TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD, USA ISPD 2012
34

TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Dec 13, 2015

Download

Documents

Austin Gordon
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

TSV-Constrained Micro-Channel Infrastructure

Design for Cooling Stacked 3D-ICs

Bing Shi and Ankur Srivastava, University of Maryland, College

Park, MD, USA

ISPD 2012

Page 2: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Outline

• Introduction and Motivation• Thermal and Power model with micro-

channels• Formulation and Micro-channel

design algorithms• Experimental results• Conclusions

Page 3: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Introduction

• Conventional air cooling might be not enough for stacked 3D-ICs.– Micro-channel based liquid cooling is

developed.

• Micro-channel heat sinks are embedded below each silicon layer and the coolant fluid is pumped through the micro-channels.

Page 4: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Schematics

Page 5: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Effectiveness

Page 6: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Motivating example

• Conventionally, straight channels are used.– But TSVs will block the route of straight

channels.

Page 7: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Introduction (cont.)

• With bended structure, the micro-channels can reach those TSV-blocked hotspot regions which straight micro-channels cannot reach.

• Compared to straight channel design, up to 87% pumping power could be saved.

Page 8: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Thermal and Power model with micro-channels

• Thermal modeling– Use RC network to represent.– Steady states: pure resistive network.– Solve GT=Q, where G is the thermal conductivity

matrix and Q is the power profile.• G depends on many factors including the

material properties, location of channels and TSVs, fluid flow rate etc.

• Hotspot is the location that its temperature T is greater than maximum temperature constraint .

Page 9: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Micro-channel power consumption• Pumping power

– where N is the total number of channels, and are the pressure drop and fluid flow rate of the n-th micro-channel.

• Laminar liquid flow– pressure drop in a straight micro-channel – L is the length of micro-channel, is hydraulic

diameter, v is fluid velocity, μ is fluid viscosity and γ is determined by the micro-channel dimension.

Page 10: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Fluid flow rate

• Fluid flow rate – are the channel width and height.

• Flow rate could be controlled by changing the pressure drop.

• Usually fluid pumps are designed to work such that all the micro-channels experience the same pressure drop.– So that higher pressure drop results in

higher flow rate and better cooling.

Page 11: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Modeling Micro-channels with bends

• Three types of region– Fully developed laminar flow region.– The bend corner.– The developing/turbulent region after the

bend.

Page 12: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Pressure drop

• Pressure drop in fully developed region

• Pressure drop in developing region

• Pressure drop in corner region

• Total pressure drop

– A quadratic function of v.

Page 13: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Total pumping power

• Solve the equation for fluid velocity.• Estimate the fluid flow rate f, and thus

estimate the thermal resistance and pumping power for this channel.

• Hence, the pumping power as well as cooling effectiveness of micro-channels with bends is a function of– Number of bends.– Location of channels.– Pressure drop across the channel.

• Slower velocity means lower cooling efficiency.– More pumping power is needed.

Page 14: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Problem to be solved

• To find micro-channel routes from one side to the other such that– The routes do not intersect.– Avoid TSVs.– Provide sufficient cooling at

minimum pumping energy.

Page 15: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Represent the routing problem

• Each grid on the layout is a node.• Edge exists if

– Two nodes are adjacent.– Non of them is a TSV.

• Formulate the problem Minimize pumping power

I/O nodes

Routable nodes

TSV constraints

Temperature constraints

Edge constraints

The same edge

Page 16: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

The grid graph

Page 17: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

But…

• This is a very complex problem since – The variables need to be discrete.– The thermal and pumping power models

are highly nonlinear.• Propose a min-cost flow based

method to do the job.

Page 18: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Overall flow

• The flow– Full scale thermal analysis.– Initial micro-channel design– Iterative refinement with thermal

analysis

Page 19: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Min-cost flow based micro-channel design

• Initialization– I/O nodes are assigned a supply/demand

of one flow unit.– All nodes in the grid graph have a

capacity one.– The edges have unlimited capacity and

are bi-directional.• Assigning the node capacity to be 1

would ensure that all the flow from inlet to outlet follows simple paths (non-intersecting and non-cyclic).

Page 20: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Cooling demand

• A silicon layer would be cooled by the micro-channels both above and below.– Unless the silicon layer is at the very top

or very bottom of the stack.• For a location that need cooling.

– is the heat load partitioning factor.– cooling demand assigned to the top.– cooling demand assigned to the bottom.

Page 21: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Cooling demand (cont.)

• The top(bottom)-most layer only cooled by its bottom(top) micro-channel.– is set to 0(1) accordingly.

• Otherwise, is set according to the ratio of number of TSVs in the adjacent layer.– Less TSVs, more space for micro-channel.

Page 22: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Cost assignment

• Higher demand leads to lower cost since we would like micro-channels to pass through high cooling demand regions.

• Let be the heat load partitioning factor of grid on silicon layer , .

Page 23: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Cost assignment (cont.)

• If the hotspot exists in both side

• If the hotspot only exists in one side

• If the hotspot does not exist in both side– The node cost is assigned to a

small positive value

Page 24: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,
Page 25: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Micro-channel refinement

• Two situation that degrade the cooling quality.– Some channels have several

bends.– It may be routed over

disproportionately large number of hotspots.

• Iteratively refine the results

Page 26: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

How to get the minimum required pumping power

• Linearly increase the pressure drop until the temperature met the goal.

Page 27: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Iterative micro-channel optimization

• The objective of minimum cost flow formulation did not capture cooling energy and/or number of bends in the channels.

• Such imbalance (in cooling demand and bend count) leads to increase in the required pressure drop and thereby increasing the pumping energy.

Page 28: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Iterative micro-channel optimization (cont.)

• The basic idea is that all the channels should have similar levels of heat load, length and number of bends.

• Based on these considerations, the initial design is refined by– Balancing the heat loads among

micro-channels.– Reducing unnecessary bends.

Page 29: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Iterative micro-channel optimization (cont.)

• Micro-channel heat load balancing:

Page 30: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Iterative micro-channel optimization (cont.)

• Bend Elimination– Identify all unnecessary bends and

replace them with equivalent straight channels or patterns with lesser corners.

– Removing corners in the hotspot region might lead to reduction in the cooling performance.

– Only remove those corners in the non-hotspot regions which can easily be identified by the thermal analysis.

Page 31: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Experimental setting

• Two-tier stacked 3D-IC with 4-core CPU on each.– Different number of TSVs which are

randomly distributed.• SPEC 2000 CPU benchmarks

– Simulate 20 such benchmarks to get power profile and randomly choose 4 of these profiles to compose a one-tier profile.

• Combine two of these power profiles to form a two-tier profile.

Page 32: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Parameters

• The area of each chip stack is • The grid size is (so grids in each layer).• The channel dimensions are .• The maximum temperature constraint .• The maximum available pressure drop is

500kPa.

Page 33: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Experimental results (cont.)

• Uses 20 micro-channels.

Page 34: TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,

Conclusions

• Micro-channel cooling will be needed in the near future.

• Proposes a flow which designs TSV-constrained micro-channel infrastructure.

• Up to 87% pumping power saving compared with the micro-channel structure using straight channels.