OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
1. When all the three phase are short circuited it gives rise to:
(a) Asymmetrical fault current(b) Symmetrical fault current(c) Zero current(d) None of the above
Ans b
2. The most common type of fault on the over head lines:
(a) Single line to ground fault(b) Double into ground fault(c) Three phase fault(d) Line to line fault
Ans a
3. Reactors are used in various point in the power system to
(a) Limit short circuit current(b) Short circuit (c) Avoid short circuit(d) None of the above
Ans a
4. The use of reactor permits installation of circuit breaker of the
(a) Lower rating(b) Higher rating(c) Same rating(d) None of the above
Ans a5. If a 5 amp. Fuse is blown frequently
house lightning circuit, it is required to
(a) Insert a fuse of higher current rating
(b) Insert a fuse of higher voltage rating
(c) Check the load(d) None of above
Ans c6. H.R.C fuse provide best protection
against(a) Open circuit(b) Short circuit
(c) Over load(d) Revers current
Ans b
7. The size of each wire is determined by
(a) The amp. Capacity of service wire
(b) Atmospheric condition(c) Voltage of the size service wire(d) None of the above
Ans a8. When a fault occure on the system a
circuit breaker(a) Open the automatically(b) Close automatically(c) Open the manually(d) None of the above
Ans a9. If the lenth of the arc of circuit
breaker increase, its will(a) Be extinguished(b) Decreases(c) Remain same(d) None of the above
Ans a10. Current chopping mainly
occure in(a) Oil circuit breaker(b) Air blast circuit breaker(c) Vaccume circuit breaker(d) SF6 gas circuit breaker
Ans b11. Capacitive current breaking
result in(a) Short circuit(b) Open circuit(c) Voltage surge(d) None of the above
Ans c12. The speed of circuit breaker
intruption in forced(air)blast circuit breaker
(a) Slow(b) Medium
Page 1
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(c) Fast(d) None of the above
Ans c13. The normal practice to specify
the making current of(a) Circuit breaker in turn of(b) RMS value(c) Peak value(d) Everage value
Ans b14. Resistance switching is
normally resorted in case of(a) Air blast circuit breaker(b) Bulk oil circuit breaker(c) Minimum oil circuit breaker(d) All type circuit breaker
Ans a15. For remote operation circuit
breaker must be required with a(a) Time delay trip(b) Shunt trip(c) Inverse time trip(d) None of the above
Ans b16. Which of the following circuit
breaker is generally used in railway application
(a) Air break circuit breaker(b) Minimum oil circuit breaker(c) Bulk oil circuit breaker(d) SF6 circuit breaker
Ans a17. Which of the following circuit
breaker is used for E.H.T application(a) Air blast circuit breaker(b) Minimum oil circuit breaker(c) Bulk oil circuit breaker(d) SF6 circuit breaker
Ans d18. In circuit breaker the arcing
contents are made of (a) Porsline(b) Copper tungstone alloy(c) Aluminmum alloy(d) Electronic opper
Ans b19. Which statement is correct(a) SF6 gas is toxic(b) SF6 gas is lighter than air(c) SF6 gas is yellow in colour(d) SF6 gas has cumgent smell
Ans a20. A relay performs the function
of(a) Fault isolation(b) Fault detection(c) Fault prevention(d) All of the above
Ans b21. The relay operating coil is
supplied through(a) Fuse(b) Instrument T/F(c) Power T/F(d) None of the above
Ans c22. Most of the relay on service on
electric power system are(a) Electronic relay(b) Electro mechanical relay(c) Thermal relay(d) None of the above
Ans b
23. Back-up protection is generally imployed for protection against
(a) Short circuit fault only(b) Open circuit fault only(c) Both a and b(d) None of the above
Ans a24. MHO relay is a(a) Voltage restrand directional relay(b) Voltage controlled over current
relay(c) Directional restand over current
relay(d) Directional restand over voltage
relay
Page 2
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
Ans a25. Different relay are mused to
protect the equipment against(a) Internal faulty(b) Reverse current(c) Over current(d) None of the these
Ans a26. The least expensive protection
for over current in L.V system is(a) Isolated(b) Oil circuit breaker(c) Reverse able fuse(d) Air breaker circuit breaker
Ans c27. Impedance relay can be used
for(a) Earth fault(b) Phase fault(c) Both (a) and (b) (d) None of these
Ans c28. If the fault occurs near the
impedance relay the V/I ratio will be(a) Higher than the value if the fault
occur away from the realy(b) Lower than the value if the fault
occur away from the relay (c) Constant for all distance (d) None of these
Ans b29. Which of the following
material can not be used for contents of switching devices
(a) Copper(b) Aluminium (c) Copper alloy(d) Siver
Ans c
30. What is the most serious problem in vaccume circuit breaker
(a) Poor arc quenching(b) Low thermal stability(c) Current chopping(d) All of these
Ans c31. The positive sequence
reactance will be equal to negative sequence reactance in case of
(a) T/F(b) Generator(c) Transmission line(d) Motor
Ans a
32. Rated making capacity of circuit breaker is equal to
(a) /2 X rated symmetrical breaking capacity
(b) 2.55 X rated symmetrical breaking capacity
(c) 1 X rated symmetrical breaking capacity
(d) None of these Ans b
33. M.H.O realy is used to protect(a) Long transmission line(b) Medium lenth transmission line(c) Short lenth transmission line(d) All of these
Ans a34. Reactance relay is used to
protection against(a) Earth fault(b) Phase fault(c) Over voltage fault(d) None of these
Ans a35. The stability of arc in vaccume
circuit breaker is depends on(a) The control material(b) Its vaccume pressure(c) The circuit paraments(d) All of these
Ans d36. Why does minimum oil circuit
breaker has less volume of oil(a) There is insulation between
contents(b) The oil between breaker contacts
has greater streath
Page 3
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(c) Solid insulation is provided for insulating the contents from earth
(d) None of these Ans c
37. Arcing on transmission line is prevented
(a) By circuit breaker(b) By protective relay(c) By inductor in the neutral(d) By capacitor in the neutral
Ans c38. The energy in a lightning
strock can be as high as (a) 10 units(b) 100 units(c) 250 units(d) 1000 units
Ans c39. In what shape of conductor
corona loss is less(a) Circular(b) Oval(c) Flat(d) Any of these
Ans a40. Merze price protection is used
to protect(a) Transmission line(b) T/F and generator(c) Motor(d) T/F
Ans c41. Switching and protection are
used under taken by(a) Switch gear(b) Fuse(c) Lightning arrestor(d) Relay
Ans a42. Distance relay operation is
depends on(a) Ratio of current to current(b) Ratio of voltage to current(c) Ratio of voltage to voltage(d) None of these
Ans b
43. Which relay is used to detect and protect internal fault of T/F
(a) Buchholze relay(b) Directional relay(c) Thermal relay(d) Distance relay
Ans a44. Surge protector provide(a) High impedance to normal
voltage(b) Low impedance to surge(c) Both a and b(d) None of these
Ans c45. An isolator operate under(a) No load condition (b) Full load condition(c) 50% of full load condition (d) At fault current
Ans a46. The lightning arrestor (L.A) is
connected(a) In series in the line(b) Between line and earth(c) To a pole near the line(d) None of these
Ans b47. Relay is using induction disc
principle operate(a) Only on D.C(b) Only on A.C(c) Either on D.C or A.C(d) None of these
Ans b48. Earthing is necessary to give
protection against (a) Voltage fluctuation(b) Over loading (c) Danger of electric shock(d) High temperature of conductor
Ans c49. The primary function of a fuse
is to(a) Protect the appliances
Page 4
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(b) Open the circuit (c) Prevent excessive current(d) Protect the line
Ans c50. The accepted value of
dielectric strength of T/F oil is (a) 30 KV(b) 40 KV(c) 30 KV/minute (30 KV/2.5
mm/minute(d) None of these
Ans c51. As compare to air the relative
dielectric strength of SF6 gas is nearly (more)
(a) 1.5 times(b) 4 times(c) 2.5 times(d) 5 times
Ans b52. Which of the following gas has
been used as insulating medium in electrical appliances
(a) Nitrogen(b) Carbon dioxide (c) Sulphur haxa floride (SF6)(d) Freon
Ans c53. Liquids are generally used as
insulating material upto stress of about
(a) 100 M volt/cm(b) 50 mv/cm(c) 50 kv/cm(d) 500 kv/cm
Ans c54. Low voltage circuit breaker
has rated voltage less than(a) 66 KV(b) 33 KV(c) 11 KV(d) 1000 volt
Ans d55. When a H.V circuit breaker is
tested for inductance it is tested for at least
(a) 5000 open-closing operation(b) 3600 open-closing operation(c) 1000 open-closing operation(d) None
Ans c56. For H.V ac circuit breaker the
rated short circuit current is passed for
(a) 12 second(b) 3 second(c) 9 second(d) None
Ans c57. Air blast circuit breaker, the
pressure of air is of the order of(a) 40-50 kg/cm2
(b) 3-5 kg/cm2
(c) 1-3 kg/cm2
(d) 20-30 kg/cm2
Ans d58. The pressure of SF6 gas in
circuit is of the order of 1-14 kg/cm2 (a) 3-5 kg/cm2
(b) 20-30 kg/cm2
(c) 18-20 kg/cm2
(d) None Ans a
59. Air blast circuit breaker can be installed on
(a) 11 kv(b) 66 kv(c) 132 kv (d) 400 kv
Ans d60. Air blast circuit breaker for
400 kv power system are designed to operate in
(a) 50 milli second(b) 5 milli second(c) 100 milli second(d) None
Ans a61. Breaking capacity of a circuit
breaker is usually expressed in term of
(a) KVA
Page 5
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(b) MVA(c) KVAR(d) MVAR
Ans c62. The capacitor switching is
easily done with(a) Air blast circuit breaker(b) Oil circuit breaker(c) Vaccume circuit breaker(d) Any of above
Ans c63. The most suitable circuit
breaker for short line fault without switching resistor is
(a) Air blast circuit breaker(b) SF6 gas circuit breaker (c) Minimum oil circuit (d) None
Ans b64. For rural electrification in a
country like india with complex network. It is preffer to use
(a) Oil circuit network(b) Minimum oil circuit breaker(c) Vaccume circuit breaker(d) Air breaker C.B
Ans c65. Where voltage are high and
current to be intrupted is low. The breaker preffered is
(a) Vaccume circuit breaker(b) Oil circuit breaker(c) Air blast circuit breaker(d) Any one of the above
Ans a66. To limit current chopping in
V.C.B the contect material used has (a) Low vapour pressure and high
conductivity properties(b) Low vapour pressure and low
conductivity properties(c) High vapour pressure and low
conductivity properties(d) None of these
Ans c
67. A 3Q circuit breaker is rated at 2000 MVA 33 KV,it making current will be
(a) 69 KA(b) 89 KA(c) 49 kilo ampere(d) None of these
Ans c68. While using air blast circuit
breaker, current chopping is a phenomenon often observed, when
(a) Long over head line switched off(b) A T/F on no load switched off(c) A bank of capacitors is switched
off(d) A heavy load switched off
Ans b69. In order to quench the arc
quickly and also optimize the dimentions, generally
(a) SF6 gas circuit breaker is prefferd(b) Air blast circuit breaker is
prefferd(c) Oil circuit breaker is prefferd(d) Minimum oil circuit breaker is
prefferd Ans b
70. A circuit breaker is a(a) P.F correcting device(b) Wave shape correcting device(c) Current intrupting device(d) A device to neutralize the effect
of transient Ans c
71. Circuit breaker usually operated under
(a) Steady state short circuit current(b) Sub-transient state of short
circuit current(c) Transient state of short circuit
current(d) None of the above
Ans c72. A circuit breaker normally
operater(a) When the line is to tested(b) When the switch is put on(c) When the power is to be supplied
Page 6
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(d) When ever fault occur is the line Ans d
73. While selecting a gas for circuit breaker, the property of gas, that should be considered is
(a) Non- toxicity(b) Non-inflame ability(c) High dielectric strength(d) All of these
Ans d74. The fault clearly time of a
circuit breaker is usually of(a) Few cycle of supply voltage(b) Five second(c) Five minotue(d) One minotue
Ans a75. For high voltage A.C circuit
breaker the rated short circuit current is passed for
(a) 0.01 second(b) 3 second(c) 0.1 second(d) 30 second
Ans c76. Out of the following circuit
breaker which one has the lowest voltage range
(a) Air break circuit breaker(b) Air blast circuit breaker(c) Tank type oil circuit breaker (balk
oil)(d) Minimum oil circuit breaker
Ans a77. In minimum oil current
breaker, used oil for(a) Insulation only(b) Arc quenching only(c) Cooling only(d) Lubrication only
Ans c78. The medium used for arc
aretinction in the air circuit breaker is
(a) Oil(b) SF6 gas
(c) Air(d) Compressed air
Ans b79. Air used in air blast circuit
breaker must(a) Have least cor(b) Be-oinized (c) Have oil mixed(d) Be free from moisture
Ans d80. Under normal condition a
circuit breaker should be inspected(a) Every day(b) Once in six month or 12 month(c) Every week(d) Once in six years to 7 years
Ans c81. In a vaccume circuit breaker,
the vaccume in the order of(a) 1 torr(b) 10-12 torr(c) 10-6 torr(d) 10-16 torr
Ans b82. Plane break oil circuit breaker
can be used upto(a) 11 kv(b) 33 kv(c) 1.1 kv(d) 132 kv
Ans a83. For E.H.V line, which of the
following circuit breaker is preffered(a) Air breaker circuit breaker(b) Bulk oil circuit breaker minimum
oil circuit breaker(c) Minimum oil circuit breaker(d) Any of the above
Ans c84. Air blast circuit breaker for
400 KV power system are designed to operate in
(a) 5 milli second(b) 500 milli second(c) 50 milli second(d) None of the above
Page 7
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
Ans b85. For high speed circuit breaker
the total clearing time is nearly (a) 1-2 cycle(b) 50 cycle(c) 7-12 cycle(d) 60 cycle
Ans a86. If the least of the all of circuit
breaker is increased its resistance will
(a) Increase(b) Remain same(c) Decreases(d) None of these
Ans a87. If the dielectric strength of the
medium between contects build up more rapidly than the re-striking voltage, then the arc will
(a) Be extinguished(b) Not be extinguished(c) Increase(d) None of the above
Ans a88. Which of the following circuit
breaker take minimum time for installation
(a) Air blast circuit breaker(b) Minimum oil circuit breaker(c) Bulk oil circuit breaker(d) SF6 gas circuit breaker
Ans c89. Bulk oil circuit breaker is
suitable for voltage upto (a) 6.6 kv(b) 11 kV(c) 36 KV(d) 132 KV
Ans c90. Which of the following circuit
breaker is most popular for out ultra H.V application
(a) Air blast circuit breaker(b) Minimum oil circuit breaker(c) Bulk oil circuit breaker (d) Vaccume circuit breaker
Ans a91. The voltage across the circuit
breaker pole, after final current zero is
(a) Recovery voltage(b) Re-striking voltage(c) Supply voltage(d) None of these
Ans a92. Which of the following circuit
breaker does not use pneumatic operating mechanism
(a) Air blast circuit breaker(b) SF6 gas circuit breaker(c) Air blast circuit breaker(d) Bulk oil circuit breaker
Ans d93. Rutien tests are conductor on(a) Minimum oil circuit breaker(b) Air blast circuit breaker(c) Oil circuit breaker(d) All of the above
Ans d94. In modern E.H.V circuit
breaker the operating time between instant of receiving tripp single and final contect separation is of the order of
(a) .001 second(b) .015 second(c) .003 second(d) .03 second
Ans d95. The circuit breaker which have
high relabilty and negaligible maintenance
(a) Air blast circuit breaker(b) Minimum oil circuit breaker(c) SF6 gas circuit breaker(d) Bulk oil circuit breaker
Ans c96. For modern circuit breaker,
the time of closing the cycle is(a) .001 second(b) .1 second(c) .01 second(d) .003 second
Page 8
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
Ans c97. The arc voltage produced in
A.C circuit breaker is always(a) Leading the arc current by 900
(b) Lagging the arc current by 900
(c) In phase with the arc current(d) None of the above
Ans c98. The transient stability of
power system can be effectively improved by
(a) Excitation control (b) Phase shifting transformer(c) Single pole switching circuit
breaker(d) Increasing the turbine value
opening Ans c
99. Which of the circuit breaker is costly
(a) Air blast circuit breaker(b) SF6 gas circuit breaker(c) Minimum oil circuit breaker(d) None of these
Ans a100. The speed of circuit
instruption in forsed air blast circuit breaker is
(a) Slow(b) Fast(c) Medium(d) None of above
Ans c101. The fault current intrupted by
modern circuit breaker attain value as high as
(a) 10000 amp(b) 100000 amp(c) 60000 amp(d) None of above
Ans b102. In modern breaker at the time
fault current the temperature inside rise up to
(a) 30000 0C(b) 90000 0C(c) 60000 0C
(d) None Ans a
103. The circuit breaker of least design, are capable of intrupting current these condition with an arc duration of
(a) 5-20 mile second(b) 5-20 second(c) 5-20 minute(d) None of the above
Ans a104. A fuse blowns of by(a) Melting(b) Arcing(c) Burning(d) None of the above
Ans a105. A fuse operate on with effect
of electric current(a) Magnetic effect(b) Heating effect(c) Electrostatic effect(d) Photo electric effect
Ans c106. A delay fuse is generally used
for the protection of(a) 3 Q motor(b) Flourocent motor(c) G.l.S lamps(d) All the above
Ans a107. As compared to rewire able
fuse a H.R.C fuse has (a) High rupturing capacity(b) High speed of operation(c) No aging effect(d) All the above
Ans d108. A fuse wire made of which
material will have relatively sharp melting action
(a) Copper(b) Tin-lead-aloy(c) Silver(d) Aluminium
Page 9
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
Ans b109. A fuse should have(a) Low resistance and high melting
point(b) Low resistance and low melting
point(c) High resistance and high melting
point(d) High specific resistance and low
melting point Ans d
110. In H.R.C fuse major portion of heat generated is dissipated by
(a) Conduction(b) Radiation(c) Convention(d) None of above
Ans a111. Which fuse material is more
suspected to oxcidation as compare to the remaining
(a) Tin lead alloy(b) Copper(c) Silver(d) None
Ans b112. Protection by fuse is generally
not use beyond(a) 10 A(b) 25 A(c) 100 A(d) 250 A
Ans c113. Which of the following is used
in liquid fuse (a) Carbon tetra chloride(b) Sulphur hexa floride(c) Distilled water(d) Transformer oil
Ans a114. A fuse is never instated in (a) Phase lime(b) Positive of d.c circuit(c) Negative of d.c circuit (d) Neutral wire
Ans d
115. H.R.C fuse posses(a) Linear time current characteristic(b) Inverse time current
characteristic (c) Parabolic time current
characteristic(d) None of the above
Ans b116. H.R.C fuse can be used up to(a) 100 A(b) 33 KA(c) 1000 A(d) 330 KA
Ans c117. Under fault condition
information to the circuit breaker is provided by
(a) Rewire able fuse(b) Relay(c) H.R.C fuse(d) All the above
Ans c118. Out door type switch gear is
generally used for voltage beyond(a) 11 KV(b) 66 KV(c) 33 KV(d) 132 KV
Ans b119. A high speed circuit breaker
can compleat its operation time(a) 1 micro second(b) 1 mili second(c) 2-3 cycle of frequency (d) 4-8 cycle of frequency
Ans c120. The power factor of arc in a
circuit breaker is (a) 0 lagging(b) 0 leading(c) 0.8 lagging(d) Unity
Ans d121. The time instant from the
instant opening contact to the
Page 10
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
instant of extinction of arc is known as
(a) Arc clearance time(b) Break time(c) Arc duration time(d) None of the above
Ans a122. The time interval from the
instant of fault to the instant of energizing the trip coil is known as
(a) Arcing time(b) Breaking time(c) Operating(d) Protection time
Ans d123. The time interval from the
instant of energizing the trip coil to the instant of opening of the contacts is known as
(a) Arcing time(b) Operating time(c) Breaking time (d) Total clearing time
Ans b124. The time interval from the
instant of fault to the instant of extinction of arc is known as
(a) Clearing time(b) Making time(c) Break time(d) None of the above
Ans a125. The breaking capacity of 3 Q
circuit breaker is given by(a) Service voltage X rated
symmetrical current(b) 3 X service voltage X rated
symmetrical current(c) /3 X service voltage X rated
symmetrical current (d) None of these
Ans c126. Which of the following is not a
part of C.breaker(a) Explosion pot(b) Current T/F(c) Fixed and moving contacts(d) Operating machenism
Ans b127. Which of the following circuit
breaker the arc energy produced will be least
(a) Air blast circuit breaker(b) Minimum oil circuit breaker(c) Plane oil circuit breaker(d) Self generated pressure oil circuit
breaker Ans a
128. Air blast circuit breaker are used above
(a) 11 KV(b) 33 KV(c) 66 KV(d) 132 KV
Ans d128 A.In case of SF6 circuit
breaker the time of intruption is(a) 1 micro second(b) 3 mili second(c) 3 second(d) 3 cycle
Ans d129. Which of the following is not
true for SF6 gas (a) SF6 gas has insulation property(b) SF6 gas is not inflame able(c) SF6 gas is poisonous(d) SF6 gas is heavier than air
Ans c130. The dielectric strength of SF6
gas at atmospheric pressure is nearly
(a) Same as that of air(b) Less than that of air(c) 21/2 time that of air(d) 10 -15 time that of air
Ans c131. The circuit breaker for E.H.T
application is (a) Air blast circuit breaker(b) SF6 gas circuit breaker(c) Minimum oil circuit breaker(d) None of these
Ans b
Page 11
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
132. Relay can be design to change in
(a) Voltage (b) Lightning intensity(c) Current (d) Any of the above
Ans d133. The operating time for high
speed relay is usually (a) 1 second(b) 1 mili second(c) 1-2 cycle(d) 10-15 cycle
Ans c134. The operating of a distance
relay is based on the measurement of any of the following, expect
(a) Admittance(b) Impedance(c) Reactance(d) Frequency
Ans d135. The operating time of a relay
with inverse time characteristic could be
(a) 2-3 cycle(b) 5-10 mili second(c) 2-3 micro second(d) 5-10 second
Ans a136. A single phasing relay is used
on(a) Single phase motor(b) Universal motor(c) Three phase motor(d) Three phase motor
Ans c137. In distance relay the operating
depends upon(a) Voltage(b) Voltage to current ratio(c) Current(d) None of the above
Ans c
138. Which relay is used for protection protecting a T/F against frame leakage
(a) Directional relay(b) Intentanious earth fault relay(c) Intentanious over voltage relay(d) Intentanious over current relay
Ans b139. Translay relay is suitable for(a) Feeder(b) The welding T/F(c) Alternator(d) None of the above
Ans a140. Merg price protection relay is
used for(a) Air cooled T/F(b) Alternator(c) Short transmission line(d) Long transmission line
Ans b141. MHO relay is used for(a) Long transmission line(b) Feeder(c) Alternator(d) Transformer
Ans a142. The pilot relay is provided to
obtained(a) Pre-set tripping(b) Delayed tripping (c) High speed tripping(d) None of the above
Ans c143. For the protection of radial
feeder the relay used must have(a) Linear time characteristic(b) Inverse time characteristic(c) Extetion time characteristic (d) None of the above
Ans b144. Reactance relay are used for
phase fault in (a) Long transmission line(b) Medium transmission line (c) Short transmission line
Page 12
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
(d) All of the above Ans c
145. In induction type relay, torque is directly proportional to
(a) Current(b) /current(c) 1/current(d) Current2
Ans d146. The relay preffered for phase
fault along long transmission line is(a) Reactance relay(b) Impedance relay(c) MHO relay(d) Buchholze relay
Ans c147. Relay preffered for phase fault
along medium transmission line is(a) MHO relay(b) Buchholze relay(c) Impedance(d) Reactance relay
Ans c148. Relay generally used for
phase fault is(a) Distance relay(b) Induction relay(c) Over current relay(d) MHO relay
Ans a149. Which of the following is not a
distance relay (a) Reactance relay(b) Induction relay(c) Buchholze relay(d) MHO relay
Ans b150. Earth fault relay are,
invariable(a) Short operating time relay(b) Long operating time relay(c) Directional relay(d) Non-directional relay
Ans c
151. A thermal protection circuit provided protection against
(a) Over voltage(b) Short circuit(c) Over load(d) Temperature rise
Ans c152. A use of air core reactors is a
generally restricted up to(a) 1.1 KV(b) 3.3 KV(c) 11 KV(d) 132 KV
Ans c153. The used oil immersed
reactance is generally restricted up to
(a) 1.1 KV(b) 33 KV(c) 11 KV(d) There is no restricted of voltage
normally Ans d
154. The reactance for the protection of transmission line are connected in
(a) Series (b) Delta(c) Parallel(d) Star
Ans a155. Any voltage surge travlling on
the transmission line, will first enter in
(a) Switch gear(b) Current transformer(c) Circuit breaker(d) Lightning arrestor
Ans d156. A lightning arrestor is always
located(a) Before the isolator(b) Before the switch gear(c) Before the transformer (d) Before the current transformer
Ans c
Page 13
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
157. The main purpose of providing lightning arrestor in a sub-station is to protect
(a) Circuit breaker(b) Relay(c) Transformer(d) Civil-structure
Ans c158. Explution type lightning
arrestor are used with system having operating voltage up to
(a) 11 KV(b) 33 KV(c) 1.1 KV(d) None of the above
Ans c159. Which of the following needs
to protect a direct stock due to lightning
(a) Power station(b) Sub-station(c) Over head transmission line(d) All of the above
Ans d160. Which of the following system
suffer most from arcing ground(a) Solid ground neutral system(b) Insulated neutral system(c) Resistance ground neutral
system(d) Reactance ground neutral
system Ans b
161. Which section of power system generally suffer from more fault as compared to the remaining
(a) Generator (b) Transmission line(c) Transformer(d) Under ground cable
Ans c162. Least no. of fault reported for(a) Cable(b) Switch gear(c) Transformer(d) Transmission line
Ans a
163. Batteries are provided at sub-station mainly for
(a) Emergency lightning (b) Voltage regulation(c) Trip circuit(d) Meter movement
Ans c164. The gap lenth of rod type
surge divertor used for 132 KV line should be
(a) 10 cm(b) 50 cm(c) 15 cm(d) 65 cm
Ans d165. Wave trap is use to trap wave
of(a) Low frequency (b) Higher frequency (c) Power frequency (d) Micro wave frequency
Ans c166. When a transmission line is
energized the wave that propagates it is
(a) Current wave only(b) Voltage wave only(c) Current and voltage wave only(d) None of above
Ans c167. A circuit breaker is rated at
2000 amp 1500 MVA,33 KV 3 Q, OCB, then the making current is
(a) 1.2 KA(b) 67 KA(c) 26.25 KA(d) None of above
Ans c
Breaking capacity = 1500 MVA voltage = 33 KV breaking current = 1500 MVA/3X33 KV 103 = 26.25 KA Making current = 2.55 X breaking current
Page 14
OBJECTIVE ELECTRICAL ENGINEERING PROTECTION
= 2.55 X 26.25 =67 KA