FEATURES • NACE MR0175 construction available for flanged cage models • 14 inch (356 mm) side/side process connections available as standard • Choice of sealed or flanged float chamber design • Service pressures up to 2193 psig (151.2 bar) for ASME B31.1 and 2240 psig (154.4 bar) for ASME B31.3 & NACE • Process temperatures up to +1000° F (+538° C) • Specific gravity ratings as low as 0.33 • Choice of NEMA 4X/7/9, Group B, C & D or EEx d IIC T6 housings • Agency approvals include FM, CSA, ATEX and SAA • ASME B31.1, B31.3 or NACE Certificate of Conformance supplied • Choice of available switch styles, including mercury, dry contact, vibration resistant, hermetically sealed, pneumatic bleed and non-bleed • Choice of single or multiple switches for single or staged applications • 1", 1 1 / 2" or 2" tank connections available in either NPT, socket weld, flanged side/side or flanged side/bottom configuration • Special materials of construction available upon request • Available with special coatings including Epoxy, Carbo Zinc ® 11 Primer and Carboline Top Coat, Dimetcote ® and Amercoat ® Carbo Zinc ® 11 is a registered trademark of Carboline Company. Amercoat ® and Dimetcoat ® are registered trademarks of Amerion Inc., Protective Coating Div. DESCRIPTION Series 3 float actuated level switches meet ASME B31.1 or ASME B31.3 requirements. They are designed to provide critical alarm set points in clean liquid applications. B3F Flanged Cage Level Switch B35 Sealed Cage Level Switch APPLICATIONS ASME B31.1 construction for use on boilers and in power plants. • Feed water heaters • Steam drums • Condensate drip pots • Flash tanks • Deaerators • Hot wells ASME B31.3 construction for use in refineries and petrochemical plants. • Gas/oil separators • Receivers • Knockout drums • Flare pots • Crude/salt water separators • Accumulators Series 3 Liquid Level Switches ASME B31.1, ASME B31.3 and NACE Construction
24
Embed
Series 3 Liquid Level Switches ASME B31.1, ASME B31.3 … · weld is performed per ASME B31.3. MATERIALS OF CONSTRUCTION ... Design calculations, design prints and weld qualifications
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
F E A T U R E S
• NACE MR0175 construction available for flangedcage models
• 14 inch (356 mm) side/side process connectionsavailable as standard
• Choice of sealed or flanged float chamber design
• Service pressures up to 2193 psig (151.2 bar) forASME B31.1 and 2240 psig (154.4 bar) for ASMEB31.3 & NACE
• Process temperatures up to +1000° F (+538° C)
• Specific gravity ratings as low as 0.33
• Choice of NEMA 4X/7/9, Group B, C & D orEEx d IIC T6 housings
• Agency approvals include FM, CSA, ATEXand SAA
• ASME B31.1, B31.3 or NACE Certificate ofConformance supplied
• Choice of available switch styles, including mercury,dry contact, vibration resistant, hermetically sealed,pneumatic bleed and non-bleed
• Choice of single or multiple switches for single orstaged applications
• 1", 11⁄2" or 2" tank connections available in eitherNPT, socket weld, flanged side/side or flangedside/bottom configuration
• Special materials of construction available uponrequest
• Available with special coatings including Epoxy,Carbo Zinc® 11 Primer and Carboline Top Coat,Dimetcote® and Amercoat®
Carbo Zinc® 11 is a registered trademark of Carboline Company.
Amercoat® and Dimetcoat® are registered trademarks ofAmerion Inc., Protective Coating Div.
D E S C R I P T I O N
Series 3 float actuated level switches meet ASME B31.1or ASME B31.3 requirements. They are designed toprovide critical alarm set points in clean liquidapplications.
B3F Flanged CageLevel Switch
B35 Sealed CageLevel Switch
A P P L I C A T I O N S
ASME B31.1 construction for use on boilers and inpower plants.
• Feed water heaters • Steam drums
• Condensate drip pots • Flash tanks
• Deaerators • Hot wells
ASME B31.3 construction for use in refineries andpetrochemical plants.
• Gas/oil separators • Receivers
• Knockout drums • Flare pots
• Crude/salt water separators • Accumulators
Series 3Liquid Level SwitchesASME B31.1, ASME B31.3and NACE Construction
2
T A N K C O N N E C T I O N S A N D
I N S T A L L A T I O N D I M E N S I O N S
In addition to the standard slip-on or weld neck R.F.
flanges, many other process, vent and drain connec-
tions are available, including:
• Socketweld • DIN
• RTJ • JIS
Special flange gasket surface finishes are also available,
and cages may be manufactured to allow special
process connections.
M A T E R I A L S O F
C O N S T R U C T I O N
Chambers and internal components on some models
available in other metal alloys.
• 304 SS • 316 SS
• Hastelloy C • Monel
• Carpenter 20 • Duplex Stainless Steel
W E L D I N G
Stress relieving of chamber welds is available for
flanged cage models.
A C T U A T I N G L E V E L S
• Special switch set points and/or differentials
• Tandem floats—where the switch actuating levels are
8 inches (203 mm) or more apart.
• Multiple switches
O P T I O N S
Many options are available for Series 3 level switches. Should you require an option not listed,consult the factory for further information.
E N C L O S I N G T U B E
Integrally welded (socket type weld) enclosing tube
design available for flanged cage models.
I N T E R F A C E C A L I B R A T I O N
Units with interface calibration are custom designed for
each application. Specific gravity differences as small as
0.10 may be addressed. Consult the factory for all
interface calibrations.
E X A M I N A T I O N S / T E S T S
Magnetrol is equipped to provide a full range of special
quality control testing, including:
• Dye penetration • Radiography
• Charpy • Magnetic Particle
• Extended Hydrostatic • Ultrasonic
• Hardness Testing
P R O D U C T D E S I G N
Pressure vessels are designed within code specified
stress limits. Design calculations, design prints and
weld qualifications are available for audit. All chamber
branch and circumferential weld joints are designed to
achieve FULL penetration.
W E L D I N G
All welding is performed by qualified welders and per
procedures required by the ASME Boiler Pressure
Vessel Code Sec. IX. Welds are visually inspected for
full penetration; and 5% radiographic inspection of
weld is performed per ASME B31.3.
M A T E R I A L S O F
C O N S T R U C T I O N
All pressure-retaining materials are procured with
Certificates of Conformance to assure compliance of
components with required standards.
H Y D R O S T A T I C T E S T
All chambers are hydrostatically tested at 1.5 times the
design pressure.
M A T E R I A L S O F
C O N S T R U C T I O N
Only NACE listed materials are used for pressure retain-
ing parts. Certificates of Conformance assure compliance
of components to required material standards.
H Y D R O S T A T I C T E S T
All chambers are hydrostatically tested at 1.5 times the
design pressure.
P R O D U C T D E S I G N
Pressure vessels are designed within code specified
stress limits. Design calculations, design prints and
weld qualifications are available for audit. All chamber
branch and circumferential weld joints are designed to
achieve FULL penetration.
W E L D I N G
All welding is performed by qualified welders and per
procedures required by the ASME Boiler Pressure
Vessel Code Sec. IX. Welds are visually inspected for
FULL penetration. All other nondestructive examination
is performed per ANSI B31.1.
M A T E R I A L S O F
C O N S T R U C T I O N
All pressure-retaining materials are procured with
Certificates of Conformance to assure compliance of
components with required standards.
H Y D R O S T A T I C T E S T
All chambers are hydrostatically tested at 1.5 times the
design pressure.
W E L D I N G
All welding is performed by qualified welders and per
procedures required by the ASME Boiler Pressure
Vessel Code Sec. IX. Carbon steel pressure boundary
parts are post weld stress relieved. All welds and heat
affected zones are hardness tested to ensure compli-
ance with NACE maximum hardness requirements.
S T A N D A R D A S M EB 3 1 . 3 C O N S T R U C T I O N
S T A N D A R D A S M EB 3 1 . 1 C O N S T R U C T I O N
3
S T A N D A R D N A C E C O N S T R U C T I O N
4
AGENCY MODEL APPROVED APPROVAL CLASSES
FM All with an electric switch mechanism and a housing Class I, Div 1, Groups C & Dlisted as NEMA 4X/7/9 Class II, Div 1, Groups E, F & G
All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & Dlisted as NEMA 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G
CSA All with a Series A. E, F, HS, HS, 2 or 3 electric switch Class I, Div 2, Groups B, C & Dmechanism and a housing listed as CSA TYPE 4X
All with an electric switch mechanism and a housing Class I, Div 1, Groups C & Dlisted as NEMA 4X/7/9 Class II, Div 1, Groups E, F & G
All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & Dlisted as NEMA 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G
ATEX All with an electric switch mechanism and an Ex II 2 G EEx D IIC T6 ATEX housing ➀
SAA All with an electric switch mechanism and a housing Ex d IIC T6 IP65listed as NEMA 4X/7/9 Class I, Div 1, Group B
CE All models Installation Category IIPollution Degree 2
DISPLACER MODELS WITH 1" PROCESS CONNECTIONSINCHES
For float operated units, levels are dependent upon the
specific gravity of the process media.
NOTE: Actuation levels for saturate steam service ratings areshown for single switch units with 1" process connections only.Consult factory for units with two and three set point and 11⁄2" or 2"process connections.
A S M E B 3 1 . 1 A C T U A T I N G L E V E L S
SATURATED STEAM SERVICE RATINGS (See model selection charts for maximum ratings)
ASME B31.1 SEALED CAGE MODELS WITH 1" PROCESS CONNECTIONSINCHES MILLIMETERS
ASME B31.1 FLANGED CAGE MODELS WITH 1" PROCESS CONNECTIONSINCHES
ASME B31.1 FLANGED CAGE MODELS WITH 1" PROCESS CONNECTIONSMILLIMETERS
Sealed Actuation LevelsCage Pressure Temperature Specific
For float operated units, minimum specific gravity andactuating levels vary depending upon the material ofconstruction code used with the unit.
For displacer operated units, minimum specificgravity and actuating levels vary depending upon thetemperature at which the unit is operated.
NOTE: The minimum specific gravity and actuating levels shownare for single switch units with 1" process connections only.
Minimum specific gravity and levels will change formultistage units and levels will change for units with11⁄2" or 2" process connections. Consult factory for thesechanges.
The level decals on the control identify the actuationlevels at the corresponding minimum specific gravity.
A S M E B 3 1 . 3 A C T U A T I N G L E V E L S
ASME B31.3 SEALED CAGE MODELS WITH 1" PROCESS CONNECTIONSINCHES MILLIMETERS
Models w/Mat. of Const. Models w/Mat. of Const.Code 1 Code 2
Model Min. Actuating Level Min. Actuating LevelCode Sp. @ Min. Sp. Gr. Sp. @ Min. Sp. Gr.
➄ Uncontrolled housing heater or drain available in NEMA 4X/7/9.Consult factory for standard part numbers.
➅ Consult factory for NEMA 4X/7//9 cast iron housings.➆ Process temperature based on +100° F (+38° C) ambient.➇ Cast iron switch enclosures are used with the Series “R” switch.
➆ Codes for an 18 inch center to center dimension are applicable to
K3F model only.
SwitchDescription
ProcessTemperature
Range° F (° C) Contacts
SetPoints
Models B35, C35 & G35 Models V35 & Z35
NEMA 4X/7/9 Aluminum Enclosure
Class I, Div 1GroupsC & D
Class I, Div 1GroupsB, C & D
ATEXEx II 2 G
EE xd IIC T6
Class I, Div 1GroupsC & D
Class I, Div 1GroupsB, C & D
ATEXEx II 2 G
EE xd IIC T6
Series BSnap Switch
-40 to +250(-40 to +121)
SPDT 123
BKABLABMA
BKJBLJBMJ
BCCBDCBEC
BKBBLBBMB
BKKBLKBMK
BC9BD9BE9
DPDT 12
BNABOA
BNJBOJ
BFCBGC
BNBBOB
BNKBOK
BF9BG9
Series CSnap Switch
-40 to +450(-40 to +232)
SPDT 123
CKACLACMA
CKJCLJCMJ
CCCCDCCEC
CKBCLBCMB
CKKCLKCMK
CC9CD9CE9
DPDT 12
CNACOA
CNJCOJ
CFCCGC
CNBCOB
CNKCOK
CF9CG9
Series DSnap Switch
-40 to +250(-40 to +121)
SPDT 123
DKBDLBn/a
DKKDLKn/a
DC9DD9n/a
DKBDLBDMB
DKKDLKDMK
DC9DD9DE9
DPDT 12
DNBDOB
DNKDOK
DF9DG9
DNBDOB
DNKDOK
DF9DG9
Series FHermetically Sealed
Snap Switch
-50 to +750(-46 to +399)
SPDT 12
FKAFLA
FKJFLJ
FCCFDC
FKBFLB
FKKFLK
FC9FD9
DPDT 12
FNAFOA
FNJFOJ
FFCFGC
FNBFOB
FNKFOK
FF9FG9
Series HSHermetically Sealed5 amp Snap Switch
with wiring leads
-50 to +400(-46 to +204)
SPDT 12
HMJHMN
HMKHMP
n/a
HMJHMN
HMKHMP
n/aDPDT 1
2HMSHMY
HMTHMZ
HMSHMY
HMTHMZ
Series HSHermetically Sealed5 amp Snap Switchwith terminal block
-50 to +400(-46 to +204)
SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
Series H1Hermetically Sealed1 amp Snap Switch
with wiring leads
-50 to +750(-46 to +399)
SPDT 1 HKJ HKKn/a
HKJ HKKn/a
DPDT 2 HKN HKP HKN HKP
Series RHigh Temperature
Snap Switch
-40 to +1000(-40 to +538) SPDT 1
2RKMRLM
RKWRLW
RU5RV5
RKMRLM3MB
RKWRLW3MK
RU5RV5
Series 3Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
3KA3LE3ME
3KJ3LG3MG
3CC3DE3EE
3KB3LB3MB
3KK3LK3MK
3C93D93E9
DPDT 12
3NA3OA
3NJ3OJ
3FC3GC
3NB3OB
3NK3OK
3F93G9
Series 2Vibration Resistant
Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
2KA2LE2ME
2KJ2LG2MG
2CC2DE2EE
2KB2LB2MB
2KK2LK2MK
2C92D92E9
DPDT 12
2NA2OA
2NJ2OJ
2FC2GC
2NB2OB
2NK2OK
2F92G9
➆➇➅
➇
SwitchDescription
MaximumSupply
Pressure
MaximumProcess
Temperature
BleedOrifice
Diameter
All Modelsexcept: B3F, G3F,
K3F & Z3Fwith 600 lb.
Head Flanges
ModelsB3F, G3F,K3F & Z3F
with 600 & 900 lb.Head Flanges
psig bar ° F ° C inches mm NEMA 1 NEMA 1
Series JBleed Type
100 7 400 204 .063 1.6 JGH JGF
50 4 400 204 .094 2.3 JHH JHF
60 4 700 371 .055 1.3 JJH JJF
Series KNon-Bleed
100 7 400 204 — — — KOF
40 3 400 204 — — KOH —
18
A S M E B 3 1 . 1 M O D E L N U M B E R S
F L A N G E D C A G E M O D E L S
MODEL NUMBER CODE
Models available for quick shipment, usually within oneweek after factory receipt of a purchase order, throughthe Expedite Ship Plan (ESP)
CAGE SIZE AND TANK CONNECTION TYPE
P Carbon steel chamber, 316L stainless steel float, 400 stainless steel sleeve, ASME B31.1 Construction
➀ Minimum specific gravity ratings apply to single stage units only.Consult factory for two or three stage units.
➁ Models are limited to maximum temperature rating of selectedswitch mechanism.
➂ Models Z3F & K3F contain 7–17 ph stainless steel floats.➃ Codes for a 16 inch center to center dimension are applicable to
G3F and G35 models with 600# flanges only.
➄ Codes for an 18 inch center to center dimension are applicableto K3F model only.
➅ Consult factory for NEMA 4X/7//9 cast iron housings.➆ Process temperature based on +100° F (+38° C) ambient.➇ Uncontrolled housing heater or drain available in NEMA 4X/7/9.
Consult factory for standard part numbers.➈ Cast iron switch enclosures are used with the Series “R” switch.
SwitchDescription
ProcessTemperature
Range° F (° C) Contacts
SetPoints
All Models except B3F, G3F, K3F & Z3Fwith 600# or 900# ANSI rating
Models B35, C35, G35, K35 and L35with Material of Construction Code 1
Models B34, V35, Z35 and all modelswith Material of Construction Code 2
NEMA 4X/7/9 Aluminum Enclosure
Class I, Div 1GroupsC & D
Class I, Div 1Group B
ATEXEx II 2 GEE xd IIC
Class I, Div 1GroupsC & D
Class I, Div 1Group B
ATEXEx II 2 GEE xd IIC
Series AMercury Switch
-20 to +550(-29 to +288)
SPDT 123
AKAALA
AKJALJ
ACCADCn/a
AKBALBAMB
AKKALKAMK
AC9AD9AE9
DPDT 12
ANAAOA
ANJAOJ
AFCAGC
ANBAOB
ANKAOK
AF9AG9
Series BSnap Switch
-40 to +250(-40 to +121)
SPDT 123
BKABLABMA
BKJBLJBMJ
BCCBDCBEC
BKBBLBBMB
BKKBLKBMK
BC9BD9BE9
DPDT 12
BNABOA
BNJBOJ
BFCBGC
BNBBOB
BNBBOB
BF9BG9
Series CSnap Switch
-40 to +450(-40 to +232)
SPDT 123
CKACLACMA
CKJCLJCMJ
CCCCDCCEC
CKBCLBCMB
CKKCLKCMK
CC9CD9CE9
DPDT 12
CNACOA
CNJCOJ
CFCCGC
CNBCOB
CNKCOK
CF9CG9
Series DSnap Switch
-40 to +250(-40 to +121)
SPDT 123
DKBDLBn/a
DKKDLKn/a
DC9DD9n/a
DKBDLBDMB
DKKDLKDMK
DC9DD9DE9
DPDT 12
DNBDOB
DNKDOK
DF9DG9
DNBDOB
DNKDOK
DF9DG9
Series EVibration Resistant
Mercury Switch
-20 to +550(-29 to +288)
SPDT 123
EKAELA
EKJELJ
ECCEDCn/a
EKBELBEMB
EKKELKEMK
EC9ED9EE9
DPDT 12
ENAEOA
ENJEOJ
EFCEGC
ENBEOB
ENKEOK
EF9EG9
Series FHermetically Sealed
Snap Switch
-50 to +750(-46 to +399)
SPDT 12
FKAFLA
FKJFLJ
FCCFDC
FKBFLB
FKKFLK
FC9FD9
DPDT 12
FNAFOA
FNJFOJ
FFCFGC
FNBFOB
FNKFOK
FF9FG9
Series HSHermetically Sealed5 amp Snap Switch
with wiring leads
-50 to +400(-46 to +204)
SPDT 12
HMJHMN
HMKHMP
n/a
HMJHMN
HMKHMP
n/aDPDT 1
2HMSHMY
HMTHMZ
HMSHMY
HMTHMZ
Series HSHermetically Sealed5 amp Snap Switchwith terminal block
-50 to +400(-46 to +204)
SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
Series H1Hermetically Sealed1 amp Snap Switch
with wiring leads
-50 to +750(-46 to +399)
SPDT 1 HKJ HKKn/a
HKJ HKKn/a
DPDT 2 HKN HKP HKN HKP
Series RHigh Temperature
Snap Switch
-40 to +1000(-40 to +538) SPDT 1
2RKMRLM
RKWRLW
RU5RV5
RKMRLM3MB
RKWRLW3MK
RU5RV5
Series 3Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
3KA3LE3ME
3KJ3LG3MG
3CC3DE3EE
3KB3LB3MB
3KK3LK3MK
3C93D93E9
DPDT 12
3NA3OA
3NJ3OJ
3FC3GC
3NB3OB
3NK3OK
3F93G9
Series 2Vibration Resistant
Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
2KA2LE2ME
2KJ2LG2MG
2CC2DE2EE
2KB2LB2MB
2KK2LK2MK
2C92D92E9
DPDT 12
2NA2OA
2NJ2OJ
2FC2GC
2NB2OB
2NK2OK
2F92G9
10
1213
14
16
16
13
15 15
21
➀ Minimum SG ratings apply to single stageunits. Consult factory for two and threestage units.
➁ Models are limited to maximum temperaturerating of selected switch mechanism.
➂ Consult factory for 14" center-to-center dimensions on models K35 andB34.
➃ Models V35 and Z35 contain 17–7 ph stainless steel floats.➄ Consult factory for Model B34 above +300° F (+149° C). Available with
single switch only.➅ Codes 11⁄2" and 2" NPT tank connections are not applicable to the B34
displacer model.➅ Model B34 not available as standard with 14" and 16" center-to-center
dimension codes.
Cast iron switch enclosures are used with the Series “R” switch.On steam applications, use Series 3 mercury switches with beadedleads.Three stage controls must use Series “3” switches.On steam applications, use Series 2 vibration resistant mercury switcheswith beaded leads.Three stage controls must use Series “2” switches.On condensing applications, temperature down-rated to +400° F(+204° C) process at +100° F (+38° C) ambient.
11
12
13
14
15
16
10
➇ Codes for a 16" center-to-center dimension are applicable to the K35,V35 and Z35 models only.
➈ Process temperature based on +100° F (+38° C) ambient.Uncontrolled housing heater or drain available in NEMA 4X/7/9 enclo-sures. Consult factory for standard part number.
11
11
22
A S M E B 3 1 . 3 a n d N A C E M O D E L N U M B E R S
➇ Codes for 150 lb. flanges are not applicable to the C34 displacer model.➈ Codes for a 16" center-to-center dimension are applicable to the K35
model only.Process temperature based on +100° F (+38° C) ambient.Uncontrolled housing heater or drain available in NEMA 4X/7/9 enclo-sures. Consult factory for standard part number.Cast iron switch enclosures are used with the Series “R” switch.On steam applications, use Series 3 mercury switches with beaded leads.Three stage controls must use Series “3” switches.On steam applications, use Series 2 vibration resistant mercury switcheswith beaded leads.Three stage controls must use Series “2” switches.On condensing applications, temperature down-rated to +400° F(+204° C) process at +100° F (+38° C) ambient.
SwitchDescription
ProcessTemperature
Range° F (° C) Contacts
SetPoints
All Models with Material of ConstructionCode 1 except B3F, C34, G3F, K3F & Z3F
with 600# or 900# ANSI rating
Model C34 & All Models with Material ofConstruction Codes 2 or N and B3F, G3F,K3F & Z3F with 600# or 900# ANSI rating
NEMA 4X/7/9 Aluminum Enclosure
Class I, Div 1GroupsC & D
Class I, Div 1Group B
ATEXEx II 2 GEE xd IIC
Class I, Div 1GroupsC & D
Class I, Div 1Group B
ATEXEx II 2 GEE xd IIC
Series AMercury Switch
-20 to +550(-29 to +288)
SPDT 123
AKAALA
AKJALJ
ACCADCn/a
AKBALBAMB
AKKALKAMK
AC9AD9AE9
DPDT 12
ANAAOA
ANJAOJ
AFCAGC
ANBAOB
ANKAOK
AF9AG9
Series BSnap Switch
-40 to +250(-40 to +121)
SPDT 123
BKABLABMA
BKJBLJBMJ
BCCBDCBEC
BKBBLBBMB
BKKBLKBMK
BC9BD9BE9
DPDT 12
BNABOA
BNJBOJ
BFCBGC
BNBBOB
BNBBOB
BF9BG9
Series CSnap Switch
-40 to +450(-40 to +232)
SPDT 123
CKACLACMA
CKJCLJCMJ
CCCCDCCEC
CKBCLBCMB
CKKCLKCMK
CC9CD9CE9
DPDT 12
CNACOA
CNJCOJ
CFCCGC
CNBCOB
CNKCOK
CF9CG9
Series DSnap Switch
-40 to +250(-40 to +121)
SPDT 123
DKBDLBn/a
DKKDLKn/a
DC9DD9n/a
DKBDLBDMB
DKKDLKDMK
DC9DD9DE9
DPDT 12
DNBDOB
DNKDOK
DF9DG9
DNBDOB
DNKDOK
DF9DG9
Series EVibration Resistant
Mercury Switch
-20 to +550(-29 to +288)
SPDT 123
EKAELA
EKJELJ
ECCEDCn/a
EKBELBEMB
EKKELKEMK
EC9ED9EE9
DPDT 12
ENAEOA
ENJEOJ
EFCEGC
ENBEOB
ENKEOK
EF9EG9
Series FHermetically Sealed
Snap Switch
-50 to +750(-46 to +399)
SPDT 12
FKAFLA
FKJFLJ
FCCFDC
FKBFLB
FKKFLK
FC9FD9
DPDT 12
FNAFOA
FNJFOJ
FFCFGC
FNBFOB
FNKFOK
FF9FG9
Series HSHermetically Sealed5 amp Snap Switch
with wiring leads
-50 to +400(-46 to +204)
SPDT 12
HMJHMN
HMKHMP
n/a
HMJHMN
HMKHMP
n/aDPDT 1
2HMSHMY
HMTHMZ
HMSHMY
HMTHMZ
Series HSHermetically Sealed5 amp Snap Switchwith terminal block
-50 to +400(-46 to +204)
SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
Series H1Hermetically Sealed1 amp Snap Switch
with wiring leads
-50 to +750(-46 to +399)
SPDT 1 HKJ HKKn/a
HKJ HKKn/a
DPDT 2 HKN HKP HKN HKP
Series RHigh Temperature
Snap Switch
-40 to +1000(-40 to +538) SPDT 1
2RKMRLM
RKWRLW
RU5RV5
RKMRLM3MB
RKWRLW3MK
RU5RV5
Series 2Vibration Resistant
Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
2KA2LE2ME
2KJ2LG2MG
2CC2DE2EE
2KB2LB2MB
2KK2LK2MK
2C92D92E9
DPDT 12
2NA2OA
2NJ2OJ
2FC2GC
2NB2OB
2NK2OK
2F92G9
Series 3Mercury Switch
-20 to +750(-29 to +399)
SPDT 123
3KA3LE3ME
3KJ3LG3MG
3CC3DE3EE
3KB3LB3MB
3KK3LK3MK
3C93D93E9
DPDT 12
3NA3OA
3NJ3OJ
3FC3GC
3NB3OB
3NK3OK
3F93G9
10 11 12
13
1516 16
17
17
14 14
➀ Minimum SG ratings apply to single stageunits. Consult factory for two and threestage units.
➁ Models are limited to maximum tempera-ture rating of selected switch mechanism.
➂ 600# and 900# flanged cage models must use switch codes listed underheading “Model C34 & All Models w/Materials of Construction Codes 2 orN and B3F, G3F, K3F & Z3F with 600# or 900# ANSI rating”.
➃ HS switches can be used with Materials of Construction Code 1 only.Example: B3F-1B80-HSG.
➄ Consult factory for 14" center-to-center dimensions on models K3F andC34.
➅ Construction Code N is not applicable to this unit due to 17–7 ph stainlesssteel float material.
➆ Consult factory for Model C34 above +500° F (+260° C). Available withsingle switch only.
Performance specifications are effective with date of issue and are subject to change without notice.The brand and product names contained within this document are trademarks or registered trademarks of their respective holders.
Q U A L I T Y
E S P
W A R R A N T Y