TP48200A. External Alarms. Special for Vodafone Project Total 15 Pages Cabinet TP48200A. External Alarms 1
Dec 31, 2015
TP48200A. External Alarms.
Special for Vodafone ProjectTotal 13 Pages
Cabinet TP48200A.
External Alarms
Huawei Technologies Co., Ltd.
Website:http://support.huawei.com
E-MAIL:[email protected]
All Rights Reserved.Address:Huawei Technologies Co., Ltd.,
Postal Code:
1
TP48200A. External Alarms.
Table of Contents1. External Alarms Description:……………………………………….…………………5
2. External Alarms Connections (4x Ethernet cable (RJ45)): …………….……………..6
3. External Alarms Integration:…………………………………………..………………9
4. Reference Pictures:…………………………………………………………………..13
2
TP48200A. External Alarms.
List of FiguresFigure 1. UIM 02A.................................................................................................................................................5
Figure 2. Terminal Block........................................................................................................................................5Figure 3. Layout Connection All External Alarms.................................................................................................6Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A............................................................................7Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block..................................................................8Figure 7. Example of External Alarm Integration................................................................................................10Figure 8. M2000 Alarm Definition.......................................................................................................................11
3
TP48200A. External Alarms.
List of TablesTable 1. Alarm Information to be Commissioned in LMT and M2000..............................................................12
4
TP48200A. External Alarms.
1. External Alarms Description:
External Alarms by Default corresponding to PMU (UIM 02A):
ALM1 Smoke Alarm ALM2 Door Open ALM3 Rect Fault ; Rect Com Fault ALM4 Load Fuse Trip; Batt Fuse Trip ALM5 Batt Temp Alarm ALM6 NULL (Not Configured)
ALM7 Main Fault ALM8 Head Lamp
ALM9 SPD Fault
Figure 1. UIM 02A
External Alarms from outside the cabinet:
ALM10 Alternative power source ALM11 AC main failure
ALM12 Beacon failure ALM13 Low level gas
ALM14 Grupo en Marcha ALM15 Reserved
ALM16 Reserved ALM17 Reserved
5
TP48200A. External Alarms.
Figure 2. Terminal Block
2. External Alarms Connections (4x Ethernet cable (RJ45)):
6
TP48200A. External Alarms.
Figure 3. Layout Connection All External Alarms
Note: Red cable connects ALM_9 (UIM 02A) to Port_0 (Terminal Block) in order to take ALM9 to the first position in UPEU_1.
2.1. UPEU_0 UIM 02A
ALM1 ALM2 ALM3 ALM4
7
TP48200A. External Alarms.
UIM 02A
Board+ - + - + - + -
DRY PIN
Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_0 Board
EXT_ALM0
UIM 02A
Board
ALM5 ALM7 ALM8 ALM9
+ - + - + - + -
DRY PIN
Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_0 Board
EXT-ALM1
Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A
2.2 UPEU_1 Terminal Block
8
TP48200A. External Alarms.
Terminal
Block
Port_0 Port_1 Port_2 Port_3
+ - + - + - + -
DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_1 Board
EXT_ALM0
Terminal Block
Port_4 Port_5 Port_6 Port_7
+ - + - + - + -
DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_1 Board
EXT-ALM1
Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block.
Note: For further details, please refer to Reference Pictures
3. External Alarms Integration:
1 st Step : Ethernet Cable Connection: UPEU_0 UIM 02A
9
TP48200A. External Alarms.
UPEU_1 Terminal Block
Note: Refer to External Alarm Connections to check connection configuration details.
2 nd Step: Add External Alarm in UPEU Board:
Note: Refer to External Alarm Description to check Alarm ID for each external alarm.
Example:
Normally the configuration will be done on the 2G BTS as follow ,
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=0, SW=OPEN, AID=65133, PT=BOOL, AVOL=HIGH;SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=1, SW=OPEN, AID=65134, PT=BOOL, AVOL=HIGH;....
Or From 3G NodeB
10
TP48200A. External Alarms.
SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;SET ALMPORT: CN=0, SRN=0, SN=18, PN=, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;Example:
SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65033, PT=BOOL, AVOL=HIGH;
Figure 6. Example of External Alarm Integration
3 rd Step : M2000 External Alarm Definition: Assign Alarm Name to Alarm ID.
Note: Refer to External Alarm Description to check Alarm Name associated to Alarm ID.
Enter M2000 Server:Monitor / Alarm Setting / NE Alarm Setting Add
11
TP48200A. External Alarms.
Figure 7. M2000 Alarm Definition.
ALARM
Cabinet No
Subrack No Slot No Port No Switch
Alarm ID
Port Type
Alarm Voltage
Alarm Name
Alarm Severity
Level (Configure
d from M2000)
(Configured from
M2000)
ALM1 0 0 18 0 ON 65133 BOOL HIGH Fuego / Major
ALM2 0 0 18 1 ON 65134 BOOL HIGH Intrusión Major
ALM3 0 0 18 2 ON 65135 BOOL HIGHFallo menor
Continua Major
ALM4 0 0 18 3 ON 65136 BOOL HIGHDistribución
Continua Major
ALM5 0 0 18 4 ON 65137 BOOL HIGHTemperatur
a Alta Major
ALM6 NULL NULL NULL NULL NULL NULL NULL NULL NULL NULL
12
TP48200A. External Alarms.
ALM7 0 0 18 5 ON 65138 BOOL HIGHFallo
Alterna Major
ALM8 0 0 18 6 ON 65139 BOOL HIGHFallo Mayor
Continua Major
ALM9 0 0 18 7 ON 65140 BOOL HIGH
Fallo Prot. Sobretensió
n Major
ALM10 0 0 19 0 ON 65141 BOOL HIGHSuministro Alternativo Major
ALM11 0 0 19 1 ON 65142 BOOL HIGHFallo
Alterna Major
ALM12 0 0 19 2 ON 65143 BOOL HIGH Baliza Major
ALM13 0 0 19 3 ON 65144 BOOL HIGHBajo Nivel
Gasóleo Major
ALM14 0 0 19 4 ON 65145 BOOL HIGHGrupo en Marcha Major
ALM15 0 0 19 5 ON 65146 BOOL HIGH Reserva Major
ALM16 0 0 19 6 ON 65147 BOOL HIGH Reserva Major
ALM17 0 0 19 7 ON 65148 BOOL HIGH Reserva Major
Table 1. Alarm Information to be Commissioned in LMT and M2000.