8/13/2019 Very GOOD Condition Monitoring Transformers
1/67
Working principle of a
transformer A transformer is static (or stationary) piece of
apparatus which:
1.Transfers electric power from one circuit toanother.
2.It does so without a change in frequency.
3.The principle is based on mutual inductionbetween two circuits linked by a commonmagnetic flux.
8/13/2019 Very GOOD Condition Monitoring Transformers
2/67
Basic parts of a transformer Basically a transformer consists o f a :
1.A primary coil or winding.
2.A secondary coil or winding.
3.A core that supports the coils or thewindings
8/13/2019 Very GOOD Condition Monitoring Transformers
3/67
8/13/2019 Very GOOD Condition Monitoring Transformers
4/67
Transformer construction
Main constructional elements of Transformers are -
A) Magnetic circuit Core & clamping structure
B) Electric Circuit Winding,Insulation, Bracing devices.
C) Terminals Tapping, Tapping switches, Terminal
Insulator, Leads , Bushings
D) Tank Oil, Cooling devices, conservator, piping,
Breather
E) Protective Circuit Buchholz relay, WTI, OTI, Oil surge relay
& Monitoring pressure relief device, MOG
8/13/2019 Very GOOD Condition Monitoring Transformers
5/67
Transformer construction
A)Magnetic Circuit:
The core provides closed path for flux. It is made up of CRGOinsulated laminations. (CRGO has iron loss of about 1.3 W / Kg at1.6 Tesla )
B)Electric Circuit:
Winding, insulation & bracing are constructional parts of electricalcircuit of transformers. This is the most vulnerable part oftransformer because of direct association with power system. Must
be designed to withstand voltage stress resulting from systemfault, transient over voltage and thermal stresses (lightening orswitching surges)
8/13/2019 Very GOOD Condition Monitoring Transformers
6/67
Transformer construction
Insulation:
Commonly used material are -
Paper or press board
Oil is used as insulating medium
Insulating varnish applied to make coil mechanicallystrong.
C) Terminal:
Leads:
Connection of winding are (copper rod or bus bar) taken tobushing.
Bushing:
Up to 33 kV porcelain bushing are used. Above 33 kV,condenser & oil filled terminal bushings are used.
8/13/2019 Very GOOD Condition Monitoring Transformers
7/67
Transformer construction
D) Transformer tank
Cooling:
Small transformers are air cooled whereas large transformers
are provided with oil or oil & air cooling .The transformer tank is designed to withstand full vacuum.
Types of Cooling:
Air insulated air cooledAN Air Natural
AF Forced Air Cooling
ANAN Natural Air cooling inside and outside transformer
8/13/2019 Very GOOD Condition Monitoring Transformers
8/67
Transformer construction
Oil immersed air cooled -
ONAN Natural Oil Circulation. Natural Air flow
ONAF Natural oil and forced air flow
OFAN Forced Oil & Natural Air CirculationOFAF Forced Oil and Forced Air Circulation
Oil immersed & water cooled
ONWF Natural Oil, water (internal) coolerOFWF Forced oil, water (external) cooler
8/13/2019 Very GOOD Condition Monitoring Transformers
9/67
Transformer construction
E) Protective devices :
Various protective devices mounted on transformer are asfollows:
Bucchholz Relay Gas actuated relay, Transformer
Internal fault.WTI/OTI Provided for alarm and / OR trip
against over load
PR Device To release internal pressure
generated in the transformer
during fault.MOG Alarm when oil level is low
Oil Surge Relay To release actual pressure
generated during fault in OLTC
8/13/2019 Very GOOD Condition Monitoring Transformers
10/67
Accessories & their functions
Terminal & Bushing : Type of Bushing, terminal is selecteddepending on voltage, currents & operating conditions. Porcelain,condenser type of oil filled bushings are used as per requirement.
Cable Boxes : Cable boxes are primarily designed for receiving
and protecting cable ends and ensure effective sealing of cableagainst ingress of moisture.
Conservator : It is provided to accommodate change in oilvolume caused due to change in loads or ambient conditions.
Breather :Whenever there is change in ambient temperature orload , there is a change in oil temperature and hence the volume ofoil. Increase in volume causes the air above oil level in conservatorto be pushed out and decrease causes air to be drawn in. Thusthe transformer breathes.
8/13/2019 Very GOOD Condition Monitoring Transformers
11/67
Accessories & their functions
When air is breathed in, moisture and dust fromatmosphere is sucked in .
Silica gel crystals absorb moisture. Color of silica gel
is blue when dry and turns pink when absorbsmoisture. Oil cup at the bottom is filled with oil which acts as
coarse filter and removes dust form outside air. Magnetic Oil Level gauge:
This is a dial instrument operated by magneticcoupling from a float on oil surface. It is normally fitted with contact to give alarm for low
oil level.
8/13/2019 Very GOOD Condition Monitoring Transformers
12/67
Accessories & their functions
Oil temperature indicator:Bourdon tube with a pointer arrangement mounted in a casecomprising of a reading dial and a glass cover. There is atemperature sensing bulb which communicates to the bourdontube through the armored capillary.
Winding temperature indicator:It comprises of following:WTI pot :mounted at top of transformer tank. Oil in pot is temp. of topoil.Imae coil:Heater coil and develops additional hear raising temperature ofoil incide heater coil.
WTI CT:Mounted on one of the line lead with secondary connected to image coilWTI: The bulb of the WTI is immersed in oil inside image col.Temperature of this oil is dependent on top oil temperature and load ontransformer.
8/13/2019 Very GOOD Condition Monitoring Transformers
13/67
Accessories & their functions
Buchholz Relay : Gas & oil operated relay detects formation ofgas or development of sudden pressure inside the oil of transformer.
Any electrical fault inside the transformer is accompanied byevolution of gas.
Pressure Relief Device: This is provided to relieve the internalpressure in the event of major fault within the transformer.
Tapping Switch: To maintain secondary voltages reasonablyconstant at load end when incoming voltage and/or load ontransformer changes, it is necessary to change the voltage ratio (I.e,
turns ratio of the winding) of the transformer.This is achieved by changing the number of turns ( HT Side) byoperating a switch called as tapping switch.
Depending on the requirement, off circuit or on load tapchangeris installed in the transformer.
8/13/2019 Very GOOD Condition Monitoring Transformers
14/67
Accessories & their functions
Radiators:The function of radiator is to limit the temperature of oil and winding bydissipating heat that is generated due to losses within transformer while inservice. When transformer is in operation warm oil rises and enters the radiatorfrom the top valve cools and then descend to enter the bottom of thetank.
Other Accessories: Inspection cover, jacking lugs, Earthing terminals,Rating Plate, Filter valve, Drain Valve, Terminal marking, Rollers etc.
8/13/2019 Very GOOD Condition Monitoring Transformers
15/67
DGA Insulating materials within transformer breakdown to
liberate gases.
The identity of these gases indicate the type of fault
and the rate of gas generation indicate the severityof fault.
Causes of fault gases can be divided into threecategories:
Corona or partial discharge
8/13/2019 Very GOOD Condition Monitoring Transformers
16/67
DGA
Pyrolisis or thermal heating
Arcing
Arcing is the most severe fault (intensity of energythat is dissipated per unit time per unit volume ofthe fault) ,less with heating, least with corona.
One of the most important technique to indicate thehealth of a transformer.
8/13/2019 Very GOOD Condition Monitoring Transformers
17/67
Major (Minor) fault gases undervarious fault conditions
8/13/2019 Very GOOD Condition Monitoring Transformers
18/67
Sampling And Labeling ProcedureSampling
Dry Weather, avoid contamination
Clean, dry, leak proof glass or stainless steelcontainer.
Equipment operating normally
Take safety precautions.
Sample bottle must be full without any air trapcompletely sealed and should be properly labeled.
8/13/2019 Very GOOD Condition Monitoring Transformers
19/67
8/13/2019 Very GOOD Condition Monitoring Transformers
20/67
FREQUENCY OF SAMPLING
NEW TRANSFORMERS
FIRST DGA TEST : BEFORE HEAT RUN TEST ONTRANSFORMER
SECOND DGA TEST : AFTER HEAT RUN TEST ONTRANSFORMER (2&24 HRS)
THIRD DGA TEST : BEFORE ENERGIZINGTRANSFORMER (B.M.)
FOURTH DGA TEST : WITHIN THREE MONTHS OFSERVICE
8/13/2019 Very GOOD Condition Monitoring Transformers
21/67
FREQUENCY OF SAMPLING
IN-SERVICE TRANSFORMERS
ANNUALLY AS A ROUTINE CKECKING
BEFORE (LATEST DATA) & AFTER FILTRATION/TOPPING UP
TRANSFORMERS AFTER OVERHAULING,
REPAIRS, MAINTANANCE
BEFORE ENERGISING TRANSFORMER
WITHIN THREE MONTHS OF SERVICE
8/13/2019 Very GOOD Condition Monitoring Transformers
22/67
Interpretation of Results
Ensure that gas concentrations are highenough to warrant further investigation.
Gas being present even in normal operatingcondition without any fault being present.
Gases might have formed on the occasion ofprevious faults or during repairs by brazing,
welding etc., and not completely removed. Since gases are produced in normal ageing
also, the service duration of the oil has to betaken into account.
8/13/2019 Very GOOD Condition Monitoring Transformers
23/67
PERMISSIBLE LIMITS OF DISSOLVED GASES IN
OIL OF A HEALTHY TRANSFORMER
GAS 10 YRS (PPM)
H2 100-150 200-300 200-300CH4 50-70 100-150 200-300
C2H2 20-30 30-50 100-150
C2H4 100-150 150-200 200-400
C2H6 30-50 100-150 800-1000
CO 200-300 400-500 600-700
CO2 3000-3500 4000-5000 9000-12000
GAS 10 YRS (PPM)
H2 100-150 200-300 200-300
CH4 50-70 100-150 200-300
C2H2 20-30 30-50 100-150
C2H4 100-150 150-200 200-400
C2H6 30-50 100-150 800-1000
CO 200-300 400-500 600-700
CO2 3000-3500 4000-5000 9000-12000
8/13/2019 Very GOOD Condition Monitoring Transformers
24/67
Condition monitoring oftransformer oil
Role of transformer oil: It is used as coolant. It is used as insulating material.
Reasons for deterioration of transformer oil
Physical contamination: Release of fibrous impurities by paper, pressboard, wood and
cotton tapes in contact with oil for longer period at elevatedtemperatures.
Due to dissolution of varnish . Due to foreign matters like dust, metallic particles and other
solid impurities Due to moisture
8/13/2019 Very GOOD Condition Monitoring Transformers
25/67
Condition monitoring oftransformer oil
Effects:
Life is reduced by high sludge formation.
Electrical properties of insulating oil get disturbed dueto conductivity of suspended particles.
Chemical deterioration:
It is due to oxidation.
Effects of oxidation:
Results in acids, sludge .Acid attack solid insulationand metal. Sludge causes poor thermal conductionand mechanical hindrance to proper oil circulation.
8/13/2019 Very GOOD Condition Monitoring Transformers
26/67
Condition monitoring oftransformer oil
Contamination of gases:
Gases are present in oil due to following:
Those which dissolve in the oil from atmosphere.
Those which are generated inside due to thermaldecomposition of oil, decomposition of oil by arcing.
Effects of gases:
The ignition of inflammable gases can be causes by
corona occurring in th air space or arcing.
8/13/2019 Very GOOD Condition Monitoring Transformers
27/67
Transformer oil testing
Transformer oil testing is carried out to detectabnormalities in transformer and based on test results
corrective actins can be taken before actual failure takesplace.
To evaluate quality of oil
To decide periodic maintenance (filtration. reclamation
etc) To know health of transformer (by DGA)
To estimate remaining life of transformer
8/13/2019 Very GOOD Condition Monitoring Transformers
28/67
Oil Testing
New oil (IS-335)- 15 tests
Oil in service (IS-1866)- 8 tests
Dielectric strength (BDV)
Dielectric dissipation factor (Tan delta)
Resistivity Neutralisation value (Acidity)
Flash point
Water content
Sludge
Interfacial tension
8/13/2019 Very GOOD Condition Monitoring Transformers
29/67
Transformer oil testing
1.Physical condition of the oil:Color ,clarity and odour gives information regardingquality of oil and presence of certain contaminants in
oil.2.Electrical strength:
Important parameter as used as insulating medium.This test gives conductive contaminants and moisturepresent in oil.
3.Water content:Reveals total water content ,leak or cellulosicdeterioration
8/13/2019 Very GOOD Condition Monitoring Transformers
30/67
Transformer oil testing
4.Specific resistance (Resistivity):This test provides a measure of the total soluble contaminants andageing products .It is numerically equal to the resistance betweenopposite faces of a centimeter cue of the oil and is expressed asohm com.
5.Dissipation factor:This test provides a measure of the total soluble contaminantsand ageing products.
6.Neutralisation value:This test gives acid present in the oil. It is the no. of milligrams ofpotassium hydroxide required to neutralise completely the acidsproduced in one gram of oil.
8/13/2019 Very GOOD Condition Monitoring Transformers
31/67
Transformer oil testing
7.Interfacial tension test:
This test provides a measure of sludge and
polar component present in oil. It isexpressed as molecular attractive forcebetween the molecules of water and oil atoil-water interface.
8.Flash point:Sudden drop in flashpoint is indicative ofunsafe working condition of transformer.
8/13/2019 Very GOOD Condition Monitoring Transformers
32/67
Scheduled of oil characteristics for transformerin service as per IS : 1866-2000
Property Highest Voltage of equipment, kV
< 72.5 72.5 to 170 > 170
Breakdown voltage (kV),
Min.
More than
30
More than 40 More than
50
Water content (ppm),Max.
Max. 95 Max. 40 Max. 20
Neutralization value (mgKOH/g), Max.
Max. 0.3 Max. 0.3 Max. .0.3
Sediment & Sludge, %by mass
ND ND ND
Resistivity @ 90C x 1012
(ohm-cm), Min.0.1 x 1012 0.1 x 1012 0.1 x 1012
8/13/2019 Very GOOD Condition Monitoring Transformers
33/67
Property Highest Voltage of equipment, kV
< 72.5 72.5 to 170 > 170
Dielectric dissipationfactor @ 90C, Max.
1.0 1.0 0.2
Interfacial tension(mN/m), Min.
15 15 15
Flash Point, (C), Min. 125 125 125
8/13/2019 Very GOOD Condition Monitoring Transformers
34/67
Condition Monitoring - Oil testing
Sr. No. Test Remedial Action for
Deviations from
permissible limits
1 Electric strength 2.5
mm gap (Break downvoltage)
Oil filtration
2 Water content Oil filtration
3 Sediment and / or
precipitable sludge
Oil filtration
8/13/2019 Very GOOD Condition Monitoring Transformers
35/67
Condition Monitoring - Oil testing
Sr.
No.
Test Remedial Action for Deviations
from permissible limits
4 Specific resistance
(Resistivity at 90 deg.C
Oil filtration if the tan value
permits other wise replace the oil
5 Dielectric dissipation factor (
tan )
Replace the oil
6 Neutralisation value (total
acidity) of the oil
Replace the oil
7 Inter facial tension of the oil
against water at room
temperature
Replace the oil
8/13/2019 Very GOOD Condition Monitoring Transformers
36/67
8/13/2019 Very GOOD Condition Monitoring Transformers
37/67
Furanic compound test
When oil soaked paper is damaged by heat, some oilsoluble compound are released into oil called furans.
Paper is made of cellulose consisting of log chains ofglucose rings joined by glycosidic bonds.
During degradation bonds are broken and glucose
rings are opened. Glucose is unstable which furtherdegrades which are more stable and oil soluble calledfurans.
8/13/2019 Very GOOD Condition Monitoring Transformers
38/67
Furanic Compounds
The most commonly found furanic derivative is 2-furfuraldehyde(2 FAL) and other derivatives are
2- furfuryl alcohol (2 FOL) ,
2- Acetyl furan (2 ACF),
5- hydroxymethyl furfuraldehyde,(5HMF)
5 methyl furfuraldehyde(5MEF).
8/13/2019 Very GOOD Condition Monitoring Transformers
39/67
FURANS AND GASES
Cellulosedegradation=Glucose+H2O+CO+CO2+Organic acids.
With DGA and furan test extent of paper damage can
be seen. CO and CO2 are determined by DGA and are
considered as level indicator for cellulosicdegradation.
In case of severe localised paper damage ,high
furans and high gas content can be seen. In case general heating slow building of furans
without necessarily seeing an increase of gascontent.
8/13/2019 Very GOOD Condition Monitoring Transformers
40/67
Degree of polymerization (DP)
Degree of polymerization (DP) is another way ofexpressing the molecular weight. Physical propertiesof the paper depends on the degree ofpolymerization of paper
M = Dp x mWhere
M= molecular weight of the polymer
Dp = the degree of polymerization
and m = the molecular weight of monomer.
8/13/2019 Very GOOD Condition Monitoring Transformers
41/67
Degree of polymerization (DP)
DP value 1000 to 1500 i.e,1000 to 1500glucose units are present in cellulose
molecule. Degradation of paper is due to temperature,
water ad oxygen.
When DP value
8/13/2019 Very GOOD Condition Monitoring Transformers
42/67
Correlation between Dp and Furan
The absolute correlation of Furan to DP isdifficult, but can be related fairly accuratelyextent through an empirical formula.
Dp = - 100 ln (2 FAL) +709
8/13/2019 Very GOOD Condition Monitoring Transformers
43/67
INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS
These tests are performed to verify state ofdryness if insulation.
These tests are intended to check overallcleanliness ,dryness ,localized defects and generalcondition of insulation system.
When DC voltage is applied across insulation, thecurrent flows is the resultant of three currents:
Capacitive charging current
Absorption current
Leakage current
8/13/2019 Very GOOD Condition Monitoring Transformers
44/67
RL
RA
C
DC Voltagesource
S
Absorption currentConduction or leakagecurrent
Capacitance charging current
8/13/2019 Very GOOD Condition Monitoring Transformers
45/67
INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS
Capacitance leakage current:
The current lasts for a few seconds as DC voltage isapplied and drops out after the insulation is chargedto its full voltage. The time depends on the size andcapacitance of the test object. Larger time for largercapacitance objects.
8/13/2019 Very GOOD Condition Monitoring Transformers
46/67
INSULATION RESISTANCE ANDPOLARISATION INDEX TESTS
Absorption leakage current: It is caused by polarisation of molecules within
dielectric material.
In low capacitance equipments the current is high forfirst few seconds and decrease slowly to nearly zero.
In high capacitance equipment or wet andcontaminated insulation ,there will be no decrease of
absorption current for long time.
8/13/2019 Very GOOD Condition Monitoring Transformers
47/67
Conduction or leakagecurrent:
Conduction or leakage current
This is the current that normally flows through the
insulation ,between conductors or conductors toground.
It increases quickly and becomes stable. This current increases as insulation deteriorates and
becomes predominant after absorption current
vanishes. It is steady and time independent .Hence the
important current for measuring insulation resistance.
8/13/2019 Very GOOD Condition Monitoring Transformers
48/67
Interpretation of results:
If IR value shows a decreasing trend it showsgradual deterioration of insulation quality due tohumidity ,dust accumulation etc..
A very sharp drop indicates insulation failure.
8/13/2019 Very GOOD Condition Monitoring Transformers
49/67
IR MEASUREMENTS
THE TEST VOLTAGES FOR IR MEASUREMENT OF
TRANSFORMER ARE AS UNDER.RATING TEST VOLTAGE
415/440 V 500 V
3.3 kV 1000 V
6.6 kV 2500 V
11 kV & ABOVE 5000 V
THE MINIMUM ACCEPTABLE LOWER LIMIT FORIR VALUES IS GIVEN IN STANDARDS AS
V L-L+ 1 M
8/13/2019 Very GOOD Condition Monitoring Transformers
50/67
Polarisation indexmeasurements
Polarisation Index=600sec IR value/60 sec IR value
PI
8/13/2019 Very GOOD Condition Monitoring Transformers
51/67
STEP VOLTAGE TEST
The DC voltage is applied in various steps and ineach step the leakage current is noted. Stepduration:60 seconds.
The variation of this leakage current (or IR) with testvoltage gives the condition of insulation.
If insulation is dry, clean and with out physicaldamages shall show the same value at all voltagelevels.
If insulation value decreases at higher voltage levels,may be due to dirt, moisture, cracking, aging etc. The application of increased voltage creates electrical
stresses on internal insulation cracks. This can revealaging and physical damage in relatively clean and dryinsulation which would have not been apparent atlower voltages.
CAPACITANCE MEASUREMENTS
8/13/2019 Very GOOD Condition Monitoring Transformers
52/67
CAPACITANCE MEASUREMENTS
THE CAPACITANCE VALUE IS DEPENDENT ON THE CHARACTERISTICS OF THE DIELECTRIC MATERIAL THE PHYSICAL CONFIGURATION OF THE ELECTRODES
A C =
d Void /impurities may discharge partially during a voltage apicationand the effective distance between eectrodes ncreases. HENCE C WILL INCREASE WITH INCREASE IN VOLTAGE,
WHICH INDICATES PRESENCE OF PD AND THE DETERIORATION
OF INSULATION
A
d
ELECTRODE
ELECTRODE
DIELECTRIC
TAN MEASUREMENTS
8/13/2019 Very GOOD Condition Monitoring Transformers
53/67
TAN MEASUREMENTS
THE TAN VALUE DIRECTLY INDICATES THE POWERDISSIPATED BY THE INSULATION
IT INCREASES WITH INSULATION DETERIORATION ANDSERVES AS AN EARLY INDICATOR OF FAILURE HAZARDS
90
Ic
Ic
v v
8/13/2019 Very GOOD Condition Monitoring Transformers
54/67
Concept of Tan
In an ideal capcitor the voltage and currentare phase shifted by 90 deg.and current
through insulation is capacitive. If there are impurities in insulation,the
resistance of insulation decrease resulting inincrease of resistive current.
Thus the total current I = Ic + Ir which leadsthe voltage by a phase angle < 90. Andlags the Ic by an angle .
2 0 .4
3 0 .6
4 5 .9
8/13/2019 Very GOOD Condition Monitoring Transformers
55/67
The tangent of this angle directlyindicates the heat dissipation that takes
place inside the dielectric material.
The values obtained on new insulationforms the reference value for periodic
measurements.
P ti l di h
8/13/2019 Very GOOD Condition Monitoring Transformers
56/67
Partial discharge:
It is an electrical discharge that occurs acrossa portion of the insulation between two
conducting electrodes without completelybridging the gap.
This results in localized, nearly instantaneousrelease of energy.
The most convention unit for quantifying thePD quantity is Pico coulomb
I t t ti f lt
8/13/2019 Very GOOD Condition Monitoring Transformers
57/67
Interprtation of results:
High value of tan-delta at low voltage gives anindication of contamination and presence of moisturecontent.
Tan-delta tip up gives an indication of void content(variation of tan delta with applied voltage).Generally tan delta values shall not increase asapplied voltage increase.
A higher tan delta tip up at a applied voltageindicates presence of voids/moistures and the
inception of partial discharges at this voltage. Increase in tan delta above passing of time also
indicates deterioration of insulation
8/13/2019 Very GOOD Condition Monitoring Transformers
58/67
Transformer protection
8/13/2019 Very GOOD Condition Monitoring Transformers
59/67
Over load Capability: Working life of transformer dependent on life of insulation
Rate of deterioration of insulation increases with increasingwinding temperature W
Winding temperature dependent on loading
Transformer has substantial over load capability
IF W< 80 deg.c use of life negligible
If transformer is operated @ 104 deg. For every hour of operation= 2 hrs of life is lost.
If transformer is operated @ 116 deg. For every hour of operation8 hrs of life is lost
Rate of using transformer life doubled for every temperatureincrease of 6 deg.c
Transformer - Protections
8/13/2019 Very GOOD Condition Monitoring Transformers
60/67
Transformer Protections
8/13/2019 Very GOOD Condition Monitoring Transformers
61/67
Period1 Period2 Period3 Total LifeLost
LossHrs./Day
24 Hrs@80oC
24 X 0.125 3
24 Hrs@98oC
24 X 1 24
9 Hrs @80oC 7 Hrs @80oC 8 Hrs @80oC 9 X 0.125 +7 X1 +8 X 2
24
24 Hrs@104oC
24 X 2 48
Transformer - Protections
T f P t ti
8/13/2019 Very GOOD Condition Monitoring Transformers
62/67
Criteria for overload operation
For normal duty cycle, current shall not exceed 150% IRAT For emergency duty, current can exceed 150% IRATprovided
associated cables, switch gear, tap changers, bushings etc. aresuitable rated.
Under no circumstances,
Windingshall exceed 140 deg.c
Oilshall exceed 115 deg.c.
Transformer - Protections
Transformer Protections
8/13/2019 Very GOOD Condition Monitoring Transformers
63/67
Transformer - Protections
Buchholz Protection: Relay installed in the pipe line between transformer tank and
conservator
Two Floats Upper float = responds to slow accumulation of gas due to mild or
incipient faults
for alarm Lower float (Vane) responds to oil surge caused by major internal
faults for trip
Relay mounting precautions Gas shall freely pass up the pipe work
Extra turbulence shall not be induced in oil stream
Relay shall be mounted on straight run of pipe line which shouldslope from transformer to conservator at an angle of 5 deg.
Operating time: 100 to 200 milliseconds
Petcock provided on top of housing to draw accumulated gas foranalysis
8/13/2019 Very GOOD Condition Monitoring Transformers
64/67
Transformer - Protections
Buchholz Protection: Gas actuated relay
Popularly used in all countries except USA
Used to detect incipient faults which may lead to major damage ifallowed to continue
Some Examples:
Hot spots on the core due to short in lamination insulation
Core bolt insulation failure
Faulty joints
Inter turn faults Loss of oil due to leakage
Depends for its operation on the fact that most internal faultsgenerate gases.
8/13/2019 Very GOOD Condition Monitoring Transformers
65/67
Maintenance Schedule
Frequency ofInspection
Item to be inspected Remarks
Daily Amb. Temp.
Oil temp.
Winding temp.
Load currentVoltage
Check whether
temp. rise is
reasonable
Check against ratedvalues
Half yearly Oil level / leakageBushingCable boxes
BreatherTap changer operationWTI/OTI
IR value
Take corrective actionif abnormality isnoticed
8/13/2019 Very GOOD Condition Monitoring Transformers
66/67
Maintenance Schedule
Frequency ofInspection
Item to be inspected Remarks
Yearly Oil testing Take correctiveaction (oil filtration
/ oil replacement)
as per the testreport
Yearly DGA analysis Over haul thetransformer ifabnormality is
indicated in the reportFive yearly orconditionmonitoringreport based
Over hauling oftransformer
Take corrective actionif abnormality isnoticed
8/13/2019 Very GOOD Condition Monitoring Transformers
67/67