Vacuum Contactors and Starters were designed for starting and controlling three-phase, 50/60 Hz, AC motors. Each contact is enclosed in a vacuum bottle to reduce and contain contact arcing. This design offers excellent performance for plugging and jogging applications.
Application Description
The Vacuum Contactors and Starters are offered in three classifications. They are NEMA rated devices up to 600V AC, Special Purpose rated devices up to 1500V AC and Mining rated devices rated up to 1500V AC. Each device is tested to different stan-dards to serve their market.
Typical applications include full voltage control of three-phase squirrel cage motors, primary control of low voltage wound rotor motors and circuit switching for low voltage capac-itors for power factor improvement.
A vacuum contactor is affected by atmospheric pressure on the bellows of the vacuum bottles. Up to an alti-tude of 6600 feet, the contactor is designed to tolerate normal variations in barometric pressure. If the contactor is to be operated above 6600 feet above sea level, consult your Eaton’s Cutler-Hammer representative.
Features
■
Rugged, compact and lightweight
■
Quiet operation
■
Electrical and mechanical interlocks available
■
Long service life
Benefits
■
Easy maintenance with front remov-able coil and auxiliaries
■
Eliminate extra surge suppressors with the standard low chop interrupters
■
Plan your preventative mainte-nance schedule by utilizing the con-tact wear indicator, standard on all vacuum bottles
Operation
The contact structure of the vacuum break contactor is located inside sealed ceramic tubes that have been evacuated of air. Any arc occurring across the contacts upon opening is automatically extinguished because ionized air is not available to sustain it — the arc breaks when the current passes through zero. The arc typically does not service beyond the first half cycle once the contacts begin to sepa-rate. The large arc chutes normally associated with contactors of this size are not required. The ceramic tube with the moving and stationary con-tacts is called a
vacuum interrupter
or
bottle
. There is one bottle for each pole on the contactor. A metal bellows (like a small, circular accordion) within the bottle allows the moving contact to be closed and pulled open from the outside without leaking air into the bottle. Both the bellow and the metal-to-ceramic seals of these state-of-the-art bottles have been refined to the point where the possibility of loss of vacuum has been virtually eliminated.
Standards and Certifications
■
NEMA Devices
❑
UL Listed File #E1491, Guide Number NLDX
❑
CSA Approved
■
Special Purpose Devices
❑
IEC 947-4-1
❑
CE Approved EN 60947-4-1
❑
UL Listed File #E1491, Guide Number NLDX
❑
CSA Approved
February 2007
CA08102001E For more information visit:
www.eaton.com
36-3Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining Rating
Product Selection
Product Selection
When Ordering Specify
■
Catalog Number
■
Heater Pack if ordering a Starter, order in quantities of three
■
Any required Accessories
Table 36-1. NEMA Rated Product Selection
�
Starters use Type B overload relay. Refer to Heater Coil Selection Table,
Page 36-5
. Starters do not include Heater Packs.
�
Coils are rated for 50/60 Hz applications.
Table 36-2. Special Purpose Product Selection
�
Starters use Type B overload relay. Refer to Heater Coil Selection Table,
NEMA Size 5 & 6 and 320A, 540A & 610A — Supplied without Line or Load Lugs.
Table 36-4. Lug Kits — Consist of 6 Lugs
Field Modification Kits
Auxiliary Electrical Contacts
Size 4 — Three Type J auxiliary contacts may be mounted on the top of Size 4 contactors to provide six auxiliary, isolated 600V, 10A contacts for use in control circuits.
Sizes 5 – 6 — Two Type J auxiliary contacts may be mounted on each side of Size 5 and 6 contactors to provide four auxil-iary, isolated 600V,10A contacts for use in control circuits.
Table 36-5. Auxiliary Electrical Contacts
Table 36-6. Horizontal Mechanical Interlock
AEGIS Powerline Filters
Ideal for applications that utilize 120V AC or 240V AC control voltage and have the likelihood of harmonics or noise being present on the control signal. These are stand-alone devices, not mounted to thecontactor.
Hardwired Surge Filler that Protects Critical Loads (3 and 5 Ampere Models)
AEGIS Powerline Filters Protect Against the Full Spectrum of Transient Disturbances
AEGIS filters the entire sine wave and is effective against both frequently occurring low energy and occasional high energy transients. High energy transients can create imme-diate damage, while low energy transients cause coil failure over time.
Table 36-7. AEGIS-HW (Hard Wire Application) Catalog Numbering System
�
Model tested at 15A UL/CSA = 16A CE.
Table 36-8. AEGIS Powerline Filters
�
See AEGIS Powerline Filters in Tab 10 of Distribution Catalog.
CA08102001E For more information visit: www.eaton.com
36-7Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingWiring Diagrams
Wiring Diagrams
Figure 36-1. Typical Wiring Diagrams
L1 L2 L3
M
M
M
M
M
T1
T2T3
Motor
StartStop
1 2 3A B
+
-
C
Coil Aux. Contact
Size 4 Contactor
D
"C"
L1 L2 L3
M
M
M
S
R
T1
T2
T3
0T
1T
2T
OL
OL
OL
Motor
StartStop
1
2 3
A B OL
95 96
+
-C
L63 Coil Aux. Contact
Sizes 5 & 6 Starter
D
"C"
EncapsulatedCoils and Diode
DisconnectMeans
February 2007
36-8
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Dimensions
Figure 36-2. Open Type Contactors and Starters — Size 4 and 160A — Approximate Dimensions in Inches (mm)
Reset
Front View Shownwithout Cover Plateand Overtravel Gauge.
Recess forAuxiliary Interlock
1.44(36.6)
MechanicalInterlock
Recess forAuxiliary Interlock
10.12(257)
.281 (7.14) Dia.3 Mtg. Holes
.28 (7.1) Dia.3 Mtg. Holes
1.44 (36.6)1.44 (36.6)
3.60(91.4)
4.83 (122.7) 5.94 (150.9)
6.11 (155.2)Max. to Reset6.34 (161.0)Hand Reset
.46(11.7)
.58(14.7)
1.31 (33.3) 1.31 (33.3).65 (16.5)
.46 (11.7)
.38 (9.7).94 (23.9)1.88 (47.8)
9.25(235)
9.97(253.2)
Reset
8.00 (203.2)
9.25(235)
.44(11.2)
4.00(101.6)
.47 (11.9) 6.61 (168)Max. to Reset6.86 (174.2)Hand Reset
.66 (16.8)
.47(11.9)
1.03(26.2)
1.13 (28.7) 4.10(104.1)1.44 (36.6)
1.44 (36.6)4.88 (124)
9.96 (253)
6.38 (162.1)
Size 4 Non-reversing Starter
1.88 (47.8) 1.88 (47.8)
6(152.4)
.28 (7.1)3 Mtg.Slots
3.5 (88.9)
2(50.8)
.44 (11.2) 5.13 (130.3)2.56 (65)
4.88 (124)
7.0 (177.8)
Rear View — Drilling Plan
Rear View — Drilling Plan
Front View
Front View
Size 4 and 160A Reversing Contactor
Size 4 and 160A Non-reversing Contactor
Side Vew
Side View
8.5(215.9)Max.
6.88(174.8)
6.63(168.4)
6(152.4)
.38 (9.7)
9.96 (253)1.44 (36.6)
1.13 (28.7)1.44 (36.6) 6.54
(166.1)
4.2 (106.7)
5.96 (151.4)4.83 (122.7)1.44 (36.6)
1.88 (47.8)
1.88 (47.8)3.6 (91.4)
.94 (23.9)
.94 (23.9)
.28 (7.1) Dia.3 Mtg. Slots
Front View Shownwithout Cover Plate
and OvertravelGauge.
1.44 (36.6)
MechanicalInterlock
Recess forAuxiliaryInterlock
Recess forAuxiliaryInterlock
Rear View — Drilling Plan Front View Side Vew
Size 4 Reversing Starter
Rear View — Drilling Plan Front View Side Vew
2.88 (73.2)
February 2007
CA08102001E For more information visit: www.eaton.com
36-9Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Figure 36-3. Open Type Contactors and Starters — Size 5 and 320A — Approximate Dimensions in Inches (mm)
8(203.2)
.38(9.7)
3.75(95.3)
1.75(44.5)
.62(15.7)
2.74 (69.6)
.38(9.7)
3.75(95.3)
4.1(104.1)
Nameplate
7.5(190.5)
6.75 (171.5)Drilling Plan — Rear View Size 5 and 320A Non-reversing Contactor
.58 (14.7)
3(76.2)
1.5(38.1)
7.28 (184.9)Term. Holes
12.5(317.5)
8.94(227.1)Term.
toTerm.
.13(3.3)
A
B
1.38(35.1)
2.75 (69.9)
A
CoilInterlockLocation
B
6.13 (155.7)
7.75 (196.9)Line End
3.37(85.6)LoadEnd
“A”Dim.
“A” Dim.
22 (558.8)5.73
(145.5)
1.5(38.1)
4.25(108)
2.5(63.5)
2.5(63.5)
3.87(98.3)
1.9(48.3)
1.62 (41.1)
4.21(106.9)
3.65 (92.7)2.5(63.5)
5.22 (132.6)Line Term.
Nameplate
1.5(38.1)
24.24 (615.7) 9.48 (240.8)
6.61 (167.9)
5.93 (150.6)
7.9 (200.7)
2.5(63.5)
2.5(63.5)
1.45(36.8)
5.09 (129.3)Load Term.
2(50.8)
Nameplate
Nameplate
TerminalClamps
AreOptional
Coil InterlockLocation
3/8-16 TapLine TerminalsSix (6) Places
3/8-16 TapLine TerminalsSix (6) Places
18.24(463.3)
14(355.6)
2.12(53.8)
16.43(417.3)
1.45(36.8)
2.5(63.5) 7.89 (200.4)
10.88(276.4)
toCenter
ofReset Rod
.33 (8.4)to Center ofReset Rod
2.48(63)
.86(21.8)
.33 x .75(8.4 x 19.1)Key Holes3 Places
.41 (10.4)Dia.
2 Holes
.33 (8.4)Slot
2 Places
.31 (7.9)Slot
2 Places
A – Two Dual Circuit Interlocks Located on Both Sides of Contactor. (When Used)B – Coil Terminals Located on Both Sides of Contactor.
A – Two Dual Circuit Interlocks Located on Both Sides of Starter. (When Used)B – Coil Terminals Located on Both Sides of Starter.
Size 5 and 320A Reversing Contactor
320A Reversing Starter
8(203.2)
.38(9.7)
7.5(190.5)
6.75 (171.5)Drilling Plan — Rear View Size 5 and 320A Non-reversing Starter
.58 (14.7)
3(76.2)1.88
(47.8)
1.5(38.1)
1.32(33.5)
.53(13.5)
2.56(65.0)
14(355.6)
18(457.2)
.14(3.6)1.38
(35.1)
2(50.8)
.33 x .75(8.4 x 19.1)Key Holes3 Places
.41 (10.4)Dia.
2 Holes
.31 (7.9)Slot
2 Places
.33 (8.4)Slot
2 Places
2.5(63.5)
24 (609.6)1.89 (48.0)
4(101.6)
22.25(565.2)
8 (203.2) Line
3.25(82.6)
10.71(272.0)
7 (177.8)Normal
or Tripped
7 (177.8)Normal
or Tripped
Type B RelayMax. Dim to Reset
Type A RelayMax. Dim to Reset
Type B RelayAutomatic Reset
6.75(171.5)
6.73(170.9)
6.61(167.9)
4.08(103.6)
February 2007
36-10
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Special Purpose and Mining RatingDimensions
Figure 36-4. Open Type Contactors and Starters — Size 6, 540A and 610A — Approximate Dimensions in Inches (mm)
Overload RelayReset Rod
2.38(60.5)
8.16 (207.3)Normal or Tripped
8.90 (226.1)
3.86 (98.0)Load
7.94 (201.7)Reset
2.67(67.8)
2.67(67.8)
1.70(43.2) 2.75
(69.9)2.75
(69.9)
12.62(320.5)
To Centerof Reset
15.94(404.9)Term.Mtg.
20.50(520.7)
WithoutTerm.
17.10(434.3)WithTerm.
8(203.2)
.38(9.7)
8.75(222.3)
12.9(327.7)Term.Holes
13.99(355.3)
6.75 (171.5) .58(14.7)
.33 (8.4)Slot
2 Places
.33 x .75(8.4 x 19.1)Key Holes
2.73(69.3)
2.73(69.3)
4.39(111.5)
5 (127)2.67 (67.8) 2.67 (67.8)
2.67 (67.8)2.67 (67.8)
7 (177.8)
3.75(95.3)
7.87(199.9)
4.88(124)
1.5(38.1)
14.01(355.9)
2.09(53.1)
18.24(463.3)
4.62(117.3)
6.5(165.1)
4.12(104.6)
17.02(432.3)
24.24(615.7)
22(558.8)
2.67(67.8)
2.67(67.8)
Size 6, 540A and 610A Reversing Contactor
4.4(111.8)
1.64(41.7)
7.84(199.1)
3.72 (94.5)Load
1.28(32.5)
Size 6, 540A and 610A Non-reversing Contactor
7.9 (200.7)
A
B
AB
CoilInterlock
CoilInterlock
A – Two Dual Circuit Interlocks Located on Both Sides of Contactor. (When Used)B – Coil Terminals Located on Both Sides of Contactor.
A – Two Dual Circuit Interlocks Located on Both Sides of Starter. (When Used)B – Coil Terminals Located on Both Sides of Starter.
Nameplate
Rear View — Drilling Plan
8(203.2)
.38(9.7)
8.75(222.3)
6.75 (171.5) .58(14.7)
.33 (8.4)Slot
2 Places
.33 x .75(8.4 x 19.1)Key Holes
Rear View — Drilling Plan
Front View Side ViewFront ViewSide Vew
Size 6 and 540A Non-reversing Starter
Front ViewSide View
5 (127)7 (177.8)
24 (609.6)
22 (558.8)
18(457.2)
21.5(546.1)
26(660.4)
16.06(407.9)
14(355.6)
4.13(104.9)
5.43(137.9)
3.23(82)
5.81(147.6)
1.75(44.5)
3.23(82)
3.23(82)
3.23(82)
1.17(29.7)
540A Reversing Starter
1.17(29.7)
8(203.2)
3.64(92.5)
6.5(165.1)
9.16 (232.7)Normal
8.94 (227.1)Reset
1(25.4)
February 2007
CA08102001E For more information visit: www.eaton.com
36-11Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Product Description■ 3-Phase Magnetic■ 3-Pole Full Voltage■ Non-reversing and Reversing■ 600 and 1500V AC Maximum■ Starters with Interchangeable
Heater OLR
Application DescriptionCutler-Hammer® Vacuum Contactors from Eaton’s electrical business are designed for starting and controlling three-phase, 50/60 Hz, AC motors. Motor full load current should not exceed the contactor current rating. These contactors are built in several versions — the nameplate on a spe-cific contactor states the authorized ratings.
Low voltage vacuum contactors can be applied to a wide range of voltages up to 1500V. These applications include full voltage control of three-phase squirrel cage motors, primary control of low voltage wound rotor motors and circuit switching for low voltage capacitors for power factor improvement.
Cat. No. AV10GNOA or V200M5CJCVacuum Break Starter
Features/Benefits■ Rugged, compact, lightweight■ Quiet operation■ Front removable coil and auxiliaries■ Electrical and mechanical interlock-
ing capability■ Low chop interrupters eliminate the
need for surge suppressors■ Contact wear indication allows for
planned maintenance program■ Long service life■ Manual push-to-reset button on
Sizes 5 and 6■ Freedom overload■ SSOL
OperationThe contact structures of these vac-uum break contactors are located inside sealed ceramic tubes which have been evacuated of air. Any arc occurring across the contacts upon opening is automatically extinguished because ionized air is not available to sustain it — the arc breaks when the current passes through zero. The arc typically does not survive beyond the first half cycle once the contacts begin to separate. The large arc chutes nor-mally associated with starters of this size are not required. The ceramic tube with the moving and stationary con-tacts enclosed is called a vacuum interrupter or a bottle, and there is one bottle for each pole of the contac-tor. A metal bellows (like a small, circu-lar accordion) within the bottle allows the moving contact to be closed and pulled open from the outside without leaking air into the bottle. Both the bel-lows and the metal-to-ceramic seals of these state-of-the-art bottles have been refined to the point where the possibility of loss of vacuum has been virtually eliminated.
Contact Force and AltitudeA vacuum contactor is affected by atmospheric pressure on the bellows of the vacuum bottles. Up to an altitude of 6600 feet, the contactor is designed to tolerate normal variations in barometric pressure. If the contactor is to be operated above 6600 feet above sea level, consult Eaton.
Standards and Certifications■ UL listed■ cUL Listed (indicates appropriate
CSA Standand investigation)■ CE Mark available■ ABS Type Approved
February 2007
36-12
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Cover Control
Non-Reversing
Flange Control KitsFor on-the-job conversion of Type 1, 3R, 4X and 12 enclosed starters. Knockouts are provided on the Type 1 flange. Type 3R, 4X and 12 have prepunched holes with removable hole plugs.
Factory InstalledTo order factory installed pilot devices, change the 9th character of the Catalog Number to the alpha shown in the table below. Example: to order an ECV0548AAA with START/STOP push-buttons and a red pilot light, change the A to a C, i.e. ECV0548ACA.
Reversing
Flange Control KitsFor on-the-job conversion of Type1, 3R, 4X and 12 enclosed starters. Knockouts are provided on the Type1 flange. Type 3R, 4X and 12 have prepunched holes with removable hole plugs.
Factory InstalledTo order factory installed pilot devices, change the 9th character of the Catalog Number to the alpha shown in the table below. Example: to order an ECV1748AAH with FOR/REV/STOP pushbuttons and 2 red pilot lights, change the A to a C, i.e. ECV1748ACH.
Table 36-14. Non-reversing Pilot Device Field Kits and Factory Installation
� Add Code Letter from table below to Catalog Number for voltage — Kits only. Example: C400T9B.
� Type 1 Non-combination, Size 4.� Type 1 Non-combination, Sizes 5 & 6; Type 3R, 4X, 12 Non-combination, all Sizes; All Combination
Control.
Table 36-15. Reversing Pilot Device Field Kits and Factory Installation
� Add Code Letter from table below to Catalog Number for voltage — Kits only. Example: C400T9B.
� Type 1 Non-combination, Size 4.� Type 1 Non-combination, Sizes 5 & 6; Type 3R, 4X, 12 Non-combination, all Sizes; All Combination
Control.� Order quantity 2 of C400T9�.
Description Factory Installed Flange Control
Field Installation Kits
Position9 Alpha
AdderU.S. $
Non-combination � Combination �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
No Cover Mounted Pilot DevicesSTART/STOP Pushbuttonswith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
ABCD
C400GK0C400GK1C400GK12 �
C400GK16 �
—C400T1——
ON/OFF Pushbuttonswith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
EFG
———
C400T2——
HAND/OFF/AUTO Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
HJK
C400GK3C400GK32 �
C400GK36 �
C400T12——
START PushbuttonON PushbuttonOFF PushbuttonRed RUN Pilot LightGreen OFFRed RUN/Green OFF Pilot Lights
LMNPQR
———C400GK42 �
C400GK41 �
C400GK46 �
C400T3C400T4C400T5C400T9 �
C400T10 �
C400T11 �
START/STOP Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
STU
———
C400T13——
ON/OFF Selector Switchwith Red RUN Pilot Lightwith Red RUN/Green OFF Lights
VWX
———
C400T14——
Rating CodeLetter
Rating CodeLetter
Rating CodeLetter
120V 60 Hz208V 60 Hz
AE
240V 60 Hz380V 50 Hz
BL
480V 60 Hz600V 60 Hz
CD
Description Factory Installed Flange Control
Field Installation Kits
Position9 Alpha
AdderU.S. $
Non-combination � Combination �
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
No Cover Mounted Pilot DevicesFOR/REV/STOP Pushbuttonswith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
ABCD
C400GK0C400GR1C400GR14 �
—
—C400T6——
UP/STOP/DOWN Pushbuttonswith 2 Red Pilot Lights
EF
C400GR2C400GR24 �
——
FOR/OFF/REV Selector Switchwith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
HJK
———
C400T15——
Two Red Pilot LightsOne Green Pilot LightTwo Red/One Green Pilot LightsOPEN/OFF/CLOSE Selector Switchwith 2 Red Pilot Lightswith 2 Red/1 Green Pilot Lights
CA08102001E For more information visit: www.eaton.com
36-13Vacuum Contactors & Starters
36
NEMA, Enclosed ControlProduct Family Overview
Catalog Number SelectionTable 36-16. NEMA Vacuum Break Catalog Numbering System
Table 36-17. Alternate “Open” Catalog NumbersListed “Open”Catalog Number
Alternate “Open”Catalog Number
AV10FNOAAV10GNOABAV10JNOAB
V200M4CJCV200M5CJCV200M6CJC
CV10FN3ACV10GN3ACV10JN3A
V201K4CJV201K5CJZ1V201K6CJZ1
E C V 0 5 5 1 A A A -
Design
V = Vacuum
Modification Codes
See Pages 36-23 – 36-32
Contactors
3 = 3 Poles
Starters
Cover Control
Coil Voltage or Motor Voltage
A = 120VB = 230VC = 460V
D = 575VE = 200VV = 380V
Disconnect Fuse Clip Ratings
A =H =J =K =
None200A/250V R200A/600V R400A/250V R
L =M =N =
400A/600V R600A/250V R600A/600V R
Breaker Ratings
A =H =J =
None150A250A
K =L =M =
400A600A800A
NEMA Size
4 5 6
Class Page
01 =02 =05 =06 =07 =
ContactorsReversing ContactorsFVNR Starter, Non-combinationReversing Starter, Non-combinationFVNR Starter, Non-combination, with CPT
36-1436-1436-1536-1536-16
16 =17 =18 =22 =23 =24 =
Combination with Disconnect SwitchReversing Combination with Disconnect SwitchCombination with Disconnect Switch, with CPTCombination with Circuit BreakerReversing Combination with Circuit BreakerCombination with Circuit Breaker, with CPT
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlContactors
Product SelectionTable 36-18. Class ECV01 — Non-reversing Contactors — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0144A3A. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.
Table 36-19. Class ECV02 — Reversing Contactors — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X
304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV024A3A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.
Field Modification KitsAuxiliary Electrical ContactsTwo Type J auxiliary contacts may be mounted on each side to provide four auxiliary, isolated 600V, 10A double break contacts for use in control circuits.
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0544AAA. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.
Table 36-23. Class ECV06 — Reversing Non-combination Starters — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X
304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0644AAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Mod-ification Code R5.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlNon-combination Starters
Table 36-24. Class ECV07 — Non-reversing Non-combination Starters with CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV0744EAA. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
CA08102001E For more information visit: www.eaton.com
36-17Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Product SelectionTable 36-25. ECV16 — Non-reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV01644AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Type 12 Non-reversing Vacuum Starter with Fused Disconnect
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-26. ECV17 — Reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV1744AAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
CA08102001E For more information visit: www.eaton.com
36-19Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-27. ECV18 — Non-reversing Combination Starters — Fusible and Non-fusible with Disconnect Switch and CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV1844EAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-28. Class ECV22 — Non-reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2244AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
CA08102001E For more information visit: www.eaton.com
36-21Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-29. Class ECV23 — Reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers — 3-Pole
� Wired for separate control.� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2344AAH. To order Type 4X
316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlCombination Starters
Table 36-30. Class ECV24 — Non-reversing Combination Starters with HMCP or Magnetic Trip Circuit Breakers and CPT — 3-Pole
� These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECV2444EAH. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
� All Type 12 enclosures are standardized with external reset. For internal reset, order Modification Code R5.� Alternate Catalog Numbers for those listed can be found in Table 36-17 on Page 36-13.� Type 12 enclosure is without safety door interlock. When safety door interlock is required, add Modification Code E11.
Starters do not include heater packs. Select 1 carton of 3 heater packs. Heater pack selection, Page 36-5.Starters with Electronic Overload, see Page 36-29 of Modification Codes.
Table 36-32. B — Breaker Modifications, Backspin Timer,Undervoltage Release, Bell Alarm, Bus Choke
� A DC bus choke may be used in place of an AC line reactor for line harmonic current reduction and for power source exceeding 500 kVA. The DC bus choke will not provide any protection for line voltage unbalance or transients.
Modification CatalogNumberSuffix
Description AdderU.S. $
Ammeter � A1 Panel Type Wired to Current Transformer in Line 1, Type 1, 12
Panel Type Wired to Current Transformer in Line 1, Type 3R, 4X
A2 Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 1, 12
Panel Type, Selector Switch and 3 Current Transformers Wired to Ammeter via Switch, Type 3R, 4X
A3 Miniature (Single-Phase), Type 1, 12
A4 Miniature with Selector Switch, Type 1, 12
A5 Switchboard (Single-Phase), Type 1, 12
Switchboard (Single-Phase), Type 3R, 4X
A6 Switchboard with Selector Switch, Type 1, 12
Switchboard with Selector Switch, Type 3R, 4X
A7 3-Panel Type (Single-Phase), Type 1, 12
3-Panel Type (Single-Phase), Type 3R, 4X
A10 3 Miniature (Single-Phase), Type 1, 3R, 4X, 12
A11 3 Switchboard Type (Single-Phase), Type 1, 12
3 Switchboard Type (Single-Phase),Type 3R, 4X
A12 Ammeter Order by Description, Type 1, 3R, 4X, 12
Auto-transformers
A8 hp Rating selection, see Enclosed Control Product Guide
A9 Order by Description
Top Mounted AuxiliaryContacts � �(Unwired)
Type Sizes 00 – 2 only(Unwired)
IEC SizesA – K Only(Unwired)Freedom Series
A13 1NO
A14 1NC
A15 1NO-1NC
A16 2NO
A17 2NC
A18 2NO-1NC
A19 1NO-2NC
A20 3NO
A21 3NC
A22 3NO-1NC
A23 2NO-2NC
A24 1NO-3NC
A25 4NO
A26 4NC
Side Mounted Auxiliary Contacts Freedom Series
A27 1NO
A28 1NC
A29 1NO-1NC
A30 2NO
A31 2NC
A32 2NO-1NC
A33 1NO-2NC
A34 3NO
Modification CatalogNumberSuffix
Description AdderU.S. $
Side Mounted Auxiliary Contacts Freedom Series, continued
A35 3NC
A36 3NO-1NC
A37 2NO-2NC
A38 1NO-3NC
A39 4NO
A40 4NC
Auxiliary Contacts �
A42 Contacts Mounted on Operating Mecha-nism of Disconnect Switch, 1NO-1NC
A43 Contacts Mounted on Operating Mecha-nism of Disconnect Switch, 2NO-2NC
A44 With Auxiliary Contact Omitted
Accelerating Relay
A46 For 2-Speed
A47 2NO/2NC 24V DC Auxiliary Relay — IT. Only
Modification CatalogNumberSuffix
Description AdderU.S. $
Breaker B1 1NO-1NC Auxiliary Contact on Breaker
B2 2NO-2NC Auxiliary Contacts on Breaker
B3 Shunt Trip on Circuit Breaker — 48 – 127V AC or DC
B4 Shunt Trip on Circuit Breaker —9 – 24V AC or DC
B5 Shunt Trip on Circuit Breaker —208 – 380V AC
B6 Shunt Trip on Circuit Breaker —415 – 600V AC or 220 – 250V DC
B8 Undervoltage Release for Breaker
B9 Current Limiter Mounted to Breaker
B10 Breaker — Order by Description
B11 Thermal Magnetic Breaker
Backspin Timer
B12 180 Seconds
Undervoltage Release
B13 Undervoltage Release for Circuit Breaker — 208 – 240V AC
B14 Undervoltage Release for Circuit Breaker — 380 – 480V AC
B15 Undervoltage Release for Circuit Breaker — 525 – 600V AC
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors
� Not available for IT. Starters.
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Control PowerTransformers
Make sure 8th character specifies primary/secondaryvoltage. SeePage 33-129.
C1 Standard Size Control Transformer, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C2 Standard Size Control Transformer,24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C42 50 VA Extra Capacity CPT 120V/60 Hz, 110V/50 Hz with 2 Primary and1 Secondary
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C3 100 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C4 100 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C5 200 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C6 200 VA Extra Capacity CPT, 24V/60 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C7 300 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C8 400 VA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
00 – 1A – H
2J – K
3L – M
4N
5P – S
6 – 9—
C9 1 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
C10 2 kVA Extra Capacity CPT, 120V/60 Hz, 110V/50 Hz Secondary with 2 Primary and 1 Secondary Fuse
C11 Control Transformer — Order by Description
C34 CPT with Power Supply for IT.
Modification CatalogNumberSuffix
Description AdderU.S. $
Power Supplies (IT. Only)
C27 Separate Control 120V AC to 24V DC
C28 Power Supply with Extra Capacity — Order by Description
Control Relays
C12 4-Pole Interposing Relay, 600V (2NO/2NC)
C13 Run Relay, 24V DC (MVX)
C14 � 4-Pole, Unwired, A600 Rtg. — 2NO-2NC
C15 � 8-Pole, Unwired, A600 Rtg. — 4NO-4NC
C16 Control Relay — Order by Description
C20 � 2-Wire Control Relay for Mechanical/Magnetic Lighting Contactors
Cover Control
C17 � Convert Position 7 to E30 Type Cover Control
C19 � Lock-Off Attachment Added on Cover Control
Current Trans-former(s)
C21 In Phase 1
C22 In Phases 1 and 2
C23 In 3 Phases
CompellingRelay
C25 � —
ControlWiring
C26 Omit Control Wiring
C30 � With Separate Control Wiring and Two 250V Fuses in Holder
C31 � With Common Control Wiring and Two 600V (Class C) Fuses in Holder
CA08102001E For more information visit: www.eaton.com
36-25Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-33. C — Control Power Transformer, IT. Power Supplies, Control Relays, Cover Control (not elsewhere defined), Current Transformers, Compelling Relay, Control Wiring, Control Circuit Breaker, Separate Control, Customer-Supplied Components, Contactors, Counter, E-Stop Relay, DC/AC Interface, Separate Source Disconnect, Bypass Contactors (Continued)
� Not available for IT. Starters.� Includes CPT, Pilot Lights, Selector Switch, Auxiliary Contacts and
Control Relay.
Table 36-34. D — Device Labels, Deceleration Relay, Drain and Breather, DeviceNet, Duplex Modifications
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Contactor/Starter
C40 � Contactor/Starter — Order by Description
Counter C41 � Operations Counter
E-Stop Relay C43 � E-Stop Relay (DeviceNet)
DC/AC Interface
C44 � DC/AC Interface Module
SeparateSource Disconnect
C45 � IEC Separate Source Disconnect for Control Circuitry
Bypass Contactorsfor IT./MVXStarters (MVX: 1/2 to 5 hp Only)
C46/J1 Isolation Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J2 Output Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J3 Bypass Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J4 Isolation/Output/Bypass Contactor
MVX 37A 66A 105 – 135A
80 – 240A 304 – 500A 650 – 720A 850A
C46/J5 3-Contactor Bypass Pkg. for MVX �
Modification CatalogNumberSuffix
Description AdderU.S. $
Device Labels D1 (each label)
Decel. Relay � D2 2-Speed
Drain andBreather(Type 7/9 Enclosure) �
D5 Drain and Breather
D6 Drain OnlyBreather OnlyD7
DeviceNet D8 DSNAP
D9 DN65
DuplexModifications
D12 Alternator Omitted (Deduct Price)
D14 START/STOP Pushbuttons — Sup-plied for Each Motor
D15 HAND/OFF/AUTO Selector Switch — Supplied for Each Motor
D16 No. 1 Lead - No. 2 Lead Selector Switch for Manual Selection of Lead Pump (Alternator is Omitted)
D17 Red RUN Pilot Light — Supplied for Each Motor
D18 Push-to-Test Red RUN Pilot Light — Supplied for Each Motor
D19 TEST Pushbutton for Each Motor
D20 CPT, 120V Secondary, 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Ea. Motor
00 – 1 2 3 4 – 9
D21 CPT w/100VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Each Motor
00 – 1 2 3 4 – 9
D22 CPT w/200VA Extra Capacity, 120V Sec., 2 Pri. Fuses & 1 Sec. Fuse — Supplied for Each Motor
00 – 1 2 3 4 – 9
D23 CPT for Duplex — Order by Description
D24 Add 2 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices
D25 Add 3 Relays to Modify Controller to Operate w/Single-Pole Pilot Devices
CA08102001E For more information visit: www.eaton.com
36-27Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-39. K — MVX Keypad
Table 36-40. L — Lightning Arrestor, Lugs, Labels, Line and Load Reactors, Lighting Contactors
� If the power source exceeds 500 kVA, 3% line unbalance, or if transient voltages from power factor capacitor switching events are present, an input line reactor must be used. The input line reactor will also reduce line current harmonics.
� The output line DV/DT filter is required when the distance from the drive to the motor exceeds 33 feet (10m). The total cable run should not exceed 165 feet (50m).
Table 36-40. L — Lightning Arrestor, Lugs, Labels, Line and Load Reactors, Lighting Contactors (Continued)
Table 36-41. M — Solid-State Controllers
Table 36-42. N — Nameplates
Modification CatalogNumberSuffix
Description AdderU.S. $
Keypad(MVX)
K1 Door-Mounted AFD Keypad (Type 1 and 12)
K2 Door-Mounted AFD Keypad (Type 3R)
K3 AFD Copy Keypad (mounted on drive)
K4 Door-Mounted AFD Copy Keypad (Type 1 and 12)
K5 Door-Mounted AFD Copy Keypad (Type 3R)
Modification CatalogNumberSuffix
Description AdderU.S. $
Lighting Arrestor
L3 Installed on Panel
Lugs L9 Special Lugs — Order by Description
Carton Label L10 Customer Marking — Specify
LineReactors(MVX)
L12 3% Input Line Reactor, 3-Phase, Open Core and Coil �
240V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
480V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
L13 3% Input Line Reactor, 1-Phase, Open Core and Coil �
480V 1/2 hp 1 hp 2 hp 3 hp
U.S. $
L14 5% Input Line Reactor, 3-Phase, Open Core and Coil �
240V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
480V 1/2 hp 1 hp 2 hp 3 hp 5 hp
U.S. $
L15 5% Input Line Reactor, 1-Phase, Open Core and Coil �
480V 1/2 hp 1 hp 2 hp 3 hp
U.S. $
L16 Line Reactor — Order by Description
LoadReactors(MVX)
L17 Output Line DV/DT Filter, Open Core and Coil �
For more information visit: www.eaton.com CA08102001E
Vacuum Contactors & Starters
36
NEMA, Enclosed ControlModification Codes
Table 36-43. P — Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell
� Not available for IT. Starters.
Table 36-43. P — Pilot Lights, Pushbuttons, Phase Relays, Potential Transformers, Power Factor Correction Capacitors, Program Timer, Percentage Timer, Photocell (Continued)
� Not available for IT. Starters.
Modification CatalogNumberSuffix
Description AdderU.S. $
Push-to-TestPilot Lights
P1 Push-to-Test Pilot Light (Red RUN)Wired to Coil
P2 Push-to-Test Pilot Light (Green OFF)Wired in Series with Auxiliary Contact
P3 Combination of P1 and P2 Above
P4 Push-to-Test Pilot Light (Amber RUN)Wired to Coil
P49 Push-to-Test Pilot Light (Green RUN)
P54 � Push-to-Test Pilot Light — RedBYPASS (MVX)
P55 � Push-to-Test Pilot Light — AmberINVERTER ENABLE (MVX)
P56 � Push-to-Test Pilot Light — RedINVERTER RUNNING (MVX)
P57 Push-to-Test Pilot Light — Green STOP
Pushbuttons P5 EMERGENCY STOP — MushroomHead
P6 � Pushbutton Omitted
P7 START/STOP
P8 ON/OFF
P9 START
P10 ON
P11 OFF
P12 � FORWARD/REVERSE/STOP
P13 � FAST/SLOW/STOP
P14 � FAST/OFF/SLOW
P15 � HIGH/LOW/STOP
P16 � HIGH/LOW
P17 � SLOW/FAST
P18 � Pushbutton with Legend Plate
P52 UP/STOP/DOWN
P53 OPEN/STOP/CLOSE
P73 START/STOP Pushbuttons Located in Top 2 Holes
Pilot Lights P19 With 1 Amber Pilot Light MarkedPOWER AVAILABLE Wired to LoadSide of 2 Fuses or Circuit Breaker
P20 Pilot Light (Amber RUN) Wired to Coil
P21 � With 1 Red Pilot Light Marked RUNWired thru NO Auxiliary Contact
P22 � With 1 Push-to-Test Red Light MarkedRUN Wired thru NO Auxiliary Contact
These fi les are the same as the last printed version of the catalog dated February 2007.For the most up-to-date information, install the Automatic Tab Updater (ATU) by visiting