LED LAMP TYPESaving Energy Implementation
>
2
PHILIPS – LED LAMP TYPE
NOVOTEL SEMARANG has been using LED lamp PHILIPS type :
• LED String White 6300K medium voltage for replace neon cathode lamp with high voltage balast at neon sign roof
• LED String Standard WW (15m/RL)for replace all fluorescent lamp 36w at Lobby, Mezzanine andall Meeting Room
• MASTER LED 7w GU10wwfor replace all halogen lamp 50w at Room and Public Area (corridor & toilet)
>
3
LED STRING WHITE 6300K MEDIUM VOLTAGE
• Location : neon sign at roof
• Technical information :- 2 unit @ 360 w => total 720 w- life time hours 50. 000 hrs - lumen 160 lm
• Saving implementation :- Before = 2 unit @ 10.450 w => total 20.900 w- After = 2 unit @ 360 w => total 720 w
- Saving = 20.900 – 720 x 100 % 20.900
= 96 %
Could you explain or provide a
picture of the 2 unit @ 10.450 W ?
>
4
LED STRING WHITE 6300K MEDIUM VOLTAGE
• Sample installation :
HATI HATI – the new standard is a WHITE LIGTHING
>
5
LED STRING STANDARD WW (15M/RL)
• Location : Lobby, Mezzanine and all Meeting Room
• Technical information :- 62 pcs@100 w + 31 pcs@60 w => total 5.066 w- life time hours 20. 000 hrs - lumen 67,5 lm
• Saving implementation :- Before = 574 pcs@36 w + 35 pcs@18 w => total
21.294 w- After = 62 pcs@100w + 31 pcs@60w => total
5.066 w - Saving = 21.294 – 5.066 x 100 %
21.294= 62,15 %
You are replacing FLC light by STRING light ?
According to our meeting :-You should not change the
Design-- keep the same quality of
light (Lum and LUX)
Show a Picture of a FLC
>
6
LED STRING STANDARD WW (15M/RL)
• Technical installation :
Wood
0,14 x 420 led = 58,8 watt max / 60 watt daya adaptor
0,14 x 700 led = 98 watt max / 100 watt daya adaptor
0,14 WLED 24Vdc
Could you provide a picture of the
lobbyBefore and After to see the LOOK
>
7
MASTER LED 7W GU10WW
• Location : Room and Public Area (toilet and corridor)
• Technical information :- 979 pcs @ 7 w => total 6.853 w- life time hours 50. 000 hrs - lumen 150 lm
• Saving information :- Before = 979 pcs @ 50 w => total 48.950 w- After = 979 pcs @ 7 w => total 6.853 w
- Saving = 48.950 – 6.853 x 100 % 48.950
= 86 %
>
8
MASTER LED 7W GU10WW
220VAC
>
9
TOTAL KWH CONSUMPTION
Difference total KWH consumption after using LED type :
MONTH
KWH 2008
ROOM SOLD 2008
KWH
2009
ROOM SOLD 2009
SELISIH
KWH
Jan 276.752 3.293 232.
000 2.98344.752 (↓)
Feb 251.600 3.506 212.
800 2.88638.800 (↓)
Mar 266.416 3.693 252.
800 3.14613.616 (↓)
Apr 272.336 3.859 243.
200 3.01329.136 (↓)
Mei 276.400 3.836 252.
800 3.29523.600 (↓)
Jun 274.272 3.723 251.
200 4.19723.072 (↓)
Jul 283.280 4.116
Agu 273.696 4.098
Sep 225.040 2.715
Okt 263.984 3.636
Nov 311.920 3.641
Des 261.056 3.856
In my opinion, you should compare the Savings between
same occupancy.Comparing Jan 2008 vs 2009 provides big savings because of the occupancy difference.Jan2008-Mai2009= 25,000
KwH is more realistic
>
10
ELECTRICITY CONSUMPTION (2008 – 2009)
Jan Feb Mar Apr Mei Jun Jul Agu Sep Okt Nov Des200,000
250,000
300,000
350,000
20082009
Start replacement Roof Signage lamp with LED
String (January
2008)
Start replacement all Halogen Lamp with
Halogen LED 7w
(December 2008)
Start replacement all TL lamp with LED
String Lamp(January
2009)
What’s happened here ?You should show the Occupancy as well for a better
analysis
>
11
THE STRENGTH & THE WEAKNESS
A. Strength :1. Life time longer 45. 000 Hrs 2. Easy installation3. Lumen ( 150 lumen )4. Save 80 – 90 % energy
B. Weakness :1. Expensive2. For replacement should be replace fitting also ( Halogen type )3. For streaming type make new installation for replacement
fluorescent Type lamp
What means “Streaming” ? Please explain
>
12
GREEN GLOBE PROGRAM
1. Saving energy
2. Reduce quantity waste for lamps
3. Not using gas like Neon, Mercury etc at list friendly with environment
>
13
GREEN GLOBE PROGRAM
FOLLOWING OUR Chief Engineer Meeting and the Presentation of the work we are doing with PHILIPS, each time you want to change lighting, you should ask yourself :
• Am I going to change the Design ? Take a picture Before and After
• What is the lighting ambiance I should keep ? LUX and LUMEN per sqm or else(contact Philips for help to mesure)
• If I use FLC or Halogene or other Lamp producing “Dangerous Gas” : How I will handle the used Bulbs after (Recycle ? Give to a specialized company ?)
• Try to set up a Grid of Return of Investment with the help of the Supplier (philips) is recommended of course)Take into consideration the REAL TIME the light is SWITCHED ON (24 HOURS is only for some specific public areas)
OUR COMMENTS
>