Top Banner

of 20

There Are Many Issues Still to Be Resolved Such as Islanding Issue

Apr 05, 2018

Download

Documents

Devesh Singh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    1/20

    There are many issues still to be resolved such as islanding issue, interconnection

    of many PV system in a connected area, cost evaluation of grid interconnected PV

    system and so on.

    The main areas of concern are

    Voltage level control

    Power quality, including harmonics, power factor and DC injection

    The real risk associated with islanding

    Rate of change of conditions and flicker

    Although they are not fully competitive with conventional power generation but

    they attract interest because

    They are clean power source

    Quite amd having no movning parts

    Can be installed near the point of power demand

    Offer high reliability, long life and low maintenance

    Offer ownership of a power source to individual and companies

    In addition they offer following advantage over standalone system

    Do not require expensive battery storage, as grid provide the backp source

    Can be integrated into buildings and other structures thus saving on cladding

    costs and land requirement.

    Technical areas to be concerned in context of achieving sfe and practical

    interconnection of single phase PV inverter generator are:

    Protection

    Operation and safety

    Power quality

    Commissioning and acceptance testing

    Protection:

    Protection of people

    Protection of electrical network

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    2/20

    Protection of the PV inverter system

    Islanding phenomenon refers to the condition which can exists whereby part

    of the network has become electrically isolated from the main network and all

    the loads within that network are being supported by the generatorsembedded within the network.

    Power quality is not the only issue which is raised by the islanding. The debate

    surrounding the risks of islanding is normally asoociated with MW scale

    generators. With these large generators the energy stored by virtue of inertial

    mass of the rotor shaft means that the consequences of an out of sync circuit

    breaker reclosure on a multi MW generator set is a major problem. This

    resulted in the generator shaft being torn out of its bearing, allowing it to

    make contacts with the generator stator and thereby completely destroyingthe generator. An out of sync reclosure is still an event that could effect the

    grid connected PV inverters, but the lack of mechanical inertia within the

    inverter should mean that the inverter is in the better position to survive such

    event without damage to itself.

    Operation & Safety:

    Firstly there is a requirement for a manual isolation switch which is easily

    accessible and lockable. This switch should isolate the PV inverter output fromboth domestic circuit and the grid supply to allow maintenance to be done to either.

    Second requirement is for the automatic protection for islanding and disconnect the

    the equipment under any fault condition ( PV array failure, inverter failure, inverter

    power transistor failure, overunder voltage, over/under frequency, islanding etc.)

    Power quality:

    It includes Harmonics, PF, flicker, EMC and DC injection.

    Harmonics:

    Harmonics are generated by the nonlinear loads. Harmonics can be viewed as a

    form of electrical pollution on the distribution network since they provide no

    useful benefits but their existence can interfere with the correct operation of

    certain types of systems connected to the network.

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    3/20

    Power Factor:

    Power factor is a technical term defining the relative displacement in time between

    the mains voltage waveform and current waveform. Real Power relates to the

    current component at peak while reactive power relates to the current component at

    zero.Flicker:

    It is normally associated with the nonlinear or pulsed loads, such as welding

    equipments. Ficker is associated with lighting and its caused by repetitive, periodic

    voltage fluctuations.

    DC Injection:

    The Islanding phenomenon, probability of occurrence, detection methods, Impact

    of islanding and mitigation.

    Multiple PV system and their effect on power quality and power system design andoperation.

    [1]

    Harmonic problems within the installation

    There are several common problem areas caused by harmonics: -

    _ Problems caused by harmonic currents:

    _ overloading of neutrals

    _ overheating of transformers_ nuisance tripping of circuit breakers

    _ over-stressing of power factor correction capacitors

    _ skin effect

    _ Problems caused by harmonic voltages:

    _ voltage distortion

    _ induction motors

    _ zero-crossing noise

    _ Problems caused when harmonic currents reach the supply

    Each of these areas is discussed briefly in the following sections.

    Problems caused by harmonic currents

    Neutral conductor over-heatingIn a three-phase system the voltage waveform from each phase to the neutral star

    point is displaced by 120 so that, when each phase is equally loaded, the

    combined current in the neutral is zero. When the loads are not balanced only the

    net out of balance current flows in the neutral. In the past, installers (with the

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    4/20

    approval of the standards authorities) have taken advantage of this fact by

    installing half-sizedneutral conductors. However, although the fundamentalcurrents cancel out, the harmonic currents do not - in fact those that are an odd

    multiple of three times the fundamental, the triple-N harmonics, add in the

    neutral.

    Figure 12 shows the effect. In this diagram the phase currents, shown at the top,

    are introduced at

    120

    intervals. The third harmonic of each phase is identical, being three times the

    frequency and one-third of a (fundamental) cycle offset. The effective third

    harmonic neutral current is shown at the bottom. In this case, 70 % third harmonic

    current in each phase results in 210 % current in the neutral.

    Case studies in commercial buildings generally show neutral currents between 150

    % and 210 % of the phase currents, often in a half-sizedconductor! There is someconfusion as to how designers should deal with this issue. The simple solution,

    where singlecored cables are used, is to install a double sized neutral, either as two

    separate conductors or as one single large conductor. The situation where multi-cored cables are used is not so simple. The ratings of multicore cables (for example

    as given in IEC 603645-523 Table 52 and BS 7671 Appendix 4) assume that the

    load is balanced and the neutral conductor carries no current, in other words, only

    three of the four or five cores carry current and generate heat. Since the cable

    current carrying capacity is determined solely by the amount of heat that it can

    dissipate at the maximum permitted temperature, it follows that cables carrying

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    5/20

    triple-N currents must be de-rated. In the example illustrated above, the cable is

    carrying five units of currentthree in the phases and two in the neutralwhile

    it was rated for three units. It should be de-rated to about 60 % of the normal

    rating. IEC 60364-5-523 Annex C (Informative) suggests a range of de-rating

    factors according to the triple-N harmonic current present. Figure 13 shows

    derating factor against triple-N harmonic content for the de-rating described in IEC

    60364-5-523 Annex C and for the thermal method used above.

    The regulatory position is under discussion at present and it is likely that new

    requirements and guidance notes will be introduced into national wiring codes in

    the near future.

    Effects on transformersTransformers are affected in two ways by harmonics. Firstly, the eddy current

    losses, normally about 10 % of the loss at full load, increase with the square of the

    harmonic number. In practice, for a fully loaded transformer supplying a load

    comprising IT equipment the total transformer losses would be twice as high asfor an equivalent linear load. This results in a much higher operating temperature

    and a shorter life. In fact, under these circumstances the lifetime would reduce

    from around 40 years to more like 40 days! Fortunately, few transformers are fully

    loaded, but the effect must be taken into account when selecting plant. The second

    effect concerns the triple-N harmonics. When reflected back to a delta winding

    they are all in phase, so the triple-N harmonic currents circulate in the winding.

    The triple-N harmonics are effectively absorbed in the winding and do not

    propagate onto the supply, so delta wound transformers are useful as isolating

    transformers. Note that all other, non triple-N, harmonics pass through. The

    circulating current has to be taken into account when rating the transformer.

    A detailed discussion on rating transformers for harmonic currents can be found in

    a later section of the Guide.

    Nuisance tripping of circuit breakersResidual current circuit breakers (RCCB) operate by summing the current in the

    phase and neutral conductors and, if the result is not within the rated limit,

    disconnecting the power from the load. Nuisance tripping can occur in the presence

    of harmonics for two reasons. Firstly, the RCCB, being an electromechanical

    device, may not sum the higher frequency components correctly and therefore trips

    erroneously. Secondly, the kind of equipment that generates harmonics alsogenerates switching noise that must be filtered at the equipment power connection.

    The filters normally used for this purpose have a capacitor from line and neutral to

    ground, and so leak a small current to earth. This current is limited by standards to

    less than 3.5 mA, and is 0.4 0.6 0.8 1.0 0 10 20 30 40 50 60 70 % third harmonic

    Cable derating factor Thermal IEC Figure 13 - Cable derating for triple-Nharmonics usually much lower, but when equipment is connected to one circuit the

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    6/20

    leakage current can be sufficient to trip the RCCB. The situation is easily

    overcome by providing more circuits, each supplying fewer loads. A later section

    of this Guide covers the problem of high earth leakage in greater detail.

    Nuisance tripping of miniature circuit breakers (MCB) is usually caused

    because the current flowing in the circuit is higher than that expected from

    calculation or simple measurement due to the presence of harmonic currents.

    Most portable measuring instruments do not measure true RMS values and can

    underestimate non-sinusoidal currents by 40 %. True RMS measurement is

    discussed in Section 3.2.2.

    Over-stressing of power factor correction capacitors

    Power factor correction capacitors are provided in order to draw a current with a

    leading phase angle to offset lagging current drawn by an inductive load such

    as induction motors. Figure 14 shows the effective equivalent circuit for a PFC

    capacitor with a non-linear load. The impedance of the PFC capacitor reduces

    as frequency rises, while the source impedance is generally inductive andincreases with frequency. The capacitor is therefore likely to carry quite high

    harmonic currents and, unless it has been specifically designed to handle them,

    damage can result. A potentially more serious problem is that

    the capacitor and the stray inductance of the supply system can resonate at or near

    one of the harmonic frequencies (which, of course, occur at 100 Hz intervals).

    When this happens very large voltages and currents can be generated, often

    leading to the catastrophic failure of the capacitor system. Resonance can be

    avoided by adding an inductance in series with the capacitor such that the

    combination is just inductive at the lowest significant harmonic. This solution also

    limits the harmonic current that can flow in the capacitor. The physical size of the

    inductor can be a problem, especially when low order harmonics are present.

    Skin effectAlternating current tends to flow on the outer surface of a conductor. This is

    known as skin effect and is more pronounced at high frequencies. Skin effect is

    normally ignored because it has very little effect at power supply frequencies but

    above about 350 Hz, i.e. the seventh harmonic and above, skin effect will

    become significant, causing additional loss and heating. Where harmonic currents

    are present, designers should take skin effect into account and de-rate cables

    accordingly. Multiple cable cores or laminated busbars can be used to helpovercome this problem. Note also that the mounting systems of busbars must

    be designed to avoid mechanical resonance at harmonic frequencies. Design

    guidance on both these issues is given in CDA Publication 22, Copper forBusbars. Problems caused by harmonic voltages Because the supply has source

    impedance, harmonic load currents give rise to harmonic voltage distortion on

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    7/20

    the voltage waveform (this is the origin of flat topping). There are two elementsto the impedance: that of the internal cabling from the point of common coupling

    (PCC), and that inherent in the supply at the PCC, e.g. the local supply

    transformer. The former is illustrated in Figure 15. The distorted load current

    drawn by the non-linear load causes a distorted voltage drop in the cable

    impedance. The resultant distorted voltage waveform is applied to all other loads

    connected to the same circuit, causing harmonic currents to flow in them - even if

    they are linear loads. The solution is to separate circuits supplying harmonic

    generating loads from those supplying loads which are sensitive to harmonics, as

    shown in Figure 16. Here separate circuits feed the linear and non-linear loads

    from the point of common coupling, so that the voltage distortion caused by the

    non-linear load does not affect the linear load.

    When considering the magnitude of harmonic voltage distortion it should be

    remembered that, when the load is transferred to a UPS or standby generator

    during a power failure, the source impedance and the resulting voltage distortionwill be much higher. Where local transformers are installed, they should be

    selected to have sufficiently low output impedance and to have sufficient capacity

    to withstand the additional heating, in other words, by selecting an appropriately

    oversized transformer. Note that it is not appropriate to select a transformer design

    in which the increase in capacity is achieved simply by forced coolingsuch a unit

    will run at higher internal temperatures and have a reduced service life. Forced

    cooling should be reserved for emergency use only and never relied upon for

    normal running.

    Induction MotorsHarmonic voltage distortion causes increased eddy current losses in motors in the

    same way as in transformers. However, additional losses arise due to the

    generation of harmonic fields in the stator, each of which is trying to rotate the

    motor at a different speed either forwards or backwards. High frequency

    currents induced in the rotor further increase losses.

    Where harmonic voltage distortion is present motors should be de-rated to take

    account of the additional losses.

    Zero-crossing noiseMany electronic controllers detect the point at which the supply voltage crosses

    zero volts to determine when loads should be turned on. This is done becauseswitching reactive loads at zero voltage does not generate transients, so reducing

    electromagnetic interference (EMI) and stress on the semiconductor

    switching devices. When harmonics or transients are present on the supply the rate

    of change of voltage at the crossing becomes faster and more difficult to identify,

    leading to erratic operation. There may in fact be several zero-crossings per half

    cycle.

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    8/20

    Harmonic problems affecting the supply When a harmonic current is drawn from

    the supply it gives rise to a harmonic voltage drop proportional to the source

    impedance at the point of common coupling (PCC) and the current. Since the

    supply network is generally inductive, the source impedance is higher at higher

    frequencies. Of course, the voltage at the PCC is already distorted by the harmonic

    currents drawn by other consumers and by the distortion inherent in transformers,

    and each consumer makes an additional contribution. Clearly, customers cannot be

    allowed to add pollution to the system to the detriment of other users, so in most

    countries the electrical supply industry has established regulations limiting the

    magnitude of harmonic current that can be drawn. Many of these codes are based

    on the UK Electricity Associations G5/3 issued in 1975, recently replaced by G5/4(2001). This standard is discussed in detail elsewhere in this Guide.

    Harmonic mitigation measuresThe measures available to control the magnitude of harmonic current drawn are

    discussed in detail in later sections of this Guide. In this section a brief overview isgiven in generic terms. Mitigation methods fall broadly into three groups; passive

    filters, isolation and harmonic reduction transformers and active solutions. Each

    approach has advantages and disadvantages, so there is no single best solution. It is

    very easy to spend a great deal of money on an inappropriate and ineffective

    solution; the moral is to carry out a thorough surveytools suitable for this

    purpose are described elsewhere in this Guide.

    Passive filtersPassive filters are used to provide a low impedance path for harmonic currents so

    that they flow in the filter and not the supply (Figure 17). The filter may be

    designed for a single harmonic or for a broad band depending on requirements.

    Sometimes it is necessary to design a more complex filter to increase the series

    impedance at harmonic frequencies and so reduce the proportion of current that

    flows back onto the supply, as shown in Figure 18. Simple series band stop filters

    are sometimes proposed, either in the phase or in the neutral. A series filter is

    intended to block harmonic currents rather than provide a controlled path for them

    so there is a large harmonic voltage drop across it. This harmonic voltage appears

    across the supply on the load side. Since the supply voltage is heavily distorted it is

    no longer within the standards for which equipment was designed and warranted.

    Some equipment is relatively insensitive to this distortion, but some is verysensitive. Series filters can be useful in certain circumstances, but should be

    carefully applied; they cannot be recommended as a general purpose solution.

    Isolation transformersAs mentioned previously, triple-N currents circulate in the delta windings of

    transformers. Although this is a problem for transformer manufacturers and

    specifiers - the extra load has to be taken into accountit is beneficial to systems

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    9/20

    designers because it isolates triple-N harmonics from the supply.

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    10/20

    The same effect can be obtained by using a zig-zag wound transformer. Zig-zagtransformers are star configuration auto transformers with a particular phase

    relationship between the windings that are connected in shunt with the supply.

    Active FiltersThe solutions mentioned so far have been suited only to particular harmonics, the

    isolating transformer being useful only for triple-N harmonics and passive filters

    only for their designed harmonic frequency. In some installations the harmonic

    content is less predictable. In many IT installations, for example, the

    equipment mix and location is constantly changing so that the harmonic culture is

    also constantly changing. A convenient solution is the active filter or active

    conditioner. As shown in Figure 20, the active filter is a shunt device. A currenttransformer measures the harmonic content of the load current, and controls a

    current generator to produce an exact replica that is fed back onto the supply on the

    next cycle. Since the harmonic current is sourced from the active conditioner, only

    fundamental current is drawn from the supply. In practice, harmonic current

    magnitudes are reduced by 90 % and, because the source impedance at harmonic

    frequencies is reduced, voltage distortion is reduced.

    [3]

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    11/20

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    12/20

    The same effect can be obtained by using a zig-zag wound transformer. Zig-zag

    transformers are star configuration auto transformers with a particular phaserelationship between the windings that are connected in shunt with the supply.

    Active FiltersThe solutions mentioned so far have been suited only to particular harmonics, the

    isolating transformer being useful only for triple-N harmonics and passive filters

    only for their designed harmonic frequency. In some installations the harmonic

    content is less predictable. In many IT installations, for example, the equipment

    mix and location is constantly changing so that the harmonic culture is also

    constantly changing. A convenient solution is the active filter or active conditioner.

    As shown in Figure 20, the active filter is a shunt device. A current transformermeasures the harmonic content of the load current, and controls a current

    generator to produce an exact replica that is fed back onto the supply on the next

    cycle. Since the harmonic current is sourced from the active conditioner, only

    fundamental current is drawn from the supply. In practice, harmonic current

    magnitudes are reduced by 90 % and, because the source impedance at harmonic

    frequencies is reduced, voltage distortion is reduced.

    [4]Grid connection issues (

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    13/20

    Off > 5 min after disturbanceNegligible EM interferenceComponent ground, GFI, disconnects Metering: where is PVconnected

    Util. side: no direct benefit to customer, (utility owns PV)Cust. side: complicated (offset load); different financial arrangementsAnswer: net metering (>35 states); not all meters allow 2-wayELEG 628 Gridconnected systems 2008 11Grid connection issues (

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    14/20

    used to perform all the required control tasks. But, in the two-stage system, a DC-DC

    converter precedes the inverter and the control tasks are divided among the twoconverters. Two-stage systems provide higher flexibility in control as compared to

    single-stage systems, but at the expense of additional cost and reduction in the reliability

    of the system [35]. During the last decade, a large number of inverter and DC-DC

    converter topologies for PV systems were proposed [35]- [39], almost saturating theresearch in this area.

    1. Maximum power point tracking (MPPT)One of the main tasks of PCUs is to control the output voltage or current of the PVarray to generate maximum possible power at a certain irradiance and temperature.

    There are many techniques that can be used for this purpose [40]- [42] with the

    Perturb-and-Observe and Incremental Conductance techniques being the mostpopular ones. A recent study [43] presented a qualitative comparison between 19

    different MPPT techniques to serve as a guideline for choosing a suitable technique.

    Partial shading of PV arrays is considered one of the main challenges that face

    MPPT techniques. In this case, there might exist multiple local maxima, but only one

    global maximum power point, as illustrated in Figure 2-9. In this case, the task of thePCU is to identify and operate at the global MPP. The research in this field is activeand several

    studies have focused on developing new MPPT techniques and PCUtopologies that can perform this task

    2. Control of the injected currentPCUs should control the sinusoidal current injected into the grid to have the samefrequency as the grid and a phase shift with the voltage at the point of connection

    within the permissible limits. Moreover, the harmonic contents of the current should

    be within the limits specified in the standards. The research in this field is mainly

    concerned with applying advanced control techniques to control the quality ofinjected power and the power factor at the grid interface [47]- [49].

    3. Islanding detection and protectionIslanding is defined as a condition in which a portion of the utility system containing

    both loads and distributed resources remains energized while isolated from the rest ofthe utility system [50]. Most of the standards require that PCUs of PV systemsshould cease

    injection of power into the grid under specific abnormal operating

    conditions of the grid including those leading to islanding [50] [51]. Islanding detection methodscan be classified into three categories [52]: 1) Communicationbased

    methods that depend on transmitting signals between the PV system and the

    grid to identify an islanding condition, 2) Passive methods that depend on monitoringa certain parameter and comparing it with a threshold value, and 3) Active methods

    that depend on imposing an abnormal condition on the grid such as injecting

    harmonic current with a specific order at the point of connection with the grid. Most

    of the recent studies have focused on assessing and comparing different islandingtechniques as well as developing new methods with minimized non-detection zones

    [53]- [56].

    4. Voltage amplificationUsually, the voltage level of PV systems requires to be boosted to match the grid

    voltage and to decrease the power losses. This task can be performed using step-up

    DC-DC converters or multilevel inverters. Three-level inverters can be used for this

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    15/20

    purpose as they provide a good tradeoff between performance and cost in highvoltage

    and high-power systems [57].

    5. Additional functionsThe control of PCUs can be designed to perform additional tasks such as power

    factor correction [58], harmonics filtering [59], reactive power control [60], and

    operating with an energy storage device and/or a dispatchable energy source such asdiesel generator as an uninterruptible power supply [61].

    2.4 Impacts of PV Systems on the GridGrid-connected PV systems are usually installed to enhance the performance of the

    electric network by reducing the power losses and improving the voltage profile of the

    network. However, this is not always the case as these systems might impose severalnegative impacts on the network, especially if their penetration level is high. Such

    negative impacts include power and voltage fluctuation problems, harmonic distortion,

    malfunctioning of protective devices and overloading and underloading of feeders.

    3.5 Potential Problems Associated with Grid-connected PV

    SystemsDespite all the benefits introduced by PV systems to electric utilities, these systems mightlead to some operational problems. One of the main factors that lead to such problems isthe fluctuations of the output power of PV systems due to the variations in the solar

    irradiance caused by the movement of clouds. Such fluctuations lead to several

    operational problems and make the output power forecast of PV systems a hard task. Inaddition, the high cost of these systems limits the possible solutions that can be adopted

    by electric utilities to reduce the severity of the operational problems that might arise due

    to these fluctuations The negative impacts of Grid-connected PV systems on the network

    operation did notreceive much attention until lately, after the noticeable increase in installation of these

    systems. The work done in this area can be classified under three main categories: 1)

    impacts on the generation side, 2) impacts on the transmission and sub-transmission

    networks, and 3) impacts on the distribution networks. However, before discussing thepossible negative impacts of installing PV systems, it is important to present an overview

    of the source of power fluctuations in these systems and discuss the data required for

    analyzing the impact of these fluctuations.

    3.5.1 Fluctuation of output power of PV systemsFluctuation of the solar irradiance due to passage of clouds over a PV array is the main

    reason behind the fluctuation of the output power of PV systems. There are 10 reportedcloud patterns, with cumulus clouds (puffy clouds looking like large cotton balls) and

    squall lines (a solid line of black clouds) causing the largest variations in the output

    power of PV systems [73]. Squall lines can cause the output power of a PV system to fall

    to zero, and thus, they lead to the worst-case scenario for the operation of the system.However, squall lines are predictable, and thus, the periods of time during which the PV

    system will be out of service can be predicted [73]. On the other hand, cumulus clouds

    result in lower loss of the PV power, but they cause the output of the PV system tofluctuate more frequently as the irradiance fluctuates due to the passage of such clouds

    [73]. The time period of fluctuations can range from few minutes to hours depending on

    the wind speed, the type and size of passing clouds, and the area covered by and topology

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    16/20

    of the PV system.

    The most severe fluctuations in the output power of PV systems usually occur atmaximum irradiance level around noon. This period usually coincides with the off-peak

    loading period of the electric network, and thus, the operating penetration level of the PV

    system is greatest. The severity of PV power fluctuations on the electric network is

    governed by several factors, such as:1. Type of clouds,

    2. Penetration level,

    3. Size of PV system,4. Location of the PV system,

    5. Topology of the PV system, and

    6. Topology of the electric network.

    3.5.2 Irradiance data required for studying the impact of PV systemsThe time resolution of the irradiance data, required for studying the fluctuations of the

    output power of PV systems, should be match for the main goal of the study as it plays an

    important role in the accuracy of the results.

    In general, the solar irradiance can be separated into two components [74]: 1)deterministic component defined by the daily, monthly and yearly climate at a certain

    location, and 2) stochastic component that comprises fluctuations around thedeterministic component and is defined by the daily weather. In cases where the expected

    output energy of a PV system is to be estimated over a period of time, either the

    deterministic component of the irradiance [74] or the hourly irradiance data can be used[75] [76]. On the other hand, if it is required to study the performance of PV systems and

    their impacts on the electric network, then the time resolution of the irradiance data

    should be high enough to include the short-term or sub-hourly fluctuations of the

    irradiance (fluctuations within one hour) [77]. Moreover, irradiance data with high timeresolution (e.g., 10-min. resolution) can lead to better prediction accuracy because the

    auto-correlation coefficients will have higher positive values as compared to thoseobtained for the data with 1-hour time resolution [78].In the following subsections, the possible negative impacts of the PV systems are

    discussed. A summary of these impacts is presented in Figure 3-1.

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    17/20

    3.5.3 Impact of PV systems on the generation sideSevere fluctuations in the output power of large PV systems might affect the generation

    in electric utilities. This is mainly due to the fact that the utilities have to follow thesefluctuations in order to compensate for any rise and fall in the generation of PV systems.

    Hence, the generating units that are scheduled to operate during the generation period of

    PV systems should have ramping rate capabilities that are suitable for the fluctuations ofthese systems. Moreover, the power fluctuations from the PV system make it difficult to

    predict the output power of these systems, and thus, to consider them when scheduling the

    generating units in the network. Most of the studies performed in this area have

    addressed this problem and tried to provide some operational solutions that can beadopted by utilities. For example, the studies presented in [79] and [80] discuss the

    impact of installing large, centralized PV plants on the operation of thermal generation

    units. The aim of these studies is to identify the penetration level of PV systems that will

    not lead to generation control problems due to passing clouds. Both studies conclude thatthe ramping rate capability of the utility is the main factor that controls the penetration

    level of PV systems. However, the analysis performed in both studies considered the

    worst-case scenarios only, without providing any details about the frequency and periodsduring which these scenarios might occur. The work in [81] introduces some factors that

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    18/20

    can affect the economical and operational values of PV systems for large-scale

    applications. Some of these factors are the generation mix, maintenance schedules,ramping rates, fuel costs, spinning reserve requirements, PV power fluctuations, and

    geographical diversification of PV systems. The study suggested some solutions that can

    be applied to the cases where the severity of the changes in the output power of the PV

    system is beyond the ramping capacity of the system. These solutions include: 1)increasing scheduled tie-line power, 2) bringing more generating units online to increase

    the overall ramping capacity of the system, and 3) decreasing the output power of the PV

    system. A rule-based dispatch algorithm was presented in [82] to take into account theproblems that might arise due to the fluctuations in the power of a 100-MW PV plant

    during the dispatch period. The method is based on predicting the solar irradiance every

    10 minutes and assumes that not all the PV power is injected into the grid. A set of rulesare proposed to provide operational plans based on the power production of the PV

    system. These rules depend mainly on the time of the year and the type of electric utility

    under study.

    In general, the generation side of an electric utility can be affected by the PV system if

    the penetration level of the PV system is comparable to the size of the generating units.However, systems with such large sizes are not expected to be widely installed in the near future

    due to the high cost of PV systems. Thus, studying the impacts on the generationside does not seem to be crucial at the time being.

    3.5.4 Impact on transmission and sub-transmission networksPV systems might cause problems in the transmission and sub-transmission networks iftheir sizes are large enough to affect these networks. The problems arise mainly due to

    power fluctuations of these systems which might lead to: 1) power swings in lines, 2)

    power reversal, 3) over and under loading in some lines, and 4) unacceptable voltage

    fluctuations in some cases [83]. The effect of large PV systems on the voltage levels andthe stability of transmission systems after fault conditions was studied in [84]. The results

    show that replacement of conventional generating units with large PV units affects thevoltage levels of the system during normal operating conditions. During fault conditions,rotors of some of the conventional generators present in the network might swing at

    higher magnitudes due to the existence of PV units. Moreover, at very high penetration

    levels of PV systems, voltage collapse might occur. In these studies, the sizes of the PV

    systems required to cause the aforementioned problems were assumed to range from 700MW to 1500 MW. According to the current market prices of PV systems, such sizes are

    not expected to be installed soon. Hence, studying the impact of PV systems on

    transmission and sub-transmission networks does not seem to be important for electricutilities at the time being.

    3.5.5 Impact on distribution networks

    The impacts of PV systems on the performance of distribution networks are currently oneof the main issues for electric utilities. This is because the size and location of the

    installed PV systems mainly influence these networks. The operational problems

    introduced by PV systems are similar to those imposed by distributed generators that

    produce constant active power, such as diesel generators and fuel cells. These problemsarise mainly due to the installation of generators at the customer side in a feeder designed

    for unidirectional power flow. They include malfunctioning of protective relays, voltage

    regulation problems, reverse power flow, as well as overloading or underloading of some

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    19/20

    feeders. Other problems arise due to the use of interfacing electronics that lead to

    harmonic distortion and parallel and series resonances if a large number of inverters areinstalled in a certain area. Moreover, the fluctuation of the output power of PV systems

    adds to the problems faced by the system operator and can deteriorate the power quality

    of the network.

    The impact of small PV systems installed on rooftops of houses has received the attentionof many researchers during the last few years. This is mainly due to the increase in

    installation of these systems due to the incentives provided by governments to residential

    customers. Typical ratings for PV systems installed on rooftops of houses range from 1to50 kW.

    The issue of harmonic distortion introduced by the power conditioning units used in

    small PV systems was the main focus of the studies presented in [85]- [87]. All casestudies showed harmonic distortions far below the limits specified in the standards. This

    is mainly because of the great advances made in the inverters technology. However, the

    filter capacitors of the interfacing inverters might lead to resonances with the electric

    network if a large number of PV systems are installed in a certain neighborhood [88] [89].

    The impact of installing small PV systems on the voltage profile of different distributionnetwork topologies was studied in [32]. The results showed that the acceptable voltage

    limits were exceeded for all networks when the size of each PV system was 200% of theload of the household. The study assumed that PV systems were installed at every node in

    the network, which might not be a realistic assumption. The results of a real case study

    presented in [90] indicate the presence of slow transients in the voltage of a mediumvoltagedistribution feeder corresponding to the frequency of fluctuations of the output

    power of small PV systems installed on rooftops. Moreover, it was concluded that the

    presence of PV systems in the network might reduce the lifetime of transformer tap

    changers due to the increase in their operation. Other studies analyzed the impact of smallPV systems on the voltage profile of a low-voltage grid [91]- [93]. However, these studies

    did not consider the fluctuations of the irradiance in the analysis.

    In general, small PV systems installed on rooftops and facades of buildings might not

    impose serious problems on the distribution network. This is mainly because the size ofthese systems requires high concentration in a small area in order to be able to affect the

    performance of the network. Such situation is not likely to happen often, as the current

    trends show that small PV systems are usually dispersed over a large area. Suchdispersion reduces the impact of fluctuations as the combined irradiance profile over the

    complete area is more smooth than that over the individual systems [8].

    Only few studies have focused on the impact of large centralized PV systems on thedistribution network. For example, the study in [94] illustrates that the improper choice of

    the location of large PV systems can affect the security of the network. Such problem

    becomes more severe if the generation of the PV system matches the peak loading of the

    electric network as this might increase the loading of some lines that are already heavilyloaded. Thus, to check the network security, the study considered the scenario when the

    maximum output power of the PV system matched the peak loading conditions of the

    network. However, the overall performance of the network, including voltage profilesand power losses, was not evaluated because no other scenarios were included.

    Moreover, no information was provided about how often or when the case of peak

    matching might occur.

  • 8/2/2019 There Are Many Issues Still to Be Resolved Such as Islanding Issue

    20/20

    In [95], the impact of installing a 5-MW PV system on the voltage regulation and

    overcurrent protection of a real distribution feeder was studied. The study shows that thePV system might cause the voltage to reach unacceptable levels during certain periods.

    On the other hand, the overcurrent protection was not affected by the operation of the PV

    system, as the inverter of the system seized to operate as soon as the fault was detected.

    The main advantage of this study is in the fact that a real case is analyzed where thecorrective devices used for voltage regulation (transformer LTCs and shunt capacitors)

    and protection were included. However, the conclusions drawn are based on simulating

    the output power of the PV system over a five-day period only and with time resolutionof 1 hour. Hence, the variations of loading during different seasons and the sub-hourly

    fluctuations are not considered in this study, even though they are essential for proper

    evaluation of the performance of the network.The impact of increasing the penetration level of PV systems on the network losses was

    analyzed in [96]. However, the analysis did not investigate the impacts of the PV system

    on other performance parameters such as the voltage profile of the network and power

    flow in the lines. To perform such a study, the power fluctuations of the PV output power

    should be simulated accurately. Thus, the hourly irradiance data used in the analysis of[96] might not be appropriate for this case.

    From the above discussions, it can be concluded that large centralized PV systems shouldbe the main concern when studying the impacts of PV systems on the performance of

    distribution networks. Upon studying these impacts, it is important to consider the

    fluctuations in the output power of the PV system as it constitutes an inherentcharacteristic for these systems. Moreover, to obtain accurate results, it is important to

    examine the performance of the network for an extended period of time in order to

    consider different possible patterns of generations from the PV system and loading

    conditions of the feeder under study. To consider these aspects, it is essential to use amethod that can manipulate the available data efficiently to be able to provide realistic

    evaluations about the performance of the network.

    major advances in power electronicstechnology using integrationas a keytechnique to achieve major improvements in:

    Performance/quality Reliability Cost