A00-01 GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS ●
A01-01 OVERALL SITE PLAN ●
A10-01 FLOOR PLAN - LEVEL 01 ●
A10-02 FLOOR PLAN - ROOF ●
A12-01 REFLECTED CEILING PLAN - LEVEL 01 ●
A13-01 FINISH PLAN AND LEGEND ●
A13-02 FLOOR PATTERN PLAN ●
A14-01 FURNITURE PLAN - LEVEL 01 ●
A20-01 BUILDING ELEVATIONS ●
A21-01 BUILDING SECTIONS ●
A31-01 EXTERIOR WALL SECTIONS ●
A31-02 EXTERIOR WALL SECTIONS ●
A32-01 EXTERIOR WALL TYPES AND DETAILS ●
A32-10 EXTERIOR ENVELOPE DETAILS - ROOF DETAILS ●
A32-11 EXTERIOR ENVELOPE DETAILS - ROOF DETAILS ●
A33-01 EXTERIOR ENLARGED WALL DETAILS ●
A40-01 INTERIOR ELEVATIONS ●
A40-02 INTERIOR ELEVATIONS ●
A40-03 INTERIOR ELEVATIONS ●
A43-01 ENLARGED TOILET ROOM PLANS AND ELEVATIONS ●
A52-01 PLAN DETAILS ●
A52-02 PLAN DETAILS ●
A61-01 INTERIOR PARTITION TYPES & DETAILS ●
A61-10 CEILING DETAILS ●
A62-01 DOOR SCHEDULE AND TYPICAL DETAILS ●
A63-01 WINDOW ELEVATIONS ●
A66-00 LAB CASEWORK SCHEDULE ●
A66-01 ENLARGED LAB PLANS ●
06-MECHANICAL
M-001 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES ●
M-002 MECHANICAL SCHEDULES ●
M-100 LEVEL 01 MECHANICAL RENOVATION PLAN ●
M-101 ROOF MECHANICAL RENOVATION PLAN ●
M-500 CONTROL SCHEMATICS AND SEQUENCES OF OPERATION ●
M-501 CONTROLS SCHEMATICS AND SEQUENCES ●
M-502 CONTROL SCHEMATICS AND SEQUENCES ●
M-900 MECHANICAL DETAILS ●
M-901 MECHANICAL DETAILS ●
07-ELECTRICAL
E001 ELECTRICAL SYMBOLS, LEGEND AND ABBREVIATIONS ●
E002 LUMINAIRE SCHEDULE ●
E010 ONE LINE DIAGRAM - DEMOLITION ●
E011 ONE LINE DIAGRAM ●
E012 ONE LINE DIAGRAM ●
E013 ONE LINE DIAGRAM ●
E050 LEVEL 01 OVERALL PLAN ●
E101B LEVEL 01 LIGHTING PLAN AREA B ●
E201B LEVEL 01 POWER PLAN AREA B ●
E202B ROOF POWER PLAN ●
E301B LEVEL 01 FIRE ALARM PLAN AREA B ●
E501 ENLARGED PLANS ●
E701 ELECTRICAL PANELBOARD SCHEDULES ●
09-PLUMBING
P-001 PLUMBING LEGEND, GENERAL NOTES AND SCHEDULES ●
P-200 PLUMBING UNDERFLOOR PLAN ●
P-201 PLUMBING FIRST FLOOR PLAN ●
P-901 PLUMBING DETAILS ●
09.2-PLUMBING
FP-001 FIRE PROTECTION LEGEND, GENERAL NOTES ANDSPECIFICATIONS
●
FP-201 FIRE PROTECTION FIRST FLOOR PLAN ●
27-TELECOMMUNICATIONS
T00-01 TELECOM INDEX ●
T01-01 TELECOM RISER DIAGRAM ●
T10-00 TELECOM SITE PLAN ●
T10-01 TELECOM FLOOR PLAN ●
T12-01 TELECOM REFLECTED CEILING PLAN ●
28-AUDIOVISUAL
TA00-01 AUDIOVISUAL INDEX ●
TA10-01 AUDIOVISUAL FLOOR PLAN ●
TA12-01 AUDIOVISUAL REFLECTED CEILING PLAN ●
TA61-01 AUDIOVISUAL DETAILS ●
TA61-02 AUDIOVISUAL DETAILS ●
TA62-01 AUDIOVISUAL SCHEMATICS ●
TA62-02 AUDIOVISUAL SCHEMATICS ●
29-SECURITY
TY00-01 SECURITY INDEX ●
TY10-01 SECURITY FLOOR PLAN ●
TY12-01 SECURITY REFLECTED CEILING PLAN ●
CONTROL JOINT
CEILING HEIGHT DESIGNATION PER AREA. WHERENO HEIGHT IS DESIGNATED, ASSUME 9'-0"
SUPPLY AIR GRILLEREFER TO MECHANICAL DRAWINGSFOR ADDITIONAL INFORMATION
SUSPENDED 2' X 2' ACOUSTICALCEILING SYSTEM
SUSPENDED 2' X 4' ACOUSTICALCEILING SYSTEM
CEILING DETAIL / SECTION TAG
SUPPLY STRIP DIFFUSER RE: MECHANICAL
SPEAKER; RE: AUDIO VISUAL DRAWINGS
CAMERA; RE: SECURITY DRAWINGS
GP
ES
EXIT LIGHTING
GYPSUM BOARD CEILING
EXPOSED STRUCTURE
RETURN AIR GRILLEREFER TO MECHANICAL DRAWINGSFOR ADDITIONAL INFORMATION
EXHAUST AIR GRILLEREFER TO MECHANICAL DRAWINGSFOR ADDITIONAL INFORMATION
XXA-XXX
SIM
EXPANSION JOINT
9' - 0" AFF
RCP LEGEND
RCP NOTES BY NUMBER
TYPE A - 1 x 4 TROFFER LIGHT
TYPE B - 2 X 4 TROFFER LIGHT
TYPE C - RECESSED DOWNLIGHT
TYPE F - EXTERIOR WALL PACK
CJ
TYPE D - LINEAR PENDANT LIGHT
TYPE E - RECESSED COVE
THE CONTRACTOR SHALL COMPARE THIS REFLECTED CEILING PLAN WITH ELECTRICAL LIGHTING PLANS, MECHANICAL SUPPLY, RETURN, AND EXHAUST PLANS. THE CONTRACTOR SHALL REPORT ANY OMISSIONS OR INCONSISTENCIES TO THE ARCHITECT.
SEE ELECTRICAL DRAWINGS FOR THE LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS, SPEAKERS, NURSE CALL DOME LIGHTS, EXIT SIGNAGE, FIRE ALARM DEVICES, WALL MOUNTED EXIT LIGHTS, ETC.
FOR FURTHER DIMENSIONS SEE LARGE SCALE PLANS, SECTIONS, ELEVATIONS, AND DETAILS.
COORDINATE GYPSUM BOARD FURR DOWN HEIGHTS WITH FULL HEIGHT CABINETS AND INTERIOR ELEVATIONS (A45 SERIES)
SPRINKLER HEAD LOCATIONS ARE NOT SHOWN ON ARCHITECTURAL REFLECTED CEILING PLANS. (BUILDING IS TO BE "FULLY SPRINKLERED") PER NFPA 13 AND OWNER'S INSURANCE COMPANY'S REQUIREMENTS.
18" MINIMUM VERTICAL CLEARANCE SHALL BE MAINTAINED BETWEEN THE BOTTOM OF EXTENDED SPRINKLER HEADS AND THE TOP OF ANY FILES, SHELVING, LOCKERS, ETC.
THE CONTRACTOR SHALL VERIFY THAT ACCESS PANELS OF TYPE SPECIFIED ARE INSTALLED IN NON-ACCESSIBLE TYPE CEILINGS WHERE SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING, OR ELECTRICAL ITEMS MAY BE REQUIRED. ACCESS PANELS SHALL BE THE FIRE RATED TYPE EQUAL TO THE RATING OF THE CEILING IN WHICH THEY OCCUR.
PRE-MANUFACTURED SHOWER UNITS ARE PROVIDED WITH LIGHT FIXTURES (REF ELECTRICAL FOR CONNECTION.)
RELOCATE SUPPLY DRAIN AND VENT PIPES TO MAINTAIN SCHEDULED CEILING HEIGHTS. COORDINATE RELOCATIONS WITH MEP ENGINEERS.
WHERE EXISTING LAY-IN CEILINGS ARE TO REMAIN, THE CONTRACTOR SHALL REPLACE ANY TILE THAT HAS BEEN DAMAGED WITH MATERIALS THAT MATCH THE EXISTING FOR COLOR, TEXTURE, PATTERN, ETC. IF UNIFORMITY CANNOT BE ACHIEVED, THE CONTRACTOR SHALL REPLACE THE ENTIRE CEILING WITHIN THE SPACE WITH NEW MATERIAL.
4B Technology Group12600 Northborough Dr. Ste. 290
Houston, Texas 77067t 832.241.0049
www.4btechnology.com
INTERIM REVIEW
DESIGN DEVELOPEMENT
ENERGY RESEARCH PARK -BUILDING 9B: PACKAGE 3 ENVELOPE & BUILD-OUT
9/7
/20
17
9:1
0:4
1 A
M
C:\
tem
p\B
LD
G9B
_A
RC
H_b
lum
erd
.rvt
A12-01
REFLECTED CEILINGPLAN - LEVEL 01
09/06/2017Author
DRRG
<<< Indicates Sheet Keynote on Plan
1/8" = 1'-0"1 LEVEL 01 - REFLECTED CEILING PLAN
NO ISSUE DATE
LE
GE
ND
DIS
RE
GA
RD
LE
GE
ND
IT
EM
S N
OT
IN
DIC
AT
ED
ON
DR
AW
ING
S
SYMBOL DESCRIPTIONABBREV.
FD/FSD
DESCRIPTIONABBREV.SYMBOL
MVD
VD
SA/OA
RA
EA/REA
OR
10
1
CARBON DIOXIDE SENSOR
N.O.
HUMIDITY SENSOR
DIFFERENTIAL PRESSURE SENSOR
MOTOR STARTER
NORMALLY CLOSED
NORMALLY OPEN
N.C.
VARIABLE FREQUENCY DRIVE
FREEZE STAT
FILTER GAUGE
DIFFERENTIAL PRESSURE SWITCH
AIRFLOW MEASURING STATION
ELECTRICAL SIGNAL
DAMPER OR VALVE ACTUATOR
HIGH PRESSURE SHUT OFF SWITCH
NEW WORK
EXISTING WORK
FIRE/FIRE SMOKE DAMPER
RETURN AIR DUCT
SUPPLY/OUTSIDE AIR DUCT
EXHAUST/RELIEF AIR DUCT
ACCESS DOOR
MOTORIZED VOLUME DAMPER
VOLUME DAMPER
SUPPLY AIR DIRECTION
OFFSET AIR QUANTITY (CFM)/EXHAUST/RETURN DIRECTION
TEMPERATURE SENSOR
THERMOSTAT
HUMIDISTAT
SMOKE DUCT DETECTOR
SMOKE DETECTOR
STATIC PRESSURE SENSOR
KEYED NOTE
REVISION TRIANGLE
DENOTES RECTANGULAR DUCTWORK
DENOTES OVAL DUCTWORK
DENOTES ROUND DUCTWORK/PIPING12"
70/22
70/22 O.
VARIABLE FREQUENCY DRIVE
ABOVE FINISHED FLOOR
BOTTOM OF DUCT
AFF
VFD
BOD
FLAT OVAL
(E)/EXIST.
FO
EXISTING
BOP BOTTOM OF PIPE
CAV CONSTANT AIR VOLUME
VARIABLE AIR VOLUMEVAV
C/C COOLING COIL
HEATING COILH/C
CFM CUBIC FEET PER MINUTE
EXHAUST FANEF
EXH EXHAUST
FAN COIL UNITFCU
GPM GALLONS PER MINUTE
NOT TO SCALENTS
SAD SOUND ATTENUATING DEVICE
AFMS AIR FLOW MEASURING STATION
VTR VENT THRU ROOF
DDC DIRECT DIGITAL CONTROL
AIR HANDLING UNITAHU
COMPRESSED AIR
CHS
CWS
CWR
HWS
CHR
CHILLED WATER SUPPLYCHS
CONDENSING WATER RETURN
CONDENSING WATER SUPPLY
CHILLED WATER RETURN
HOT WATER SUPPLY
CWS
CWR
HWS
CHR
THREE-WAY CONTROL VALVE
TWO-WAY CONTROL VALVE
BUTTERFLY VALVE
SOLENOID VALVE
VENTURI FLOW TUBE
THERMOMETER WELL
PLUG VALVE
GAGE COCK
VALVE BOX
CHECK VALVE
GLOBE VALVE
GATE VALVE
BALL VALVE
PRESSURE RELIEF VALVE
# OF STEAM RETURN
# OF STEAM SUPPLY
PRESSURE REDUCING VALVE
HOT WATER RETURN
PRV
STRAINER
ANCHOR
FLEXIBLE JOINT
GAGE
REDUCER
UNION
THERMOMETER
RV
HWR
A
#R
#S
HWR
#S
#R
A
PCR PCR PUMP CONDENSATE RETURN
CR CR CONDENSATE RETURN
H
T
TEMPORARY WORK
CO2
HS
ES
DP
VFD
FS
G
DPS
HP
AFMS
S
TS
DD
HS
SP
ORT
MECHANICAL SYSTEMS INFORMATION
TYPES OF SYSTEMS
DESIGN CONDITIONS
OFFICE, CLASSROOM, AND AUDITORIUM
LABORATORY CLASSROOMS
SUMMER OUTSIDE (DEG. F DB/WB) (ASHRAE 1% DRY BULB/WET BULB)
WINTER OUTSIDE (DEG F) (ASHRAE 99.6% HEATING DB)
SUMMER INSIDE:
OFFICES, CONFERENCE ROOMS, LABS
ELECTRICAL ROOMS
WINTER INSIDE (OCCUPIED SPACES)
FRESH (OUTSIDE) AIR (PER ASHRAE 62-2010)
OFFICES, CONFERENCE ROOMS
CORRIDORS
LABORATORIES OCCUPIED (MINIMUM)
STORAGE ROOMS
JANITORS ROOMS
97.4 F / 79.1 F
24.8 F DB
75 F DB, 50%RH
80 F DB
70 F DB
5 CFM/P + 0.06 CFM/SQ.FT
0.06 CFM/SQ.FT
10 CFM/P + 0.06 CFM/SQ.FT
OR 6 AIR CHANGES/HR
0.12 CFM/SQ.FT
1 CFM/SQ.FT. EXHAUST
SINGLE ZONE DX ROOFTOP AIR HANDLING UNIT WITH COOLING COIL SERVING VAV TERMINALS WITH ELECTRIC HEATING COILS. OUTSIDE AIR IS MODULATED BY CO2 READINGS.
SINGLE ZONE DX ROOFTOP AIR HANDLING UNIT WITH COOLING COIL SERVING VAV TERMINALS WITH ELECTRIC HEATING COILS. OUTSIDE AIR IS PRE-TREATED VIA AN ENERGY RECOVERY WHEEL WITHIN THE RTU AND MODULATED BY CO2 READINGS.
GE
NE
RA
L N
OT
ES
THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS.
IN ANY CASE WHERE A PIPE OR DUCT SHOWN ON A PLAN SHEET DIFFERS FROM THAT SHOWN IN A SCHEMATIC OR DETAIL, USE THE LARGER OF THE TWO SIZES SHOWN.
PIPING SHOWN ON EACH PLAN IS RUN ABOVE THE CEILING ON THE FLOOR WHERE IT IS SHOWN UNLESS OTHERWISE NOTED.
ALL ELEVATIONS INDICATED IN THIS WAY (8'-0") ARE THE ELEVATIONS FROM THE FINISHED FLOOR DIRECTLY BELOW TO THE BOTTOM OF THE BARE PIPE OR DUCT.
MOUNT TEMPERATURE AND HUMIDITY SENSORS 44 INCHES ABOVE FINISHED FLOOR AND CENTERED ABOVE THE LIGHT SWITCHES WHERE BOTH OCCUR IN THE SAME LOCATION, UNLESS OTHERWISE NOTED.
PROVIDE FIRE DAMPER, ACCESS DOOR IN ALL DUCTWORK PIERCING FLOORS, AND 2 HOUR FIRE RATED WALLS.
COORDINATE LOCATION OF CEILING DIFFUSERS AND GRILLES WITH LIGHTING. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS.
DUCT RUN-OUTS TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK SIZE.
SUPPLY DUCT BRANCH TO TERMINAL BOXES SHALL BE SAME SIZE AS BOX INLET SIZE UNLESS OTHERWISE NOTED. REFER TO 07/M-901.
DUCT SIZE SHOWN ARE NET FREE AIR PASSAGE DIMENSIONS. DUCTS ARE NOT LINED, BUT ARE EXTERNALLY INSULATED.
COORDINATE INSTALLATION OF EQUIPMENT AND PIPING WITH ELECTRICAL CONTRACTOR TO INSURE NEC CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS.
DIFFUSER & GRILLE SCHEDULE NOTES
1. MAX NC-30 FOR ALL AIR DEVICES. NC SHALL BE CALCULATED AS PER AHRI 885-2008 ASSUMING LAY-IN ACOUSTICAL TILE.2. PROVIDE INTEGRAL OBD FOR SIDEWALL DIFFUSERS AND GRILLES.3. ALL DIFFUSERS IN GYP. BOARD CEILINGS TO HAVE FLOATABLE EDGE TRIM.
AIR DEVICE NOMENCLATURE
[A]5000
TYP 10
DIFFUSER MARK
NUMBER OF DIFFUSERS
DEVICE CFM
Document incomplete.Not intended for permit, bidding or construction.
FAN POWERED TERMINAL BOX CONNNECTION DETAIL W/ELECTRICALHEAT
M-901
RECTANGULAR DUCT SUPPORTED BY UNISTRUT DETAIL M-900
REFRIGERANT PIPE THRU ROOF DETAIL M-900
RETURN AIR SOUND ATTENUATOR DETAIL M-901
ROOF MOUNTED EXHAUST FAN DETAIL M-901
ROOF TOP UNIT DETAIL M-901
SCHEDULE - DIFFUSER & GRILLE
MARK
CFM
RANGE NECK SIZE SUPPLY RETURN EXHAUST TYPE PATTERN MANUFACTURER & MODEL NUMBER
A 0-180 6'' X 24" X 24" PLAQUE 4-WAY PRICE ASPD FULL FACE ALUMINUM CONSTRUCTION
B 181-350 8'' X 24" X 24" PLAQUE 4-WAY PRICE ASPD FULL FACE ALUMINUM CONSTRUCTION
C 351-450 10'' X 24" X 24" PLAQUE 4-WAY PRICE ASPD FULL FACE ALUMINUM CONSTRUCTION
D 451-710 12'' X 24" X 24" PLAQUE 4-WAY PRICE ASPD FULL FACE ALUMINUM CONSTRUCTION
F 0-1000 22" X 22" X 24" X 24" PERF. FACE PERF PRICE APDDR, NON-DUCTED ALUMINUM CONSTRUCTION
H 161-275 8'' X 24" X 24" PERF. FACE PERF PRICE APDDR ALUMINUM CONSTRUCTION
I 276-435 10'' X 24" X 24" PERF. FACE PERF PRICE APDDR ALUMINUM CONSTRUCTION
J 436-625 12'' X 24" X 24" PERF. FACE PERF PRICE APDDR ALUMINUM CONSTRUCTION
L RE: DWGS RE: DWGS X SIDEWALL GRILLE DOUBLE DEFLECTION PRICE 620 FS, 3/4" BLADE SPACING ALUMINUM FACE AND FRAME
M RE: DWGS RE: DWGS X X SIDEWALL GRILLE SINGLE DEFLECTION PRICE 630 FL ALUMINUM FACE AND FRAME
W 161-275 8'' X 24" X 24" PERF. FACE PERF PRICE APDDR ALUMINUM CONSTRUCTION
NO ISSUE DATE
SINGLE DUCT TERMINAL BOX SCHEDULE GENERAL NOTES
A. ABOVE SELECTIONS BASED ON PRICE MODEL SDV.B. INLET SIZE INDICATED IS THE MINIMUM INLET SIZE ACCEPTABLE. MANUFACTURER MAY INCREASE INLET SIZE IF NECESSARY TO MEET
PROJECT REQUIREMENTS.C. MAX SP IN.WG IS THE MAXIMUM STATIC PRESSURE DROP ALLOWED THROUGH THE BOX AND COIL AT SCHEDULED MAXIMUM CFM.D. PROVIDE CONTROL POWER TRANSFORMER PER SPECIFICATIONS. DIV 26 SHALL PROVIDE SINGLE POINT POWER CONNECTION AS
SCHEDULED ABOVE. DIV. 23 TO PROVIDE UNIT ELECTRICAL DISCONNECT.
SINGLE DUCT TERMINAL BOX SCHEDULE NOTES
1. TERMINAL BOX HAS NO ELECTRIC HEATING COIL.
FAN POWERED TERMINAL BOX SCHEDULE GENERAL NOTES
A. ABOVE SELECTIONS BASED ON PRICE MODEL FDC (SERIES).B. INLET SIZE INDICATED IS THE MINIMUM INLET SIZE ACCEPTABLE. MANUFACTURER MAY INCREASE INLET SIZE IF NECESSARY TO MEET PROJECT REQUIREMENTS.C. EXTERNAL STATIC PRESSURE INCLUDES LOSSES DUE TO DUCTWORK AND AIR DEVICES. INCLUDE ELECTRIC HEATING COIL PRESSURE DROP, FILTER PRESSURE
DROP, AND INTERNAL LOSSES WHEN CALCULATING TOTAL FAN STATIC PRESSURE AND SELECTING TERMINAL BOX.D. MAXIMUM STATIC PRESSURE IS THE MAXIMUM ALLOWABLE AIRSIDE STATIC PRESSURE LOSS THROUGH THE BOX AT SCHEDULED MAXIMUM PRIMARY FLOW.
(PARALLEL BOX). FOR SERIES BOX, IT IS THE MAXIMUM PRESSURE DROP THROUGH THE BOX INLET.E. PROVIDE CONTROL POWER TRANSFORMER PER SPECIFICATIONS. DIV 26 SHALL PROVIDE SINGLE POINT POWER CONNECTION AS SCHEDULED ABOVE.F. THE SCHEDULED LEAVING AIR TEMPERATURE (LAT) IS THE BOX LEAVING AIR TEMPERATURE (SUPPLY AIR TEMPERATURE). THE SCHEDULED ENTERING AIR
TEMPERATURE (EAT) IS THE AIR TEMPERATURE ENTERING THE HEATING COIL.
FAN POWERED TERMINAL BOX SCHEDULE NOTES
1. TERMINAL BOX HAS NO ELECTRIC HEATING COIL.
PACKAGED DX ROOFTOP AIR HANDLING UNIT SCHEDULE NOTES
1. SUPPLY AIR FANS SHALL BE EQUIPPED WITH VFD'S.2. EACH UNIT SHALL BE EQUIPPED WITH MULTIPLE STAGES OF COOLING FOR PRECISE TEMPERATURE CONTROL. MINIMUM OF
ONE DIGITAL SCROLL OR VFD DRIVEN COMPRESSOR PER UNIT.3. PROVIDE ROOF CURB WITH VIBRATION ISOLATION. REFER TO SPECIFICATIONS.4. UNIT SHALL USE R-410A REFRIGERANT AND MEET ASHRAE 90.1-2013 MINIMUM EFFICIENCIES.
DX FAN COIL UNIT SCHEDULE NOTES
1. PROVIDE REFRIGERANT PIPING BETWEEN UNIT AND FCU. CONDENSING UNIT MANUFACTURER TO SIZE REFRIGERANT PIPING. FCU AND CONDENSING UNIT SHALL BE BY SAME MANUFACTURER.
2. PROVIDE SINGLE POINT POWER CONNECTION. SEPARATE BUT ADJACENT DISCONNECT SWITCH TO BE PROVIDED AND INSTALLED BY DIVISION 26.
3. PROVIDE, WITHOUT EXCEPTION, MINIMUM MOTOR HORSEPOWER (SIZE) AS SCHEDULED.4. FAN COIL UNIT HAS NO AUXILIARY HEATING COIL.
FAN SCHEDULE NOTES
1. PROVIDE ALUMINUM INSECT SCREEN.2. COAT INSIDE/OUTSIDE OF FAN PER SPECIFICATIONS.3. PROVIDE ROOF CURB. PRE-WIRED DISCONNECT SWITCH. VERIFY ROOF PITCH.4. PROVIDE WITH FACTORY MATCH STARTER/DISCONNECT TO BE INSTALLED BY DIV. 26.5. PROVIDE PRE-WIRED MOTORIZED BACKDRAFT DAMPER.
Document incomplete.Not intended for permit, bidding or construction.
EF-9B-1 EXHAUST CENTRIFUGAL BELT 6120 0.75 2.03 3 460 3 60 1075 DDC GREENHECK MODEL GB. NOTE 1,2,3,4,5
EF-9B-2 EXHAUST CENTRIFUGAL DIRECT 450 0.35 0.08 1 460 3 60 1170 DDC GREENHECK MODEL QEID. NOTE 4
NO ISSUE DATE
DN
1 3 5 7 9 11
A
G
OFFICE148
OFFICE146
OFFICE144
VESTIBULE100
OPEN STAFF OFFICE120
OFFICE142
OFFICE152
OPEN STAFF OFFICE118
CONFERENCE122
FIRERISER
RM - 9B101
CLASSROOM115
OFFICE140
C
E.
OPEN OFFICE / BULLPEN102C
OFFICE154
OFFICE150
AUDITORIUM111
LOADING ZONE117
2 4 8 106
JAN106B
MEN106A
WOMEN108A
COMPUTER LAB110
TEACHINGLABORATORY
112
LAB SUPPORT113
OFFICE138
OFFICE136
OFFICE134
OFFICE132
IDF133
TEACHINGLABORATORY
116
OPEN OFFICE BULLPEN
124
VESTIBULE103
OPEN191B
OPEN102B
OPEN102A
CORRIDOR193
CORRIDOR191
STORAGE126
ELECTRICAL130
CORRIDOR192
B
D
F
LAB STORAGE114
OPENOFFICE
BULLPEN
135STORAGE137
MEN106
WOMEN108[220]
VV-9B-04
[440]VV-9B-03
[1520]VV-9B-24
[1130]VV-9B-23 [875]
VV-9B-20
[350]VV-9B-19
[875
]V
V-9
B-1
8
[795]VV-9B-16
[300]VV-9B-15
[320]VV-9B-12
[510]VV-9B-11
[2170]VV-9B-06
[1840]VV-9B-05
FCU-9B-1
TS
TS
TS
TS
TS
TS TS TS TS
TS
TS TS
TS
TS
TS
TS
TS
TS
[1925]FCV-9B-03
TS
TS
TSTS
TS
[2110]VV-9B-07
[440]VV-9B-02
[2295]VV-9B-01
[1145]VV-9B-10
TS
TS
[1925]FCV-9B-04
[2600]FCV-9B-02
[2600]FCV-9B-01
[2600]FCV-9B-05
VV-9B-14
460[D]
460[D] 460
[D]
455[D]
460[D]
435[C]
435[C]
435[C]
435[C]
430[C]
435[C]
435[C]
435[C]
435[C]
430[C]
430[C]
195[B]
195[B]
190[B]
195[B]
190[B]
190[B]
190[B]
190[B]
245[B]
245[B]
245[B]
245[B]
255[B]
255[B]
275[B]
310[B]
170[A]
300[B]
380[C]
380[C]
380[C]
380[C]
380[C]
380[C]
370[C]
220[B]
TS
24"/18"
12"/
14"
12"/14"
20"/18"
[855]VV-9B-08
30"/
20"
36"/20"
80"/
28
" S
A
[875]VV-9B-17
250[B] 12"/12"
[250]VV-9B-22
12"/14"12"/14"
100[A]
12"/12"18"/18"
435[C]
435[C]
440[C]
440[C]
440[C]
435[C]
440[C]
435[C]
12"/14"
12"/14"
24"/
20" 12"/10"
435[L]
12"/10"435[L]
12"/10"435[L]
12"/10"435[L]
12"/10"430[L]
12"/10"430[L]
12"/10"375[L]
12"/10"375[L]
12"/10"370[L]
12"/10"370[L]
12"/10"370[L]
12"/10"370[L]
12"/10"370[L]
12"/10"435[L]
12"/10"435[L]
12"/10"435[L]
12"/10"435[L]
12"/10"430[L]
10"/12"430[L]
245[B]
240[B]
310[B]
50"/20" RA
12"/10"TYP. 5
385[L]
20"/
18"
TYP. 5385[L]
[480]VV-9B-13
12"/12"
14"/14"12"/12"
12"/12"
50"/24" SA
40"/24"
[760]VV-9B-09
80[A]
85[A]20"/18"
36"/20"28"/20"20"/18"
350[B]
350[B]
350[B]
350[B]
350[B]
360[C]
200[B]
350[B]
[800]VV-9B-14
200[B]
175[A]
TS
20"/
18"
22"/
18"
18"ø
24"/
18"
50"/
24
" S
A
36"/24"
24"/20"
20"/18"
[875]VV-9B-21
20"/16"
16"/16"
250[B]
[1080]VE-9B-01[2520]
VE-9B-02
[2520]VE-9B-03
20"/
20"
12"/12"
TS
525[J]
525[J]
525[J]
525[J]
16"/16" 12"/12"
525[J]
525[J]
525[J]
16"/14"
16"/14"
8"/6"100[M]
14"/12"
14"/12"
16"/14"12"/12"
12"/12"
40"/24"
24"/20"
[2100]VE-9B-06
14"/12"
430[C]
70"/20"
350[I]
12"/12" RA
12"/12" RA
12"/12"450[L]
[2100]VE-9B-04
[350]VE-9B-05
12"/12"450[L]
12"/12"
14"/14"450[M]
TS
230[H]
230[H]
260[H]
260[H]
12"/12"
365[C]365
[C]
75[A]
75[A]
12"/12"
1
[1465]VV-9B-2618"/16"
TS
CO2
CO2
CO2
CO2
CO2
6"/6"100[L]
[450]EF-9B-2
14"/14"450[M]
30"/20" RA
14"/14"
[450]VV-9B-25
14"/12"
45[A]
GENERAL NOTES
A. REFER TO DIFFUSER SCHEDULE FOR SIZE OF RUNOUT AND DIFFUSER CONNECTION SIZE.
B. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF TERMINAL BOX AND LAB TRAC VALVES INSTALLATION DETAILS.
C. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF DIFFUSER INSTALLATION AND CONNECTION DETAILS.
D. CONTRACTOR SHALL PROVIDE CLEARANCE IN FRONT AND AT SIDES OF TERMINAL BOX UNIT CONTROL PANEL AND J-BOX AS REQUIRED BY N.E.C. (36 INCHES).
E. PROVIDE DUCTWORK TRANSITIONS AS REQUIRED AT TERMINAL BOX INLET AND DISCHARGE CONNECTIONS.
F. PROVIDE TURNING VANES IN ALL RECTANGULAR DUCT ELBOWS.
G. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF RETURN AIR TRANSFER DUCT INSTALLATION.
H. REFER TO MECHANICAL DETAIL SCHEDULE FOR DUCT PENETRATION THROUGH FIRE RATED PARTITION DETAIL LOCATION. PROVIDE ACCESS DOORS IN DUCTWORK AT FIRE DAMPERS AND FIRE/SMOKE DAMPERS. IDENTIFY ACCESS DOORS IN ACCORDANCE WITH SPECIFICATIONS.
I. INSULATE EXTERIOR OF ALL SUPPLY AIR DUCTWORK AND THE TOP OF ALL SUPPLY AIR DIFFUSERS.
J. PIPING AND DUCTWORK ARE NOT PERMITTED IN ELECTRICAL ROOMS, ELEVATOR MACHINE ROOMS AND COMMUNICATION ROOMS.
K. PROVIDE YOUNG REGULATORS FOR ALL DAMPERS LOCATED ABOVE HARD OR INACCESSIBLE CEILINGS. YOUNG REGULATORS SHALL BE PROVIDED WITH SOLID SHAFT CONNECTION; CABLE CONNECTION TO REGULATOR WILL NOT BE ACCEPTED.
L. ALL RETURN GRILLES SHALL BE MARK [F] UNLESS OTHERWISE NOTED.
NORTHNORTH
0'
Document incomplete.Not intended for permit, bidding or construction.
1 INTERNALLY LINE THE SUPPLY AIR DUCTWORKFROM THE POINT INDICATED BACK TO THE RTUDISCHARGE CONNECTION.
NO ISSUE DATE
20
20
15
2
M1/4
M1/4
1 3 5 7 9 11
A
G
C
E.
2 4 8 106
B
D
F
CU-9B-1
EF-9B-1
AHU-9B-3
AHU-9B-1
AHU-9B-2
1 2 3 4 5 6 7 8 9 10
11
A
B
C
D
E
F
G
80"/
28
" S
A
50"/
20"
RA
1
CD
CD
CD
1
GENERAL NOTES
A. REFER TO DIFFUSER SCHEDULE FOR SIZE OF RUNOUT AND DIFFUSER CONNECTION SIZE.
B. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF TERMINAL BOX AND LAB TRAC VALVES INSTALLATION DETAILS.
C. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF DIFFUSER INSTALLATION AND CONNECTION DETAILS.
D. CONTRACTOR SHALL PROVIDE CLEARANCE IN FRONT AND AT SIDES OF TERMINAL BOX UNIT CONTROL PANEL AND J-BOX AS REQUIRED BY N.E.C. (36 INCHES).
E. PROVIDE DUCTWORK TRANSITIONS AS REQUIRED AT TERMINAL BOX INLET AND DISCHARGE CONNECTIONS.
F. PROVIDE TURNING VANES IN ALL RECTANGULAR DUCT ELBOWS.
G. REFER TO MECHANICAL DETAIL SCHEDULE FOR LOCATION OF RETURN AIR TRANSFER DUCT INSTALLATION.
H. REFER TO MECHANICAL DETAIL SCHEDULE FOR DUCT PENETRATION THROUGH FIRE RATED PARTITION DETAIL LOCATION. PROVIDE ACCESS DOORS IN DUCTWORK AT FIRE DAMPERS AND FIRE/SMOKE DAMPERS. IDENTIFY ACCESS DOORS IN ACCORDANCE WITH SPECIFICATIONS.
I. INSULATE EXTERIOR OF ALL SUPPLY AIR DUCTWORK AND THE TOP OF ALL SUPPLY AIR DIFFUSERS.
J. PIPING AND DUCTWORK ARE NOT PERMITTED IN ELECTRICAL ROOMS, ELEVATOR MACHINE ROOMS AND COMMUNICATION ROOMS.
K. PROVIDE YOUNG REGULATORS FOR ALL DAMPERS LOCATED ABOVE HARD OR INACCESSIBLE CEILINGS. YOUNG REGULATORS SHALL BE PROVIDED WITH SOLID SHAFT CONNECTION; CABLE CONNECTION TO REGULATOR WILL NOT BE ACCEPTED.
L. ALL RETURN GRILLES SHALL BE MARK [F] UNLESS OTHERWISE NOTED.
NORTHNORTH
0'
Document incomplete.Not intended for permit, bidding or construction.
1 ROUTE RTU CONDENSATE TO DISCHARGE INNEAREST GUTTER FOR STORM DRAINCOLLECTION.
NO ISSUE DATE
NOTE: FVV TERMINALS SIMILAR, BUT FAN IS ON PLENUM INLET
WHERE INDICATED ON DRAWINGS
HEATING COIL WHERE INDICATED ON SCHEDULE. HEATING COIL SHALL BE LOCATED AT PLENUM INLET OF PARALLEL BOXES.
PRIMARY AIR
FILTER
SA
H
C
DDC TS
CO2
TS
SEQUENCE OF OPERATION
FAN POWERED VAV TERMINAL WITH HEAT
1. THE FAN POWERED BOXES SHALL BE CONTROLLED BY A FACTORY MOUNTED TERMINAL EQUIPMENT CONTROLLER (TEC).
2. THE TERMINAL BOXES SHALL OPERATE BASED UPON OCCUPANCY SCHEDULE. WHEN THE TERMINAL BOXES ARE SCHEDULED TO BE IN OPERATION, THEY SHALL MAINTAIN SPACE TEMPERATURE SETPOINT. DURING UNOCCUPIED MODE, THE TERMINAL BOXES SHALL BE DE-ENERGIZED AND THE PRIMARY DAMPERS SHALL BE CLOSED.
3. A SPACE TEMPERATURE SENSOR THROUGH THE DDC SYSTEM SHALL MODULATE THE NORMALLY CLOSED VAV DAMPER ACTUATOR TO MAINTAIN THE DESIRED SPACE TEMPERATURE INDEPENDENT OF THE DUCT STATIC PRESSURE DURING THE COOLING CYCLE.
4. FOR TERMINAL BOXES THAT SERVE ROOMS WITH CO2 SENSORS, THE DDC SYSTEM SHALL ALARM WHEN THE C02 LEVEL EXCEEDS THE SETPOINT (900 PPM, INITIAL, ADJUSTABLE) BY MORE THAN 10%.
5. NIGHT SETBACK
A. WHEN THE CENTRAL SYSTEM FAN IS OFF, THE VAV BOX FAN SHALL REMAIN DE-ENERGIZED WHEN THE ROOM TEMPERATURE IS ABOVE NIGHT SETBACK LOW SET POINT. UPON A DECREASE IN ROOM TEMPERATURE BELOW THE SET POINT (50˚F, FIELD ADJUSTABLE), THE FAN TERMINAL SHALL BE ENERGIZED TO PROVIDE INDUCED PLENUM AIR TO THE ROOM. ON FURTHER DROP IN TEMPERATURE BELOW SET POINT, THE NORMALLY CLOSED HW CONTROL VALVE SHALL BE MODULATED TO MAINTAIN DESIRED SPACE TEMPERATURE.
B. A NIGHT-TIME HIGH SET POINT TEMPERATURE SHALL ALSO BE MAINTAINED BY THE DDC SYSTEM. NIGHT-TIME HIGH SET POINT (55˚F, FIELD ADJUSTABLE) SHALL BE USED TO DE-ENERGIZE FAN UPON A RISE IN TEMPERATURE ABOVE NIGHT SETBACK HIGH SETPOINT. BOTH HIGH AND LOW NIGHT-TIME SET POINTS SHALL BE ADJUSTABLE FROM THE DDC.
6. SERIES TERMINAL UNIT FAN OPERATION (FCV, REFER TO TERMINAL BOX SCHEDULE.)
A. THE FAN WILL RUN CONSTANTLY. WITH SPACE TEMPERATURE ABOVE SET POINT, THE UNIT SHALL SUPPLY MAXIMUM OF SCHEDULED CFM. UPON A SIGNAL FOR LESS COOLING, THE PRIMARY AIR ACTUATOR SHALL PROPORTIONALLY REDUCE THE PRIMARY AIRFLOW UNTIL MINIMUM AIRFLOW IS REACHED. THROUGHOUT THIS SEQUENCE, THE FAN SHALL REMAIN ENERGIZED.
B. THE FAN WILL BE ENERGIZED TO PROVIDE CONSTANT FLOW OF INDUCED PLENUM AIR. UPON A FURTHER DROP IN ROOM TEMPERATURE BELOW SET POINT, THE ELECTRIC HEATING COIL WILL BE MODULATED TO SATISFY THE SPACE REQUIREMENTS.
C. PRIOR TO STARTING THE CENTRAL SYSTEM FAN, THE TERMINAL BOX FAN SHALL BE STARTED.
POINT SUMMARY
UH ERP BUILDING 9B
FVV & FCV TERMINAL UNITS
Heating Coil
Primary Air Damper
Space Temperature (Adjustable)
Fan
START/
STOP
DIGITAL
OPEN/
CLOSE
ON/OFF
X
OUTPUT
4 - 20
MA
X
ANALOG
0-10
VDC
X
1 - 18
PSI
OTHER AUXILIARY
CONTACT
PRESSURE
SWITCH
DIGITAL
LOW TEMP
SWITCH
END
SWITCH
SMOKE
DET. AUX
INPUT
CUR. MON.
RELAY
TEMP.
X
X
PRESS.
ANALOG
FLOW
(CFM,GPM)
X
HUMIDITY OTHER GRAPHIC
X
SOFTWARE
OTHER ALARM
HEATING COIL (WHERE SCHEDULED)
SPACE
PRIMARY AIR SA
H
C
TS
TSDDC
SEQUENCE OF OPERATION
SINGLE DUCT TERMINAL BOX (CV, VV)
1. THE VAV BOXES SHALL BE CONTROLLED BY A FACTORY MOUNTED TERMINAL EQUIPMENT CONTROLLER (TEC).
2. THE TEC SHALL MONITOR THE SPACE TEMPERATURE AND MODULATE THE AIRFLOW AND THE ELECTRIC HEATING COIL TO MAINTAIN SPACE TEMPERATURE SETPOINT (ADJUSTABLE).
3. THE VAV TERMINAL UNIT IS CONTROLLED WITHIN USER DEFINED MAXIMUM AND MINIMUM SUPPLY AIR VOLUME SETTINGS. THE CONTROLLER MONITORS THE ROOM TEMPERATURE SENSOR AND AIR VELOCITY SENSOR AND MODULATES THE SUPPLY AIR DAMPER IN SEQUENCE WITH THE ELECTRIC HEATING COIL TO MAINTAIN THE ROOM TEMPERATURE AT SET POINT. SUPPLY AIR VOLUME REMAINS AT MINIMUM WHEN THE ELECTRIC HEATING COIL IS ENERGIZED.
4. THE TEC SHALL MONITOR THE INLET AIR FLOW AND MODULATE THE DAMPER TO MAINTAIN PRESSURE INDEPENDENT CONTROL AT DESIGN AIR FLOW (ADJUSTABLE).
5. THE TEC SHALL MONITOR THE DISCHARGE AIR TEMPERATURE FOR ALL TERMINAL BOXES THAT HAVE HEATING COILS.
POINT SUMMARY
UH ERP BUILDING 9B
VV & CV TERMINAL UNITS
Heating Coil (where scheduled)
Primary Air Damper
Space Temperature (Adjustable)
START/
STOP
DIGITAL
OPEN/
CLOSE
ON/OFF
OUTPUT
4 - 20
MA
ANALOG
0-10
VDC
X
X
1 - 18
PSI
OTHER AUXILIARY
CONTACT
PRESSURE
SWITCH
DIGITAL
LOW TEMP
SWITCH
END
SWITCH
SMOKE
DET. AUX
INPUT
CUR. MON.
RELAY
TEMP.
X
X
PRESS.
ANALOG
FLOW
(CFM,GPM)
X
HUMIDITY OTHER GRAPHIC
X
SOFTWARE
OTHER ALARM
POINT SUMMARY
UH ERP BUILDING 9B
(SPLIT SYSTEM)
Evaporator Unit
Condensing Unit
Space Temperature (Adjustable)
START/
STOP
DIGITAL
OPEN/
CLOSE
ON/OFF
OUTPUT
4 - 20
MA
ANALOG
0-10
VDC
1 - 18
PSI
OTHER AUXILIARY
CONTACT
PRESSURE
SWITCH
DIGITAL
LOW TEMP
SWITCH
END
SWITCH
SMOKE
DET. AUX
INPUT
CUR. MON.
RELAY
TEMP.
X
PRESS.
X
ANALOG
FLOW
(CFM,GPM)
HUMIDITY OTHER GRAPHIC
X
SOFTWARE
OTHER ALARM
X
C
C
TO DDC
FILTER
(SPACE)
SEQUENCE OF OPERATION
SPLIT SYSTEM
1.
2.
3.
THE SPLIT SYSTEM MANUFACTURER'S CONTROLS SHALL CONTROL THE EVAPORATOR UNIT AND CONDENSING UNIT TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 70F(ADJUSTABLE).
A CURRENT SENSOR SHALL MONITOR THE FAN STATUS AND THE CONDENSING UNIT STATUS.
THE DDC SHALL MONITOR THE SPACE TEMPERATURE AND ALARM WHEN SPACE TEMPERATURE REACHES 5F(ADJUSTABLE) ABOVE SETPOINT .
TO
CONDENSING
UNIT
DX
CONDENSING UNIT
TO DDC
EVAPORATOR UNIT
TO
EVAPORATOR
UNIT
CS
CS
X X
Document incomplete.Not intended for permit, bidding or construction.
X SUPPLY FAN INTEGRAL TO UNIT.SUPPLY FAN (ON VFD) X X
SUPPLY AIR TEMPERATURE X X
COMPRESSOR(S) STATUS X X
GENERAL ALARMS X
AMPS X X
HIGH/LOW VOLTAGE ALARM XOUTSIDE AIR FLOW MEASURINGSTATION X
DUCT STATIC PRESSURE X
MISC. FANS POINTS & SEQUENCES
CS
MISC. FANS SEQUENCE OF OPERATIONS
1. THE EXHAUST FANS ARE EQUIPPED WITH ECM MOTORS THAT SHALL BE USED FOR AIR BALANCING.
2. THE FANS SHALL OPERATE AT A CONSTANT SPEED.
3. A CURRENT MONITORING RELAY ON EACH FAN SHALL BE USED TO MONITOR FAN STATUS.
TO DDC
GRAVITY BACKDRAFT DAMPER BY FAN MANUFACTUER.
RTU-9B-1,2
TODDC
VFD
OUTSIDE AIR
PKG DX AHU
DD
TO FIRE ALARM
SUPPLY AIR
RETURN AIR
SEQUENCE OF OPERATION (RTU-9B-1,2)
GENERAL
1. THE UNIT SHALL BE STARTED AND STOPPED BY THE DDC SYSTEM BASED UPON AN OCCUPANCY SCHEDULE PROVIDED BY THE OWNER.
2. ALL INTERNAL CONTROLS SHALL BE BY THE AHU MANUFACTURER. EACH UNIT SHALL HAVE A SEPARATE/INDEPENDENT BACNET INTERFACE WITH THE DDC SYSTEM.
SUPPLY AIR FAN
1. THE SUPPLY AIR FAN SPEED WILL BE MODULATED BY THE RTU INTERNAL CONTROLLER BASED ON STATIC PRESSURE SETPOINT AND FEEDBACK FROM THE BAS.
2. THE BAS SHALL MONITOR SUPPLY AIR TERMINAL BOX DAMPER POSITIONS, AND RESET THE STATIC PRESSURE SETPOINT IN INCREMENTS OF 0.01" W.G. (ADJUSTABLE) AT 15 MINUTE INTERVALS TO MAINTAIN ALL SUPPLY AIR TERMINAL DAMPERS AT 85% OR LESS OF FULL OPEN. THE INITIAL STATIC PRESSURE SETPOINT SHALL BE 1.0" W.G. (ADJUSTABLE).
SUPPLY AIR TEMPERATURE
1. THE SUPPLY AIR TEMPERATURE WILL BE CONTROLLED BY THE RTU INTERNAL CONTROLLER BASED ON THE SUPPLY AIR TEMPERATURE SETPOINT PROVIDED BY THE BAS (53F DB INITIAL, ADJUSTABLE).
OUTSIDE AIR
1. THE OUTSIDE AIRFLOW SHALL BE MONITORED BY THE RTU VIA ON BOARD AFMS. THE OUTSIDE AIR DAMPER SHALL BE MODULATED BY THE RTU TO MAINTAIN THE OUTSIDE AIRFLOW SETPOINT PROVIDED BY THE BAS.
SAFETIES
1. SMOKE DUCT DETECTORS LOCATED AT THE SUPPLY AIR DISCHARGE AND RETURN AIR INLET OF THE AIR UNIT SHALL ALARM (VIA THE FIRE ALARM SYSTEM) WHENEVER SMOKE IS DETECTED IN THE AIR UNIT. THE SUPPLY AIR FAN SHALL BE DE-ENERGIZED VIA HARD WIRED INTERLOCK.
2. THE RTU SHALL MONITOR STATIC PRESSURE ON THE DISCHARGE OF THE FAN, AND SHALL DE-ENERGIZE THE SUPPLY FAN WHENEVER STATIC PRESSURE EXCEEDS 3.5" W.G. (FIELD ADJUSTABLE), AND AN ALARM SHALL BE SENT TO THE DDC.
3. THE RTU SHALL MONITOR STATIC PRESSURE ON THE INTAKE OF THE FAN, AND SHALL DE-ENERGIZE THE SUPPLY FAN WHENEVER STATIC PRESSURE EXCEEDS NEGATIVE 2.0" W.G. (FIELD ADJUSTABLE), AND AN ALARM SHALL BE SENT TO THE DDC.
4. INTERNAL ALARMS FROM THE RTU SHALL BE BROADCASTED THROUGH THE BUILDING AUTOMATION SYSTEM.
DD
TO FIRE ALARM
D
X
SP
Document incomplete.Not intended for permit, bidding or construction.
X SUPPLY FAN INTEGRAL TO UNIT.SUPPLY FAN (ON VFD) X X
SUPPLY AIR TEMPERATURE X X
COMPRESSOR(S) STATUS X X
GAS HEATER STATUS X X
ALARMS X
AMPS X X
HIGH/LOW VOLTAGE ALARM X
SUPPLY DUCT STATIC PRESSURE X
EXHAUST DUCT STATIC PRESSURE X
SEQUENCE OF OPERATION (RTU-9B-3)
GENERAL
1.THE UNIT SHALL BE STARTED AND STOPPED BY THE DDC SYSTEM.
2. ALL INTERNAL CONTROLS SHALL BE BY RTU MANUFACTURER. EACH UNIT SHALL HAVE A SEPARATE/INDEPENDENT BACNET INTERFACE WITH DDC SYSTEM.
SUPPLY AIR FAN
1. THE SUPPLY AIR FAN SPEED WILL BE MODULATED BY THE RTU INTERNAL CONTROLLER BASED ON STATIC PRESSURE SETPOINT AND FEEDBACK FROM THE BAS.
2. THE BAS SHALL MONITOR SUPPLY AIR TERMINAL BOX DAMPER POSITIONS, AND RESET THE STATIC PRESSURE SETPOINT IN INCREMENTS OF 0.01" W.G. (ADJUSTABLE) AT 15 MINUTE INTERVALS TO MAINTAIN ALL SUPPLY AIR TERMINAL DAMPERS AT 85% OR LESS OF FULL OPEN. THE INITITIAL STATIC PRESSURE SETPOINT SHALL BE 1.0" W.G. (ADJUSTABLE).
EXHAUST AIR FAN
1. THE EXHAUST AIR FAN SPEED WILL BE MODULATED BY THE RTU INTERNAL CONTROLLER BASED ON STATIC PRESSURE SETPOINT AND FEEDBACK FROM THE BAS.
2. THE BAS SHALL MONITOR EXHAUST AIR TERMINAL BOX DAMPER POSITIONS, AND RESET THE STATIC PRESSURE SETPOINT IN INCREMENTS OF 0.01" W.G. (ADJUSTABLE) AT 15 MINUTE INTERVALS TO MAINTAIN ALL EXHAUST AIR TERMINAL DAMPERS AT 85% OR LESS OF FULL OPEN. THE INITITIAL STATIC PRESSURE SETPOINT SHALL BE NEGATIVE 1.0" W.G. (ADJUSTABLE).
SUPPLY AIR TEMPERATURE
1. THE SUPPLY AIR TEMPERATURE WILL BE CONTROLLED BY THE RTU INTERNAL CONTROLLER BASED ON THE SUPPLY AIR TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE) AS INDICATED THROUGH THE BAS.
2. THE INTERNAL RTU CONTROLS SHALL UTILIES VARIABLE SPEED CONTROLLERS AND HOT GAS BYPASS TO ACHIEVE LEAVING TEMPERATURE
OUTSIDE AIR
1. THE OUTSIDE AIRFLOW SHALL BE EQUAL TO THE TOTAL EXHAUST AIRFLOW PLUS 500 CFM (ADJUSTABLE).
ENERGY WHEEL
1. THE RTU IS EQUIPPED WITH AN ENERGY RECOVERY WHEEL. THE INTERNAL RTU CONTROLS SHALL MODULATE THE SPEED OF THE WHEEL TO ACHIEVE LEAVING AIR TEMPERATURE SETPOINT.
2. THE ENERGY RECOVERY WHEEL SHALL ONLY BE UTILIZED DURING NORMAL OPERATIONS. IT SHALL BE TURNED OFF DURING ECONOMIZER MODE.
ECONOMIZER
1. THE RTU SHALL BE EQUIPPED WITH AN ENTHALPY BASED ECONOMIZER. WHENEVER THE OUTSIDE AIR ENTHALPY VALUE IS BELOW 28 BTU/LB., THE RTU SHALL ENTER ECONOMIZER MODE. DURING ECONOMIZER MODE, THE RTU WILL SUPPLY 100% OUTSIDE AIR, AND SHALL BYPASS THE ENTHALPY WHEEL. RELIEF AIR SHALL BE TRACKED TO MAINTAIN THE OFFSET, AS INDICATED ABOVE.
2. WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 50°F (ADJUSTABLE), THE RTU SHALL EXIT ECONOMIZER MODE AND MIX RETURN AIR AND OUTSIDE AIR TO MAINTAIN THE LEAVING SUPPLY AIR TEMPERATURE SETPOINT.
SAFETIES
1. SMOKE DUCT DETECTORS LOCATED AT THE SUPPLY AIR DISCHARGE AND RETURN AIR INLET OF THE AIR UNIT SHALL ALARM (VIA THE FIRE ALARM SYSTEM) WHENEVER SMOKE IS DETECTED IN THE AIR UNIT. THE SUPPLY AIR FAN SHALL BE DE-ENERGIZED VIA HARD WIRED INTERLOCK.
2. THE RTU SHALL MONITOR STATIC PRESSURE ON THE DISCHARGE OF THE FAN, AND SHALL DE-ENERGIZE THE SUPPLY FAN WHENEVER STATIC PRESSURE EXCEEDS 4.5" W.G. (FIELD ADJUSTABLE), AND AN ALARM SHALL BE SENT TO THE DDC.
3. THE RTU SHALL MONITOR STATIC PRESSURE ON THE INTAKE OF THE FAN, AND SHALL DE-ENERGIZE THE SUPPLY FAN WHENEVER STATIC PRESSURE EXCEEDS NEGATIVE 2.0" W.G. (FIELD ADJUSTABLE), AND AN ALARM SHALL BE SENT TO THE DDC.
4. INTERNAL ALARMS FROM THE RTU SHALL BE BROADCASTED THROUGH THE BUILDING AUTOMATION SYSTEM.
5. THE INTERNAL RTU CONTROLS SHALL INTERLOCK THE OPERATION OF THE SUPPLY AND EXHAUST AIR FANS. IF EITHER FAN FAILS, THE RTU SHALL DE-ENERGIZE THE REMAINING FAN/UNIT AND SEND AN ALARM TO THE DDC SYSTEM.
RTU-9B-3
TODDC
VFD
OUTSIDE AIR
PKG DX AHU
SPDD
TO FIRE ALARM
RELIEF AIR
VFD
SUPPLY AIR
EXHAUST AIR
ECONOMIZER BYPASS
ENERGY RECOVERY WHEEL
DD
TO FIRE ALARM
D
X
SP
RETURN AIR
TODDC
Document incomplete.Not intended for permit, bidding or construction.