 70072-0109-12 TECHNICAL  NOTE 05/2007 Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2006 Schneider Electric.  All rights reserved. www.powerlogic.com Upgrading PowerLogic ®  ION ® Device Firmware Each ION meter uses  firmware  to store operating software. You can upgrade most ION devices to a newer version of operating software  by simply upgrading its firmware. NOTE The ION6200 meter cannot be upgraded using software. Consult Schneider Electric if you wish to upgrade this device. NOTE Ensure that the firmware version you are upgrading to is compatible with the meter you are planning to upgrade. There are two ways to upgrade firmware:  using ION Setup and using the Device Upgrader component  of ION Enterprise. In This Document  General Upgrad ing Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Using a Laptop Computer to Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2 Upgrading Devices via a ModemGate Connection . . . . . . . . . . . . . . . . . . . . . . . . .  2 Meter I/O Module Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2 Upgrading Firmware Using ION Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Upgrading Firmware Using ION Enterprise . . . . . . . . . . . . . . . . . . . . . . . . . 6 Before Using the Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Make sure your data logs are current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6 Modifying the transmit delay for Ethernet devices . . . . . . . . . . . . . . . . . . . . . . . . .  7 Using the Device Upgrader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  Additional Information  Your meter’s technical  documentation  Online ION  Enterprise Help  Online ION  Setup Help
10

UpDate Firmware_70072-0109-12

Nov 01, 2015

Download

Documents

Rapport Rodrigo

Procedimento para upgrade medidor ION
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 70072-0109-12TECHNICAL NOTE 05/2007

    Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

    2006 Schneider Electric. All rights reserved.

    www.powerlogic.com

    Upgrading PowerLogic ION Device FirmwareEachIONmeterusesfirmwaretostoreoperatingsoftware.YoucanupgrademostIONdevicestoanewerversionofoperatingsoftwarebysimplyupgradingitsfirmware.

    NOTEThe ION6200 meter cannot be upgraded using software. Consult Schneider Electric if you wish toupgrade this device.

    NOTEEnsure that the firmware version you are upgrading to is compatible with the meter you are planning toupgrade.

    Therearetwowaystoupgradefirmware:usingIONSetupandusingtheDeviceUpgradercomponentofIONEnterprise.

    In This Document

    General Upgrading Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2UsingaLaptopComputertoUpgrade .................................... 2UpgradingDevicesviaaModemGateConnection ......................... 2MeterI/OModuleBehavior ............................................. 2

    Upgrading Firmware Using ION Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Upgrading Firmware Using ION Enterprise . . . . . . . . . . . . . . . . . . . . . . . . . 6BeforeUsingtheDeviceUpgrader.......................................6Makesureyourdatalogsarecurrent ..................................... 6ModifyingthetransmitdelayforEthernetdevices ......................... 7UsingtheDeviceUpgrader .............................................8

    Additional Information

    Yourmeterstechnicaldocumentation OnlineIONEnterpriseHelp OnlineIONSetupHelp

  • General Upgrading Considerations Upgrading ION Device Firmware

    Page 2 2006 Schneider Electric. All rights reserved.

    General Upgrading Considerations

    Using a Laptop Computer to UpgradeLaptopcomputersgenerallyhavedifferentdefaultpowerpropertiesthandesktopcomputers.Incorrectpoweroptionscanadverselyaffectdeviceupgrading,becausetheconnectionbetweenthelaptopandthedevicemustbemaintainedinordertocompletetheupgradesuccessfully.Ifthelaptopsharddiskshutsdownorthelaptopenterssystemstandbymode,thisconnectionisbrokenandtheupgradeproceduremustberestarted.

    Ifyouareupgradingameterusingalaptopcomputer,followtheseguidelines:

    Plugthelaptopcomputerintoawalloutlet.Donotrunthelaptoponitsbattery.

    Configuretheharddiskssothattheydonotshutdownafteracertainperiodoftime(i.e.settonever).

    Turnoffpowersuspension(e.g.systemstandby)andhibernateoptions.

    Disableoptionsthatpowerdownthelaptopwhenitisclosed.Thispreventsashutdownifthelaptopisaccidentallyclosed.

    Disablethescreensaver;screensaverscanburdentheCPU.

    Upgrading Devices via a ModemGate ConnectionThemaximumacceptablebaudrateforupgradingviaModemGateis56.6kps.EnsurethatthebaudrateontheModemGatecommunicationsportandthebaudrateonthemetertobeupgradedaresettothisorlower.

    Meter I/O Module BehaviorThestateofyourmetersI/Omodulesmaychangeduringanupgrade.Theywillreverttoprevioussettingsoncetheupgradeiscomplete.

  • Upgrading ION Device Firmware Upgrading Firmware Using ION Setup

    2006 Schneider Electric. All rights reserved. Page 3

    Upgrading Firmware Using ION SetupPerformingadeviceupgradeinIONSetupinvolves:

    upgradingthedevicefirmware,and

    upgradingthedevicetemplate.

    YoucanobtainyourdeviceslatestfirmwareandtemplatefromTechnicalSupport.Savethefilesinthe.../IONSetup/TEMPLATEfolderforeasyaccess.

    Upgrading the device firmware and template

    1. OpenIONSetupandselectthedeviceyouwanttoupgradefromthelefthandpane.

    2. OpentheSetupAssistantintherighthandpane.

    3. SelecttheTemplatescreenfromthelistofscreensinthelefthandpaneofSetupAssistant.

    4. SelecttheFirmwareUpgradetab,thenclicktheUpgradebutton.

    Ifyouarepromptedforyourmeterpassword,typeitinthenclickOK.

    NOTEIf you want to retain customized meter template settings, other than those listed in the Template PasteOptions dialogue box (see Step 7), click on the Save to PC tab and click Save. Save your template as a.DCF file. Choose this file in Step 6 instead of the file obtained from Technical Support.

  • Upgrading Firmware Using ION Setup Upgrading ION Device Firmware

    Page 4 2006 Schneider Electric. All rights reserved.

    5. Browsetothe.UPGfile(devicefirmware)thatyoudownloadedfromthewebsiteandclickOpen.

    WhenyouarepromptedforyourIONSetuppassword,typeitandclickOK.

    6. Browsetothe.DCFfile(devicetemplate)thatyoudownloadedfromthewebsite(orsavedfromyourmeterinStep4)andclickOpen.

  • Upgrading ION Device Firmware Upgrading Firmware Using ION Setup

    2006 Schneider Electric. All rights reserved. Page 5

    7. ClearanyoptionsthatyoudonotwanttoretainthenclickOK.

    8. Tracktheprogressoftheupgrade.

    Afterthefirmwaredownloadiscomplete,IONSetupwillattempttoverifythefirmware.Iftheverificationfails,contactTechnicalSupport.

    NOTESome meters display a Checking RMP Status message. RMP stands for Rapid Meter Programming,which downloads the template to the meter in less than 5 minutes (for meters and firmware that supportRMP).

    Whenyougetamessagethattheupgradeiscomplete,clickExit.

  • Upgrading Firmware Using ION Enterprise Upgrading ION Device Firmware

    Page 6 2006 Schneider Electric. All rights reserved.

    Upgrading Firmware Using ION EnterpriseIONEnterprisesoftwareincludesadeviceupgradeutilitynamedDeviceUpgrader,whichyoucanusetoupgrademostIONdevicesandcertainmetercomponents(suchastheION7330Ethernetcard,ION7700Xpresscard,orMGT)inyoursystem.WiththeDeviceUpgradeutility,youcanupgradethefirmwareonasingleIONdeviceorupgrademultipleIONdevicesofthesametypeinasinglesession.YouaccesstheDeviceUpgraderutilityfromtheManagementConsole.

    NOTEA Supervisor password authority (level 5) is required to upgrade ION devices.

    Thefollowinginstructionsdetailhowtoupgradeoneormoredevicesofthesametype.Ifyouneedtoupgradedevicesthataredifferenttypes,youmustperformthefollowinginstructionsforeachdevice.Forexample,ifyouneedtoupgradeanION7330meterandanION7330Ethernetcard,thenyouhavetoperformthefollowinginstructionsonceforthemeter,andthenagainfortheEthernetcard(orviceversa).

    SomeIONdevicesrequirethatyouupgradethecomponentsinacertainorder.Forexample,whenupgradingtheION7700,youmustupgradetheXpressCardfirmwarefirst,thentheION7700meterfirmware,thenfinallytheMGTfirmware.Consultyourproductsdocumentationformoreinformation.

    Before Using the Device UpgraderPleasereadthissectionbeforeyoubeginyourupgrade.Therecommendationspresentedherecanhelpwithyourdeviceupgradingprocedure.

    Make sure your data logs are currentDatastoredinthemetersmemoryislostduringthefirmwareupgrade.Thisincludeswaveforms,Min/Maxvalues,andinformationstoredinDataRecorderandIntegratormodules.Ensureyourdatalogsareuptodate(i.e.theIONLogInserterServiceiscaughtup)beforeyoucommenceupgrading.

    Ensuring the data logs are current

    1. LaunchVistaandopentheuserdiagramofthedeviceyouplantoupgrade.

    2. ClicktheDataLogViewerforvoltageorotherparametersthatupdatequickly(e.g.everyfifteenminutes).

    3. Lookatthetimestampcolumn.

  • Upgrading ION Device Firmware Before Using the Device Upgrader

    2006 Schneider Electric. All rights reserved. Page 7

    IfthetimestampiscurrentifthedateiscorrectandthecurrenttimeiswithinthetimestampintervalthentheIONLogInserterServiceiscaughtup.

    Notethatthetimestampintervalisthedurationbetweentimestamps.Inthisexample,thetimestampintervalis15minutes.

    Modifying the transmit delay for Ethernet devicesForEthernetenabledION8800,ION8600orION7550/ION7650meters,youcansettheTransmitDelayparameterto0forfasterfirmwareupgrades.NotethatyoushouldalsosettheUseAck/NacksparametertoNowhenyoumodifythetransmitdelayforthesedevices.

    UpgradingfirmwareforION7300seriesmetersrequiresaminimumtransmitdelayof50ms;however,itisrecommendedthatthedefault150mstransmitdelaybeused.Checkthissettingbeforeyouattempttoupgradeyourdevice.Failuretohaveaminimumof50mstransmitdelayforION7300seriesdevicesmayresultinupgradefailure.

    Configuring device transmit delay

    1. StarttheManagementConsole.ClicktheDevicesiconinthelefthandpane.

    2. RightclickthedeviceyouwanttoupgradeinthelistofdevicesandselectProperties.

    3. RightclickinthedialogboxandselectAdvancedProperties.

    4. SetTransmitDelaytoatleast50ms(150msisrecommended)forION7300seriesmeters,orsetTransmitDelayto0forION7550,ION7650,ION8600andION8800meters(setUseAck/NackstoNoforthislattergroupofdevicestoo.)

    5. ClickOK.

    This must be set to a minimum of 50 ms for ION7300 series meters (150 ms is the default).

  • Using the Device Upgrader Upgrading ION Device Firmware

    Page 8 2006 Schneider Electric. All rights reserved.

    NOTEWhen upgrading the firmware for devices in serial and modem sites, it is recommended that you keepthe transmit delay at the sites default (i.e. 150 ms for both serial and modem sites).

    Using the Device Upgrader1. StartManagementConsoleandselectTools>System>DeviceUpgrader.

    2. TypeyourIONEnterpriseusernameandpassword,andclickOK.

    Aninformationwindowdisplays,containingtipsandwarningsabouttheupgradeoperation.ClickOK.

    3. TheDeviceUpgradewindowdisplays.

    4. SelecttheIONdeviceyouwanttoupgradefromListDevicesofType.TheDeviceUpgradelistsallthedevicesoftheselectedtypeintheSelectDevicestoUpgradebox.

    Choose the type of device that you want to upgrade. (In this case, it is an ION7650.)

    This area lists all available devices of the specified type. Highlight the device(s) to upgrade.

    When upgrading multiple devices, specify whether the utility should halt if a certain number of device upgrades fail.

    Save/Restore framework is enabled by default, so custom frameworks are not lost during upgrade.

    Click this button to browse your system for the upgrade file.

  • Upgrading ION Device Firmware Using the Device Upgrader

    2006 Schneider Electric. All rights reserved. Page 9

    5. Selectthedevice(s)youwanttoupgradefromSelectDevicestoUpgrade.Toselectmultipledevices,holddownCtrlwhileclickingeachdevice.

    TheSave/RestoreFrameworkcheckboxisselectedbydefault.Thiskeepsacopyofyourcurrentframeworktemplateduringtheupgrade.

    CAUTIONIf you uncheck the Save/Restore Framework check box, the current framework template for each selecteddevice is deleted when the firmware upgrade is complete, leaving no framework configuration in theupgraded devices. Any custom frameworks you have on the device are also deleted.

    If you intend to replace the meters framework configuration with a new template, it is recommended thatyou upgrade via ION Setup. See Upgrading Firmware Using ION Setup on page 3 for information.

    6. Ifyouareupgradingmultipledevices,specifyintheFailureHandlingareahowtheDeviceUpgraderrespondstoanunsuccessfulupgrade:

    SelectHaltAftertospecifythenumberoffaileddeviceupgradesthatcanoccurbeforeDeviceUpgraderstops.Bydefault,theutilityissettostopafterthefirstfailedupgrade.

    SelectIgnoreAlltoattempttoupgradealloftheselecteddevicesregardlessofanyfailures.

    7. IntheSelectRevisionsection,clickSelectFile.Navigatetotheupgrade(.upg)filethatyouwanttouseandclickOpen.

    ThisfilewillbedownloadedtoallthedevicesthatarehighlightedintheSelectDevicestoUpgradelist.

    8. ClickUpgradetoupgradetheselecteddevice(s).

    TheUpgradeStatusboxshowseachstageintheupgradeprocess,andthePercentCompletedbarindicatestheprogressofeachupgrade.EachcompletedupgradeisnotedintheUpgradeStatusbox.

    Enterthemeterpassword(s)whenpromptedtodoso.

    NOTEIf connection to the device is lost, or if power to the device is interrupted during an upgrade, restart theDevice Upgrade utility procedure.

    9. DownloadandinstalltheIONsoftwareupdatesforyournewfirmwarefromthewebsite.

    In this example, an ION7300 Ethernet card is the device selected for upgrade.

    Select the ION7300 meter that contains the ION7300 Ethernet card that will be upgraded.

    General Upgrading ConsiderationsUpgrading Firmware Using ION SetupUpgrading Firmware Using ION EnterpriseBefore Using the Device UpgraderUsing the Device Upgrader

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice