Top Banner

of 67

Very GOOD Condition Monitoring Transformers

Jun 04, 2018

Download

Documents

martinez_josel
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    1/67

    Working principle of a

    transformer A transformer is static (or stationary) piece of

    apparatus which:

    1.Transfers electric power from one circuit toanother.

    2.It does so without a change in frequency.

    3.The principle is based on mutual inductionbetween two circuits linked by a commonmagnetic flux.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    2/67

    Basic parts of a transformer Basically a transformer consists o f a :

    1.A primary coil or winding.

    2.A secondary coil or winding.

    3.A core that supports the coils or thewindings

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    3/67

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    4/67

    Transformer construction

    Main constructional elements of Transformers are -

    A) Magnetic circuit Core & clamping structure

    B) Electric Circuit Winding,Insulation, Bracing devices.

    C) Terminals Tapping, Tapping switches, Terminal

    Insulator, Leads , Bushings

    D) Tank Oil, Cooling devices, conservator, piping,

    Breather

    E) Protective Circuit Buchholz relay, WTI, OTI, Oil surge relay

    & Monitoring pressure relief device, MOG

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    5/67

    Transformer construction

    A)Magnetic Circuit:

    The core provides closed path for flux. It is made up of CRGOinsulated laminations. (CRGO has iron loss of about 1.3 W / Kg at1.6 Tesla )

    B)Electric Circuit:

    Winding, insulation & bracing are constructional parts of electricalcircuit of transformers. This is the most vulnerable part oftransformer because of direct association with power system. Must

    be designed to withstand voltage stress resulting from systemfault, transient over voltage and thermal stresses (lightening orswitching surges)

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    6/67

    Transformer construction

    Insulation:

    Commonly used material are -

    Paper or press board

    Oil is used as insulating medium

    Insulating varnish applied to make coil mechanicallystrong.

    C) Terminal:

    Leads:

    Connection of winding are (copper rod or bus bar) taken tobushing.

    Bushing:

    Up to 33 kV porcelain bushing are used. Above 33 kV,condenser & oil filled terminal bushings are used.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    7/67

    Transformer construction

    D) Transformer tank

    Cooling:

    Small transformers are air cooled whereas large transformers

    are provided with oil or oil & air cooling .The transformer tank is designed to withstand full vacuum.

    Types of Cooling:

    Air insulated air cooledAN Air Natural

    AF Forced Air Cooling

    ANAN Natural Air cooling inside and outside transformer

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    8/67

    Transformer construction

    Oil immersed air cooled -

    ONAN Natural Oil Circulation. Natural Air flow

    ONAF Natural oil and forced air flow

    OFAN Forced Oil & Natural Air CirculationOFAF Forced Oil and Forced Air Circulation

    Oil immersed & water cooled

    ONWF Natural Oil, water (internal) coolerOFWF Forced oil, water (external) cooler

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    9/67

    Transformer construction

    E) Protective devices :

    Various protective devices mounted on transformer are asfollows:

    Bucchholz Relay Gas actuated relay, Transformer

    Internal fault.WTI/OTI Provided for alarm and / OR trip

    against over load

    PR Device To release internal pressure

    generated in the transformer

    during fault.MOG Alarm when oil level is low

    Oil Surge Relay To release actual pressure

    generated during fault in OLTC

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    10/67

    Accessories & their functions

    Terminal & Bushing : Type of Bushing, terminal is selecteddepending on voltage, currents & operating conditions. Porcelain,condenser type of oil filled bushings are used as per requirement.

    Cable Boxes : Cable boxes are primarily designed for receiving

    and protecting cable ends and ensure effective sealing of cableagainst ingress of moisture.

    Conservator : It is provided to accommodate change in oilvolume caused due to change in loads or ambient conditions.

    Breather :Whenever there is change in ambient temperature orload , there is a change in oil temperature and hence the volume ofoil. Increase in volume causes the air above oil level in conservatorto be pushed out and decrease causes air to be drawn in. Thusthe transformer breathes.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    11/67

    Accessories & their functions

    When air is breathed in, moisture and dust fromatmosphere is sucked in .

    Silica gel crystals absorb moisture. Color of silica gel

    is blue when dry and turns pink when absorbsmoisture. Oil cup at the bottom is filled with oil which acts as

    coarse filter and removes dust form outside air. Magnetic Oil Level gauge:

    This is a dial instrument operated by magneticcoupling from a float on oil surface. It is normally fitted with contact to give alarm for low

    oil level.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    12/67

    Accessories & their functions

    Oil temperature indicator:Bourdon tube with a pointer arrangement mounted in a casecomprising of a reading dial and a glass cover. There is atemperature sensing bulb which communicates to the bourdontube through the armored capillary.

    Winding temperature indicator:It comprises of following:WTI pot :mounted at top of transformer tank. Oil in pot is temp. of topoil.Imae coil:Heater coil and develops additional hear raising temperature ofoil incide heater coil.

    WTI CT:Mounted on one of the line lead with secondary connected to image coilWTI: The bulb of the WTI is immersed in oil inside image col.Temperature of this oil is dependent on top oil temperature and load ontransformer.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    13/67

    Accessories & their functions

    Buchholz Relay : Gas & oil operated relay detects formation ofgas or development of sudden pressure inside the oil of transformer.

    Any electrical fault inside the transformer is accompanied byevolution of gas.

    Pressure Relief Device: This is provided to relieve the internalpressure in the event of major fault within the transformer.

    Tapping Switch: To maintain secondary voltages reasonablyconstant at load end when incoming voltage and/or load ontransformer changes, it is necessary to change the voltage ratio (I.e,

    turns ratio of the winding) of the transformer.This is achieved by changing the number of turns ( HT Side) byoperating a switch called as tapping switch.

    Depending on the requirement, off circuit or on load tapchangeris installed in the transformer.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    14/67

    Accessories & their functions

    Radiators:The function of radiator is to limit the temperature of oil and winding bydissipating heat that is generated due to losses within transformer while inservice. When transformer is in operation warm oil rises and enters the radiatorfrom the top valve cools and then descend to enter the bottom of thetank.

    Other Accessories: Inspection cover, jacking lugs, Earthing terminals,Rating Plate, Filter valve, Drain Valve, Terminal marking, Rollers etc.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    15/67

    DGA Insulating materials within transformer breakdown to

    liberate gases.

    The identity of these gases indicate the type of fault

    and the rate of gas generation indicate the severityof fault.

    Causes of fault gases can be divided into threecategories:

    Corona or partial discharge

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    16/67

    DGA

    Pyrolisis or thermal heating

    Arcing

    Arcing is the most severe fault (intensity of energythat is dissipated per unit time per unit volume ofthe fault) ,less with heating, least with corona.

    One of the most important technique to indicate thehealth of a transformer.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    17/67

    Major (Minor) fault gases undervarious fault conditions

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    18/67

    Sampling And Labeling ProcedureSampling

    Dry Weather, avoid contamination

    Clean, dry, leak proof glass or stainless steelcontainer.

    Equipment operating normally

    Take safety precautions.

    Sample bottle must be full without any air trapcompletely sealed and should be properly labeled.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    19/67

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    20/67

    FREQUENCY OF SAMPLING

    NEW TRANSFORMERS

    FIRST DGA TEST : BEFORE HEAT RUN TEST ONTRANSFORMER

    SECOND DGA TEST : AFTER HEAT RUN TEST ONTRANSFORMER (2&24 HRS)

    THIRD DGA TEST : BEFORE ENERGIZINGTRANSFORMER (B.M.)

    FOURTH DGA TEST : WITHIN THREE MONTHS OFSERVICE

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    21/67

    FREQUENCY OF SAMPLING

    IN-SERVICE TRANSFORMERS

    ANNUALLY AS A ROUTINE CKECKING

    BEFORE (LATEST DATA) & AFTER FILTRATION/TOPPING UP

    TRANSFORMERS AFTER OVERHAULING,

    REPAIRS, MAINTANANCE

    BEFORE ENERGISING TRANSFORMER

    WITHIN THREE MONTHS OF SERVICE

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    22/67

    Interpretation of Results

    Ensure that gas concentrations are highenough to warrant further investigation.

    Gas being present even in normal operatingcondition without any fault being present.

    Gases might have formed on the occasion ofprevious faults or during repairs by brazing,

    welding etc., and not completely removed. Since gases are produced in normal ageing

    also, the service duration of the oil has to betaken into account.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    23/67

    PERMISSIBLE LIMITS OF DISSOLVED GASES IN

    OIL OF A HEALTHY TRANSFORMER

    GAS 10 YRS (PPM)

    H2 100-150 200-300 200-300CH4 50-70 100-150 200-300

    C2H2 20-30 30-50 100-150

    C2H4 100-150 150-200 200-400

    C2H6 30-50 100-150 800-1000

    CO 200-300 400-500 600-700

    CO2 3000-3500 4000-5000 9000-12000

    GAS 10 YRS (PPM)

    H2 100-150 200-300 200-300

    CH4 50-70 100-150 200-300

    C2H2 20-30 30-50 100-150

    C2H4 100-150 150-200 200-400

    C2H6 30-50 100-150 800-1000

    CO 200-300 400-500 600-700

    CO2 3000-3500 4000-5000 9000-12000

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    24/67

    Condition monitoring oftransformer oil

    Role of transformer oil: It is used as coolant. It is used as insulating material.

    Reasons for deterioration of transformer oil

    Physical contamination: Release of fibrous impurities by paper, pressboard, wood and

    cotton tapes in contact with oil for longer period at elevatedtemperatures.

    Due to dissolution of varnish . Due to foreign matters like dust, metallic particles and other

    solid impurities Due to moisture

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    25/67

    Condition monitoring oftransformer oil

    Effects:

    Life is reduced by high sludge formation.

    Electrical properties of insulating oil get disturbed dueto conductivity of suspended particles.

    Chemical deterioration:

    It is due to oxidation.

    Effects of oxidation:

    Results in acids, sludge .Acid attack solid insulationand metal. Sludge causes poor thermal conductionand mechanical hindrance to proper oil circulation.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    26/67

    Condition monitoring oftransformer oil

    Contamination of gases:

    Gases are present in oil due to following:

    Those which dissolve in the oil from atmosphere.

    Those which are generated inside due to thermaldecomposition of oil, decomposition of oil by arcing.

    Effects of gases:

    The ignition of inflammable gases can be causes by

    corona occurring in th air space or arcing.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    27/67

    Transformer oil testing

    Transformer oil testing is carried out to detectabnormalities in transformer and based on test results

    corrective actins can be taken before actual failure takesplace.

    To evaluate quality of oil

    To decide periodic maintenance (filtration. reclamation

    etc) To know health of transformer (by DGA)

    To estimate remaining life of transformer

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    28/67

    Oil Testing

    New oil (IS-335)- 15 tests

    Oil in service (IS-1866)- 8 tests

    Dielectric strength (BDV)

    Dielectric dissipation factor (Tan delta)

    Resistivity Neutralisation value (Acidity)

    Flash point

    Water content

    Sludge

    Interfacial tension

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    29/67

    Transformer oil testing

    1.Physical condition of the oil:Color ,clarity and odour gives information regardingquality of oil and presence of certain contaminants in

    oil.2.Electrical strength:

    Important parameter as used as insulating medium.This test gives conductive contaminants and moisturepresent in oil.

    3.Water content:Reveals total water content ,leak or cellulosicdeterioration

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    30/67

    Transformer oil testing

    4.Specific resistance (Resistivity):This test provides a measure of the total soluble contaminants andageing products .It is numerically equal to the resistance betweenopposite faces of a centimeter cue of the oil and is expressed asohm com.

    5.Dissipation factor:This test provides a measure of the total soluble contaminantsand ageing products.

    6.Neutralisation value:This test gives acid present in the oil. It is the no. of milligrams ofpotassium hydroxide required to neutralise completely the acidsproduced in one gram of oil.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    31/67

    Transformer oil testing

    7.Interfacial tension test:

    This test provides a measure of sludge and

    polar component present in oil. It isexpressed as molecular attractive forcebetween the molecules of water and oil atoil-water interface.

    8.Flash point:Sudden drop in flashpoint is indicative ofunsafe working condition of transformer.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    32/67

    Scheduled of oil characteristics for transformerin service as per IS : 1866-2000

    Property Highest Voltage of equipment, kV

    < 72.5 72.5 to 170 > 170

    Breakdown voltage (kV),

    Min.

    More than

    30

    More than 40 More than

    50

    Water content (ppm),Max.

    Max. 95 Max. 40 Max. 20

    Neutralization value (mgKOH/g), Max.

    Max. 0.3 Max. 0.3 Max. .0.3

    Sediment & Sludge, %by mass

    ND ND ND

    Resistivity @ 90C x 1012

    (ohm-cm), Min.0.1 x 1012 0.1 x 1012 0.1 x 1012

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    33/67

    Property Highest Voltage of equipment, kV

    < 72.5 72.5 to 170 > 170

    Dielectric dissipationfactor @ 90C, Max.

    1.0 1.0 0.2

    Interfacial tension(mN/m), Min.

    15 15 15

    Flash Point, (C), Min. 125 125 125

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    34/67

    Condition Monitoring - Oil testing

    Sr. No. Test Remedial Action for

    Deviations from

    permissible limits

    1 Electric strength 2.5

    mm gap (Break downvoltage)

    Oil filtration

    2 Water content Oil filtration

    3 Sediment and / or

    precipitable sludge

    Oil filtration

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    35/67

    Condition Monitoring - Oil testing

    Sr.

    No.

    Test Remedial Action for Deviations

    from permissible limits

    4 Specific resistance

    (Resistivity at 90 deg.C

    Oil filtration if the tan value

    permits other wise replace the oil

    5 Dielectric dissipation factor (

    tan )

    Replace the oil

    6 Neutralisation value (total

    acidity) of the oil

    Replace the oil

    7 Inter facial tension of the oil

    against water at room

    temperature

    Replace the oil

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    36/67

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    37/67

    Furanic compound test

    When oil soaked paper is damaged by heat, some oilsoluble compound are released into oil called furans.

    Paper is made of cellulose consisting of log chains ofglucose rings joined by glycosidic bonds.

    During degradation bonds are broken and glucose

    rings are opened. Glucose is unstable which furtherdegrades which are more stable and oil soluble calledfurans.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    38/67

    Furanic Compounds

    The most commonly found furanic derivative is 2-furfuraldehyde(2 FAL) and other derivatives are

    2- furfuryl alcohol (2 FOL) ,

    2- Acetyl furan (2 ACF),

    5- hydroxymethyl furfuraldehyde,(5HMF)

    5 methyl furfuraldehyde(5MEF).

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    39/67

    FURANS AND GASES

    Cellulosedegradation=Glucose+H2O+CO+CO2+Organic acids.

    With DGA and furan test extent of paper damage can

    be seen. CO and CO2 are determined by DGA and are

    considered as level indicator for cellulosicdegradation.

    In case of severe localised paper damage ,high

    furans and high gas content can be seen. In case general heating slow building of furans

    without necessarily seeing an increase of gascontent.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    40/67

    Degree of polymerization (DP)

    Degree of polymerization (DP) is another way ofexpressing the molecular weight. Physical propertiesof the paper depends on the degree ofpolymerization of paper

    M = Dp x mWhere

    M= molecular weight of the polymer

    Dp = the degree of polymerization

    and m = the molecular weight of monomer.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    41/67

    Degree of polymerization (DP)

    DP value 1000 to 1500 i.e,1000 to 1500glucose units are present in cellulose

    molecule. Degradation of paper is due to temperature,

    water ad oxygen.

    When DP value

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    42/67

    Correlation between Dp and Furan

    The absolute correlation of Furan to DP isdifficult, but can be related fairly accuratelyextent through an empirical formula.

    Dp = - 100 ln (2 FAL) +709

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    43/67

    INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS

    These tests are performed to verify state ofdryness if insulation.

    These tests are intended to check overallcleanliness ,dryness ,localized defects and generalcondition of insulation system.

    When DC voltage is applied across insulation, thecurrent flows is the resultant of three currents:

    Capacitive charging current

    Absorption current

    Leakage current

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    44/67

    RL

    RA

    C

    DC Voltagesource

    S

    Absorption currentConduction or leakagecurrent

    Capacitance charging current

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    45/67

    INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS

    Capacitance leakage current:

    The current lasts for a few seconds as DC voltage isapplied and drops out after the insulation is chargedto its full voltage. The time depends on the size andcapacitance of the test object. Larger time for largercapacitance objects.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    46/67

    INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS

    Absorption leakage current: It is caused by polarisation of molecules within

    dielectric material.

    In low capacitance equipments the current is high forfirst few seconds and decrease slowly to nearly zero.

    In high capacitance equipment or wet andcontaminated insulation ,there will be no decrease of

    absorption current for long time.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    47/67

    Conduction or leakagecurrent:

    Conduction or leakage current

    This is the current that normally flows through the

    insulation ,between conductors or conductors toground.

    It increases quickly and becomes stable. This current increases as insulation deteriorates and

    becomes predominant after absorption current

    vanishes. It is steady and time independent .Hence the

    important current for measuring insulation resistance.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    48/67

    Interpretation of results:

    If IR value shows a decreasing trend it showsgradual deterioration of insulation quality due tohumidity ,dust accumulation etc..

    A very sharp drop indicates insulation failure.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    49/67

    IR MEASUREMENTS

    THE TEST VOLTAGES FOR IR MEASUREMENT OF

    TRANSFORMER ARE AS UNDER.RATING TEST VOLTAGE

    415/440 V 500 V

    3.3 kV 1000 V

    6.6 kV 2500 V

    11 kV & ABOVE 5000 V

    THE MINIMUM ACCEPTABLE LOWER LIMIT FORIR VALUES IS GIVEN IN STANDARDS AS

    V L-L+ 1 M

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    50/67

    Polarisation indexmeasurements

    Polarisation Index=600sec IR value/60 sec IR value

    PI

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    51/67

    STEP VOLTAGE TEST

    The DC voltage is applied in various steps and ineach step the leakage current is noted. Stepduration:60 seconds.

    The variation of this leakage current (or IR) with testvoltage gives the condition of insulation.

    If insulation is dry, clean and with out physicaldamages shall show the same value at all voltagelevels.

    If insulation value decreases at higher voltage levels,may be due to dirt, moisture, cracking, aging etc. The application of increased voltage creates electrical

    stresses on internal insulation cracks. This can revealaging and physical damage in relatively clean and dryinsulation which would have not been apparent atlower voltages.

    CAPACITANCE MEASUREMENTS

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    52/67

    CAPACITANCE MEASUREMENTS

    THE CAPACITANCE VALUE IS DEPENDENT ON THE CHARACTERISTICS OF THE DIELECTRIC MATERIAL THE PHYSICAL CONFIGURATION OF THE ELECTRODES

    A C =

    d Void /impurities may discharge partially during a voltage apicationand the effective distance between eectrodes ncreases. HENCE C WILL INCREASE WITH INCREASE IN VOLTAGE,

    WHICH INDICATES PRESENCE OF PD AND THE DETERIORATION

    OF INSULATION

    A

    d

    ELECTRODE

    ELECTRODE

    DIELECTRIC

    TAN MEASUREMENTS

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    53/67

    TAN MEASUREMENTS

    THE TAN VALUE DIRECTLY INDICATES THE POWERDISSIPATED BY THE INSULATION

    IT INCREASES WITH INSULATION DETERIORATION ANDSERVES AS AN EARLY INDICATOR OF FAILURE HAZARDS

    90

    Ic

    Ic

    v v

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    54/67

    Concept of Tan

    In an ideal capcitor the voltage and currentare phase shifted by 90 deg.and current

    through insulation is capacitive. If there are impurities in insulation,the

    resistance of insulation decrease resulting inincrease of resistive current.

    Thus the total current I = Ic + Ir which leadsthe voltage by a phase angle < 90. Andlags the Ic by an angle .

    2 0 .4

    3 0 .6

    4 5 .9

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    55/67

    The tangent of this angle directlyindicates the heat dissipation that takes

    place inside the dielectric material.

    The values obtained on new insulationforms the reference value for periodic

    measurements.

    P ti l di h

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    56/67

    Partial discharge:

    It is an electrical discharge that occurs acrossa portion of the insulation between two

    conducting electrodes without completelybridging the gap.

    This results in localized, nearly instantaneousrelease of energy.

    The most convention unit for quantifying thePD quantity is Pico coulomb

    I t t ti f lt

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    57/67

    Interprtation of results:

    High value of tan-delta at low voltage gives anindication of contamination and presence of moisturecontent.

    Tan-delta tip up gives an indication of void content(variation of tan delta with applied voltage).Generally tan delta values shall not increase asapplied voltage increase.

    A higher tan delta tip up at a applied voltageindicates presence of voids/moistures and the

    inception of partial discharges at this voltage. Increase in tan delta above passing of time also

    indicates deterioration of insulation

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    58/67

    Transformer protection

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    59/67

    Over load Capability: Working life of transformer dependent on life of insulation

    Rate of deterioration of insulation increases with increasingwinding temperature W

    Winding temperature dependent on loading

    Transformer has substantial over load capability

    IF W< 80 deg.c use of life negligible

    If transformer is operated @ 104 deg. For every hour of operation= 2 hrs of life is lost.

    If transformer is operated @ 116 deg. For every hour of operation8 hrs of life is lost

    Rate of using transformer life doubled for every temperatureincrease of 6 deg.c

    Transformer - Protections

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    60/67

    Transformer Protections

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    61/67

    Period1 Period2 Period3 Total LifeLost

    LossHrs./Day

    24 Hrs@80oC

    24 X 0.125 3

    24 Hrs@98oC

    24 X 1 24

    9 Hrs @80oC 7 Hrs @80oC 8 Hrs @80oC 9 X 0.125 +7 X1 +8 X 2

    24

    24 Hrs@104oC

    24 X 2 48

    Transformer - Protections

    T f P t ti

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    62/67

    Criteria for overload operation

    For normal duty cycle, current shall not exceed 150% IRAT For emergency duty, current can exceed 150% IRATprovided

    associated cables, switch gear, tap changers, bushings etc. aresuitable rated.

    Under no circumstances,

    Windingshall exceed 140 deg.c

    Oilshall exceed 115 deg.c.

    Transformer - Protections

    Transformer Protections

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    63/67

    Transformer - Protections

    Buchholz Protection: Relay installed in the pipe line between transformer tank and

    conservator

    Two Floats Upper float = responds to slow accumulation of gas due to mild or

    incipient faults

    for alarm Lower float (Vane) responds to oil surge caused by major internal

    faults for trip

    Relay mounting precautions Gas shall freely pass up the pipe work

    Extra turbulence shall not be induced in oil stream

    Relay shall be mounted on straight run of pipe line which shouldslope from transformer to conservator at an angle of 5 deg.

    Operating time: 100 to 200 milliseconds

    Petcock provided on top of housing to draw accumulated gas foranalysis

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    64/67

    Transformer - Protections

    Buchholz Protection: Gas actuated relay

    Popularly used in all countries except USA

    Used to detect incipient faults which may lead to major damage ifallowed to continue

    Some Examples:

    Hot spots on the core due to short in lamination insulation

    Core bolt insulation failure

    Faulty joints

    Inter turn faults Loss of oil due to leakage

    Depends for its operation on the fact that most internal faultsgenerate gases.

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    65/67

    Maintenance Schedule

    Frequency ofInspection

    Item to be inspected Remarks

    Daily Amb. Temp.

    Oil temp.

    Winding temp.

    Load currentVoltage

    Check whether

    temp. rise is

    reasonable

    Check against ratedvalues

    Half yearly Oil level / leakageBushingCable boxes

    BreatherTap changer operationWTI/OTI

    IR value

    Take corrective actionif abnormality isnoticed

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    66/67

    Maintenance Schedule

    Frequency ofInspection

    Item to be inspected Remarks

    Yearly Oil testing Take correctiveaction (oil filtration

    / oil replacement)

    as per the testreport

    Yearly DGA analysis Over haul thetransformer ifabnormality is

    indicated in the reportFive yearly orconditionmonitoringreport based

    Over hauling oftransformer

    Take corrective actionif abnormality isnoticed

  • 8/13/2019 Very GOOD Condition Monitoring Transformers

    67/67