Top Banner
Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012
23

Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Apr 01, 2015

Download

Documents

Kourtney Merry
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Reading a GE PSLF *.epc into PWS

Tracy Rolstad

Avista System Planning

WECC PWSUG, 14 March 2012

Page 2: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Open Case, Select <GE EPC format (with options)>

Page 3: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

What Options (these are defaults)?

Page 4: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Start with GE

• Nothing is sacred about the GE defaults. Change them!

• Solve the case, multiple times…

• GE uses an estimated mismatch

• So, solve in GE three times or so

• Save the solved case as an *.epc file

Page 5: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Read into PWS and Solve

• Read in case, note mismatches, understand them

• Lock all controls down, solve in PWS (set gen voltage control)

Check Interface flows against GE…

– GE allows double counting the same line

• PWS does NOT allow double counting

• Note Mismatch resolution in log

PWS Zero Impedance Line is very, very small

– GE uses X=0.00029 (0.725 ohms @ 500 kV)

– PWS uses X=0.00001 (0.025 ohms @ 500 kV)

Page 6: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Mismatch Table

Page 7: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Mismatches in State Variable View

Page 8: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Mismatches in Input Data View

Page 9: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.
Page 10: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

After Fixing GE Bface Error

• Errors after removing extra BFACE entry

Total MW Error (i.e. sum) = -19.5

Max MW Error = 3.7 (North to South California, Path 24)

Min MW Error = -4

Page 11: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Read the Log, Understand and Take Action

Page 12: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Read into PWS and Solve

• Unlock all controls, solve in PWS

Check log for AGC movement

– May need to “Zero out transactions”

• If GE transaction table isn’t manually updated by WECC staff

Check Interface flows against GE…

– Should get pretty much the same answer on path flows

Check for multiple islands

Page 13: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Zeroing Out Transactions

Page 14: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Voltage Control for Generators

• Allocate across buses using the user-specified remote regulation percentages. This option is what is used by default and most closely matches the sharing seen in RAW files.

• Allocate so all generators are at same relative point in their [min .. max] var range. This option most closely matches the sharing seen in a few EMS solutions PowerWorld has seen.

• Allocate across buses using the SUM OF user-specified remote regulation percentages. This option most closely matches the sharing seen in EPC files.

• Note: Generators at the same bus always allocate vars so they are at the same relative point in their [min…max] range

Page 15: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Var Sharing

Bus: CABGOR12 (48061)

Nom kV: 13.80

Area: NORTHWEST (40)Zone: AVA: Coeur D'Alene (441)

System State

ID 1 ID 2

CAB GORG

CKT 1

81%

A

MVA

CABGOR12

1.0046 pu

13.86 KV

81.26 Deg 0.00 $/MWh

55.000 MW

22.299 Mvar

65.000 MW

8.714 Mvar

0.00 MW

0.00 Mvar

1.0716 tap

120.0 MW

31.0 Mvar

123.9 MVA

48059

1.0478 pu

240.99 KV

Page 16: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Comparing PWS to GE VAr “Answer”

CABGOR12

55 MW 22 Mvar

65 MW 9 Mvar

CABGOR12 #1

VAr % across range-CE

1.00

0.00

76.61%

CABGOR12 #2

VAr % across range-CE

1.00

0.00

76.61%

31.7 Mvar -8.5 Mvar

18.7 Mvar -24.0 Mvar

CABGOR12

55 MW 16 Mvar

65 MW 16 Mvar

CABGOR12 #1

VAr % across range-CE

1.00

0.00

60.95%

CABGOR12 #2

VAr % across range-CE

1.00

0.00

93.68%

31.7 Mvar -8.5 Mvar

18.7 Mvar -24.0 Mvar

Page 17: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Check Case Summary and Slack Bus Generator

Quantity GE PWS

Load MW 169427.5 169427.5

Gen MW 175697.1 175693.0

Losses MW 6269.8 6263.5

Buses count 18205 18585

Load MVAr 31767.3(t_area)

31718.3

Load MVAr* 32291.53 31718.3

Slack MW 538.0 543.01

* Summed directly from load record

Page 18: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Look for Places to Establish “Test Flows”

Page 19: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Check Performance in Contingent Environment

Bus: BENEWAH (48037)

Nom kV: 230.00

Area: NORTHWEST (40)

Zone: AVA: Palouse (446)

System State

ID s

MOSCOW

CKT 1

PINE CRK

CKT 1

SHAWNEE

CKT 1

BOULDER

CKT 1

BENEWAH

CKT 1

A

MVA

A

Amps

A

Amps

A

Amps

BENEWAH

1.0158 pu

233.64 KV

58.54 Deg

0.00 $/MWh

0.000 Mvar

0.00 MW

0.00 Mvar

61.0 MW

-18.7 Mvar

63.8 MVA

48249

1.0200 pu

234.61 KV

0.0 MW

0.0 Mvar

0.0 MVA

48317

1.0397 pu

239.14 KV

67.1 MW

-16.1 Mvar

69.0 MVA

48385

1.0181 pu

234.16 KV

166.3 MW

20.1 Mvar

167.6 MVA

48524

1.0156 pu

233.59 KV

1.0059 tap

38.3 MW

14.8 Mvar

41.0 MVA

48035

1.0015 pu

115.17 KV

Page 20: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Participation Factor Note (Added Post Meeting)

• During the second WECC PWS Users Group we noticed that PWS was parsing the Gen MVA field of the *.epc file and setting Participation Factors on that field. In many cases this value is merely set to 100 MVA (for example the large units located in the third power house at Grand Coulee).

• Users should be alert to this behavior and manually set Participation Factors to be based on Pmax

Typically setting Participation Factors to Pmax is the desired setting for dispatching make-up power during contingency analysis, etc.

Page 21: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Setting Participation Factors

Page 22: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.

Questions?

• PWS will provide similar, but not exact results when compared to GE (or PTI)

• Heuristics abound…

What is “right?” Good reason to use multiple tools

• VAr dispatch of generation has an impact, especially on the initialization point for transient stability

• Zero impedance line representations have some impact

• Recommendation

• Presume that both software provide reasonably accurate possible solution points

• Take five minutes to understand the case read!!!

Page 23: Reading a GE PSLF *.epc into PWS Tracy Rolstad Avista System Planning WECC PWSUG, 14 March 2012.