STRUCTURAL ANALYSIS REPORT ACGI JOB #11-6405 175’ Monopole Tower Verizon Site – NF126 – Nags Head 5401 S. Croatan Highway Nags Head, NC 27959 For F.C.I. Towers, Inc. Virginia Beach, VA 9221 Lyndon B. Johnson Freeway, Suite 204, Dallas, TX 75243 Tel: 972-231-8893, Fax: 972-231-8033 www.allprocgi.com July 14, 2010 November 17, 2011 - Revised for (18) Coaxes ______________________ Approved By: 11/17/2011 Joji George, P.E.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
STRUCTURAL ANALYSIS REPORT
ACGI JOB #11-6405
175’ Monopole Tower Verizon Site – NF126 – Nags Head
5401 S. Croatan Highway Nags Head, NC 27959
For
F.C.I. Towers, Inc. Virginia Beach, VA
9221 Lyndon B. Johnson Freeway, Suite 204, Dallas, TX 75243 Tel: 972-231-8893, Fax: 972-231-8033
www.allprocgi.com
July 14, 2010 November 17, 2011 - Revised for (18) Coaxes
TABLE OF CONTENTS ANALYSIS SUMMARY ................................................................................................... 3 SCOPE & SOURCE OF INFORMATION ........................................................................ 3
SOURCE OF INFORMATION ...................................................................................... 3 ANALYSIS METHODS & DATA .................................................................................... 3
SITE DATA .................................................................................................................... 4 TOWER DATA .............................................................................................................. 4 TOWER HISTORY ........................................................................................................ 4 EXISTING TOWER LOAD DESCRIPTION ................................................................ 5
CONCLUSIONS................................................................................................................. 6 RESULT SUMMARY - TOWER .................................................................................. 6
1. ANALYSIS SUMMARY The existing 175’ Monopole Tower located in Nags Head, NC was reanalyzed for the existing and proposed antenna loads as authorized by F.C.I. Towers, Inc. Based on the results of the analysis, the existing tower with loading mentioned on page 5 is found to be in compliance with TIA/EIA-222-G, Structural Standards for Steel Antenna Towers and Antenna Supporting Structures for 130 mph (3-sec. wind gust) and 2009 North Carolina State Building Code and IBC2006. 2. SCOPE & SOURCE OF INFORMATION The purpose of this structural reanalysis is to determine whether the existing structure is capable of supporting the proposed and existing loading as noted on page #5 of this report with the T-Mobile coax installed outside the monopole.
SOURCE OF INFORMATION Tower Data: F.C.I. Towers,
Inc. Tower data as per original Structural Design Report by Sabre Towers & Poles, ref job #08-01164, dated 01/29/2008 and Structural Analysis by Allpro Consulting Group, Inc, ACGI #10-1797, dated 07/14/2010.
Foundation Data: F.C.I. Towers, Inc.
Foundation data as per original Structural Design Report by Sabre Towers & Poles, ref job #08-01164, dated 01/29/2008.
Soil Data: F.C.I. Towers, Inc.
Soil Data as per geotechnical report by GET Solutions, Inc., ref job #EC07-192G, dated 06/12/2007.
Loading Data: F.C.I. Towers, Inc.
Existing antenna loads as per Tower Mapping by Tim Miles with F.C.I. Towers, Inc., dated 06/08/2010 and Structural Analysis by Allpro Consulting Group, Inc, ACGI #10-1797, dated 07/14/2010.
Authorization: F.C.I. Towers, Inc.
Jason Hamill
3. ANALYSIS METHODS & DATA The analysis was performed in accordance with Telecommunication Industry Association specification TIA/EIA-222-G. The tower was modeled using RISA Tower, a 3-D finite element program. RISA Tower is a general-purpose modeling, analysis, and design
program created specifically for communication towers using the EIA-222-C, EIA-222-D, or TIA/EIA-222-F standards. The 3-D model included the tower, with existing appurtenances and all proposed loads.
SITE DATA Site Name: Verizon – Nags Head Client Site Number: NF126 City, State: Nags Head, NC County: Dare County, NC Code Wind Load Requirement: TIA -222-G / IBC2006 / 2009 North Carolina State
Building Code – 130 mph 3-Sec gust wind or 30 mph with 0.25” ice. Structure Class II. Exposure Category C. Topographic Category 1.
Owner Wind Load Requirement: N/A Wind Load Used: TIA -222-G / IBC2006 / 2009 North Carolina State
Building Code – 130 mph 3-Sec gust wind or 30 mph with 0.25” ice. Structure Class II. Exposure Category C. Topographic Category 1.
TOWER DATA
Tower Type: 18 sided slip joined Monopole Steel Tower Height: 175’ / 174’ total pole length Cross Section: 18 sided Steel Strength: 65 ksi Type of Foundation: Drilled Pier Tower Owner: -
TOWER HISTORY Tower Manufacturer / Model: Sabre Towers & Poles Date of Manufacture: 2008 Previous Modifications: Unknown Original Design Code Reqts: EIA/TIA-222-G 130 mph / 30 mph + 0.25” ice
Existing (1) 4’ Whip antenna mounted on (1) standoff mount
- (1) 1 5/8” Internal
-
Notes:
1. Certain conservative assumptions were taken on the area of the mounts. 2. Shielding on TX lines is taken as to best represent the conditions that were conveyed to ACGI in
the data provided or as per site inspection. 3. ACGI should be notified of any discrepancies found in the data listed in this report.
Foundation Foundation is in compliance when comparing to original design reactions: Moment (kip-ft) : 6633 < 6968.33 Axial (kips) : 50 < 69.801 Shear (kips) : 58 < 62.044
Pass Pass Pass
As per the results of the analysis, existing tower is capable of withstanding the proposed and existing antenna loads. Maximum tower member stresses are below 100%, making it acceptable under the TIA/EIA-222-G/2009 North Carolina State Building Code/IBC2006 code requirements. Based on review of tower foundation data and comparisons of the original design reactions with the current reactions, the foundation is satisfactory for the new reactions.
5. RECOMMENDATIONS The existing tower is recommended for the proposed additional loads. No additional loads except as mentioned in this report should be added to the tower without further structural analysis.
6. DISCLAIMER Installation procedures and related loading are not within the scope of this analysis. A contractor experienced in similar work should perform all installation work. The engineering services provided by Allpro Consulting Group, Inc. (ACGI) are limited to the computer analysis and calculations of the structure with the proposed and existing loads. This analysis is considered void if the loading mentioned in this report is changed or is different as installed. It is assumed that the existing structure is properly maintained and is in good condition free of any defects. Scope of this analysis does not include existing connections, except as noted in this report. ACGI does not make any warranties, expressed or implied in connection with this engineering analysis report and disclaims any liability arising from deficiencies or any existing conditions of the original structure. ACGI will not be responsible for consequential or incidental damages sustained by any parties as a result of any data or conclusions included in this Report. The maximum liability of ACGI pursuant to this report shall be limited to the consulting fee received for the preparation of the report.
TOWER DESIGN NOTES1. Tower is located in Dare County, North Carolina.2. Tower designed for Exposure C to the TIA-222-G Standard.3. Tower designed for a 130 mph basic wind in accordance with the TIA-222-G Standard.4. Tower is also designed for a 30 mph basic wind with 0.25 in ice. Ice is considered to increase
in thickness with height.5. Deflections are based upon a 60 mph wind.6. Tower Structure Class II.7. Topographic Category 1 with Crest Height of 0.00 ft8. Tower in code compliance with IBC 2006 and 2009 North Carolina State Building Code.9. TOWER RATING: 93.3%
Tower Input Data There is a pole section. This tower is designed using the TIA-222-G standard. The following design criteria apply:
Tower is located in Dare County, North Carolina. Basic wind speed of 130 mph. Structure Class II. Exposure Category C. Topographic Category 1. Crest Height 0.00 ft. Nominal ice thickness of 0.2500 in. Ice thickness is considered to increase with height. Ice density of 56 pcf. A wind speed of 30 mph is used in combination with ice. Temperature drop of 50 °F. Deflections calculated using a wind speed of 60 mph. Tower in code compliance with IBC 2006 and 2009 North Carolina State Building Code.. A non-linear (P-delta) analysis was used. Pressures are calculated at each section. Stress ratio used in pole design is 1. Local bending stresses due to climbing loads, feedline supports, and appurtenance mounts are not considered.
Options
Consider Moments - Legs Distribute Leg Loads As Uniform Treat Feedline Bundles As Cylinder Consider Moments - Horizontals Assume Legs Pinned Use ASCE 10 X-Brace Ly Rules Consider Moments - Diagonals Assume Rigid Index Plate √ Calculate Redundant Bracing Forces Use Moment Magnification √ Use Clear Spans For Wind Area Ignore Redundant Members in FEA √ Use Code Stress Ratios √ Use Clear Spans For KL/r SR Leg Bolts Resist Compression √ Use Code Safety Factors - Guys √ Retension Guys To Initial Tension √ All Leg Panels Have Same Allowable Escalate Ice √ Bypass Mast Stability Checks Offset Girt At Foundation Always Use Max Kz √ Use Azimuth Dish Coefficients Consider Feedline Torque Use Special Wind Profile √ Project Wind Area of Appurt. Include Angle Block Shear Check √ Include Bolts In Member Capacity √ Autocalc Torque Arm Areas Poles √ Leg Bolts Are At Top Of Section √ SR Members Have Cut Ends Include Shear-Torsion Interaction √ Secondary Horizontal Braces Leg Sort Capacity Reports By Component Always Use Sub-Critical Flow Use Diamond Inner Bracing (4 Sided) √ Triangulate Diamond Inner Bracing Use Top Mounted Sockets Add IBC .6D+W Combination
Base Plate Data Base plate is square √ Base plate is grouted Anchor bolt grade A615-75 Anchor bolt size 2.2500 in Number of bolts 20 Embedment length 84.0000 in f'c 3 ksi Grout space 2.0000 in Base plate grade A633-60 Base plate thickness 3.0000 in Bolt circle diameter 75.3750 in Outer diameter 73.3800 in Inner diameter 54.7500 in Corner clippled 15.0000 in Base plate type Plain Plate