-
t §
SIEMENS i fw
SpaceMaker IIMOTOR
CONTROLLER
W A R N I N G
Dangerous voltages are present inside controller
compartments.Always use safety precautions when entering.
De-Energize all incoming power if conditions exist which are
thecontrary to those described in this instruction book or which
areotherwise unusual. ICD 6031-01A20X2850-04
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
CONTENTSPage PageINTRODUCTION
GENERAL INFORMATION ....WARRANTYGENERAL DESCRIPTION
Door HandleAutomatic Shutter MechanismSeparately Accessible
Control Compartment . ...2
RECEIVING .INSPECTIONSTORAGE ..
ADJUSTMENT*•FUSE REPLACEMENT•ARC CHUTES•LSI, GUIDE PLATE, and
ANTI-RACKING
MECHANISM•CARRIAGE RACKING MECHANISM ... .
Power Plugs & Rear Racking ShaftCarriage Racking HooksDoor
Handle & Side Shaft
•RACKING SHAFT INTERLOCKINSTALLING THE INTERLOCKCARRIAGE STOP
SAFETY LEVERCARRIAGE POSITION INDICATOROPERATING CIRCUITSCONTACTOR
DROPOUT TIMESERVICE DOLLYCARRIAGE DISCONNECT
FINGER ASSEMBLIES•EMERGENCY ENTRANCE
1 101 1012 112 12
132 133 133 13
1415
INSTALLATIONCUBICLE MOUNTING. ...CONNECTIONS
Control ConnectionsEQUIPMENT CHECKOUT
ElectricalMechanical
153 163 166 1666 166 16
OPERATIONK'ORMAITEST
MAINTENANCEGENERALCARRIAGE RACKING MECHANISMAIR-BREAK
CONTACTORTROUBLE SHOOTING CHARTPARTS IDENTIFICATION
99 17
1718-2425-27
*Pay close attention to these pages. This information is very
important.
The information contained within i9 intended to assist operating
personnel byproviding information on the general characteristics of
equipment of this type. Itdoes not relieve the user of
responsibility to use sound Practices and SafetyProcedures in the
installation, application, operation and maintenance of
theparticular equipment purchased.If drawings or other
supplementary instructions for specific applications areforwarded
with this manual or separately, they take precedence over
anyconflicting or incomplete Information in this manual.
\SIEMENS-ALLISP.O. Box 89, Wichita Falls, Texas 76307
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
INTRODUCTION
GENERAL INFORMATIONThis Manual provides complete instructions on
instal -lation , operation and maintenance , and will be of
valueonly when read and applied by all personnelresponsible for the
equipment.
rear - mounted , isolated , low voltage control
devicecompartment.
Two full voltage squirrel -cage motor controllerscan be mounted
one above the other in the 36 -in. wide.32 - in. deep, 90 - in .
high cubicle. Each controller has afull rating of 1500 hp maximum
at 2300 volts or 2500 hpmaximum at 4000- 5000 volts. At unity power
factor , themaximum ratings of synchronous motor controllers
are1750 hp at 2300 volts and 3000 hp at 4000-5000 volts.With
current limiting fuses , each controller has aninterrupting
capacity of 200 MVA at 2200- 2500 volts or350 MVA at 4000- 5000
volts.
Mounted in the high voltage compartment are thecurrent
transformers, stationary disconnect plugs ,shutter and racking
mechanisms, line and load
Pay particular attention to the information aboutinterlocks and
their adjustments. These paragraphs arestarred.
WARRANTYSee sales contract .
GENERAL DESCRIPTIONEach SpaceMaker If controller consists of a
stationary ,rigid, self-supporting steel enclosure with a
fronthinged , high voltage compartment door containing a
inMin* AUI*
•"MfNS *UI1
Fig 1 •Single and two-high SpaceMaker II controller for
squirrel-cage motors.
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
Separately Accessible Control CompartmentThe isolated low
voltage control is accessible through ahinged door in the high
voltage compartment door.Access to the control compartment is
permitted at alltimes for operational inspection by turning the
twosiotted -head V\ turn latches. This compartmentcontains all of
the control and metering devicesrequired by the particular
application and permitted byspace limitations.
connections, mechanical and electrical interlocks, andthe
drawout contactor. The contactor itself mounts thecurrent limiting
power fuses , the movable disconnectfingers , the control power
transformer with two currentlimiting primary fuses and two
secondary fuses , adouble - throw (test - normal) knife switch and
a discon*necting control terminal block. (A separate manual
isavailable with information on the contactor - ICD6030.)
Door HandleRECEIVING — Handle With CareConvenient operation of
the racking mechanism is pro-
vided by the externally operated door handle whichrotates 180
degrees from the contactor “Connected” tothe "Open ” position . A
coupling on the door handleassembly permits opening the door only
in the door“Open” position. An indicator on the handle
givespositive indication of the mechanism position: that is
,carriage “Connected” , carriage “Disconnected” , ordoor * ‘Open’ *
. The door handle can be locked with up tothree padlocks in either
the “Connected ” or “Dis-connected” position.
Before moving or unpacking any units, examine allshipping
sections to determine if any damage has oc-curred in transit . If
damage is detected , unpack the unitand thoroughly inspect the
contents for damage. (SeeInspection.) The contactor carriages and
the controllercubicle are shipped in separate packages. Check
theentire shipment against the packing list for anyshortages ,
Determine the extent of the damage orshortage , if any, and notify
the carrier and yourSiemens- Allis sales office immediately.
Automatic Shutter Mechanism The cubicles and carriages are
shipped on separatewooden bases. Move the cubicles by lifting with
a craneusing the lifting angles provided. Lift the carriages
asshown in Fig. 3. Do not lift with racking hooks at rear
ofcarriage. If no crane facilities are available , rolling orother
methods may be used , but apply force only towooden shipping
pallet. Do not place carriages intocubicle until the units are at
the permanent location , allthe suggested inspections have been
made , and the
Installation” Section of this book has been read. Ifunits will
not be used immediately, see “Storage”.
An isolating shutter covers the line terminals when theracking
mechanism is in the carriage “Disconnected”or the door in the
“Open” position. This preventsoperating and maintenance personnel
from accidentlycoming into contact with the live line
terminals.
4 I
OVERLOADRELAY
i
Fig. 2 - Overload relay mounted in the SpaceMaker IIcontroller
front access compartment.
-2-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
c. Check that the control transformer primary fuses areproperly
positioned in their respective clips and arenot damaged.
d. Operate the contactor manually by pulling down thearmature of
the magnet to close the contacts. Uponreleasing , the movable
contact assembly should fallfreely.
e. Check the control panel on the side of the contactorto assure
that all wire connections are secure andthat the circuit is in good
operating condition.
f. Check the condition of the arc chutes.g. When more than one
controller is involved in an
installation , make certain that each carriage ismatched with
the nameplate in its respective com-partment . A stick -on
nameplate , provided on thecarriage and the compartment , gives the
followingdata: controller part number, carriage part
number,controller rating, control transformer and
currenttransformer ratios, fuse ratings, overload relay set -ting
and wiring diagram drawing number.
I
^i/ i'M,
M ViTViUBiFig. 4 - Remove this shipping angle only after
cubicles have
been mounted and leveled.
INSPECTIONRemove all packaging, blocking, and external
bracing.Do Not remove the angle iron brace (See Fig. 4) acrossthe
bottom of the front of the cubicle opening until theunits have been
leveled and bolted into place. Inspectas follows:a. Check all
components for evidence of loose bolts ,
nuts, accessories, freedom from distortion and forgeneral good
condition.
b. Inspect the main power fuses for proper mounting.The fuse
clips should also be checked for distortion.
STORAGEIf the controller will not be installed in its
operatinglocation , store it in a clean , dry place along with
thecarriages. Never store the controller and carriages in
anenvironment for which they were not designed. If spaceheaters are
furnished, keep them energized.
ter INSTALLATIONCAUTION
Controllers must be installed on a flat, level foundation.Slope,
if any, must be toward the rear. Slope must not exceed 1/8
inch.
CUBICLE MOUNTING not equal within 1 /8”. Also examine alignment
, perpage 7.The importance of mounting the cubicle on a flat
and
level foundation cannot be overstated. All four cornersof the
cubicle must be touching, securely bolted , andcontinuously
supported across the front and back. Pro-vide an apron extending a
minimum of three feet on thesame level as the front of each cubicle
for inserting andremoving the carriage . Install the extreme left
handunit at least 14” from any obstruction to allow thecompartment
floor to swing wide enough for thecarriage movement in or out .
Remove all temporaryblocking, packing, ties , retaining tape, etc.
from alldevices and mechanisms. Remove the angle iron (Fig.4)
across the bottom of the front of the cubicle. This wasonly a
temporary shipping brace and can be discarded.If the side lift
angles were used , remove these andreplace the hardware furnished
in the bolt holes. Touchup any scratches with the spare paint
provided. Correctany cubicle distortions, installation or
shippingdamage, etc . if diagonal measurements of cubicle are
CONNECTIONS(Refer to Figs. 5- 11 and Tables I , II and III)Make
all incoming power , load , and control connectionsin accordance
with the information given in these tablesand illustrations. Make
all connections as indicated inthe connection diagrams. The cable
arrangementsgiven for incoming line connections are maximum
sizebased on compartments being free of incoming
lineaccessories.
However, a limited number of accessories (e .g.potential
transformers , current transformers, lightningarrestors , surge
capacitors, etc.) may be used depend -ing on the size of the
accessory and the available space.Consult the factory when numerous
devices arerequired in incoming line compartments.
For units without bus, the incoming cables are con -nected to
the line terminals in each compartment of a
“3—
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
two-high controller. For a single controller in the
lowercompartment, the incoming cables are connected to theline
terminals in the lower compartment. In all cases,the outgoing motor
leads connect to the currenttransformers, located on the left -side
wall of thecompartment.
3 CONOUIT SPACE INFIXED TOP PLATEtI zriinr.z
rafrfr -“BUS 20
DUCT
2-t TOP VIEW36* or 24-
WIDE CUBICLE7/8 ** 1234 1/4 T1 LINEUP CAN BfEXTENDED IN £
ITHER^DIRECTION
ft>
*•fV 7\/ .CONOUIT SPACEIN FLOOR
/
CONOUITSPACE
IN FLOOR
3 FRONT VIEWVERTICAL ENTRY OF CABLE
3 R8 CD«D/ \
NOTESXJ1/ \/ •1- INCOMING LINE CAN ENTER FROMEITHER END Of
LINEUP .
* 2-llN{UP CAN BE EXTENDED ONLYON OPPOSITE END Of INC . LINE
.
p
1 CONDUIT SPACE INBUS DUCT END COVERI In5 *7-26- 17?4DUCTI l/J
FLOOR PLAN «*> FLOOR PLAN(Sin
36 O* 24"» 5 0 1 1 /7-l 5 '8 2 13 3 2 0 2i 1 WIDE CUBICLEI5 14
-S I 4 i96Jjk:p - “rX\C0NDUIT SPACE
IN TOP OFCUBICLE
*2r”-P"-- x LX- J
1 "T 3Tli -f -VISIDE VIEW FRONT VIEW-J L —iI 1
HORIZONTAL ENTRY OF CABLE: r — —I 1---1-_-_x“T- 1 CUTOUT
INBOTTOM OFBUS DUCT
1
fig. 7 - Cable Entrances (Refer Table III).TOP VIEW TOP VIEW
4 I*— 36 - - 2 4 - -
i 1E2 4T f ''TVW > f BUS 20DUCTW XT.SEE TABLE I == =Lr —
-CONDUIT SPACEIN TOP
FRONT VIEW FRONT v IE wTOP VIEWCABLE ENTRANCE IN
FULL HEIGHTM 36WIDE INCOMINGLINE CUBICLE
CABLE ENTRANCE INFULL HEIGTH 24-WIDE INCOMINGLINE CUBICLE
24 362 24
pFig. 5 •Cable Entrances (Refer Table I). CONDUITSPACE IN
BUSDUCT END "COVER
! ((1 >101I 1 .\ \ 116to 7JAJ c :::B
5 OO oSIDE VIEW FRONT VIEWJ 1 h>P. P-4 1i (NON-SHIELDED
CABLE)VERTICAL OR HORIZONTAL ENTRY OF CABLEBUS joDUCT JL_„PT 24
36-•ACONDUIT SPACE
IN BOTTOM-'-'"'" ItDI 3tVi 24AtTOP VIEW CONDUITSPACE IN BUS
DUCT END >COVER .
I
20 « - 1 •REMOVABLECOVER PLATE 14~ *r* r% r* -—s\ -1 4t 1 I4 4i
i 4 M lH 11U U
(SHIELDED CABLE )VERTICAL OR HORIZONTAL ENTRY OF CABLE
INCOMING LINE TOBUS COMPARTMENTTOP ENTRY WITH TOP HAT
f:O («FRONT VIEWSIDE VIEW
Fig. 8 * Cable Entrances (Refer Table HI).:ig. 6 - Cable
Entrances (Refer Table II).— 4 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
MAXIMUM CABLE SIZE PER PHASE
Shltldtd With |Siren Con#si Potheads(4 ) 500 MCM ! (2) Size 750
MCM
Cubic 1«Width Eni!3L Nonshleldtd
Top ( 4 ) 500 MCM36*'Of Of
( 3) 750 MCM 750 MCM: 6' 500 MCM ( 6i 500 MCM ! (2) Size 750
MCM36” BoHorn of Of'4 ', 750 MCM t f 4 * 750 MCM
500 MCM (2) Size 500 MCM24” (3 ) 500 MCMTooOf or
(2i 750 MCM(2) 750 MCM( 2) Size 750 MCM24” Bottom i ( 4 ) 500
MCM ( 4) 500 MCM
oror212186
Fig 9 * Cable connections for incoming line and outgoing
motorconnections Shutter removed to make incoming cabie
terminalsaccessible
(3 ) 750 MCM(31 750 MCM
TABLE I Figure 5 * 24 or 36 inch auxiliary cubicle.
£
*-*I I Shi »1 dad WithEntry 1 Nonshitldad i Strosi
ConesCubicleWidth RemarksMax. of 3bus feed C.T.mounted inbus
duct
i
| < 3 > 750 MCM j ( 21 750 MCMBottom : per phase | per
phase1C”
I*
_TABLE II Figure 6 * Incoming line through vertical bus duct
on
either end of lineup.
"1Shielded WithStress ConesEntry Orifice Nonshielded Remarks
(1) 250 MCM 12” Wide topplate24M W x 10"H top hat
20X 6Vertical
20X16 [ 2 ) 750 MCM (2) 750 MCMVertica I
(1) 250 MCM(2) 500 MCM
Horizontal 20X 6Horizontal 20X16 (2 ) 500 MCM 24” W x 10°
H top hat
TABLE Ml Incoming lines to bus compartment maximum cablesizes
per phase. Figures 7 and 8
223015Fig 10 - Line cables internally connected between upper
and lowercompartments.
When a nine-plug carriage used on reversing controllers is
furnished , stub cables are provided for thecustomer to connect the
incoming line to the lineterminals.
When a two* high (Style Y ) controller is furnished ,the
interconnections between the upper and lowercompartments are
factory installed. When the con-troller is furnished with a bus,
interconnections fromthis bus to the line terminals are factory
installed. Theinsulated tube furnished only on two- high
controllers ,permits pulling motor cables through an
energizedcompartment .
l
NOTH: All ' line terminals are energized unless theincoming line
is opetied.
If larger size incoming cables or more cables perphase (See
Table I ) arc required , a special compart -ment can he supplied.
These additional compartmentscan also provide the space
requirements for metering ,potheads. current transformers, etc.
— 5 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
Control Connections*4 . Check remote sequence interlocking
connections for
correctness of contact and make certain conduitwiring is not
grounded. ( Extremely long remote con -trol runs in conduit of a
few hundred feet or moremav prevent the control relays from
dropping opento stop motor because of capacitance between wiresin
the conduit . If this condition exists , use inter -posing DC
control relays. Consult factory regardingthis situation. )
5 . Exercise extreme care that all secondary circuits ofcurrent
transformers are closed. The open circuitscan occur when
instruments are shipped separatelyor are mounted reinotclv.
6. Check all control devices for any foreign matter.All devices
must be free to function normally.
4
7 . Check all fuses for continuity and proper rating.(See page
10 for fuse replacement . )
8. Check settings on all protective relays using appro-priate
instruction manuals.
Remote control or metering connections are made tothe terminal
blocks located on the left -side wall of thecompartment and are
accessible from the low voltagecontrol compartment . If the control
devices are locatedin a separate compartment , the remote
connections willnormally be made to terminal blocks located in
thatcompartment. Be sure to remove any temporaryjumpers when
connecting the remote devices.
EQUIPMENT CHECKOUTCheckout all equipment systematically prior to
engi -neering and placing in service . This checkout can
beperformed by the installer or operator or contact yourSiemens
Allis sales representative for a quotation forthe services of a
serviceman. The following is arecommended check list sequence
:Electrical1. Check all high voltage cable ( including factory in
-
stalled) for rght and proper connections. Make sureall proper
mechanical and electrical clearances havebeen maintained.
2. Check all power connections behind protectivebarriers or
shutters.
3. Check all external power and control connectionsagainst
wiring diagrams.
Mechanical1. Match the fused carriage with the corresponding
cubicle. Check the rating data of the label on thefront left -
hand side of the carriage with the inside ofthe compartment
door.
SHUTTER
MECHANICAL*̂ 4jy'lNTERL0CKi J \l iMAIN LEAbSTATIONARY
PLUGS
CONTACTOR /GUIDE TRACKS
ELECTRICALINTERLOCK
Fig 12 - Note Label “FRONT"Fig 11 - Layout ( f SpaceMaker 2-high
(Style Y ) controller compartments.—6 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
REAR SHUTTER SHAFTRACKING PINS
ACUBICLEREAR SHEET
MECHANICAL RACKINGINTERLOCK
1—a11-1 'Bi r * - s ir -GUIDE PLATE/ (MUST BE LEVEL)
SHIMMING WASHERSNOTES 1 ADJUSTMENT TO BE MADE WITH SHUTTER
MEOIANISM IN FULLY CLOSEO
POSITION (SIDE SHAFT FLAT UPWARD)2 CARRIAGE GUIOE RAIL ON GUIDE
PLATE SHOULD BE PERPENDICULARTO THE R E A R SHUTTER SHAFT3 LSI
SHOULD BE PERPENDICULAR TOGUlDE PLATE TO ADJUST. ADD
SHIMMING WASHERS 00 NOT BEND THE SUPPORT BRACKET ORTHE SPRl^C
CONTACT
Fig. 14. •Line switch interlock and racking interlock
dimensions.
4»F0R 9- PLUGCONTACTOR 7[1] Guide Plate or Support Plate\2\
Guide Rail(3) Hold down bolts(4] Anti-racking Interlock|5] Line
Switch Interlock |LSI)[6| Shutter Panel[7) Racking Pins[8) Side
Shaft (note flat spot 8A|[9) Rear Shaft
o
RACKINGSHAFT
ITT O3Doz
1*STATIONARYPLUG TERMINALS f(£>£ OTOP or SUPPORT
PLATEFig. 13 * SpaceMaker II Controller Cubicle.
i .\2. Check arc chutes in carriage for proper placement.Examine
chutes to make certain they are not crackedor have pieces broken
off. If any pieces are missing,check contactor carefully for any
fragments that mayhave fallen into the mechanism. Any
foreignmaterial that prevents contactor operation could endin
extensive damage. (See page 10 for arc chuteplacement.)
3. Check contactor and fuse interphase barriers. (SeeFig. 12. )
Barriers must be in place with the edgeslabeled “front” as
shown.
4. Check racking interlock manually to assure freemovement.
Check spring for proper placement . (Seepage 11 for
adjustment.)
With the spring in place and the plunger stillnot operating
freely, check for binding of the inter -lock mechanism.
Some special controllers , such as reversers .have two-high and
/ or side by side units with inter -compartmental linkage between
anti- racking inter -locks that prevent opening any one
compartmentdoor when any of the contactors in the other com-
SIDE VIEW
Fig. 15 * Alignment of stationary plug terminals on rear
compartment wallshould be checked before inserting carriage.
partments are closed . Consult factory for adjustmentof these
multi- linkage interlocks.
At this point , check the guide plate (supportplate). This plate
, the LSI and the interlocks havebeen factory adjusted. Check
dimensions as shownin Fig. 14. (See page 11 for adjustment . )
5. Rotate the side shaft of the cubicle to make certainthat the
shutters move freely. Check alignment ofthe stationary power plugs
on the rear compartmentwall according to the dimensions shown in
Fig. 15.(Illustration shows a nine plug carriage.) The dimen-sions
to the centers of the plug terminals are meas-ured from the top of
the plate which supports thecarriage wheels. (See page 13 for
adjustment.)Leave the side shaft in a position with the flat
sidehorizontal and facing upward so it will mate withdoor handle
coupling. (See page 12 for adjustment.)— 7 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
STOP BRACKET
ANGLE SEAL
&r .**Tig. t6 Stop bracket and angle seal (Angle seal only
on special NEMA
enclosures) .Fig 17 - Locking pin holds dolly safely to
controller frame.
(Refer page 28}
6. Clean guide plate and compartment floor thoroughly.Assemble
stop bracket (See Fig . 16) to guide plateper Fig. 37.
NOTE: Some NEMA special purpose enclosures havean angle at the
bottom of the compartment(Fig. 16) to form a seal with a gasket on
thelower inside of the compartment door. Removethis angle only to
roll carriages in or out of com-partments. When carriage has been
installedand completely checked for proper operation ,replace this
angle.
i
For upper compartments , use the transferdolly. The carriages
can be safely lifted onto thedolly with a rope sling and chain
hoist . Place therope sling under the four ends of the carriage
sideplates, as shown in Fig. 3, but not across the knifeswitch or
fuses. Do not lift with racking hooks. Besure that the locking bars
are in place while the car-riage is on the dolly and that the dolly
is level andproperly adjusted to the height of the upper com
-partments.
Fig. 18 - Transfer dolly permits safe removal of carriage from
uppercompartment (Refer page 28)
8. Remove control circuit plug from clamp on left sideof
compartment and plug into mate on carriage. (SeeFig. 19.) Tighten
the two fasteners and check thatall'leads are secure to plug - in
block. CONTROLLERTEST. The controller can be tested in this
position.See the instruction label posted to the carriage nextto
the knife switch for test procedure. (See Fig. 20.)After a
successful test , MOVE THE CARRIAGESWITCH INTO THE NORMAL (UP)
POSITION,turn the external racking door handle upwards , sothe
pointer indicates open , arid close the compart -ment door. The
door handle bearing must mate withthe shaft when the flat spot on
the shaft is facingupward. (See Fig. 13.) If the handle does not
fit ,adjust as shown on page 13.
Position the dolly in front of the proper com -partment and
insert the dolly locking pin. (See Fig.17 & 18.) Make sure no
cord or wire is in the pathof carriage wheels.
7. Roll the carriage into the compartment (with thegrooved left
wheels straddling the guide rail ) as faras the racking shait
safety interlock will allow . Thisinterlock pijevents ramming the
carriage completelyinto the compartment while thestop bracket to
butt against guide rail .
Idoor is open. Turn
-8-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
*
DISCONNECTINGTERMINALBLOCK
/ OCEDURE1.%
Fig. 19 - The disconnecting terminal block connects all
secondary wiring tothe carriage.
9. Rack in carriage by turning handle 180°clockwise until the
handle is vertical and the pointerindicates the carriage is
"Connected’ \ A snappingaction will be noticed as the racking
mechanismlocks in near the end of the racking travel.-
Fig 20 - Knife switch used to test controller.
not rack in easily , adjust the racking hooksas shown on page
13. Also check the gear meshas shown on page 12.
counter
Tf all of the above steps have been checked , and adjust -ments
are correct , the rnoior controller is ready foroperation. Proceed
to the section on Operation.NOTE: DO NOT USE FORCE. If the carriage
does
OPERATION
The- standard SpaceMaker II circuit for a full-voltage,
squirrel-cage motor controller is shown in Fig. 21.
TEST
Leave the control disconnect block attached to the carriage
andmove the carriage several feet from the compartment. The
controlcircuit will not operate because the primary and secondary
of thecontrol power transformer are open.
NORMAL
With the control knife switch in the normal position, the
carriageracked to the "Connected" position and the incoming line
ener-gized , pressing the start button energizes the master relay
coil( MR ). A contact of MR energizes the contactor rectifier and
coilcircuit, and another MR contact provides half of the start
buttonseal. An M contact completes the seal when M closes to apply
powerto the motor. The start button can then be released.
The main contactor may be supplied with a coil circuit
requiringeither 115 volts or 230 volts A C. Depending on the type
of coilfurnished, perform the following steps to test the
controller:
230VAC Contactor - Connect a single-phase, 230 volt , 60HZpower
source to points 13 and 14 on the compartment terminalboard. If the
control circuit includes 115V devices, then the testpower must be
from a three-wire 230/115V source connected toterminals 13, 14 and
15 with point 15 grounded.
Pressing the stop button de-energizes the master relay. The
con-tacts of MR open, de-energizing the main contactor and
breakingthe start button seal. The M contact in the seal circuit
opens whenthe main contactor drops out.
115VAC Contactor - Connect a single-phase, 115 volt. 60HZpower
source to points 9 and 13 on the compartment terminalboard. Ground
, if any. must he connected to terminal 9
In the case of an overload, the normally closed overload
contact( OL) in series with the master relay coil will open, and
the sequ-ence will be the same as a normal stop. After returning
the circuitto the start conditions, the motor may be pul back on
line throughthe normal start sequence.
After connecting test power, move the knife switch to the
testposition. The control circuit will now function in the normal
man-ner. Always return the knife switch to the normal position
whentesting is completed.
—9 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
/
fINCOMING LINEe * ‘‘
uTT u.sUJc/1 FUSEFUSEDu.
ControlTransformer
AW ControlTransformernnX X X ramocrr
1 .nr tnF“V?I F 9 ^ouOL *? &ML ir, 'T3 01l I OL CUST. TEST
SOURCE115V \ct CTCT CUST TEST SOURCE230 V »D
START
MR M
9*T2 11T3T1 Elnd.Motor MR MiMRriMR
SP SP,Tsp
“ LEGEND — HH YYCT .... Current TransformerK5 .... Knife
SwitchLSI .... Line Switch Inter lock
Main ContactorMaster RelayOver load Relay
REC .... Rect i f ierSurge Protec tor
»*v> Oo o cAC'ACAC RR»R S M
1 1 (Ms 1 M TR S M»-Q IVM
MR S M4*OL LWLW
21B • 115VAC CONTACTOR OPERATIONSP 21 A • 230VAC CONTACTOR
OPERATION
ADJUSTMENTThis section describes and illustrates all
adjustmentsfor the carriage and compartment.
CAUTIONMake sure the arc chute is properly inserted* rearend to
back, as shown in Fig. 23. Failure to insertthe arc chute properly
will result in damage to thecontroller.
•FUSE REPLACEMENT (See Fig. 22)Remove fuse barriers if
necessary. Place fuses in theholders so that the target button on
the end of the fuseis toward the front of the carriage. If the fuse
blows , thetarget will extend 3/8 to 1/2 in. Remove fuses from
theholders by lifting one end and withdrawing the otherend from the
fuse clip . If difficulty is encountered inremoving the fuse, a
screwdriver handle or wrench maybe placed under the fuse , between
the fuse and the fusetongue, and a prying motion used . Replacement
fusesshould fit tightly against the semi-circular stop locatedat
the bottom of the fuse holder.
To remove arc chutes , lift the back end of the chuteuntil it
releases and then lift the entire chute upward ,slide forward and
out.
1 f*< * r v '.. M t/ ;a ;Jr - - . 1 f.'i% 1i '3
r i- v, f. \
:i
v*ARC CHUTESTo insert arc chutes, slide in rear of chutes first
, thenpush down on front and back of chutes, making surethat the
arc runners are properly seated over thestationary contacts. Arc
chutes are properly seatedwhen a positive click is felt on both
ends of the chuteand the groove on the side of the arc chutes is
horizon -tally even with the blowout plates.
vT
n• '•«
Fiq. 22 - No special tools required for fuse
installation.—10-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
spring to prevent over bending when carriage is rackedin.
DO NOT CHANGE THE LENGTH OF THEMATING CONTACT STUDS (See Fig.
24). These studshave been factory set with an assembly Fixture.
Thissetting must be maintained to allow interchangingcarriages in
various compartments. Remember thatsubstitution of carriages
requires matching data withcompartment door labels.
SHIM TO SUITWITH *10WASHERS
LEAFn SWING
3Fig. 23 Inserting arc chuteGUIDEPLATE
tzr:TOP VIEWSiUE VIEW
Fig. 25 - Adjust LSI with washers as shownNormally, when the
carriage is in the racked in
position, the leaf spring will be 50% compressed. (SeeFig. 26
and Instructions page 12.)
STUDS24 - Mating contact studs for LSI
*LSI , GUIDE PLATE, AND ANTI-RACKINGMECHANISM
(Refer to Fig. 13, 14, and 24 thru 28)Check dimensions as shown
in Fig. 14.If the plumb line dimensions check indicates both inter
-locks have shifted the same amount and in the samedirection ,
loosen the four bolts that hold down theentire guide plate (Fig.
13). Shift the guide plate untilthe proper dimensions are obtained.
(Guide plate clear -ance holes are oversized to permit adjustment.)
Tightenthe four bolts securely.
If adjustment of the LSI only is required , observethe
following: Adjust any obvious distortions to the leafspring. A
stefci backing plate is located behind the Fig. 26 • Handle shows
line switch interlock relationship.
1 1
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
Adjust LSI by adding washers .as shown in Fig. 25. Afurther
check of the LSI is as follows:
If adjustment of the anti-rack interlock is required,observe the
following:
1. Connect a buzzer and battery to terminals 9 and 11.(If there
is power to the unit , connect a 300 voltmeter to terminals 9 and
11.)
1. Loosen the two mounting nuts. (See Fig. 27.)2. Shift the
interlock assembly to the front or rear as
required.2. Rack the carriage in until buzzer sounds or VM indi
-
cates contact. 3. Use the dimensions shown in Fig. 14. The
plungermust clear the interference post on the carriage by/4"
maximum at B when the carriage is racked in.
(See Fig. 28)3. Rack carriage out slowly. Contact should be
broken
at 35° to 45° of handle rotation. (See Fig . 26 . )
PLUNGERCARRIAGE RACKING MECHANISM
The gear meshing of the side and back racking shaftscannot be
off one tooth in either direction for properoperation. Proper
meshing can be checked by makingthe checking Fixture showm in Fig.
29 , and using it asfollow's:
r1/4 000oio
“"XT)+ . V« APPROX0 943 Ii
APPROX .M.F. 1/4 or 5/16 C R. STEEL
‘ -VFig. 29 - Gear mesh checking fixture.ADJUSTMENT NUTS
r
Fig. 27 - Anti-racking interlock.
PADDLE
INTERFERENCE POST
Fig. 30 • Fixture placement for checking gear mesh.Fig. 20 -
Interference post on carriage.
-12—
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
•Carriage Racking HooksThe carriage must be drawn into proper
electrical con -tact with even pul! on the racking hooks . If any
inter -ference occurs , adjust the hooks forward or back untilthe
carriage rolls freely. The hooks may also requireadjustment up or
down to obtain proper carriage lock -ing. The point indicated in
Fig . 32 should be 28 3, 4 in.from the floor to the top of the slot
in the racking hook .
*Door Handle and Side ShaftRemove the screw that fastens the
handle to the squareshaft of the coupling. Remove the handle ,
pointer andlock plate , spring washer and indicating plate ,
carefullynoting the assembly sequence. Loosen but do notremove the
three bearing screws which are nowexposed.Fig 31 - Front side snaft
support.
Close the door and position the coupling and bear -ing for
proper mating to the side shaft . The door latch ,which is mounted
on the inside flange of the cubicle ,may need adjustment to clear
the coupling. With thedoor closed and the coupling in its proper
position ,tighten the three bearing alignment screws. Re-assemble
the door handle in the proper sequence anddouble check for proper
indication and handle position.(See Fig. 33. )
With the side shaft turned so that the flat ishorizontal and the
stop pin is against the stop on thefront bearing support , place
the checking fixture on theshutter drive arm pin on the racking cam
t Fig . 30). Theedge of the fixture should be flush with the side
shaftwith the shutter completely closed. With the side
shafthorizontal , adjust the front and rear side shaft supportsfor
free mechanism movement and minimal end plav.
To change the gear mesh , remove the front and rearside shaft
supports . (See Fig. 31 . ) Disengage the gear -ing and rotate the
side shaft to the proper meshposition. Reinstall the front and rear
supports and alignas described above.
BEARINGSCREWS
r 'r .v -• - '-- -A*.:-- - - "~-
•Power Plugs and Rear Racking ShaftCheck dimensions as shown in
Fig. 15. If the shaftheight is off , adjust the channel support .
If anindividual set of plugs is out of position, adjust the indi
-vidual insulator support independently.
ADJUSTMENTBOLTS
Fig 33 - Disassembled door handle showing the bearing
alignmentscrews
RACKING SHAFT SAFETY INTERLOCKA safetv interlock is provided on
the SpaceMakercompartment racking shaft mechanism . The shaft lock(
Figure 34 ) consists of a lock bracket ( 48) and com -ptession
spring (49 ) mounted on the racking shaft at thefiom bearing
support . 1 he lock bracket prevents rota -tion ol the racking
shall through inteifrrence with thestop pin when the compartment
door is open. Thepm pose ol this safetv feature is to lock the
line.shuttersdosed when the compartment door is open.
GUIDE PLATEFig 32 - Racking hook dimension.
-1 3-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
49
tI l I[ \ I':rri i£"SIDE VIEW D 43
Fig 35 - Interlock with Door Closed and Shutter Open.
2726 49nT1\ H-
'11r H 1
SIDE VIEW 7 ° 4350Fig 34 - SpaceMaker II Shaft Interlock
Installation CLEARANCEWithout this interlock , the racking
mechanism can beoperated freely by hand or other externally
appliedforce to open the shutters and expose the energized
lineterminals . With the interlock the shutters can beopened for
inspection purposes by bypassing the inter-lock. This is done by
pressing the lock bracket inward tothe point where the pin clears
the bracket and thenrotating the shaft 180° by hand ( Figure
35).
Fig. 36 * Interlock with Door Closed and Shutter Closedarc of
180°. The new mechanism is not adaptable to theolder SpaceMaker
model which employed a reversibleratchet type racking handle which
rotates through 320°.The new shaft lock mechanism can be simply
installedon SpaceMaker II units without the need for machiningany
of the exist ing parts . If this safety feature is to beadded on
existing controllers , one lock bracket 25-204 *209-001 and one
compression spring 25- 120 - 212 * 001 arerequired for each
SpaceMaker II racking compartment .Proceed as follows to install
the lock bracket and springin the field. Refer to Figures 34 and
44.
WARNINGPerform this operation with extreme care. High
voltageexists on the terminals.
CAUTION CAUTIONPerform this inspection only with the carriage
removedfrom the compartment. Be sure to rotate the shaft backto its
original position so the shutters are closed afterthe inspection
(Figure 36).
Throughout this installation , carriage must be removedfrom
cubicle and unit must be disconnected from theline to de-energize
the line stabs located behind theshutter .
In normal racking operation, the interlock is releasedonly when
the compartment door is fully closed. As thedooi is closed , the
racking handle coupling (23) engagesthe front edge of the lock
bracket (48) and pushes itback to provide clearance for the stop
pin (50) as theracking shaft (26) rotates. The lock bracket is held
inthe disengaged posit ion with spring compressed duringall racking
functions. The compression spring will drivethe lock bracket
forward to lock the shaft only when thecarriage is disconnected ,
the operating handle is in the“open posit ion and the door is open
. High voltagecompartment door must be pushed and held fullyclosed
against the spring pressure before handle can berotated .
1. Drive out roll pin (5U ) from collar (28) and rackingshaft
(26).
2. Unbolt and remove rear bearing ( 29 ) and bearingbracket ( 27
) from cubicle.
3. Pull bearing bracket ( 27) and collar ( 28) from rackingshaft
.
4. Reassemble parts on shaft (26) in the following order:back
half of the bracket (48). collar (28), bearingbracket (27) , spring
( 49) , and front half of bracket (48).
5. Reinstall the front and rear supports , making surethat
shutters are closed when the shaft has the flatside horizontal and
facing up. (See Carriage RackingMechanism , page 12.)
6. With shutters closed and shaft with flat side up,reinsert
roll pin and drive through collar and shaft .The pin should be
flush with top of collar and onthe right side ( when facing unit )
of the bearingbracket s lower lip.
7 . Disassemble and remove door mechanical interlockwhich
connects from door to guide plate.
INSTALLING THE INTERLOCK ON EXISTINGCONTROLLERS
be field -The shaft ir j ierlock safety mechanism caninstalled
on j existing early model ( Pre - 1971 ) Space -Maker II
controllers : these are equipped with theformed square tube handle
which rotates through an
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
The racking shaft safety interlock mechanism describedabove
includes all of the safety functions that wereprovided by the door
operated mechanical interlock.This mechanism consisted of an
interference cammounted on floor plate at left hand side of
carriage andactuated by curved connecting rod attached at lowerleft
hand corner of compartment door. The mechanismblocks complete entry
of the SpaceMaker carriage intothe compartment when door is open
and permits entryonly when compartment door is about 4" from
beingfully closed. The door -operated mechanical safetyinterlock is
now superseded by the new shaft interlockmechanism.
GUIDEPLATE
GUIDE RAIL
STOP LEVER14 171 633 002
O
Fig. 38 Location of Stop Lever in Shipping Position
(Figure 38). After the SpaceMaker unit has been set inits final
location , remove and discard the temporaryshipping angle (Figure
4). The carriage stop lever in itsshipping position will block
entry of carriage. The leverthus must be unbolted from its
temporary position andinstalled on the threaded stud as showm in
Figure 40.The friction nut provided to hold the bracket in
placemust be turned down on the stud to the point where thelever
can still be moved freely by hand.
| ; CAUTIONMake certain that the stop lever is properlyinstalled
at its operating location in eachSpaceMaker carriage disconnect
compart *'ment . An instruction label (Figures 37 and40) is
provided showing the relocation of thestop lever from its temporary
shipping posi *tion to its permanent position.
IMPORTANT INSTRUCTIONSBEFORE CARRIAGE IS PLACED INTO
COMPARTMENTSTOP LEVER MUST BE REMOVED FROM SHIPPINGPOSITION &
ASSEMBLED AS SHOWN.
NUT TO BETIGHTENED TOALLOW FREE
Q QJ MOVEMENT OFSTOP LEVER
!\vx OT \O \O
\STOP LEVERGyiDE PLATE
25-118-524-002Fig. 37 - Stop Lever Assembly instruction
Label
CARRIAGE STOP SAFETY LEVERA change has been made in the design
and in the ship-ping installation of the carriage stop lever shown
in itsoperating location in Figure 37. This lever is mountedon the
floor plate at the front left corner. When thecarriage is inserted
, the lever blocks the left frontcarriage wheel with the carriage
in the “disconnectedposition . The stop lever must be rotated
parallel to theguide rail by hand before the carriage can
becompletely inserted in the compartment. When thecompartment door
is closed , the door flange rotates thelever counterclockwise thus
blocking the carriage wheelbehind the interference end of the stop
lever (Fie . 40).When the door is closed , the interference end of
thelever should contact the guide rail and thus preventmotion of
the carriage. Bend the tab on the end of thelever that contacts the
door if necessary, so that thiscondition exists. When the door is
opened , manuallyrotate the lev^r clockwise so it is parallel to
the guiderail and the carriage can then be removed. The inter
-ference end of the lock lever has been redesigned toprovide
greater interference and added strength.A somewhat different
arrangement for the carriagestop lever exists for NEMA special
gasketed enclosuretypes where formed steel sealing strips are
boltedacross the bottom of the SpaceMaker compartments .See Figure
16. The purpose of these strips is to providea scaling edge to bear
against the gasket material onthe inside of the door. Where these
sealing strips areinstalled , the operating end of the lever has
beenshortened and will be in position to block the carriagewith the
strip in place. The formed strip must be tem -porarily removed when
the carriage is initially installedin its compartment or when the
carriage is to beremoved from ^ ts compartment . The sealing strip
must^ . be in position at all other times in order to provide
aneffective seal fpr the SpaceMaker compartment .A new temporary
location is provided for the carriageguide rail on the left hand
side of the compartment floor
SPACEMAKER CARRIAGE POSITION INDICATORA carriage position
indicator plate (Figure 39) is nowrstandard^ , equipment in each
SpaceMaker carriagecompartment . The indicator plate (part number
25*118-524-003) is mounted at the right front on thecompartment
floor ( Figure 40) and is readily visible assoon as the compartment
door is opened. This indicatorsupplements the carriage position
indication providedby the racking handle when compartment door
isclosed. A large arrow on the indicator plate indicatesthe normal
location of the carriage in theconnected” position. The plate can
readily be installedon existing units without any machining
operation .
* »
dis -* i
EABtCARRIAGE BASEANY CARRIAGE POSITION IN
FROM ARROW INDICATES UNSAFECONDITIONS CONTRARY TO
INSTRUCTIONS 20 X 2850.CARRIAGE MAY BE ENERGIZED"OISCONNECT
INCOMING POWER
BEFORE ENTERING
DANGERKEEP OUT
IF FRONT EDGE OFCARRIAGE BASE IS
NOT AT ARROW WHEN"DISCONNECTED"
75 H8 574 UOJ
Fig. 39 - Carriage Position Indicator Plate
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
SPACEMAKER OPERATING CIRCUITS service dolly will not accommodate
an upper com -partment. The construction of a lightweight
portableplatform is normally recommended to service
bottomcompartment carriages when SpaceMaker units areinstalled on a
pad above aisle elevation. The factoryshould be consulted where
service dollies are requiredfor heights above 52".
Certain controllers are now furnished without the masterrelay.
The circuit shown in Figure 21 is modified to usepilot devices to
directly energize the contactor rectifier.
TYPE 456 CONTACTOR Choice of Dropout TimeA choice of opening
time after de -energization of theSpaceMaker type 456 contactor is
available. This isaccomplished by alternate connections between ter
-minals R and S in the DC operating coil circuit asindicated in the
circuit diagram (Figure 21). Carriageterminals R and S correspond
to compartmentterminals 25 and 26 for most SpaceMaker
controllers.
CARRIAGE DISCONNECT FINGER ASSEMBLIESAn increase in the contact
pressure has been made inthe power disconnect finger assemblies
item 1. Figure41 , part number 71 - 240-055* 501 . An increase
inpressure of contact fingers was initiated for improvedperformance
in corrosive environments such as papermills and chemical plants.
The original music wiresprings had a 15 pound rating and were zinc
plated anddichromate treated. Disconnect finger assemblies nowbeing
supplied are equipped with stainless steelsprings rated at 25
pounds and have an orange color foreasy identification.
Standard circuits are arranged to provide an inherentdropout
time of 400- 500 milli seconds for the type 456contactor on
deenergizing its coil circuit . Thisoperation is provided by
opening the AC input to theoperating rectifier only. The dropout
delay has provenextremely beneficial in maintaining
uninterruptedmotor operation on power systems experiencing
severevoltage dips of short duration. The operating circuit ofthe
type 456 contactor also remains sealed at approxi-mately 40 %
normal voltage .
SpaceMaker carriages equipped with the new, higherpressure
disconnect finger assemblies with orangesprings require a slightly
higher racking force. Contactfinger of stationary terminals are
factory coated with athin film of high temperature lubricant in
order tominimize racking forces and to provide increased life
ofsilver plating . The presence of thin lubricating film
willincrease the wear life of silver plating by a factor of 10or
more. Lubricant such as AC contact lubricant (8.0 oz.tube , 15-171-
370-002) should be applied thinly on thecontact surfaces cf
disconnect fingers and stationarycontacts.
Certain special controller applications require a muchfaster
dropout time where contactors are used for faultinterruption within
50 MV'A capability or where thefaster dropout time is needed for
close up streamprotective coordination. A dropout time of 70-80
milli-seconds can readily be obtained. This is accomplishedby
simultaneously opening the AC input and DC outputcircuits of the
contactor operating rectifier. The fastdropout circuit would thus
be provided by the additionof a master relay (MR) normally open
contact betweenterminals R and S in the output circuit of the
rectifier.In practice , this is normally accomplished by
removingthe jumper between terminals 25-26 on the compart -ment
terminal blocks and connecting in the relaycontact as described.
The quick dropout feature may bealready provided in the original
factory SpaceMakercontrollers to correlate with specific
applicationrequirements.
‘EMERGENCY ENTRANCETo gain access to the high voltage
compartment:
WARNINGAFTER IT HAS BEEN DEFINITELY DETER-MINEDTHAT A
MALFUNCTION HAS OCCURED,THE FOLLOWING PROCEDURES ARE TO BEPERFORMED
BY AUTHORIZED PERSONNELONLY. ALL POWER TO THE CONTROL MUSTBE
REMOVED BEFORE THESE PROCEDURESARE ATTEMPTED, AND POWER MUST
REMAINOFF UNTIL THE CONTROLLER IS IN OPER-ATING CONDITION.
SERVICE DOLLYThe service
-
Fig. 40 - Installation and Adjustment of Stop Lever
MAINTENANCEInspect the air - break contactor at least once a
month , or more often if the contactor operates on arapid or
heavy- duty cycle. Examine the contacts foralignment and wear. With
the contactor closed , alignthe movable contacts with the
stationary contacts sothat the contact surfaces bear with firm and
uniformpressure. Replace badly pitted or burned contacts
im-mediately. If contact surfaces are only roughened ,smooth down
with a fine file. See contactor instructionmanual for maintenance
instructions.
GENERALThe importance of regular and thorough inspection
andcleaning prodecures cannot be overemphasized. A rou -tine
inspection once a week will suffice when the controlis operating
under normal conditions. Under severeoperating conditions , such as
dusty or contaminatedatmospheres , it is suggested that a more
frequentcheck be made .
CARRIAGE RACKING MECHANISMThe carriage racking mechanism must
operate smooth-ly. Onlv a light coating of grease is required on
thebearing points of the mechanism and on the gears tokeep the
movement operating smoothly. section’s Equipment Checkout
can be used for a maintenance inspection . For
isolatedirregularities in equipment operation , use the
“TroubleShooting chart ”. The pages following that chart
includespare parts indentification . Order spare parts throughyour
Siemens- Allis representative .
The “Installation i *
AIR-BREAK CONTACTORW A R N I N G
MAKE CERTAIN THAT THE CONTACTOR ANDITS OPERATING MECHANISM ARE
DISCON-NECTED FROM ALL POWER SOURCES BEFOREATTEMPTING INSPECTION OR
REPAIR OPER-ATIONS.
-17 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE SHOOTING CHARTTROUBLE REMEDYCAU5E
Compartment doornot square withcubicle opening.
Cubicle not bolted down, tightly onperfectly level surface.
Using a level , add shims as necessaryat mounting bolts and
fasten mountinghardware securely .
Cubicle sprung out of shape. Straighten or repair cubicle.Door
hinges not properly adjusted. Add spacer washers as shims
between
hinge flange and cubicle flange at topor bottom hinge as
required tocompensate for error.
Handle improperly assembled. See section on “ Adjustment ”.
Cubicle or door sprung. Straighten or repair.Door will notclose
completely;door handlemechanism doesnot line up withoperating
shaftwhen door isclosed.
Cubicle not level . Check level , shim and tighten mount -ing
bolts .
Door handle assembly out of adjustment. See section on “
Adjustment”.
Vertical position of compartment door outof position .
Remove door hinge pins and add or re-move adjusting washers
between hingebracket and bearing tube until correctheight
adjustment is obtained.
Side shaft may have been manuallyrotated and not returned to
normal'position.
DANGER: High voltage ter-minals may be exposed, inn. shaftby
hand counterclockwise until frontstop pin hits stop with flat of
shaft endup and horizontal.
Right - hand ^ideof carriage rubsagainst shaftbracket or
doorhandle couplingrubs againstcarriage.
Cubicle sprung or not level . Straighten and level .
Loosen four mounting nuts and shiftplate for correct
position.
Guide plate for carriage platform out ofposition.
Door not fully closed to allow properengagement between shaft
and handlesocket.
Close door firmly and correct anyinterference that prevents door
fromreaching fully closed position.
Removewheeis and check for interfer-ence between wheel and
carriageframe. Look for and remove anyforeign material or rust in
wheelbearing or shaft.
Locked carriage wheels.SpaceMaker car-riage will notrack in
withoperating handle.
Foreign objects or materials on compart -ment guide plate in
path of carriagewheels.
Plate must be free of all foreign parti-cles , including gravel
, hardware andso forth.
Check elevation of carriage fingers andstationary plug terminals
, setting ele -vations in accordance with instructionbook.
Interference between carriage disconnectfingers and compartment
stationaryplugs.
—18—
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
REMEDYTROUBLE CAUSE(corn’d .) Shutter may be binding or
operating links
connected to rear racking shaft may be offor broken .
Check insulated shutter hardware forbreakage.
Improper mesh between side pinion gearand rear racking gear.
See section on “Adjustment ” .
Replace entire shaft.Broken or bent racking shaft .
See section on “Adjustment”.Mechanical interlock interference.
Inter*locks out of adjustment or improperly set.
Carriage racking hooks hit racking shaftpins. Check height
position of shaft locationand position of racking hooks on
SpaceMaker carriage in accordancewith instruction book. Adjust
so thatedges of hooks will pass over theracking pins with shutters
down.
•Inner phase barriers in SpaceMaker car-riage installed
backwards.
Check each fuse barrier and contactorbarrier to make certain
that each is inproper direction and properly seated.
Check for signs of scraping or rubbingon carriage and other
moving parts;check for freedom of operation ofracking mechanism by
operating shaftby hand and making ctrcessary adjust -ments or
corrections.
Carriage racks inbut requires un-usual and abnor -mal racking
force.
Partial interference or improper rackingmechanism.
Adjust both carriage hooks evenly atcorrect position in
accordance with“Adjustment” section.
Racking pins not engaging carriage hooksat proper position.
Carriage disconnect fingers and/or sta-tionary power plugs in
need of lubrication. See Page 16 for lubrication procedure.
Carriage will notrack out withracking handle.
SpaceMaker contactors in controller maybe energized. Operate
stop button to stop motor be-fore attempting to rack out
carriages.Racking mechanism may be broken ordefective. Disconnect
incoming power, obtainentrance to compartment by removing
door handle assembly and removedoor-operated mechanical safety
inter-lock screws in lower left -hand corner ofdoor; remove
sufficient mechanism toallow carriage to be withdrawn andmake
necessary repairs or adjustments.
Mechanical jamming of contactor inclosed position, causing
contactor to beblocked in by mechanical safety interlock.
Disconnect incoming power, removedoor interlock hardware at
lower left -hand corner of door and removehandle assembly to gain
entrance tocompartment. Remove the carriageand check the contactor
thoroughly todetermine cause for jamming in the
—19—
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE CAUSE REMEDY
closed position. Such causes might bewelded contacts , broken
arc chute ,foreign material in contactor mechan -ism , loose or
broken contactor parts ,excessive rust , corrosion or dust ,
etc.Refer to Type 456 high voltageair - break contactor instruction
manualICD6030 for this maintenance. Contac-tor should be completely
restored tonormal before returning it to service .
Carriage will notrack out withracking handle,(cont ' d.)
Jamming of mechanical interlock al -though contactor open. Rack
carriage all the way back in with
racking handle. This should reducefriction at the point of
contact betweenthe plunger of the anti- rack interlockmechanism and
the interference plateon the carriage. If this is not success-ful ,
remove door interlock hardwareand handle assembly to gain access
tocompartment. Disconnect incomingpower. Mechanical interlock ,
locatedon right -hand side sheet , must be setforward to allow' 1
/16 to 1 /8- in.clearance between interference plung-er and stop
plate on contactor whencontactor is closed. If position is
satis-factory , check for broken spring orbinding in mechanical
interlock assem -bly. In -.eilock should release abruptlywhen
operated by hand.
SpaceMaker car-riage can beracked out butrequires
abnormalracking force.
Friction or binding in racking mechan-ism.
Correct alignment and free slidingshutter mechanism.
Racking hooks on carriage not adjustedequally.
See section on “Adjustment ”.
Adjust and align compartment guideplate, mechanical interlocks ,
rackingshafts, shutter mechanism , carriagehooks and other details
in strict ac-cordance w'ith instruction book.
Entire compartment and carriage out ofadjustment and
alignment.
SpaceMaker car-riage forces shut-ters open When itis pushed
intocompartment.
Carriage striking movable shutter duringracking operation.
Set alignment and proper mesh ofside shaft and rear shaft .
Replace orrepair movable shutter driving arms.
Binding of safetyshutter mechan-ism or breakingof insulated shut
-ter hardware. Add additional insulated spacer wash -
ers between shutter sections to provideadditional clearance, or
replace shutterassembly if warpage is severe ordamage has
occurred.
Warpage of safety shutters.
I
-20-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE CAUSE REMEDY(cont ’d.) Rough handling during
transportation
and installation.Adjust shutter assembly and replacebroken
insulated hardware.
Apparent absenceof control powerwith carriageracked in.
Incoming power line not energized. Close feeder circuit breaker
or tieswitch.
Electrical interlock switch ‘ LSI” notadjusted properly.
See section on “ Adjustment” , specifi-cally the LSI.
Check three main motor power fuses,control transformer primary
fuses , andcontrol transformer secondary fusesand replace if
blown.
Blown fuses.
Control cable not plugged into Space-Maker carriage.
This is the disconnect type terminalblock that must be connected
in orderto provide circuitry between compart -ment and carriage.
The mating halvesof the terminal block must be engaged,and clamp
screw's at top and bottomtightened to hold halves together.
Con-trol wire connections in the block aremade through slide - type
terminals.See that all terminals are securely inposition.
Switch 9' I d be in “normal” positionfor operation from control
transformerpower. When carriage is racked out ,switch can be placed
in test position tooperate contactor through normal se-quence ,
with auxiliary power connectedto compartment terminal block.
Placeswitch in “normal” position beforeracking carriage in to
operate motor.
Test -normal control switch on left - handside of carriage not
in proper position.
Overload relays or other protective relaysin operated or “trip”
position.
Reset relays to close contacts and com-plete control circuit
.
Check wiring and connection diagramcarefully to make certain
that all ex -ternal or alternate connections havebeen made
satisfactorily. This is es-pecially true where remote protectiveor
control devices are used. Whereremote AC ammeters or wattmetersare
used , shorting jumpers in theSpaceMaker compartment must beremoved
when external connectionsare made. Check all terminal con -nections
to make certain that they aretight and are making metal- to-
metalcontact .
Missing jumpers , loose connections ,remote connections ,
etc.
-21-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE CAU5E REMEDYSequence of control circuit being
inter-rupted.
Check for and correct remote deviceconnections, tripped
protective con-tacts , burned out coils on relays and
contactors, faulty rectifiers , blownfuses , mechanical
interference in theoperation of relays and contactors,burned
contacts , broken contactsprings , excessive dust or other
foreignmaterials in mechanism and betweencontacts.
Motor will notstart , althoughnormal controlvoltage avail
-able.
Contactor doesnot pick up, al -though controlcircuit
voltageavailable .
Contactor held open by mechanical inter -lock .
Rack in contactor completely. Resetinterlock on guide plate if
not incorrect position. Check interlock forfreedom of
operation.
Arc chutes or phase barriers not properlyinstalled in
contactor.
Make certain that phase barriers are inproper direction and in
proper positionand that arc chutes are in proper direc -tion , with
arc runners properly seated.
Check coil and rectifier. Make certainthat the long wipe
normally closed con -tact is in proper working condition andis open
in the closed magnet positionto reduce seal current ( refer to
Type456 high voltage air- break contactor in-struction book , ( ICD
6030). Check formechanical interference or f reignmaterials in
contactor mechanism andin magnet air gap. Make certain allcontactor
parts are in satiifactoryoperating condition and are
properlylightened.
Burned out coil or rectifier on Type 456contactor.
Burnout of Type456 contactorrectifier.
Faulty operation of normally closed longwipe contact.
Replace or correct normally closed con -tact assembly or
operating finger ifnecessary . Normally closed contactmust open as
magnet reaches fullyoperated position to reduce coil sealcurrent
.
Voltage surges from power line. Check protective surge
suppressoracross DC terminals of rectifier.
Burnout of operating magnet coil . Replace magnet coil and check
circuitfor shorted terminals , etc .Limit starting load and running
load tomotor capabilities.
Motor overloaded .Overload relaystrip during start -ing or soon
aftermotor is up tospeed.
Motor being started too frequently atclose intervals.
Jogging and starting operations mustbe limited to capabilities
of the motor .Check starting limitations in motor in -struction
manual before repeatedstarts.
— 22—
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE CAUSE REMEDYExcessive acceleration time. The starting of
high inertia loads may not
permit the use of standard overload relayapplication. Where
accelerating timeapproaches 12 seconds or more , specialoverload
relay by pass devices andcircuits would usually be required.
Con-tact the factory regarding such problemsand supplv complete
data on Iocked -rotor starting current and total acceler -ating
time under maximum load condi-tions.
(corn 'd . )
Low line voltage. Line voltage should be maintained be-tween +
10 % and -10 % of motor name -plate voltage.
Overload relaystrip during motoroperation.
Reduce load or correct conditions causingoverload.
Motor being overloaded.
Overload relay not adjusted to motorcapabilities.
Adjust relay setting in accordance withinstructions for the
overload relay. Ad-justment should correspond to thermalrating of
the motor, including tempera-ture rise, duty and service
factor.
Incorrect relay installed. Contact factory .
Sec in accordance with relay instructions.Relays set
incorrectly.
Relay tripping mechanism jammed. Replace relay .Overload
relaysfail to trip onoverloadcurrent.
Check relay selection and adjustment peroverload relay
instructions.
Incorrect relay or relay set incorrectly.
Current transformers with improper ratioor with short -circuited
secondary ter -minals.
Current transformers must have a step-down ratio to correspond
to full loadmotor current and relay selection. Pro-tective jumpers
may be provided at cur -rent transformer secondary terminals oron
terminal block connections to guardagainst open transformer
secondary cir -cuit . and jumpers must be removedbefore placing
equipment in operation.
Use Megger and other test instruments tolocate fault and correct
.
Blow ing ofmotor powerfuses.
Short circuit on the load side of the motorfuses.
Jogging or too frequent starting. On frequent starting, fuses
accumulateabnormal heat and cool more slowly thando overload
relays. Since fuses moreclosely follow' cooling and heating ofmotor
windings , successive starting oper -ations must be limited to the
safe capacityof the motor to prevent fuse blowing from
-23-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
TROUBLE CAU5E REMEDYthis cause . Check size radix on
fusenameplate against data lahe! on carriageand data label in
Space.\hikrr compart -ment. All three* must ngiee . Fuses
arcselected on the basis ot motor full loadcurrent , locked - rotor
current and startingtime. Approximate sizes can be deter -mined
from Siemens - Albs price booksection .
(cont ’d . ) (corn d . )
Fuses internally damaged because ofimproper handling .
Motor power fuses are made up of multi -ple strands ot fine
silver ribbon whichmay be broken if fuses are dropped
orroughlystrands can be broken without the triptarget indicating a
blown fuse. Handlefuses carefully , installing them in clips ontop
of the SpaceMaker carriage , withtarget indicator toward the front
.
handled . Several individual
Blowing of pri -mary controltransformer fuses.
Replace or repair transformer .Shorted primary winding in
controltransformer.
Fuse ma\ be “open ” due to roughhandling before installing .
Replace fuse.
Secondary fuses not properly coordi -nated.
Melting characteristic of secondary fuseshould not intersect
melting characteris -tic of primary fuse. Rating of standardNFC
fuse should not exceed twice thesecondary current rating.
Blowing of sec-ondary controltransformer fuses.
Abnormal current or short circuit incontrol .
Check for faulty operation of long wipeeconomizing contacts ,
shorted magnetcoils , shorted rectifiers, grounds, loose orbent
connections , mechanical binding inrelay and contactor mechanisms,
ex -cessive operations and incorrect secondary terminal
connections.
Overheating ofcarriage dis-connect fingers.
Improper alignment and overtravel onstationary terminals.
Adjust position and alignment of sta -tionary terminals in hack
of compartmentin accordance with instruction hook.
Loose mounting hardware or brokensegment springs.
All mounting hardware must he secure ,and all current carrying
surfaces must heclean before boiling. Contact springs foreach pair
of fingers must he in place andhave original temper. Contact
surfaces onfingeis and stationary terminals must hefree of deep
voids , corrosion , oxidationand foreign materials, such as dust .
etc .Imperfect finger assemblies are a serioushazard and should be
replaced . Makesure that the finger retainer shims are inplace.
I
-24-
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
©©
©
©©
© ©©©
Fig. 41 - SpaceMaker II Carriage
CONTACTOR CARRIAGE- PARTS LIS^Item Description Part No.
Qty.No.
Disconnect Fingers w/RetainerFuse ClampOuter ClipInner ClipFuse
Block 2-Pole**Fuse Block 1-Polc*Knife Switch 2-Polc * *Knife Switch
1-Polc *Control Power Fuse ClipWheel AssemblyDisconnect
BlockElectrical Interlock AssemblyControl Transformer Primary
FuseControl Circuit FuseMain Power FuseControl Power
TransformerRacking Hook R.H.Racking Hook L.H.Fuse Barrier (inner
)Fuse Barrier (outer )Phase Barrier ( inner )Phase Barrier (outer
)
1
71-240-055-50114-234-755-00114-234-753-00114-234-754-00100-871-237-10700-871-237-10114-147-049-00125-131-277-00125-127-701-00114-147-042-50114-231-983-50114-170-239-501
62 63 6i4 65 15A 16 16A 17 48 49 110 1] See RecommendedInitial
Stock ofReplacement Parts11 212 1* or 2**13 314 115 14-232-
744-50214-232-744-50114-231-648-00214-231-648-00314-133-
795-00114-147-023-001
116 117 218 219 220 2iSee contactor Instruction Manual for all
other parts ( ICD6030)
* — 115VAC Contactor Operating Voltage* * — 230VAC Contactor
Operating Voltage — 25 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
v*
."li-v 'v -s *.
Fig. 42 * Ooor handle Fig. 43 - Rear view of door handle
assembly
OOOR HANDLE ASSEMBLY- PARTS KIT
Item Part Identification Parts Kit No Qty.No.HandleIndicator and
Lock PlateSpring WasherSpacer WasherIndicating PlateSpace
WasherPadlock PlateBearingCoupling
•IS*16*17*18*19 25-103-302-801*20212223
•NOTE: Items 15 through 20 are in sequential order .
i
— 26 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com
-
(38)
©
Fig 44 - Inside view SoaceMaker Jl compartment'-PAGEMAKER II
COMPARTMENT-PARTS LIST
Item Description Part No. Qty.No.24 Unc Switch Interlock
Wiring Harness with Plug {230V Contactor)Wiring Harness with
Plug* ( 230V Contactor)Wiring Harness with Plug {115V Contactor
)Wiring Harness with Plug* (115V Contactor)Racking Shaft
AssemblyRearing BracketCollar ( Behind bearing bracket )Rear
BearingDoor LatchMechanical Interlock AssemblyCiuide PlateShutter
Shaft AssemblyStationary ShutterMovable ShutterScrewWasherWasher (
Phenolic)Spacer ( Nylon)Rivet ( Nylon )Shutter Actuating
ArmShoulder Screw ( Nylon )Hex Nut ( Nylon )Washers (Phenolic
)Terminal InsulatorTerminalTerminalTerminalShaft Lock
BracketSpringRoll Pin
14*170-240-50125-104-745-50125-104-745-50225-104-745-50625-104-745-50725-
201-574-50125-103-256-00114-171-914-00114-174-843 00114-171-772-
00114-323- 199-50114- 233-126-50125-201-587-50114-
231-663-00114-231-662-00100- 6 17-481-U0200-653-109 -
14614-423-344-01625-102-615-00100 -671-501-06014-170-748-00114-171-
239-00200-639 039 -11614-423-344-01414-323-043-50114-1 71
-874-00114- 171 -874 - 00214-147-037-00125-204-209-00125-120-
212-00100-671-177-386
125125A
25 B25C
111261271281i 291301311321
i33
1341351363“ *3* *
36A37
5383
«
394402412422434442452461473481491501
Used on one-high 90” controller (Style Z ) with carnage in lower
and low voltagecontrol in upper compartment.Order both items for
replacement.•* 97 —
www.nationalswitchgear.comCourtesy of NationalSwitchgear.com