 in.[635 mm] 38.375 975 66.375 1686 MPL43225
MP35X11PED 16.625 in.[422 mm] 30.0 762 72.0 1829 MPL64225
MP Meter-Pak
Unit
Wireway Unit
Grade
MeasurementGuideWireway
Extension
Bottom of Device
Bottom Meter Height
Top Meter Height
12 in.
18 in.
Underground Service Wireway One-Foot Extension Selection Guide*
For applications requiring additional depth, or for sloped grades, the one-foot extension can be installed to the bottom of the underground service wireway with supplied hardware.
*Selection based on Underground Service Wireway catalog numbers.
Wireway Extension Catalog Number
Wireway Catalog Number
MP12X11PEDEXT MP43X11PEDMP35X11PED
MP12X8PEDEXT MP43X8PED
MP Meter-Pak™ Meter CentersCatalog Number Description
1903/2008 © 2008 Schneider Electric All Rights Reserved
Catalog Number Description
Number Segment
Character Description MP H 4 4 125
Device Name MP Meter-Pak Meter Center
Socket/Bypass Type
Blank Ring Type
R Ringless with 5th Jaw
H Ringless with Horn Bypass and 5th Jaw
L Ringless with Lever Bypass, Jaw Release and 5th Jaw
Bus Ampacity
2 200 A
3 300 A
4 400 A
5 500 A
6 600 A
8 800 A
Number of Meter Sockets
2 2-Positions MP, MPH, MPL, and MPR
3 3-Positions MP, MPH, MPL, and MPR
4 4-Positions MP, MPH, MPL, and MPR
5 5-Positions MP, MPH, and MPR
6 6-Positions MP, MPH, MPL, and MPR
Max. Tenant Circuit Breaker Amperage
125 125 A
200 200 A
225 225 A
MP Meter-Pak™ Meter Centers
20© 2008 Schneider Electric All Rights Reserved 03/2008
Select MP Meter-Pak meter center short circuit current rating RMS symmetrical amperes from table on page 3, then make selections from the following:
Step 1: Select Ring or Ringless Type MP Meter-Pak™ Meter Centers
Ampere RatingNumber of Positions
Metering Equipment
Ring-Type, 4-Jaw Catalog Number
Ringless Type, 5-Jaw
No BypassCatalog Number
Horn BypassCatalog Number
Lever Bypass Catalog Number
125 A(Use QO® Circuit
Breakers)
2 MP22125 MPR22125 MPH22125 —
3 MP33125 1 MPR33125 MPH33125 —
4 MP44125 1 MPR44125 MPH44125 —
5 MP55125 1 MPR55125 MPH55125 —
6 MP66125 1 MPR66125 MPH66125 —
200 A(Use QOM2
Circuit Breakers)
2 MP42200 1 MPR42200 MPH42200 —
3 MP43200 1 MPR43200 MPH43200 —
4 MP64200 1 MPR64200 MPH64200 —
5 MP85200 1 MPR85200 MPH85200 —
6 MP86200 1 MPR86200 MPH86200 —
225 A(Use QB, QD, QG or QJ
Circuit Breakers)
2 — — — MPL32225
3 — — — MPL53225
4 — — — MPL64225
1 Meets EUSERC standards with addition of lug landing kit, MMSK2.
Step 2: Select Tenant Circuit Breakers
DeviceType
Ampere Rating
10,000 AIR 120/240 Vac
22,000 AIR 120/240 Vac
25,000 AIR 120/240 Vac
42,000 AIR 120/240 Vac
65,000 AIR 120/240 Vac
100,000 AIR 120/240 Vac
125 A
40 QO240 QO240VH — QOH240 — —
50 QO250 QO250VH — QOH250 — —
60 QO260 QO260VH — QOH260 — —
70 QO270 QO270VH — QOH270 — —
80 QO280 QO280VH — QOH280 — —
90 QO290 QO290VH — QOH290 — —
100 QO2100 QO2100VH — QOH2100 — —
125 QO2125 QO2125VH — QOH2125 — —
200 A
100 QOM2100MM QOM2100MVH — — — —
125 QOM2125MM QOM2125MVH — — — —
150 QOM2150MM QOM2150MVH — — — —
175 QOM2175MM QOM2175MVH — — — —
200 QOM2200MM QOM2200MVH — — — —
225 A
40 QO240 2 QO240VH 2 — QOH240 2 — —
50 QO250 2 QO250VH 2 — QOH250 3 — —
60 QO260 2 QO260VH 2 — QOH260 3 — —
70 QBP22070TM — QDP22070TM — QGP22070TM QJP22070TM
80 QBP22080TM — QDP22080TM — QGP22080TM QJP22080TM
90 QBP22090TM — QDP22090TM — QGP22090TM QJP22090TM
100 QBP22100TM — QDP22100TM — QGP22100TM QJP22100TM
110 QBP22110TM — QDP22110TM — QGP22110TM QJP22110TM
125 QBP22125TM — QDP22125TM — QGP22125TM QJP22125TM
150 QBP22150TM — QDP22150TM — QGP22150TM QJP22150TM
175 QBP22175TM — QDP22175TM — QGP22175TM QJP22175TM
200 QBP22200TM — QDP22200TM — QGP22200TM QJP22200TM
225 QBP22225TM — QDP22225TM — QGP22225TM QJP22225TM2 Requires use of EZM125QOA adapter (order separately).3 Order only. Not stocked in PDS.
MP Meter-Pak™ Meter CentersProduct Selection
2103/2008 © 2008 Schneider Electric All Rights Reserved
Step 3: Choose Accessories and / or Replacement Parts
Accessories—DescriptionCatalog Number
5th Jaw Kit (one per kit) 5J
Barrel Lock Head Protector Kit (use on MPH, MPL and MPR only; barrel lock not included) MMBLC
QO Adapter for Bolt-on QB, QD, QG and QJ Tenant Circuit Breakers (40–125 A, 2-pole) EZM125QOA
Horn Bypass Kit (use on MPR and MPH only) MMHB
Manual Slider Type Bypass:
125 A Ring Type 2-Position Top Meter (only) MM125MB 1
125 A and 200 A Ring Type MM200MB 1
Sealing Rings:
Snap-type Aluminum (standard) 29209-100-01
Screw-type Aluminum 29008W
Snap-type Stainless Steel ARP00026
LEXAN® Meter Socket Closing Plate 29007
Optional Lug Kits (3 Lugs per kit):
(1) 1/0-600 AWG/kcmil or (2) 1/0-250 per phase Al/Cu MMLK250 2 3
(2) 3/0-500 AWG/kcmil per phase Al/Cu MMLK500 3
(2) 2-600 AWG/kcmil per phase Al/Cu MMLK600 3
Semi-flush Kits:
125 A, 2-Position MPSF12
125 A, 3- and 4-Position MPSF14
125 A, 5- and 6-Position MPSF16
200 A, 2- and 3-Position MPSF23
200 A, 4-Position MPSF24
200 A, 5- and 6-Position MPSF26
NEMA/EUSERC Lug Landing Kit: For 3- through 6-position 125 A and all 200 A devices.Each pad rated 600 A maximum and includes (2) 1/2-13 studs and mounting hardware.
MMSK2 3
NEMA Lug Landing Kit:For use ONLY on MPL32225, MPL53225 and MPL64225 with optional lugs (see Table on page 16 for lugs) MMSK4
1 The meter center short circuit current rating is 10,000 RMS symmetrical amperes when manual slider-type bypass is used. Not rated for continuous duty.2 Standard lug for 3- through 6-position 125 A and 2- through 4-position 200 A devices.3 Cannot be installed on 2-position 125 A devices.
MP Meter-Pak™ Meter Centers
22© 2008 Schneider Electric All Rights Reserved 03/2008
Dimensions
Supplied with ACP Closing Plate (for Underground Service).
Order Type A Hub Separately (for Overhead Service).
3.67[93]
1.97[50]
7.10[180] 0.19
[5]
12.28[312]9.37[238]
1.38[35]
24.31[617]
2.56[65]
Embossed Mounting Holes(4 Locations)
0.25 Dia. [6]
37.50[953]
9.00[229]
LinePhaseLugs 18.50
[470]
11.25[286]
8.62[219]
C, D, F
6.97[177]
3.77[96] 4.70
[119]
LineNeutralLug
12.13[308]
1.79[45]
0.83[21]
2.09[53]
1.75[44]
C, D, F
4.70[119]
3.08[78]
8.14[207]
A or B300Hub ProvisionD, F, G
A
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
MP22125MPR22125MPH22125
Mounting Feet
2.56[65]
From Top to Center of Embossed
Mounting Holes
24.31[617]
C, D, F
1.75[44] 3.77
[96]
6.97[177]
0.42[11]
Dia.
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
Dimensions: in.
[mm]
2.32[60]
0.38[10]
Dia.
0.95[24]
1.73[44]
MP Meter-Pak™ Meter CentersProduct Selection
2303/2008 © 2008 Schneider Electric All Rights Reserved
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
Supplied with ACPL Closing Plate (for Underground Service).
Order Type A–L Hub Separately (for Overhead Service).
6.07[154]
2.76[70]
24.34[618] 12.00
[305]4.87[124]
Top Position Omitted on 3-Position Unit
7.28[185](NTS)
0.75[19]
47.37[1203]
6.53[166]
LinePhaseLugs
CoverLiftingHandles
3.44[87]
Typical
48.12[1222]
9.00[229]
TypicalC, D, F
5.58[142]
24.19[614]
1.75[44]
2.29[58]
6.85[174]10.05[255]
13.50[343]
5.25[133]
2.84[72] 11.19
[284]
23.62[600]
MP33125MPR33125MPH33125
MP44125MPR44125MPH44125
A–L Hub ProvisionE, F, G, H, I, J
A–L Hub ProvisionE, F, G, H
A, B
A, B
C, D, F
3.00[76]
9.00[229]3.20
[81]
4.75[121]
1.78[45]
1.80[46]
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
Mounting Feet
0.42[11]
Dia.
Dimensions: in.[mm]
0.38[10]
Dia.
0.95[24]
1.73[44]
24© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Product Selection
N
Dimensions: in.
[mm]
Supplied with ACPL Closing Plate (for Underground Service).
Order Type A Hub Separately (for Overhead Service).
6.00[152]
3.00[76]
14.92[379]
2.99[76]
1.75[44]
15.23[387]
39.46[926]
4.70[119]
12.00[305]
7.36[187]
2.76[70]
Top Position Omitted on 5-Position Unit
LinePhaseLugs
CoverLiftingHandles
3.44[87]
Typical
C, D, F
2.95[75]
2.65[67]
42.37[1076]
23.62[600]
9.00[229]
Typical
11.19[284]
20.75[527]
5.85[149]
7.75[197]9.05[230] 36.31
[922]
3.02[77]
6.22[158]
9.42[239]
7.28[185](NTS)
0.75[19]
41.62[1057]
6.53[166]
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
2.61[66]
18.02[458]
3.20[81]
C, D, F
A, B
3.20[81]
A
15.07[383]
A-L Hub ProvisionG, H, I, J
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
0.42[11]
Dia.
1.73[44]
0.95[24]
Mounting Feet
MP55125MPR55125MPH55125
MP66125MPR66125MPH66125
0.38[10]
Dia.
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
MP Meter-Pak™ Meter CentersProduct Selection
2503/2008 © 2008 Schneider Electric All Rights Reserved
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
Supplied with ACPL Closing Plate (for Underground Service).
Order Type A Hub Separately (for Overhead Service).
9.70[246] 3.70
[94]
2.58[66]
29.44[748]
7.25[184]
8.28[210](NTS)
C, D, F
7.53[191]
LinePhaseLugs
LineNeutralLugs 9.00
[229]Typical
12.22[310]
24.62[625]
28.00[711]
31.50[800]
43.41[1103]
2.25[57]
2.70[69]
29.31[744]
12.15[309]
6.10[155]
12.55[319]
8.38[213]
MP42200MPR42200MPH42200
MP43200MPR43200MPH43200
C, D, F A, B
1.94[49]
2.66[68]
15.48[393]
3.33[85]
(Typ.) 9.20[234]
10.41[264]
3.04[77]
A-L Hub ProvisionG, H, I, J
0.75[19]
42.66[1084]
Top Position Omitted on 2-Position Unit
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
0.42[11]
Dia.
1.73[44]
0.95[24]
Mounting Feet
0.38[10]
Dia.
3.00[76]
Dimensions: in.
[mm]
26© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Product Selection
Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately
(for Overhead Service). 9.70[246] 3.70
[94]
0.75[19]
29.31[744]
2.58[66]
29.44[748]9.82
[249]7.36[187]
8.25[210](NTS)
LinePhaseLugs
LineNeutralLugs
C, D, F
52.00[1321]
28.00[711]
9.00[229]Typ.
12.22[310]
24.62[625]
31.50[800]
51.25[1302]
7.53[191]
8.38[213]
12.55[319]5.85
[149]
2.23[57]
5.65[144]
2.45[62] 12.15
[309]
10.37[263]
C, D, FA, B1.94
[49]
2.66[68]
3.33[85]
(Typ.)15.48[393]
3.00[76]
9.20[234]
MP64200MPR64200MPH64200
Dimensions: in.
[mm]
A-L Hub ProvisionG, H, I, J
3.04[77]
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
0.42[11]
Dia.
0.38[10]
Dia.
1.73[44]
0.95[24]
Mounting Feet
MP Meter-Pak™ Meter CentersProduct Selection
2703/2008 © 2008 Schneider Electric All Rights Reserved
20.12[511]
2.66[68]
6.20[68]
0.42 Dia.[11]
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Seal Bracket
0.10[3]
Dia. 0.10[3]
x 0.40[10]
Slot
0.42[11]
Dia.
0.38[10]
Dia.
1.73[44]
0.95[24]
Mounting Feet
Supplied with ACPL Closing Plate (for Underground
Service). Order Type A-L Hub Separately (for Overhead Service).
26.34[669]20.34
[517]
2.58[66]
46.68[1186]
9.82[249]
7.36[187]
12.00[305]
9.82[249]Top Left
Position Omitted on 5-Position Unit
LinePhaseLugs
LineNeutral
Lugs
C, D, F
8.28[210](NTS)
0.75[19]
42.66[1084]
7.53[191]
43.41[1321]
28.25[718]
9.00[229]Typ.
12.22[310]
24.50[622]
31.50[800]
2.23[57]
2.95[75]
6.35[161]
8.60[218]
29.25[743]
46.56[1183]
5.00[127]
10.81[275]
14.20[361]
C, D, F A, B, CA-L Hub ProvisionG, H, I, J
3.33[85]
(Typ.)
4.53[115]
1.93[49]
MP85200MPR85200MPH85200
MP86200MPR86200MPH86200
3.04[77]
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
Dimensions: in.
[mm]
12.15[309]
28© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Product Selection
Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately
(for Overhead Service).
8.36[212]
2.62[67]
2.81[71]
19.43[494]
Cover Knockout for use with Utility Barrel Lock
Individual Meter Socket Covers; Ringless Style (Supplied with Cover Sealing Latches)
C, D, E, F
60.25[1530]
14.00[356]
34.00[864]
26.76[680]
7.10[180]
2.20[56]
3.25[83]
4.12[105]
10.47[266]
4.43[113]
LineNeutralLugs
21.87[556]
5.72[145]
9.62[244](NTS)
0.34[9]
1.50[38]
0.75[19]
To Top of Mounting Channel
Mounting Channel Detail
0.42[11]
Dia.
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
(2) 1/2–13 Studs
1.75[44]
1.75[44]
C, D, E, FA, B
3.00[76]
8.87[225]
5.34[138]
1.89[48]
4.50[114] 1.87
[48]5.37[136]
9.00[229]
5.93[151]
2.68[68]
A-L Hub Provision E, F, G, H, I, J
Tenant Circuit Breaker Doors (Lockable)
Dimensions: in.
[mm]
Lug Detail
MPL32225
LinePhase Lugs
Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
0.95[24]1.73
[44]
0.38[10]
Dia.
Mounting Foot
Seal Bracket
0.13[3]
Dia. 0.10[3]
x 0.50[13]
Slot
0.44[11]
Dia.
MP Meter-Pak™ Meter CentersProduct Selection
2903/2008 © 2008 Schneider Electric All Rights Reserved
Dimensions: in.
[mm]Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
9.68[246] 0.34
[9]
1.50[38]
0.75[19]
To Top of Mounting Channel
Mounting Channel Detail
0.95[24]
1.73[44]
0.38[10]
Dia.
Mounting Foot
Seal Bracket
0.13[3]
Dia. 0.10[3]
x 0.50[13]
Slot
0.44[11]
Dia.
0.42[11]
Dia.
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately
(for Overhead Service).
11.30[287]
4.80[122]
MPL53225
2.75[70]
35.37[898]
10.87[276]
Tenant Circuit Breaker Doors (Lockable)
53.12[1349]
LinePhaseLugs
LineNeutralLugs
28.10[714]
24.10[612]
17.62[448]
14.00[356]
13.32[338]
6.32[161]
3.20[81]
C, D, E, F
Individual Meter Socket Covers: Ringless Style (Supplied with Cover Sealing Latches}
26.40[671]
4.50[114]
2.53[84]
10.10[257]
13.90[353]
C, D, E, FA-L Hub Provision E, F, G, H, I, J35.25
[895]6.00[152]
2.11[54]
2.07[53] 5.86
[149]9.65[245]
13.44[341]
2.84[72]
10.25[260]
4.05[103]
A, B 3.11[79]
Cover Knockout for use with Utility Barrel Lock
30© 2008 Schneider Electric All Rights Reserved 03/2008
MP Meter-Pak™ Meter Centers Product Selection
Supplied with ACPL Closing Plate (for Underground Service). Order Type A-L Hub Separately
(for Overhead Service)
11.30[287]
2.75[70]
4.80[122]
35.37[898]
67.37[1711]
31.62[803]
38.50[978]
41.87[1064]
Tenant Circuit Breaker Doors (Lockable)
Cover Knockout for use with Utility Barrel Lock
Individual Meter Socket Covers; Ringless Style (Supplied with Cover Sealing Latches)
2.53[64]C, D, E, F
3.20[81]
7.00[178]
LinePhaseLugs
LineNeutralLugs
14.00[356]
13.32[338]
26.40[671]
4.50[114]
13.90[353]
10.10[257]
6.32[161]
35.25[895]
C, D, E, FA–L Hub ProvisionE, F, G, H, I, J
A, B
2.11[54]
6.00[152]
2.07[53] 5.86
[149]9.65[245] 13.44
[341]2.84[72]
10.25[260]
4.05[103]
3.11[79]
1.73[44]
0.95[24]
0.38[10]
Dia.
Mounting Foot
Seal Bracket
0.13[3]
Dia.
0.44[11]
Dia. 0.10[3]
x 0.50[13]
Slot
0.42[11]
Dia.
0.09 Dia.[2]
0.09[2] x 0.33
[8]Slot
Ringless Cover Latch
9.68[246](NTS)
0.34[9]
1.50[38]
0.75[19]
To Top of Mounting Channel
Mounting Channel Detail
MPL64225
Dimensions: in.
[mm]Knockouts
SymbolConduit Size Hole Diameter
in. mm in. mm
A 0.50 13 0.88 22
B 0.75 19 1.25 32
C 1.00 25 1.38 35
D 1.25 32 1.75 44
E 1.50 38 2.00 51
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.63 92
I 3.50 89 4.13 105
J 4.00 102 4.63 118
MP Meter-Pak™ Meter CentersProduct Selection
3103/2008 © 2008 Schneider Electric All Rights Reserved
125 A DevicesFifth Jaw
Factory Installedon Ringless Device
N
Neutral,Service Groundand Equipment
Grounding Terminals
MP22125MPR22125MPH22125
Omitted on 3-Position Unit
Omitted on 5-Position Unit
MP33125MPR33125MPH33125
MP44125MPR44125MPH44125
MP55125MPR55125MPH55125
MP66125MPR66125MPH66125
NLine
EquipmentGroundingTerminals
Neutral andService Ground
N
Line
EquipmentGroundingTerminals
Neutral andService Ground
Fifth JawFactory Installed
on Ringless Device
Fifth JawFactory Installed
on Ringless Device
MP64200MPR64200MPH64200
N
Line
EquipmentGroundingTerminals
Neutral andService Ground
Fifth JawFactory Installed
on Ringless Device
Fifth JawFactory Installed
on Ringless Device
Fifth JawFactory Installed
on Ringless Device
Omitted on 2-Position Unit
Omitted on 5-Position Unit
MP42200MPR42200MPH42200
MP43200MPR43200MPH43200
MP85200MPR85200MPH85200
MP86200MPR86200MPH86200
NLine
EquipmentGroundingTerminals
Neutral andService Ground
N
Line
EquipmentGroundingTerminals
Neutral andService Ground
200 A Devices
Neutral and ServiceGrounding Terminals
Line
Equipment GroundingTerminals
Equipment GroundingTerminals
Neutral and ServiceGrounding Terminals
Line
Line
Equipment GroundingTerminals
Neutral and ServiceGrounding Terminals
225 A Devices
ø ø
ø ø
ø ø
ø
ø
ø ø
ø ø
ø ø
ø
ø
ø ø ø ø
ø ø
ø ø
ø ø
ø ø
øø
ø
ø
øø
øø
øø
øø
øø
ø
ø
øø
øø
øø
øø
ø
ø
øø
øø
øø
ø ø
ø ø
øø
øø
øø
øø
øø
øø
ø ø
øø
øø
øø
MPL32225 MPL53225MPL64225
4141CT0701 © 2008 Schneider Electric All Rights Reserved
Schneider Electric USA1601 Mercer RoadLexington, KY 40511 USA1-888-SquareD (1-888-778-2733)www.us.SquareD.com
Schneider Electric Canada19 Waterman Avenue,M4B 1 Y2Toronto, Ontario1-800-565-6699www.schneider-electric.ca
03/2008
Square D, [D], Meter-Pak, and QO are trademarks or registered trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries. Other marks used herein may be the property of their respective owners.