70072-0109-12TECHNICAL NOTE 05/2007
Electrical equipment should be installed, operated, serviced,
and maintained only by qualified personnel. No responsibility is
assumed by Schneider Electric for any consequences arising out of
the use of this material.
2006 Schneider Electric. All rights reserved.
www.powerlogic.com
Upgrading PowerLogic ION Device
FirmwareEachIONmeterusesfirmwaretostoreoperatingsoftware.YoucanupgrademostIONdevicestoanewerversionofoperatingsoftwarebysimplyupgradingitsfirmware.
NOTEThe ION6200 meter cannot be upgraded using software. Consult
Schneider Electric if you wish toupgrade this device.
NOTEEnsure that the firmware version you are upgrading to is
compatible with the meter you are planning toupgrade.
Therearetwowaystoupgradefirmware:usingIONSetupandusingtheDeviceUpgradercomponentofIONEnterprise.
In This Document
General Upgrading Considerations . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 2UsingaLaptopComputertoUpgrade
....................................
2UpgradingDevicesviaaModemGateConnection .........................
2MeterI/OModuleBehavior
............................................. 2
Upgrading Firmware Using ION Setup . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 3
Upgrading Firmware Using ION Enterprise . . . . . . . . . . . .
. . . . . . . . . . . . .
6BeforeUsingtheDeviceUpgrader.......................................6Makesureyourdatalogsarecurrent
.....................................
6ModifyingthetransmitdelayforEthernetdevices
......................... 7UsingtheDeviceUpgrader
.............................................8
Additional Information
Yourmeterstechnicaldocumentation OnlineIONEnterpriseHelp
OnlineIONSetupHelp
-
General Upgrading Considerations Upgrading ION Device
Firmware
Page 2 2006 Schneider Electric. All rights reserved.
General Upgrading Considerations
Using a Laptop Computer to
UpgradeLaptopcomputersgenerallyhavedifferentdefaultpowerpropertiesthandesktopcomputers.Incorrectpoweroptionscanadverselyaffectdeviceupgrading,becausetheconnectionbetweenthelaptopandthedevicemustbemaintainedinordertocompletetheupgradesuccessfully.Ifthelaptopsharddiskshutsdownorthelaptopenterssystemstandbymode,thisconnectionisbrokenandtheupgradeproceduremustberestarted.
Ifyouareupgradingameterusingalaptopcomputer,followtheseguidelines:
Plugthelaptopcomputerintoawalloutlet.Donotrunthelaptoponitsbattery.
Configuretheharddiskssothattheydonotshutdownafteracertainperiodoftime(i.e.settonever).
Turnoffpowersuspension(e.g.systemstandby)andhibernateoptions.
Disableoptionsthatpowerdownthelaptopwhenitisclosed.Thispreventsashutdownifthelaptopisaccidentallyclosed.
Disablethescreensaver;screensaverscanburdentheCPU.
Upgrading Devices via a ModemGate
ConnectionThemaximumacceptablebaudrateforupgradingviaModemGateis56.6kps.EnsurethatthebaudrateontheModemGatecommunicationsportandthebaudrateonthemetertobeupgradedaresettothisorlower.
Meter I/O Module
BehaviorThestateofyourmetersI/Omodulesmaychangeduringanupgrade.Theywillreverttoprevioussettingsoncetheupgradeiscomplete.
-
Upgrading ION Device Firmware Upgrading Firmware Using ION
Setup
2006 Schneider Electric. All rights reserved. Page 3
Upgrading Firmware Using ION
SetupPerformingadeviceupgradeinIONSetupinvolves:
upgradingthedevicefirmware,and
upgradingthedevicetemplate.
YoucanobtainyourdeviceslatestfirmwareandtemplatefromTechnicalSupport.Savethefilesinthe.../IONSetup/TEMPLATEfolderforeasyaccess.
Upgrading the device firmware and template
1.
OpenIONSetupandselectthedeviceyouwanttoupgradefromthelefthandpane.
2. OpentheSetupAssistantintherighthandpane.
3.
SelecttheTemplatescreenfromthelistofscreensinthelefthandpaneofSetupAssistant.
4. SelecttheFirmwareUpgradetab,thenclicktheUpgradebutton.
Ifyouarepromptedforyourmeterpassword,typeitinthenclickOK.
NOTEIf you want to retain customized meter template settings,
other than those listed in the Template PasteOptions dialogue box
(see Step 7), click on the Save to PC tab and click Save. Save your
template as a.DCF file. Choose this file in Step 6 instead of the
file obtained from Technical Support.
-
Upgrading Firmware Using ION Setup Upgrading ION Device
Firmware
Page 4 2006 Schneider Electric. All rights reserved.
5.
Browsetothe.UPGfile(devicefirmware)thatyoudownloadedfromthewebsiteandclickOpen.
WhenyouarepromptedforyourIONSetuppassword,typeitandclickOK.
6.
Browsetothe.DCFfile(devicetemplate)thatyoudownloadedfromthewebsite(orsavedfromyourmeterinStep4)andclickOpen.
-
Upgrading ION Device Firmware Upgrading Firmware Using ION
Setup
2006 Schneider Electric. All rights reserved. Page 5
7. ClearanyoptionsthatyoudonotwanttoretainthenclickOK.
8. Tracktheprogressoftheupgrade.
Afterthefirmwaredownloadiscomplete,IONSetupwillattempttoverifythefirmware.Iftheverificationfails,contactTechnicalSupport.
NOTESome meters display a Checking RMP Status message. RMP
stands for Rapid Meter Programming,which downloads the template to
the meter in less than 5 minutes (for meters and firmware that
supportRMP).
Whenyougetamessagethattheupgradeiscomplete,clickExit.
-
Upgrading Firmware Using ION Enterprise Upgrading ION Device
Firmware
Page 6 2006 Schneider Electric. All rights reserved.
Upgrading Firmware Using ION
EnterpriseIONEnterprisesoftwareincludesadeviceupgradeutilitynamedDeviceUpgrader,whichyoucanusetoupgrademostIONdevicesandcertainmetercomponents(suchastheION7330Ethernetcard,ION7700Xpresscard,orMGT)inyoursystem.WiththeDeviceUpgradeutility,youcanupgradethefirmwareonasingleIONdeviceorupgrademultipleIONdevicesofthesametypeinasinglesession.YouaccesstheDeviceUpgraderutilityfromtheManagementConsole.
NOTEA Supervisor password authority (level 5) is required to
upgrade ION devices.
Thefollowinginstructionsdetailhowtoupgradeoneormoredevicesofthesametype.Ifyouneedtoupgradedevicesthataredifferenttypes,youmustperformthefollowinginstructionsforeachdevice.Forexample,ifyouneedtoupgradeanION7330meterandanION7330Ethernetcard,thenyouhavetoperformthefollowinginstructionsonceforthemeter,andthenagainfortheEthernetcard(orviceversa).
SomeIONdevicesrequirethatyouupgradethecomponentsinacertainorder.Forexample,whenupgradingtheION7700,youmustupgradetheXpressCardfirmwarefirst,thentheION7700meterfirmware,thenfinallytheMGTfirmware.Consultyourproductsdocumentationformoreinformation.
Before Using the Device
UpgraderPleasereadthissectionbeforeyoubeginyourupgrade.Therecommendationspresentedherecanhelpwithyourdeviceupgradingprocedure.
Make sure your data logs are
currentDatastoredinthemetersmemoryislostduringthefirmwareupgrade.Thisincludeswaveforms,Min/Maxvalues,andinformationstoredinDataRecorderandIntegratormodules.Ensureyourdatalogsareuptodate(i.e.theIONLogInserterServiceiscaughtup)beforeyoucommenceupgrading.
Ensuring the data logs are current
1.
LaunchVistaandopentheuserdiagramofthedeviceyouplantoupgrade.
2.
ClicktheDataLogViewerforvoltageorotherparametersthatupdatequickly(e.g.everyfifteenminutes).
3. Lookatthetimestampcolumn.
-
Upgrading ION Device Firmware Before Using the Device
Upgrader
2006 Schneider Electric. All rights reserved. Page 7
IfthetimestampiscurrentifthedateiscorrectandthecurrenttimeiswithinthetimestampintervalthentheIONLogInserterServiceiscaughtup.
Notethatthetimestampintervalisthedurationbetweentimestamps.Inthisexample,thetimestampintervalis15minutes.
Modifying the transmit delay for Ethernet
devicesForEthernetenabledION8800,ION8600orION7550/ION7650meters,youcansettheTransmitDelayparameterto0forfasterfirmwareupgrades.NotethatyoushouldalsosettheUseAck/NacksparametertoNowhenyoumodifythetransmitdelayforthesedevices.
UpgradingfirmwareforION7300seriesmetersrequiresaminimumtransmitdelayof50ms;however,itisrecommendedthatthedefault150mstransmitdelaybeused.Checkthissettingbeforeyouattempttoupgradeyourdevice.Failuretohaveaminimumof50mstransmitdelayforION7300seriesdevicesmayresultinupgradefailure.
Configuring device transmit delay
1.
StarttheManagementConsole.ClicktheDevicesiconinthelefthandpane.
2.
RightclickthedeviceyouwanttoupgradeinthelistofdevicesandselectProperties.
3. RightclickinthedialogboxandselectAdvancedProperties.
4.
SetTransmitDelaytoatleast50ms(150msisrecommended)forION7300seriesmeters,orsetTransmitDelayto0forION7550,ION7650,ION8600andION8800meters(setUseAck/NackstoNoforthislattergroupofdevicestoo.)
5. ClickOK.
This must be set to a minimum of 50 ms for ION7300 series meters
(150 ms is the default).
-
Using the Device Upgrader Upgrading ION Device Firmware
Page 8 2006 Schneider Electric. All rights reserved.
NOTEWhen upgrading the firmware for devices in serial and modem
sites, it is recommended that you keepthe transmit delay at the
sites default (i.e. 150 ms for both serial and modem sites).
Using the Device Upgrader1.
StartManagementConsoleandselectTools>System>DeviceUpgrader.
2. TypeyourIONEnterpriseusernameandpassword,andclickOK.
Aninformationwindowdisplays,containingtipsandwarningsabouttheupgradeoperation.ClickOK.
3. TheDeviceUpgradewindowdisplays.
4.
SelecttheIONdeviceyouwanttoupgradefromListDevicesofType.TheDeviceUpgradelistsallthedevicesoftheselectedtypeintheSelectDevicestoUpgradebox.
Choose the type of device that you want to upgrade. (In this
case, it is an ION7650.)
This area lists all available devices of the specified type.
Highlight the device(s) to upgrade.
When upgrading multiple devices, specify whether the utility
should halt if a certain number of device upgrades fail.
Save/Restore framework is enabled by default, so custom
frameworks are not lost during upgrade.
Click this button to browse your system for the upgrade
file.
-
Upgrading ION Device Firmware Using the Device Upgrader
2006 Schneider Electric. All rights reserved. Page 9
5.
Selectthedevice(s)youwanttoupgradefromSelectDevicestoUpgrade.Toselectmultipledevices,holddownCtrlwhileclickingeachdevice.
TheSave/RestoreFrameworkcheckboxisselectedbydefault.Thiskeepsacopyofyourcurrentframeworktemplateduringtheupgrade.
CAUTIONIf you uncheck the Save/Restore Framework check box, the
current framework template for each selecteddevice is deleted when
the firmware upgrade is complete, leaving no framework
configuration in theupgraded devices. Any custom frameworks you
have on the device are also deleted.
If you intend to replace the meters framework configuration with
a new template, it is recommended thatyou upgrade via ION Setup.
See Upgrading Firmware Using ION Setup on page 3 for
information.
6.
Ifyouareupgradingmultipledevices,specifyintheFailureHandlingareahowtheDeviceUpgraderrespondstoanunsuccessfulupgrade:
SelectHaltAftertospecifythenumberoffaileddeviceupgradesthatcanoccurbeforeDeviceUpgraderstops.Bydefault,theutilityissettostopafterthefirstfailedupgrade.
SelectIgnoreAlltoattempttoupgradealloftheselecteddevicesregardlessofanyfailures.
7.
IntheSelectRevisionsection,clickSelectFile.Navigatetotheupgrade(.upg)filethatyouwanttouseandclickOpen.
ThisfilewillbedownloadedtoallthedevicesthatarehighlightedintheSelectDevicestoUpgradelist.
8. ClickUpgradetoupgradetheselecteddevice(s).
TheUpgradeStatusboxshowseachstageintheupgradeprocess,andthePercentCompletedbarindicatestheprogressofeachupgrade.EachcompletedupgradeisnotedintheUpgradeStatusbox.
Enterthemeterpassword(s)whenpromptedtodoso.
NOTEIf connection to the device is lost, or if power to the
device is interrupted during an upgrade, restart theDevice Upgrade
utility procedure.
9.
DownloadandinstalltheIONsoftwareupdatesforyournewfirmwarefromthewebsite.
In this example, an ION7300 Ethernet card is the device selected
for upgrade.
Select the ION7300 meter that contains the ION7300 Ethernet card
that will be upgraded.
General Upgrading ConsiderationsUpgrading Firmware Using ION
SetupUpgrading Firmware Using ION EnterpriseBefore Using the Device
UpgraderUsing the Device Upgrader
/ColorImageDict > /JPEG2000ColorACSImageDict >
/JPEG2000ColorImageDict > /AntiAliasGrayImages false
/CropGrayImages true /GrayImageMinResolution 300
/GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true
/GrayImageDownsampleType /Bicubic /GrayImageResolution 300
/GrayImageDepth -1 /GrayImageMinDownsampleDepth 2
/GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true
/GrayImageFilter /DCTEncode /AutoFilterGrayImages true
/GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict >
/GrayImageDict > /JPEG2000GrayACSImageDict >
/JPEG2000GrayImageDict > /AntiAliasMonoImages false
/CropMonoImages true /MonoImageMinResolution 1200
/MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true
/MonoImageDownsampleType /Bicubic /MonoImageResolution 1200
/MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000
/EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode
/MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None
] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false
/PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000
0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true
/PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ]
/PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier ()
/PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped
/False
/Description > /Namespace [ (Adobe) (Common) (1.0) ]
/OtherNamespaces [ > /FormElements false /GenerateStructure
false /IncludeBookmarks false /IncludeHyperlinks false
/IncludeInteractive false /IncludeLayers false /IncludeProfiles
false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe)
(CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector
/DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling
/LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile
/UseDocumentBleed false >> ]>> setdistillerparams>
setpagedevice