Top Banner

of 14

Seismic Suspend Ceiling-1

Aug 07, 2018

Download

Documents

johnking5555
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/20/2019 Seismic Suspend Ceiling-1

    1/30

    CPA T-Bar Guidelines Page 1 of 15

    Revision Date: 10/2012

    General Requirements/Checklist for:

    Commercial

    SUSPENDED CEILING

    SYSTEMS INSPECTION 

    City of Palo Alto (CPA) 

    Building Inspection Division Inspection Request Line: 650 329-2496 

    Building Division  Inspection Code IVR# 304

    Codes/Standards Enforced:

    2010 CBC, ASCE 7-50, ASTM C

    635, 636, CISCA 3-4

    Palo Alto Municipal Code (PAMC)The information provided in this document is general and intended as a guide only. Each project is unique and

    additional requirements may be enforced as deemed appropriate.

    REQUIRED ITEMS  All existing tenant improvement suspended ceiling  systems installed prior to January 1,

    2008 in areas affected by renovation, structural repair, or alterations must be upgraded tomeet seismic requirements set forth in CISCA 3-4/UBC Standard 47-18. (See CISCA Guidelinesfor Seismic Upgrade requirements following checklist)

    PLANS/SHOP DRAWINGS/ICC ES REPORT  Contractor shall provide City of Palo Alto Inspector with engineered  “heavy duty” suspended

    ceiling system plans/shop drawings/manufacturer’s installation requirements at time of

    inspection.  Plan must include engineering specifications for compression struts, wall attachments, and

    layout for seismic joints when areas in excess of 2500 square feet.  Provide inspector with current ICC ES Report for suspended ceiling system.

    SPECIAL INSPECTION  City of Palo Alto adopted policy #15 on 07/09/2009  of   ICC Tri-Chapter Uniform Code

    Committee - Special Inspection is not required  for suspended ceiling.

    MINIMUM CODE REQUIREMENTS  Suspended Ceilings (2010 CBC 2506.2.1/ASCE 7-05 13.5.6)

    Seismic Design Categories D requirements for Suspended Ceiling Systems shall be

    designed and installed in accordance with ASTM C635, ASTM C636, and the CISCA forSeismic Zones 3-4 as modified by the following:

     

     A heavy duty T-bar grid system shall be used.

      The width of the perimeter supporting closure angle shall be not less than 2 inches. Approved perimeter seismic clips may be used in lieu of 2 inch wall angle and shall beinstalled per manufacturer’s instruction and ICC-ESR reports information.

     

    In each orthogonal (orthogonal means "involving right angles") horizontal direction, oneend of the ceiling grid shall be attached to the closure angle.

     

    The other end in each horizontal direction shall have a 0.75 inches clearance from thewall and shall rest upon and be free to slide on a closure angle.

    For ceiling areas exceeding 1,000 ft2, horizontal restraint of the ceiling to the structuralsystem shall be provided.

      The tributary areas of the horizontal restraints shall be approximately equal.(Manufacturer may required vertical post every 12 square feet)EXCEPTION:  Rigid braces are permitted to be used instead of diagonal splay wires.  Braces and attachments to the structural system above shall be adequate to limit

    relative lateral deflections at point of attachment of ceiling grid to less than 0.25inch for the loads prescribed in Section 13.3.1.

  • 8/20/2019 Seismic Suspend Ceiling-1

    2/30

    CPA T-Bar Guidelines Page 2 of 15

    MINIMUM CODE REQUIREMENTS (continued)

    For ceiling areas exceeding 2,500 ft2, a seismic separation joints or full height partition thatbreaks the ceiling up into areas not exceeding 2,500 ft2 shall be providedEXCEPTION

      Structural analyses of the ceiling bracing system for the prescribed seismic forces thatdemonstrate ceiling system penetrations and closure angles provide sufficient clearanceto accommodate the anticipated lateral displacement.

    Except where rigid braces are used to limit lateral deflections, sprinkler heads and otherpenetrations shall have a 2 inches oversize ring, sleeve, or adapter through the ceiling tileto allow for free movement of at least 1 inch in all horizontal directions.

      Alternatively, a swing joint that can accommodate 1 inch of ceiling movement in allhorizontal directions is permitted to be provided at the top of the sprinkler headextension. (see example illustrations for flex drops)

    o  Changes in ceiling plan elevation shall be provided with positive bracing. (See exampleillustrations below)

    Cable trays and electrical conduits shall be supported independently of the ceiling per ASCE7-05 chapter 13 requirements.

    Integral Construction.  As an alternate to providing large clearances around sprinklersystem penetrations through ceiling systems, the sprinkler system and ceiling grid arepermitted to be designed and tied together as an integral unit. (ASCE 7-05 13.5.6.3)

     

    Such a design shall consider the mass and flexibility of all elements involved, includingthe ceiling system, sprinkler system, light fixtures, and mechanical (HVAC)appurtenances. Such design shall be performed by a registered design professional.

      Perimeter hangers - terminal ends of each cross runner and main runner shall be supportedindependently a maximum of 8” inches from each wall or ceiling with number12 gage wire orapproved wall support. 

      Vertical wires shall be attached to the suspension member and to the support above with a

    minimum of three turns.

     

    Trapeze or equivalent device may be used where obstruction precludes direct suspension.

      Seismic separation joints shall be installed per manufacturer’s specifications & approved plans.

      Vertical hangers:  Suspension wires shall not be smaller than #12 gauge spaced at 4’ oncenter or #10 gauge at 5’ on center along each main runner.

     

    Compression strut/seismic posts are typically required every 144 sq. ft., starting a maximum6’-0” from perimeter with seismic wires (4) directions @ max. 45 degrees from horizontal.

      Partitions Tied To Suspended Ceilings (ASCE 7-05 13.8)o

     

    General. Partitions that are tied to the ceiling and all partitions greater than 6ft in heightshall be laterally braced to the building structure.

     

    Such bracing shall be independent of any ceiling splay bracing.

      Bracing shall be spaced to limit horizontal deflection at the partition head to becompatible with ceiling deflection requirements as determined in Section ASCE 7-0513.5.6 for suspended ceilings and elsewhere in this section for other systems.EXCEPTION: Partitions that meet all of  the following conditions:1) The partition height does not exceed 9 ft.2)

     

    The linear weight of the partition does not exceed the product of 10lb times theheight (ft) of the partition.

    3) The partition horizontal seismic load does not exceed 5 psf.

  • 8/20/2019 Seismic Suspend Ceiling-1

    3/30

    CPA T-Bar Guidelines Page 3 of 15

     

    Fire ratings shall comply with the requirements of the 2010 California Building Code chapter7, UL listing, Office of the State Fire Marshal’s listing, and installation per the manufacturer’ssuspended ceiling system installation manual.o  The components and installation details must conform to the U.L. or SFM approval for the

    design number specified.o

     

    Custom designs which combine components from different approved designs but have notbeen tested as a complete assembly are not acceptable .

    For schools and Essential Services Buildings, bracing assemblies are required for each 96square feet.

    The first bracing assembly is required not more than four (4) feet from each wall.o   A minimum of one bracing assembly is required between any two adjacent expansion cut-

    outs on runners being braced.

    Fire Separation Marking and Identification Requirements

     

    Fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectivelyand permanently identified with signs or stenciling. (2010 CBC section 703.6) O  Such identification shall: 

     

    Be located in accessible concealed floor, floor-ceiling or attic spaces;  Be repeated at intervals not exceeding 30 feet measured horizontally along the wall or

    partition; and  Include lettering not less than 0.5 inch in height, incorporating the suggested wording:

    "FIRE AND/OR SMOKE BARRIER-PROTECT ALL OPENINGS," or other wording.Exception: Walls in Group R-2 occupancies that do not have a removable decorativeceiling allowing access to the concealed space.

     ABOVE CEILING INSULATION

      Concealed installation.  Insulating materials, where concealed as installed in buildings ofany type of construction, shall have a flame spread index of not more than 25 and a smoke-

    developed index of not more than 450. (2010 CBC section 719.2)o  Facings. Where such materials are installed in concealed spaces in buildings of Type III,

    IV or V construction, the flame spread and smoke-developed limitations do not apply tofacings, coverings, and layers of reflective foil insulation that are installed behind and insubstantial contact with the unexposed surface of the ceiling, wall or floor finish.  (2010CBC 719.2.1)Exception:   All layers of single and multilayer reflective plastic core insulation shall comply with

    Section 2613.

     

    Exposed installation.  Insulating materials, where exposed as installed in buildings of anytype of construction , shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450. (2010 CBC 719.3)

      Surface insulation  or other purposes shall be considered interior finish if they cover 10percent or more of the wall or of the ceiling area, and shall not be considered decorative  materials or furnishings. (2010 CBC 806.1)o  Paper faced insulation is not permitted in exposed above ceiling areas, the open side of

    furred spaces, and ventilated interstitial spaces due to the potential of embers igniting thepaper.

    Quilted foil-backed or un-faced fiberglass batts and blankets are better suited to conditionsof potential fire hazards.

    Use approved quilted foil-backed insulation such as “Reflectix Insulation” in areas where a

    vapor barrier is required and use as a fix when paper back insulation is exposed.

  • 8/20/2019 Seismic Suspend Ceiling-1

    4/30

    CPA T-Bar Guidelines Page 4 of 15

    ELECTRICAL  Abandoned cables are not permitted to remain. CEC 800.52 (b  

      Junction boxes  and similar enclosures shall be accessible and shall have required workingclearances CEC 314.29, 110.26(a)  

      Cables and raceways shall not be supported by ceiling grids. CEC 300.11(a)  

    CEILING MOUNTED AIR TERMINALS

     

     Air terminals weighing less than 20 pounds shall be positively attached using sheet metalscrews. Minimum of two screws are to be installed on each side of the terminal, near thecorners, and fastened into the main runners.

     

     Air terminals weighing 20 lbs but not more than 56 pounds, in addition to the above, shallhave two #12-gage hangers connected from the terminal or service to the ceiling systemhangers or to the structure above. These wires may be installed with limited slack.

      Air terminals weighing more than 56 pounds shall be supported directly from the structureabove by approved hangers.

    RETURN AIR PLENUMS  Verify that all materials meet the applicable flame spread rating for return air plenums and

    ducts noted as “plenum rated”.

     

    Equipment and devices shall be permitted only when necessary for their direct action upon, orsensing of, the contained air. CEC 300.22 (b)  

      Verify that fire damper is clear and operational. CBC  

      Communication plenum rated cable  (CMP) shall be listed as suitable for use in ducts,plenums and listed as having adequate fire resistant and low smoke producing characteristics.CEC 800.179 (a), CEC 800.154 (a)  

    LIGHTING FIXTURE SUPPORTS  Only “Heavy-Duty”  systems listed for Seismic Design Category D shall be used in the City of

    Palo Alto.

     

     All lighting fixtures shall be positively attached to the suspended ceiling system with 4 screws -typically one at each corner.

     

    Wires required to the fixture:o

     

    Fixture less than 56 lbs: two no. 12-gage hangers connected from the fixture housing tothe structure above. These wires may be installed with limited slack.

    o  Fixtures more than 56 lbs shall be supported directly from the structure above by approvedhangers.

    Pendant Hung Fixtures shall be supported directly from the structure above with #9 gaugewire without using the ceiling suspension system for direct support.

     ASCE 7-05 CHAPTER 13 SEISMIC BRACING EXEMPTIONS FOR PIPING SYSTEMS

    The exemptions that apply specifically to seismic bracing for piping systems are covered inSection 13.6.8 of ASCE 7-05.  The provisions of this section do not cover elevator system piping which is covered in Section

    13.6.10 of ASCE 7-05.  Also not covered in this section is fire protection piping. Fire protection piping will be covered

    in a separate publication.  The piping considered in this section is assumed to be high-deformability piping.

    o  This implies pipes made from ductile materials that are joined by welding, brazing, orgroove type couplings, similar to Victaulic couplings, where the grooves in the pipe havebeen roll formed rather than cut.

  • 8/20/2019 Seismic Suspend Ceiling-1

    5/30

    CPA T-Bar Guidelines Page 5 of 15

     ASCE 7-05 CHAPTER 13 SEISMIC BRACING EXEMPTIONS FOR PIPING SYSTEMS(continued)

      Limited deformability piping on the other hand, would be pipes made of ductile materials thatare joined by threading, bonding, or the use of groove type couplings where the grooves inthe pipe have been machine cut.o

     

    Low deformability piping would be comprised of pipes made from relatively brittle materials

    such as cast iron or glass.The 12 inch Rule (ASCE 7-05 Section 13.6.8-1]1):  No restraints will be required for piping that meets the requirements of the 12 inch Rule for

    the entire piping run. The 12 inch Rule will be said to apply to a piping run if:o

     

    The piping is supported by rod hangers.o

     

    For single clevis supported pipe, all of the hangers in the piping run are 12 inches or less inlength from the top of the pipe to the supporting structure.

    o  For trapeze supported pipe, all of the hangers in the piping run are 12 inches or less inlength from the top of the trapeze bar to the supporting structure.

    The past practice by SMACNA and other recognized authorities in the industry to call for the

    connection between the hanger and the supporting structure to be “non-moment generating”.

     

    This means that the connector must be one that allows the piping run to swing freely on itshangers without introducing a bending moment in the hanger.o

     

    There must be sufficient space around the piping run to accommodate the expected motionof the pipe as it sways back and forth with the earthquake motion in the building.

    o  Connections between the piping and the interfacing components must be designed and/orselected to accept the full range of motion expected for both the pipe and the interfacingcomponent.

    Single Clevis Supported Pipe in Seismic Design Categories D (ASCE 7-05 Sections 13.6.8-2a and13.6.8-2c)

     

    For single clevis supported piping in buildings assigned to Seismic Design Categories D forwhich the Component Importance Factor is equal to 1.5, and for which the nominal size is 1inch or less; no seismic restraint is required.

      For single clevis supported piping in buildings assigned to Seismic Design Categories D forwhich the Component Importance Factor is equal to 1.0, and for which the nominal size is 3inches or less; no seismic restraint is required.

  • 8/20/2019 Seismic Suspend Ceiling-1

    6/30

    CPA T-Bar Guidelines Page 6 of 15

    Exemptions for Trapeze Supported Pipe per VISCMA Recommendations

    Neither ASCE 7-98-02 nor ASCE 7-05 specifies how the piping is to be supported.  The point is that many pipes of the exempted size may be supported on a common trapeze

    bar using hanger rods of the same size as would be specified for a single clevis supportedpipe.o

     

    Keep in mind that the purpose of the seismic restraints is to make sure the pipe moves

    with the building.o  The amount of force that the hanger rod must carry will be a direct function of the weight

    of pipe being supported.o  There must be some limit to how much weight a trapeze bar can support for a given

    hanger rod size before seismic restraint is required.

     VISCMA (Vibration Isolation and Seismic Control Manufacturer’s Association) has investigated thisissue and can make the following recommendations on the application of the exemptions inSections 5.4 and 5.5 above to trapeze supported pipe, www.viscma.com.  The following basic provisions must apply:

    o  The hangers must be ASTM A36 all-thread rod.o 

    The threads must be roll formed.o

     

    The pipes must be rigidly attached to the hanger rods.o

     

    Provisions must be made to avoid impact with adjacent pipe, duct, equipment, or buildingstructure, or to protect the pipe from such impact.

    Trapeze Supported Pipe in Seismic Design Category D: (ASCE 7-05 Sections 13.1.4-5, 13.6.8-2a, and 13.6.8-2c)  For trapeze supported piping in buildings assigned to Seismic Design Category D, which have a

    Component Importance Factor equal to 1.5, and for which the nominal size is 1 inch or less,no seismic restraint is required if:o  The trapeze bar is supported by 3/8-16 UNC, or larger, hanger rods.o

     

    The maximum hanger spacing is 7 ft. on center.o

     

    The total weight supported by the trapeze bar is 4 lbs/ft or less.  For trapeze supported piping in buildings assigned to Seismic Design Category D, which have a

    Component Importance Factor equal to 1.0, and for which the nominal size is 3 inches or less,no seismic restraint is required if:o

     

    The trapeze bar is supported by ½”-13 UNC, or larger, hanger rods.o  The maximum hanger spacing is 10 ft. on center.o  The total weight supported by the trapeze bar is 25 lbs/ft or less.

      The Seismic Design Category to which the project has been assigned must be known.o

     

    This should be noted on the issued permit plans.o  The design professional responsible for the piping system must assign an appropriate

    Component Importance Factor to the system. As a sidebar to the previous statement, it should be noted that the specification for the buildingmay increase the Seismic Design Category in order to ensure an adequate safety margin and thecontinued operation of the facility. This is a common practice with schools, government buildings,and certain manufacturing facilities.

    The building owner has the prerogative, through the specification, to require all of the pipingsystems to be seismically restrained. Careful attention to the specification must be paid, as someor all of the exemptions in this section may be nullified by specification requirements that aremore stringent than those provided by the code.

  • 8/20/2019 Seismic Suspend Ceiling-1

    7/30

    CPA T-Bar Guidelines Page 7 of 15

    DETAILS

    REFERENCES

    STANDARDS

  • 8/20/2019 Seismic Suspend Ceiling-1

    8/30

    CPA T-Bar Guidelines Page 5 of 12

    EXAMPLES OF DRYWALLL SUSPENDED CEILING SYSTEM - NO MIXING COMPONENTS  

    EXAMPLES OF DRYWALLL SUSPENDED CEILING SYSTEM - NO MIXING COMPONENTS  

  • 8/20/2019 Seismic Suspend Ceiling-1

    9/30

    CPA T-Bar Guidelines Page 6 of 12

    EXAMPLES OF FLEXIBLE SPRINKLER SUSPENDED CEILING SYSTEM ATTACHMENTS

    If the "cross-runners" are not the scarrying capacity as the "main-runnsupplementary #12 gauge hangerwires shall be attached at each sid

  • 8/20/2019 Seismic Suspend Ceiling-1

    10/30

    CPA T-Bar Guidelines Page 7 of 12

    EXAMPLES OF SEISMIC CONNECTORS FOR SUSPENDED CEILING SYSTEMS

  • 8/20/2019 Seismic Suspend Ceiling-1

    11/30

    CPA T-Bar Guidelines Page 8 of 12

    EXAMPLES OF SEISMIC CONNECTORS FOR SUSPENDED CEILING SYSTEMS

  • 8/20/2019 Seismic Suspend Ceiling-1

    12/30

    CPA T-Bar Guidelines Page 9 of 12

    EXAMPLES OF SEISMIC CONNECTORS FOR SUSPENDED CEILING SYSTEMS

  • 8/20/2019 Seismic Suspend Ceiling-1

    13/30

    CPA T-Bar Guidelines Page 10 of 12

    EXAMPLES OF SEISMIC CONNECTORS FOR SUSPENDED CEILING SYSTEMS

  • 8/20/2019 Seismic Suspend Ceiling-1

    14/30

    CPA T-Bar Guidelines Page 11 of 12

  • 8/20/2019 Seismic Suspend Ceiling-1

    15/30

    CPA T-Bar Guidelines Page 12 of 12

  • 8/20/2019 Seismic Suspend Ceiling-1

    16/30

    STANDARD FOR EXISTING SUSPENDED CEILING SYSTEM

    UPGRADES

  • 8/20/2019 Seismic Suspend Ceiling-1

    17/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    18/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    19/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    20/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    21/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    22/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    23/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    24/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    25/30

  • 8/20/2019 Seismic Suspend Ceiling-1

    26/30

    U.B.C. STANDARD 47-18

    T-BAR CEILING INSTALLATIONS

    EXISTING

    SYSTEMS

    Systems installed prior to

    Jan 1

    2008 shall

    be

    upgraded

    to

    meet 1997 Standards 47 18.

    UBC

    STANDARD

    47 18

    INSTALLATION

    REQUIREMENTS AND ILLUSTRATIONS

    Part 11 1 ns tall a lon

    Scope

    Sec. 47.1808. This standard describes procedures for the installation o suspen

    sion systems for acoustical

    tile

    and lay-in panels.

    Installation of Components

    Sec. 47.1809. a) Hangers. Hangers shall be attached to the bottom edge

    of

    the

    wood joists or to the vertical face of the wood joists near the bottom edge. Bottom

    edge attachment devices shall be an approved type.

    In

    concrete construction mount hangers using cast-in-place hanger wires hanger

    inserts or other hanger attachment devices shall be an approved type. If greater

    center-to-center distances than 4

    feet

    0 inch are used for the hangers reduce the

    load-carrying capacity of the ceiling suspension system commensurate with the ac·

    tual center-to-center hanger distances used.

    Hangers shall

    be

    plumb and shall not press against insulation covering ducts or

    pipes.

    If some hangers must

    be

    splayed offset the resulting horizontal force

    by

    brac

    ing,

    countersplaying or other acceptable means.

    Hangers formed from galvanized sheet metal stock shall be suitable for suspend

    ing

    carrying channels or main runners from

    an

    existing structure provided that the

    hangers do not yield twist or undergo other objectionable movement.

    Wire

    hangers

    for

    suspending carrying channels or main runners from an existing

    structure shall be prepared from a minimum of No. 12-gage galvanized soft-an

    nealed mild steel wire.

    Special attachment devices that support the carrying channels or main runners

    shall be

    approved to support

    five

    times the design load.

    b) Carrying Channels. The carrying channels shall be installed so that they are

    all

    level to within Y inch i n 12 feet.

    Leveling

    shall

    be

    performed with the supporting hangers taut.

    Local

    kinks or bends shall not

    be

    made

    in

    hanger

    wires as

    a means

    o

    leveling car

    rying

    channels.

    In installations where hanger wires are wrapped around carrying channels the

    wire

    loops

    shall

    be tightly formed to prevent any vertical movement or rotation of

    the

    member

    within the loop.

    1368

  • 8/20/2019 Seismic Suspend Ceiling-1

    27/30

      988 EDITION 47-18

    c) Msin Runners. Main runners shall

    be

    installed so that they are all

    level lO

    within Y inch in

    12

    feet.

    Where main runners are supported directly

    by

    hangers, leveling shall

    be

    per-

    formed with the support.ing hanger taut.

    Local kinks or bends shall not be made in hanger wires as a means of

    leveling

    main runners.

    In

    installations where hanger wires are wrapped through or around main runners,

    the wire loops shall be tightly wrapped and sharply bent.

    d) Cross Runners. Cross runners shall be supported by either main runners or by

    other cross runners to within

    X

    inch

    of

    the required center distances. This tolerance

    shall be noncumulative beyond

    12

    feet.

    Intersecting runners shall form a right angle.

    The exposed surfaces

    of

    two intersecting runners shall

    lie

    within a vertical distance

    of 0.015 inch

    of

    each other

    with

    the abutting cross) member always above the con

    tinuous main) member.

    e) Splines. Splines used to form a concealed mechanical joint seal between adja

    cent tiles shall

    be

    compatible with the tile kerf design so that the adjacent tile

    will

    be

    horizontal when installed. Where splines are longer than the dimension between

    edges of supporting members running perpendicular

    to

    the splines, place the splines

    so that they rest either all above or all below the main running members.

    f)

    Assembly Devices. Abutting sections of main runner shall be joined

    by

    means

    of suitable connections such

    as splices, interlocking ends, tab locks, pin locks, etc. A

    joint connection shall be judged suitable both before and after ceiling loads are im

    posed

    if the joint provides sufficient alignment so that the exposed surfaces of two

    abutting main runners lie within a vertical distance of 0.015 inch of each other nd

    within a horizontal distance of 0.0

    S

    inch of each other.

    There shall be no visually apparent angular displacement

    of

    the longitudinal axis

    of one runner with respect to the other.

    Assembly devices shall provide sufficient spacing control so that horizontal gaps

    between exposed surfaces of either abutting or intersecting members shall not exceed

    0.020 inch.

    Spring

    wire dips

    used for supporting main runners shall maintain tight contact

    between

    the main runners and the carrying channels when the ceiling loads are im

    posed on the runners.

    g)

    Ceiling Fixtures. Fixtures installed in acoustical tile or lay-in panel ceilings

    shall be mounted

    in

    a manner that will not compromise ceiling performance.

    Fixtures shall not be supported from main runners or cross runners if the weight

    of the fixtures causes the total dead load to

    e x ~ e d

    the deflection capability of

    the

    ceiling suspension system.

    In

    such cases, the fixture load shall be supported by sup

    plemental hangers within 6 inches

    of

    each corner, or the fixture shall

    be

    separately

    supported.

    Fixtures shall not

    be

    installed so that main runners or cross runners will be eccen

    trically loaded except where provision

    is

    inherent in the system or

    is

    separately

    pro-

    vided for)

    to

    prevent undesirable section rotation or displacement, or both.

    In

    ny

    case, runners supporting ceiling fixtures shall not rotate more than 2 degrees after

    the

    fixture loads are imposed.

    Where fixture installation would produce rotation of runners in excess of

    2

    degrees, install fixtures with the use of suitable accessory devices. These devices shall

    support the fixture

    in

    such a manner that the main runners and cross runners

    will be

    loaded symmetrically rather than eccentrically.

    369

  • 8/20/2019 Seismic Suspend Ceiling-1

    28/30

    47 18

    U.B.C. STANDARDS

    Part l l l Latmal Design Requirements

    Scope

    Sec. 47.1810. Snspencled ceiling which

    are

    designed

    and

    constructed

    to

    support ceiling

    panels or tiles, with or without lighting fixtures, ceiling mounted air terminals or other

    ceiling

    mounted

    services shall comply with

    the

    requirements of this standard.

    EXCEPTIONS: I. Cci

    ling

    an· a of 14 4 square feet or less surrounded by walls which connect

    dir..:ctly to

    the

    stn1cture above shnll be exempt from the lateral load design requirements of these

    ~ t a n d a r d s

    2. Ceilings constr11ctrd of l ~ t h and plaster or gypsum board. screw or nail attached to

    suspcndrd members tlmt support a ceiling on one level extending from wall to wall.

    Minimum Design Loads

    Sec

    47.1811.

    a) Lateral Forces. Such ceiling systems and their connections to the

    building structure shall be designed and constructed to resist a lateral force specified

    in

    Chapter

    3

    of he Uniform Building Code.

    Where

    the ceiling system provides lateral support for nonbearing partitions, it shall be

    designed for the prescribed lateral force reaction

    from

    the partitions u specified in Section

    47.1815.

    Connection of lighting fixtures

    to

    the

    ceiling system shall

    be

    designed for a lateral force

    of

    100 percent of

    the

    weight of

    the

    fixture in addition to

    the

    prescribed vertical loading as

    specified in Section 47 1813

    b) Grill

    Members, Connectors anu Expansion Devices. The main runners and cross

    runners

    of the ceiling system and their splices, intersection connectors and expansion

    devices

    shall

    be

    designed

    and

    constructed to carry a mean ultimate test load

    of

    not less than

    180

    pounds or

    twice the actual load, whichever is greater,

    in

    tension with

    a

    5-degree

    misalignment of the members in any direction, and in compression. In lieu of 5-degree

    misalignment, the load may be applied with a l-inch eccentricity on a sample not more than

    24

    inches

    long

    each

    side of

    the

    splice. The connections at splices and intersections all shall be

    of the

    mechanical interlocking type.

    Where the composition or configuration of ceiling systems members or assemblies and

    their connections

    are

    such that calculations of their allowable load-carrying capacity cannot

    be made in accordance

    with

    established methods of analysis, their performance shall be

    established by test.

    Evaluation of test results shall be made on the basis of

    the

    mean values resulting from tests

    of not

    fewer than

    three identical specimens, provided

    the

    deviation of any individual test

    result from

    the

    mean

    value does not exceed plus or minus I 0 percent. The allowable load

    carrying capacity as determined

    \ ly

    test shall

    not

    exceed one half of the mean ultimate test

    value.

    (c)

    Substantiation. Each ceiling systems manufacturer shall furnish lateral loading

    capacity and displac

    1

    ement or elongation characteristics for his systems, indicating the

    following:

    I.

    Maximum

    bracing pattern

    and

    minimum wire

    siz.es.

    2. Tension and compression force capabilities of main runner splices, cross runner

    connections

    and

    expansion devices.

    All tests shall be conducted by

    an

    approved testing agency.

    Installation

    Sec.

    47.1812. (a)

    Vertical Hangers. Suspension wires shall be not smaller than No.

    12

    gage

    spaced

    at 1 feel on center or No. 10 gage at 5 feet on center along each main runner

    unless

    calculations justifying the incre

  • 8/20/2019 Seismic Suspend Ceiling-1

    29/30

      988 EDITION

    47-18

    Each vertical wire shall be attached

    to the

    ceiling suspension member

    and to the

    support

    above with a minimum of three turns. Any connection device at the supporting construe lion

    shall be capable of carrying not less than 100 pounds.

    Suspension wires shall not hang more than l

    in

    6 out-of-plumb unless countcrsloping

    wires are provided.

    Wires

    shall not attach

    to

    or bend around interfering material or equipment. A trapeze or

    equivalent device shall be used where obstructions preclude direct suspension. Trapeze

    suspensions shall

    be

    a minimum

    of

    back-to-back

    11/4-inch

    cold-rolled channels

    for

    spans

    exceeding

    48

    inches.

    (b) Perimeter Hangers.

    the

    terminal ends of each cross runner and main runner shall

    be

    supported independently a maximum of 8 inches from each wall or ceiling discontinuity

    with No. 12 gage wire or approved wall support. •

    c) Lateral Force Bracing. Where substantiating design caltulations

    are

    not provided,

    horizontal restraints shall be effected by four No. I 2 gauge wires secured to the main runner

    within 2 inches of

    the

    cross runner intersection

    and and

    splayed 90 degrees from each other

    at

    an

    angle not exceeding

    5

    degrees from the plane

    of the

    ceiling. A strut fastened

    to the

    main

    runner shall

    be

    extended

    to

    and

    fastened

    to

    the structural members supporting

    the

    roof or

    floor above. The strut shall be tH.lcquatc to resist

    the

    vertical component

    i n u t l ~ c t l by

    the

    bracing wires. These horizontal restraint points shall be placed 12 feet on center in both

    directions with the first point within 6 feet from each wall. Attachment of the restraint wires

    to

    the structure above shall be adequate for the load imposed.

    Lateral force bracing members shall be spaced a minimum

    of

    6 inches from all horizontal

    piping or duct work that

    is

    not provided with bracing restraints for horizonta I forces. ·Bracing

    wires shall be attached to the grid and to the structure

    in

    such a manner that they can support a

    design load of not less than 200 pounds or

    the

    actual design load, whichever

    is

    greater, with a

    safety factor of 2.

    d) Perimeter Members. Unless perimeter members are a structural part of the approved

    system, wall angles or channels shall be considered as aesthetic closers and shall

    have

    no

    structural value assessed

    to

    themselves or their method

    of

    attachment

    to

    the walls.

    or

    tile

    ceilings, ends of main runners

    and

    .cross members shall be tied together

    to

    prevent their

    spreading.

    e)

    Attachment of Members to the Perimeter.

    To

    facilitate installation, main runners

    and cross runners

    may

    be attached to the perimeter member at two adjacent walls with

    clearance between the wall and the runners maintained

    at

    the other two walls or as otherwise

    shown or described for

    the

    approved system.

    Lighting Fixtures

    Sec.

    47.1813.

    Only intermediate

    and

    heavy duty

    c;eiling

    systems

    as defined in

    Section

    47.1802

    may be used for the support of lighting fixtures.

    All

    lighting fixtures shall

    be

    positively attached

    to the

    suspended ceiling system. The

    attachment device shall have a capacity of 100 percent of the lighting fixture weight acting in

    any

    direction.

    When intermediate systems are used, No.

    12

    gage hangers shall

    be

    attached

    to the

    grid

    members within 3 inches of each corner of each fixture. Tandem fixtures may utilize

    common wires.

    Where heavy duty systems are used, supplemental hangers are not required if a 8 inch

    modular hanger pattern

    is

    followed. When cross runners are used without supplemental

    hangers

    to

    support lighting fixtures, these

    c;ross

    runners must provide the same

    carrying

    capacity as the main runner.

    Lighting fixtures weighing less than 56 pounds shall have,

    in

    addition to the require rnents

    . 1371

  • 8/20/2019 Seismic Suspend Ceiling-1

    30/30

    47-18

    U.B.C. STANDARDS

    outlined above,

    two

    No.

    12

    gage hangers connected from the fixture housing

    to

    the structure

    above.

    These wires may

    be

    slack.

    . Lighting fixtures weighing

    56

    pounds or

    more

    shall be supported directly from the

    structure above by approved hangers.

    Pendant-hung lighting fixtures shall be supported directly from the stnrcture above using

    No. 9 gage wire

    or

    approved alternate support wjthout using the ceiling suspension system

    for

    direct support.

    Mechanical Services

    t

    J J

    2. S

    C Q f 2 1.-1.. ')'

    I\'-.) tb

    ,.,,

    -'

    \ i ~ \A A A 11 j2. \..- .. tv V R.._

    . ~ n t e d air terminals or services weighing

    less'

    tthan

    20

    pounds shall

    be

    ositivel attache_