Top Banner
R-4430 Saint Louis, Missouri Markham, Ontario 314-553-3600 905-948-3411 white-rodgers.com emersonclimate.com The Emerson logo is a trademark and a service mark of Emerson Electric Co. Specifications Replaces: Amana C64301-1 C6431001 Arcoaire 32312-00 3232140 Armstrong 39840B001 44614-001 44614-002 46257-001 47181-001 R46257-001 R46614-002 R47181-001 Carrier 150-83-6A 621-xxx CES0110063-00 CES0110063-01 CES0110063-02A CES0130024-00 CES0130024-01 CES0130076 HK25SZ359A HK32EA001 HK32EA003 HK32EA007 HK32EA008 HK32FA003 HK32FA006 Coleman 3030A374 Comfortmaker 1029-2 34332100 34332101 Evcon 9218-374 Fast 1093410 Goettl 305007 Goodman 1084-03-2022 1084-200D 20293901 B1226006 B1226008 LR40061 PCBDM101 PCBDM130 PCBDM133 PCBDM160 Heil Quaker HQ1052757 Heil/Tempstar 1087952 1087953 1173636 CEPL130524-01 Honeywell ST74A1004 ST74A1020 ST74A1038 ST74A1053 ST74C1002 ICM DFORB24A2I300 DFORB-AB1004 DFORF DFOSP24A2 ICM300C ICM301C ICM302C ICM303C ICM304 ICM307 ICM316 ICM317 ICM318 ICM319 ICM320 ICM321 ICM322 ICM323 W1001-4 ICP 1052757 1069364 Intertherm 6208800 Lennox 100269-01 100269-02 100269-04 100269-05 11K7101 1507N170027 29M0101 29M0201 30W87 33G9501 34M6301 46K67 56M3701 68J2901 68J8401 78H6801 84W8801 86G1601 97M81 LB-101263A LB-101263B Nordyne 620880 621301A 621579B 621579C 624519A 624608 624626 624633 624644 624656 624700 917012 917178 917178A 920338 Ranco DT2 Rheem 47-102684-01 47-102684-02 47-102684-03 47-102684-04 47-102684-07 47-102684-08 47-102684-83 47-102685-01 47-102685-02 47-102685-03 47-102685-04 47-102685-05 47-102685-06 47-102685-84 47-21517-11 47-21517-13 47-21517-14 47-21517-16 47-21517-17 47-21517-18 47-21517-22 47-21517-23 47-21517-24 47-21517-82 47-21517-88 47-21517-92 47-21776-01 47-21776-06 47-21776-86 DDL-013002-0RH DDL-013002-1RH DDL-013102-1RH DDL-017002-2RH DDL-017102-1RH DDL-017702-1RH DDL-117702-3RH DDL-122131-2RH Robertshaw DT2-1000 TD-10 SnyderGeneral 1395-329 CEBD430524-04B Tempstar/ICP 1084-100 1084-83-1008 1087562 Trane 21C140501G18 21C140501G27 21C140501G36 21C140501G37 21C140501G38 21C140501G42 21C140501G44 21C140501G45 21C140501G53 21C140501G54 21C140501G55 21C140501G60 21C142827G01 CNT01106 CNT01108 CNT01129 CNT01152 CNT01431 CNT01510 CNT01642 CNT01923 CNT01924 CNT01926 CNT02514 CNT02515 CNT02516 CNT02920 CNT02935 CNT03715 CNT03716 CNT04362 CNT04363 CNT04364 CNT04366 CNT04368 CNT04695 CNT05001 CNT05008 CNT05009 CNT05010 CNT05482 CNT05875 Weatherking 840-4-5548 White-Rodgers 47D40-801 47D43-101 47D43-111 47D43-111 02 47D43-811 90-621 York 031-00872-001 031-00872-002 031-00872-003 031-00872-701 031-00872-702 031-00872-703 031-01222-000 031-01251-000 031-01268-000 031-01954-000 031-01975-000 031-09104-000 031-09170-000 331-01975-001 331-01975-102 331-09139-000 9218-3741 S1-03100872701 S1-03109170000 S1-33101954000 S1-33101975102 Cross Reference: Replaces virtually all single stage defrost controls, including: Universal Heat Pump Defrost Control For Single Stage Applications 47D01U-843 Electrical Rating Control Voltage: 24 VAC 50/60 Hz Line Voltage: 208/240 VAC 50/60 Hz Input Ratings: Outdoor PSC Fan: 0.5 HP @ 240 VAC, 0.125 HP @ 120 VAC Contactor Coil: 24 VAC Aux Heat (D/W/X2): 24 VAC Reversing Valve: 24 VAC Operating Temperature Range -40° to 150°F (-40° to -65°C) Humidity Range 0 - 95% relative humidity, non condensing Dimensions / Mounting 5.75”W x 4.72”L x 1.75”H Replacement Kit Contents Defrost control board, wiring harnesses, coil and ambient temp sensors, mounting accessories and labels. Auxiliary Heat Lockout Above the selected temperature, auxiliary heat will only run during defrost operation. Selectable from 0° to 40°F or off*. Compressor Lockout Below the selected temperature the compressor does not operate, except in defrost cycle. Selectable from -10° to 45°F or off*. Reversing Valve Shift Delay Limit excessive noise in and out of a defrost cycle. Selectable 0, 12 or 30* second delay. Short-Cycle Protection 0, 3 or 5* minute selectable delay between cycles. Brownout Protection Auto shut off when control voltage drops below 16 VAC for more than 4 seconds . Selectable On* or Off. Random Start Delay Delays operation for a random delay after power outage to protect the compressor and avoid brownouts. Selectable On* or Off. Timing Specifications All timing is accurate to +/- 5% of nominal over the full temperature and voltage range at 60 Hz. All timings are 20% longer when operated with 50 Hz power supply. *=Default Setting For complete, up to date cross reference information, install WRMobile on your iOS or Android smartphone today.
1

Universal Heat Pump Defrost Control ... - copeland-scroll.comcopeland-scroll.com/.../Documents/cross-reference.pdf · Fast 1093410 Goettl 305007 Goodman 1084-03-2022 ... Compressor

Mar 11, 2018

Download

Documents

hoangdang
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Universal Heat Pump Defrost Control ... - copeland-scroll.comcopeland-scroll.com/.../Documents/cross-reference.pdf · Fast 1093410 Goettl 305007 Goodman 1084-03-2022 ... Compressor

R-4430

Saint Louis, Missouri Markham, Ontario314-553-3600 905-948-3411

white-rodgers.comemersonclimate.com

The Emerson logo is a trademark anda service mark of Emerson Electric Co.

Specifications

Replaces:

AmanaC64301-1C6431001Arcoaire32312-003232140Armstrong39840B00144614-00144614-00246257-00147181-001R46257-001R46614-002R47181-001Carrier150-83-6A621-xxxCES0110063-00CES0110063-01CES0110063-02ACES0130024-00CES0130024-01CES0130076HK25SZ359AHK32EA001HK32EA003HK32EA007HK32EA008HK32FA003HK32FA006Coleman3030A374

Comfortmaker1029-23433210034332101Evcon9218-374Fast1093410Goettl305007Goodman1084-03-20221084-200D20293901B1226006B1226008LR40061PCBDM101PCBDM130PCBDM133PCBDM160Heil QuakerHQ1052757Heil/Tempstar108795210879531173636CEPL130524-01HoneywellST74A1004ST74A1020ST74A1038

ST74A1053ST74C1002ICMDFORB24A2I300DFORB-AB1004DFORFDFOSP24A2ICM300CICM301CICM302CICM303CICM304ICM307ICM316ICM317ICM318ICM319ICM320ICM321ICM322ICM323W1001-4ICP10527571069364Intertherm6208800Lennox100269-01100269-02100269-04100269-0511K7101

1507N17002729M010129M020130W8733G950134M630146K6756M370168J290168J840178H680184W880186G160197M81LB-101263ALB-101263BNordyne620880621301A621579B621579C624519A624608624626624633624644624656624700917012917178917178A920338RancoDT2

Rheem47-102684-0147-102684-02 47-102684-03 47-102684-04 47-102684-07 47-102684-08 47-102684-83 47-102685-01 47-102685-02 47-102685-03 47-102685-04 47-102685-05 47-102685-06 47-102685-84 47-21517-11 47-21517-13 47-21517-14 47-21517-16 47-21517-1747-21517-1847-21517-2247-21517-2347-21517-2447-21517-8247-21517-8847-21517-9247-21776-0147-21776-0647-21776-86DDL-013002-0RHDDL-013002-1RHDDL-013102-1RHDDL-017002-2RH

DDL-017102-1RHDDL-017702-1RHDDL-117702-3RHDDL-122131-2RHRobertshawDT2-1000TD-10SnyderGeneral1395-329CEBD430524-04BTempstar/ICP1084-1001084-83-10081087562Trane21C140501G1821C140501G2721C140501G3621C140501G3721C140501G3821C140501G4221C140501G4421C140501G4521C140501G5321C140501G5421C140501G5521C140501G6021C142827G01CNT01106CNT01108CNT01129CNT01152CNT01431

CNT01510CNT01642CNT01923CNT01924CNT01926CNT02514CNT02515CNT02516CNT02920CNT02935CNT03715CNT03716CNT04362CNT04363CNT04364CNT04366CNT04368CNT04695CNT05001CNT05008CNT05009CNT05010CNT05482CNT05875Weatherking840-4-5548White-Rodgers47D40-80147D43-10147D43-11147D43-111 0247D43-81190-621

York031-00872-001031-00872-002031-00872-003031-00872-701031-00872-702031-00872-703031-01222-000031-01251-000031-01268-000031-01954-000031-01975-000031-09104-000031-09170-000331-01975-001331-01975-102331-09139-0009218-3741S1-03100872701S1-03109170000S1-33101954000S1-33101975102

Cross Reference: Replaces virtually all single stage defrost controls, including:

Universal Heat Pump Defrost ControlFor Single Stage Applications

47D01U-843

Electrical RatingControl Voltage: 24 VAC 50/60 HzLine Voltage: 208/240 VAC 50/60 HzInput Ratings: Outdoor PSC Fan: 0.5 HP @ 240 VAC, 0.125 HP @ 120 VAC Contactor Coil: 24 VAC Aux Heat (D/W/X2): 24 VAC Reversing Valve: 24 VAC

Operating Temperature Range -40° to 150°F (-40° to -65°C)

Humidity Range 0 - 95% relative humidity, non condensing

Dimensions / Mounting 5.75”W x 4.72”L x 1.75”H

Replacement Kit ContentsDefrost control board, wiring harnesses, coil and ambient temp sensors, mounting accessories and labels.

Auxiliary Heat LockoutAbove the selected temperature, auxiliary heat will only run during defrost operation. Selectable from 0° to 40°F or off*.

Compressor LockoutBelow the selected temperature the compressor does not operate, except in defrost cycle. Selectable from -10° to 45°F or off*.

Reversing Valve Shift Delay Limit excessive noise in and out of a defrost cycle. Selectable 0, 12 or 30* second delay.

Short-Cycle Protection0, 3 or 5* minute selectable delay between cycles.

Brownout Protection Auto shut off when control voltage drops below 16 VAC for more than 4 seconds . Selectable On* or Off.

Random Start DelayDelays operation for a random delay after power outage to protect the compressor and avoid brownouts. Selectable On* or Off.

Timing SpecificationsAll timing is accurate to +/- 5% of nominal over the full temperature and voltage range at 60 Hz. All timings are 20% longer when operated with 50 Hz power supply.

*=Default Setting

For complete, up to date cross reference information, install WRMobile on your iOS or Android smartphone today.