Property of American Airlines
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
95
CHAPTER 3
Maintenance
3.1 Servicing
3.1.1 Introduction
This section contains instructions for Servicing, Inspecting and Preventive Maintenance on the GF10COMBO air conditioning unit.
To ensure that the unit is kept in correct operation condition, it must be inspected and maintainedon a regular basis. Proper cleaning on the air filter at recommended intervals will help in preventingdamage or failure of the unit, and provide optimum performance.
Overhaul Intervals: Under normal operating conditions and with proper preventive maintenancepractices, the GF10 COMBO will provide years of excellent service. Typically 20.000 to 30.000 hours(depending upon local conditions).
3.1.2 Refrigeration system
Refrigeration section access
Access door for the refrigeration section is located at right side of the unit.
WARNING!
WHEN WORKING WITH REFRIGERANTS, GOGGLES SHOULDALWAYS BE WORN. CONTACT WITH REFRIGERANT MAY CAUSE
INJURY.
S.A. LEBRUN - 13, rue Gerard - 7020 NIMY (Belgium), Phone : +32 65 403030, Fax : +32 65 3460 17, e-mail : [email protected] - Bank account number : IBAN : BE54 3700 1714 0997 - BIC :
BBRUBEBB - TVA : BE421.297.922 - registration number : 421.297.922/08.27.12
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Cannopy disassemblyFor some inspection or repair, it may be necessary to remove the polyester canopy following below
instructions:
(a) Dismounting air outlet
Dismount the 12 screws inside the air outlet.
Figure 3.1: Dismounting air outlet.
– 96 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(b) Dismounting canopy fixation right side
Open the door and dismount the 4 bolts on the bottom of the canopy
Figure 3.2: Dismounting canopy fixation - right side.
– 97 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(c) Dismounting air inlet grid
Figure 3.3: Dismounting air inlet grid
– 98 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(d) Dismounting canopy fixation - left side
Once the air grids are removed, dismount the 4 bolts on the bottom of the canopy.
Figure 3.4: Dismounting canopy fixation - left side.
– 99 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(e) Mounting lifting beam
To avoid breaking the canopy when lifting it, you have to use a proper lifting beam, havinghanging point at the vertical of canopy lifting points (see figure 3.5)
Figure 3.5: Mounting lifting beam
– 100 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(f) Lifting canopy
Figure 3.6: Lifting canopy
– 101 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(g) Full access to unit
Once the canopy is removed, you have full acces to every components.
Figure 3.7: Full access to unit.
– 102 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Refrigerant Leak Testing
A leak free system assures trouble system operation and performance. Loss of refrigerant willbe accompanied by reduced system efficiency and capacity. It will also cause repeated activation ofsystem safety monitors, shutting down the unit. Leak testing should be accomplished at scheduledintervals, and after any work has been accomplished on the unit.
Check the liquid line glass in order to control the flow of refrigerant and the humidity in the coolingcircuit.
If a leak has occurred, it may spread refrigerant throughout the interior of the unit, making locatingthe leak difficult. The interior of the unit should be aired prior to testing. When a leak is detectedbut you are unable to pinpoint the location, use compressed air to blow the area free of vapour, thenimmediately retest before the leaking vapour spreads.
Utilize a draft free area when leak testing to prevent the loss of vapour from small leaks. Insurethat the testing area is free of compressor oil, which may contain dissolved refrigerant, giving falsetest indications.
The testing method used here is the Electronic Leak Detector. This is the easiest method for leakdetection. Electronic leak detectors can be used in areas where an open flame is not permitted. Adetecting probe is passed over the area of a suspected leak. If a leak is present, the detector sounds ahigh frequency alarm or signals by a flashing light, depending on the model used.
Refrigerant leak repair
(a) Locate leak as described above.
(b) Using a refrigeration recovery system compatible with R134a, pump refrigerant from the systemand dispose.
(c) Replace drier if necessary, see sight glass for moisture indication.
(d) Correct leak as described below.
(e) If no leaks are present, pump out system and then evacuate system to at least 270 [Pa], holdfor 30 minutes. Break vacuum with nitrogen and raise system pressure to 0 to 0.34 bars. Re-evacuate system to 270 [Pa]. Repeat this for a total of three times, then charge the system withR134a.
WARNING!
ENSURE ADEQUATE VENTILATION DURING REPAIRS.PHOGENE GAS, A DEADLY POISON, IS GENERATED WHEN
REFRIGERANT IS EXPOSED TO FLAME.
– 103 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(f) Leak repair procedure :
• Thoroughly clean paint, dirt and oil film from adjacent piping. Use a wire brush, sandclothor sandpaper.
• Wrap nearby parts with water-soaked cloths to protect them from heat damage duringrepairs.
• If a solder joint requires repair, disassemble the joint and clean away any refrigerant oilwhich may be present. Oil traces will not allow a leak-proof solder repair to be made.After cleaning, reassemble the parts and solder.
• Solder repairs the leak. For copper to copper piping, use Lastek 34 (30% silver) typeL-AG30CD.
• Reassemble and tighten any connections previously loosened.
• If the plumbing system has been opened for repair, evacuate the system previously open toa vacuum of 405 [Pa]. Add dry nitrogen to raise pressure to 10,3 [bar].
• Open all previously closed valves.
• Perform a pressure check for leaks with foam products.
• If all leaks are repaired, evacuate system to 270 [Pa] at least three times.
Refrigerant charging
Charge procedure method:
Prior to starting, weigh the bottle of refrigerant to be used for charging, and record its weight.
(a) Using a recovery/charging unit, add approximately 10 kg of R134a to the cooling section thatwas repaired.
(b) Check all valves are open.
(c) Start the unit (compressor running).
(d) Charge the remainder of the refrigerant through the suction port until the liquid sight glassshows clear.
WARNING!
USE ONLY R134A REFRIGERANT. IF ANY OTHER TYPE OFREFRIGERANT IS USED, THE UNIT WILL NOT FUNCTION
PROPERLY.
– 104 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Moisture in a refrigerant system. Evacuation of moisture
The strainer/drier in the system is designed to remove particles and small amounts of moisturewhich may enter the system during minor servicing or fault conditions. Major moisture intrusionthrough fault or contamination may require complete system evacuation for moisture removal.
Moisture in a refrigerant system is directly or indirectly the real cause of more problems andcomplaints than all other causes combined. Moisture in a system can be classified as visible andinvisible. Rarely is liquid water found in a system, normally all intrusive moisture will be in the formof vapour. A single drop of moisture in a system can cause ”freeze-ups”’. Moisture can be picked upby the refrigerant and be transported through the lines as a fine mist, causing ice crystals to format the point of expansion (expansion valve). These ice crystals will retard or stop the flow of therefrigerant, causing a reduction or complete loss of cooling. As the expansion valve warms due to thelack of refrigerant, the ice melts and passes through the expansion valve. The moisture will then cyclethrough the system until it again returns to the expansion valve, and the cycle is repeated. The resultis intermittent cooling. Moisture can also cause corrosion, which can present serious problems, oftennot apparent until severe damage has occurred. Moisture, combined with refrigerants, can create acidswhich in turn greatly increase the corrosion of metals and copper plating.
Refrigerant oil has an attraction for moisture and will absorb it rapidly if left open to the atmo-sphere. Water formed acids mix with refrigerant oil, the two forming a closely bonded mixture offine globules. The effect is called ”sludging”’ and greatly reduces the lubricating ability of the oil.The corrosion caused by the presence of this moisture in the form of ”sludge”’ can plug fine strainers,expansion valves and capillary tubes. Because it usually contains acids, sludge will corrode whateverit clings to, accelerating system damage. It is imperative that only fresh oil from unopened containersbe used. Previously opened oil provides too great a danger of system moisture intrusion.
The most effective means in removing moisture from a system is to utilize a high (deep) vacuumpump. A high vacuum pump is capable of removing all moisture from a hermetic system by reducinginternal system pressures to the boiling point of water at normal temperatures. The vacuum pumpdoes not ”suck out”’ the liquid moisture, but rather causes it to boil into a vapour state at which timeit can be harmlessly removed from the system and exhausted through the vacuum pump.
The ideal vacuum pump should evacuate the system to at least 500 microns, and must also becapable of holding that vacuum throughout the dehydration process. It must pull that vacuum onthe entire system and not simply at the intake of the pump. This pump is able to remove moistureat an ambient temperature of 26oC or over. The adequate pump to be used for this cooling system ismentioned in the Support Test Equipement section.
– 105 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.1.3 Air handling system
Air Filter - Cleaning Instruction
Regularly, you have to clean the filters according to the instructions below.
(a) Dismounting the air inlet grid
Figure 3.8: Inlet grid Figure 3.9: Grid dismounted
Once the grid is removed you get access to the prefilters
Figure 3.10: Prefilters
– 106 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
(b) Taking out the prefilters
• Unlock and open the hooks at the four corners of each filter
Figure 3.11: Unlocking hook Figure 3.12: Opening hook
• Pull the prefilter out of the frame, you get access to the filter behind
Figure 3.13: Pulling out prefilter Figure 3.14: Filter
– 107 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
• Pull the filter out of the frame
Figure 3.15: Pulling out filter
• Repeat those operations for the other prefilters and filters
(c) Cleaning the filters.
• When the filters are dismounted, blow some compressed air through the filter in the oppositedirection of the air flow in operation
• Clean-up the remaining dusts on the air inlet face with a vacuum-cleaner.
3.2 Maintenance Schedule
3.2.1 Consumable Materials
The table below indicates the list of consumable materials requested to perform good servicing of theGF10 COMBO .
Drier filter
1 x 848CM. (ref: 2863950)
Air filters
2 x PreFiltres (1750011)2 x Filtres (1750010)
Table 3.1: Consumable material
– 108 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.2.2 Support Test Equipment Required
The equipments listed below are required to perform an adequate maintenance and inspection of theGF10 COMBO :
Connection - PLC TELEMECANIQUE
(Automaton)Software SoMachine (Vers.3.1)Communication cable USB Type A to USB Mini
Connection - TELEMECANIQUE Display
Software Vijeo DesignerCommunication cable ETHERNET TCP/IP
Outils pour installation de refroidissement
Vacuum pump ITE MK 162DSManifold 4 V - ITE 2804 BC + connectionRatchet spanner TOTALINE 127 CVacuum meter REFCO DV-150Multimeter (current, voltage, frequency)Thermometer
Table 3.2: Support test equipments
– 109 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.2.3 Inspection
The following pages are provided as guidance to establish a proper service schedule. This periodicpreventive maintenance inspection schedule should be established and maintained. The followingschedule meets the minimum requirements necessary to ensure safe reliable service under normaloperating conditions. It may be modified as required to meet varying operating and environmentalconditions.
WARNING!
EXTREME CAUTION MUST BE USED WHILE MAKING SERVICEINSPECTIONS WITHIN THE UNIT. NEVER SERVICE THE UNIT ALONE.
SWITCH OFF THE GROUND SWITCH BEFORE PERFORMING ANYMAINTENANCE OPERATION. FAILURE TO FOLLOW THIS PRECAUTION
COULD RESULT IN SERIOUS INJURY OR DEATH.
Contact the Guinault customer service to obtain the reference, products, replacement procedureor maintenance of pieces relating to :
• The general structure
• The control panel
• The alternator
Guinault customer service:
Tel : +33 2 38 63 84 00Fax : +33 2 38 76 97 64E-mail : [email protected]
Otherwise, contact Lebrun customer service:
Tel : +32 65 40 30 30Fax : +32 65 34 60 17E-mail : [email protected]
– 110 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Figure 3.16: Diesel Engine
Daily
• Diesel Engine
– Check and fill if necessary the lube oil (see 1 on figure 3.16)
– Check the coolant liquid level (see 2 on figure 3.16)
– Check for leaks
– Check the engine dry/suction air filter (see 3 on figure 3.16)
• Unit
– Check the general wear.
– Check drawbar handling, its braking and locking pedal.
– Check the no copper is visible on the cables.
– Check that the plug terminals are not damage or corroded
– Check that the indicator lights of the operating unit come on when the ignition is switchedon.
– Clean the reflectors
– About cooling liquid, consult the engine documentation.
After every 200 operating hours
Cleaning of the unit outdoor prefilters with compressed air and with a vacuum cleaner (see figure3.10 in chapter 3.1.3).
– 111 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
• Check the temperatures and pressures against what reported on the machine history logbook.
• Check oil level of the compressor
• control bolts tightening
• Visual inspection if the status of cable insulation.
• The oil level in the compressors (while in operation) (see figure 3.17). If the level is low, checkingwill be made again 3 to 4 hours later.
After every 500 operating hours
The electrical safeguards should be checked every 500 hours.
• Cleaning or eventual replacement of unit outdoor filters (see figure 3.9 and chapter 3.1.3).
• Change the lube oil of the engine (see 1 on figure 3.16)
• Replace the oil filter cartridge of the engine (see 4 on figure 3.16)
• Inspection:
– The general aspect of the compressors (see figure 3.17) .
– The presence of refrigerant in the sightglass (after +/- 30 minutes of continuous operation).
– The lack of foam in the oil crankcase (see 1 on figure 3.17).
– The good state of the steelcasing, paint, hinges, door handles, wheels, etc...
– The presence of traces of unusual humidity under the unit.
– The cleanness of the condenser with eventual cleaning.
Figure 3.17: Compressor elements
– 112 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
• Measure:
– The working temperatures (ambience, outlet of supplied air, inside the unit).
– The air pressure.
– The voltage on the terminal block of each battery with a multimeter. If voltages are lowerthan 10,6 V, replace them.
• Check:
– The working state of control and visual devices
– Check the air inlets and outputs on the rear bodywork, clean if necessary.
– Check the mechanical strength of the reflectors and beacons.
– Control panel:
∗ LEDs,
∗ Shut-off contactor,
∗ Refrigerating and ventilation test.
– The operation of the crankcase heater.
– The proper functionning of the drainage.
– Clean and grease the battery lugs (Open the battery cut-off switch for this operation).
– Check the V-belt of the motor (tighten or replace if necessary)
– Check the starter connections, battery charging alternator connections, the engine’s varioussensors connections.
– Check hose attachment.
– Check that the fuse holder terminal blocks, contactors and the rectifier are in good condi-tion, tighten the connections and fixations if necessary.
– Check that the bundles are correctly connected to the control panel
– Check the board connectors are properly connected.
– Check the 400Hz and 28VDC unit contactors when the generator is at rated speed.
• Electrical safeguards:
– Activate the start-up cycle.
– Place a multimeter on the 400 Hz plug output and turn on the power switch.
– Measure the voltage
– Move the RS525’s P9 potentiometer to trigger the 400 Hz over and under-voltage safeguards(reposition the potentiometer in its original position between each triggering operation).
– Adjust the voltage to its original value.
• Engine safeguards:
– Contact Guinault customer services
– 113 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
CAUTION!
THE DISCHARGE OF CONDENSATES IS ONLY ALLOWED IF THE INNERPRESSURE IS ABOVE +/- 10 [mBAR].
After every 1000 operating hours or twice a year
• Diesel engine
– Replacement of the fuel filter and pre-filter cartridge (see 5 & 6 on figure 3.16)
– Cleaning of the radiator (drain lube oil/condensate)
– Check the flexible fuel leakage lines
– Check the battery and cable connections
– Check the preheating plug
– Check the monitoring, warning system
– Check the fixings, hose connections(renew if damaged)
– Check the cooling system bearings (rubber and retaining elements)
• Towbar
– Check the manoeuvrability. If necessary, apply 10g of grease to the drawbar axle, 10 to 20gon the cables and the parts that rub cables and on the Capstan joint.
– Check the braking system.
– To adjust: In the high and low position, release the lock-nuts and tighten the cable toobtain effective braking. After adjustment, check that the brake is free when 8 to 10 cmabove the stop in the low position.
• Alternator
– Check the alternator grilles are not blocked, clean with dry air.
– Check the installation of the terminal board and the electrical connections.
• Cooling system and accessories
– Dry clean the engine cooling system and its accessories.
• Current safeguards:
– Use a three-phase load bank and check the 400 Hz distribution cable’s permissible overload.
– Use a Resistive load bank and check different overload points (consult the monitoringcurves).
After every 5000 operating hours
• Pump out and clean the fuel tank
– 114 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
After every 10000 operating hours
• Replacement of the oil and oil filter of the compressor
• Replacement of 400Hz alternator bearing
Once a year
• Performance tests of the unit in ”cooling”’ working modes.
• Tests and adjustments of the different safety devices on the unit.
– Refrigeration part:
∗ HP/BP pressostat (see PSL and PSH1 on figure 3.17),
– Aerodynamic part:
∗ Safety pressostat (see PSH3 on figure 3.17),
• Checking of the absorbed powers.
• Checking of the condenser’s fan.
• Checking of the capacity regulation valve working order.
• Checking of the cooling system of the engine
• Checking of the exhaust system of the engine
• Cleaning of the air filter of the engine
• Replacement of the battery
• Cleaning of the fuel filter and replacement if necessary
• Replacement of the dehydrator filter (see 6 on figure 3.17).
• Control the charge of refrigerant and adapt the complementary charge.
• Greasing of the steering axles at the front of the unit.
• Greasing of the brake system and checking of its good working order.
• General inspection of:
– The air handling unit (presence of humidity, air leakage, bad fixings, ...),
– The fixings of the refrigeration piping,
– The piping insulation,
– The correct fixings of temperature sensors,
– The fixings of side panels,
– The good state of the panels acoustic insulation,
– The detection of any trace of rust,
– 115 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– The eventual presence of refrigerant leakage,
– The cleaning of the electrical brushes,
– The eventual tightening of terminals.
CAUTION!
PRESENCE OF ANY MAGNETIC DEVICE NEAR THE PLC MUST BE AVOIDED.
– 116 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.2.4 Electronic board replacement procedure
All board replacement operations are performed with the battery cut-off switch open.
RS678: Relay (Electrical cabinet)
• Make sure the battery cut-off switch is open (no voltage on B1)
• Replace the fuse(s) if the fault has been identified and put the unit into service.
• If the board must be replaced, unscrew the cable bundle mounted on the B1 terminal with aNo. 8 spanner.
• Check that the cables are clearly identified.
• Disconnect the boards by grasping the connector and not the cable bundle.
• Unscrew the 4 mounting screws.
• Remove then replace the board, taking care to use the dedicated screws and nuts.
• Reconnect the connectors, screw the cable to the B1. Fix tightly to ensure a good connection.
• Close the battery cut-off switch and return to service.
– 117 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
RS525: 200V / 400Hz Regulator (Electrical cabinet)
• Make sure the battery cut-off switch is open.
• Disconnect the XB5 connector by grasping the connector, and not the cable bundle.
• Using a No. 8 spanner, unscrew the 3 mounting screws on the metal case.
• Remove and replace the board.
• Screw the board onto the cabinet.
• Reconnect the XB5 connector and return to service. Fix tightly to ensure a good connection.
– 118 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
RS944 : Sequencer (Electrical cabinet)
handling
The RS944 digital board must be handled with care. It will be packaged in anantistatic bag. The operator must avoid touching the components. It is prohibited to
manipulate the board before being electrically discharged by touching a ground point.
• Make sure the battery cut-off switch is open.
• Disconnect all connectors by grasping the connector and not the cable bundle.
• Using a No. 8 spanner, unscrew the 3 mounting screws on the metal case.
• Remove and replace the board.
• Screw the board onto the cabinet.
• Reconnect all the connectors and return to service. Fix tightly to ensure a good connection.
– 119 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.2.5 Maintenance Table of the cooling unit
We recommend you to maintain the unit according tothese guidelines and frequencies. The number of oper-ating hours refer to average market conditions. Otherfrequencies and hours may be applicable depending onenvironmental conditions and other market data. Inthis case, please contact Guinault-Lebrun .
Eve
ry200
hou
rsor
wee
kly
Eve
ry500
hou
rsor
twic
ea
year
Ev e
ry4000
hou
rsor
twic
ea
year
Ev e
ry8000
hou
rsor
on
cea
year
THE COMPRESSOR
Check the oil •Check the general aspect •Check the refrigerant charge •Check the operating data •Check the protection devices and all compressor moni-toring parts
•
Check electrical cable connections on tight fitting •Check the tightening torques •Perform a tightness test •Update date protocol •THE ELECTRICAL MOTORS
Initial Inspection (Only once) •Regreasing See lubricant plate
Permanent lubrication (with coupling output) •Cleaning Depending on degree of local fooling
Main inspection After the first 16000 h or after 2 years
GENERAL INSPECTION
Clean the outdoor prefilters •Clean the outdoor filters (replace if necessary) •The lack of foam in the oil crankcase •The air handling unit :- presence or trace of humidity •- air leakage, bad fixings, etc... •The cleanness of the condenser. Clean if necessary. •The good state (paint, trace of rust, fixing,...) of the sideand acoustic insulation panels, the steelcasing, the doorhandels, the hinges, the wheels, etc...
• •
The tightening of terminals if necessary •The replacement of the safeguard battery in the PLC •The cleaning of the 3 electrical panels •
continued on next page
– 120 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
continued from previous page
Eve
ry200
hou
rsor
wee
kly
Eve
ry500
hou
rsor
twic
ea
year
Ev e
ry4000
hou
rsor
twic
ea
year
Eve
ry8000
hou
rsor
on
cea
year
Greasing of the steering axles at the front of the unit andof the brake system + checking of its good working order
•
Fixings and insulations of the piping •Presence of refrigerant leakage •The correct fixing of temperature sensors •Replacement of the dehydrator filter •TESTS
The working state of control and visual devices •Checking of the condenser’s 2 fans •Checking of the control panel :- Shut-off contactor •- Refrigerating and ventilation test •- Leds •Measuring of the working temperatures (ambiance, outletof supplied air, inside the unit)
•
Measuring of the number of operating hours •Measuring of the air pressure •Checking of the correct working of the water discharge •Checking of the good working of the crankcase resistance •Tests and adjustments of the different safety devices onthe unit- Refrigeration part: HP/BP pressure switch •- Aerolic part: Safety pressure switch •Performance tests of the unit in ”cooling” working modes •Checking of the absorbed powers •
Table 3.3: Cooling unit maintenance planning
– 121 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.2.6 Maintenance Table of the internal generator
For maintenance and inspection of the engine, it is necessary to refer to instruction manual of theengine prevailing on following tables. The general maintenance of the unit consist to execute periodicoperations on substantive bodies. Operations to execute are defined according to the hours of operationand are summarized in tables below.
ALL INTERVENTION on the engine beam, open cover, spinningmotor, is prohibited to any person not qualified.
INTERNAL WASHING OF THE GROUP WITH A PRESSUREWASHER IS NOT ALLOWED.
Please find here after the maintenance operationsto be carried out on the engine. It is necessary torefer to the engine manufacturer maintenance man-ual,supplied with the ACU. The following panels,issued by Guinault-Lebrun , can not replace theengine manuals.
Eve
ry10
hou
rsor
dai
ly
Eve
ry50
0h
ours
Eve
ry10
00h
ours
orye
arly
Eve
ry20
00h
ours
orev
ery
two
yea
rs
Eve
ry45
00h
ours
Dep
end
son
nee
ds
THE ENGINE
Check engine oil level •Check coolant liquid level •Check fuel filter •Replace engine oil and oil filter •Replace fuel filter •Check crankcase vent filter •Check Radiator support & engine shock absorbers(to be replaced if deteriorated) •Check electrical wiring •Replace air filter •Check the belt tension (1) •Check the cooling circuit •Check the engine intake system •Replace crankcase vent filter •Check the crankshaft damper •Check the engine speed •Replace the coolant liquid •Check the valve clearance •Replace the crankshaft vibration damper •Clean or replace air filter cartridge (2) •
continued on next page
– 122 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
continued from previous page
Eve
ry10
hou
rsor
dail
y
Eve
ry500
hou
rs
Eve
ry1000
hou
rsor
yearl
y
Eve
ry2000
hou
rsor
ever
ytw
oyea
r
Eve
ry4500
hou
rs
Dep
end
son
nee
ds
Replace fan or alternator belt •Check the injectors •Check the exhaust pipe •Check the preheating resistance •Visual control of engine leak • •Control the water hose fixation •Test bench at rated load during 1h •Clean the turbocharger •Adjusting of rocker arms play •Draining water from the fuel prefilter •Draining water from the fuel tank •Clean the radiator • •
Table 3.4: Internal generator maintenance planning
Note:
• (1): During the running in period (first 50 hours), check daily the tension of the belts.
• (2): Air filter replacement depends on surrounding conditions (dust, ...)
• After first 100 hours, replace engine oil and oil filter.
– 123 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.3 Troubleshooting
3.3.1 General
This section contains troubleshooting information to assist, to locate and to correct operating troubleswhich may develop in the unit. Each malfunction for an individual component, unit or system isfollowed by a list of tests or inspections which will help the technician to determine probable causesand corrective action to take.
The test/inspections and corrective actions should be performed in the order listed. Troubleshoot-ing is a logical and systematic process of determining and correcting the cause of a malfunction. Theprocess begins with verification of the malfunction. This may often involve an operational check-outof the unit. After the trouble has been verified, identify all components in the circuit whose failurecould cause the symptoms observed during the operational check-out. The technician should start bychecking those items which are highest in probability of causing the problem. Inspect and test eachcomponent, until the exact cause of the problem is determined and corrected.
WARNING!
USE EXTREME CARE TO AVOID CONTACT WITH HIGH VOLTAGELEADS AT ALL TIMES. REMOVE ALL JEWELRY, SUCH AS RINGS,
WATCHES, CHAINS, ETC..., THAT COULD COME INTO CONTACT WITHEXPOSED LEADS AND WIRES. FAILURE TO COMPLY MAY RESULT IN
SEVIER ELECTRICAL SHOCK OR DEATH, AND/OR CAUSE DAMAGE TOEQUIPMENT.
WARNING!
EAR PROTECTION DEVICES MUST BE WORN WHEN IN THEIMMEDIATE VICINITY OF THIS UNIT DURING OPERATION. REPEATEDEXPOSURE TO HAZARDOUS NOISE CAN CAUSE PERMANENT HEARING
LOSS.
WARNING!
REFRIGERANTS, OILS AND OTHER PRODUCTS CAN READILY BEABSORBED THROUGH THE SKIN AND INTO THE BLOOD STREAM.
WASH IMMEDIATELY AFTER COMING INTO CONTACT WITH THESEPRODUCTS.
– 124 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.3.2 Fault Indication
Fault display
• At the time of the occurrence of a GPU or engine fault, the following symbol flashes:
• Press this symbol to access the fault history:
Figure 3.18: GPU fault screen display
The color advise on the fault status:
RED = Fault active (ongoing)ORANGE = Warning active (ongoing)GREEN = fault/warning non-active
– 125 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
• In the case of engine faults, pressing on the error message allows access to the next screen inorder to get the SPN/FMI code:
Figure 3.19: SPN / FMI code
• Below the main faults, their consequences and the required actions for recommissioning:
400Hz DISTRIBUTION
Fault descriptionon the display
Faultwarn-inglight
Generatorstatus
Action
400 Hz over-voltagefault
Solid Enginestopped
Press Reset, restart the start-up cycle,
400 Hz under-voltagefault
Check the voltage on the display
400 Hz over-frequency fault
Solid Enginestopped
Press Reset, restart the start-up cycle,
400 Hz under-frequency fault
Check the frequency on the display
400 Hz over-amperage
Solid Engine notstopped
Press Reset, activate distribution
By-pass active EF Flashing X
– 126 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
28VDC DISTRIBUTION
Fault description onthe display
Start-Resetindi-catorlight
Generatorstatus
Action
28VDC over-voltagefault
Solid Engine notstopped
Press Reset, activate distribution
28VDC under-voltagefault
28VDC over-amperagefault
Solid Engine notstopped
Press Reset, activate distribution
28VDC rectifier fault Solid Engine notstopped
Wait 10 minutes, press Reset, acti-vate distribution
By-pass active EF Flashing X
OTHER:
Fault description onthe display
Start-Resetindi-catorlight
Generatorstatus
Action
Start-up failure Solid Enginestopped
Press Reset, restart the start-up cy-cle After several attempts, contactSAV Guinault
Fuses input rectifier600V
Solid Enginestopped
Check the condition of the fuses Q1and Q2. Press Reset, restart thestart-up cycle.
Low fuel level (enginestopped)
Solid Enginestopped
Fill the tank > 50%. Restart thestart-up cycle
Low fuel level Solid Engine notstopped
Stop the engine as soon as possible.Top up fuel. Restart the start-upcycle
Rectifier overheating600V (engine stopped)
Solid Enginestopped
Wait for the cooling of the 600V rec-tifier. Press Reset, restart the start-up cycle
Rectifier overheating600V (PCA stopped)
Solid Engine notstopped
Wait for the cooling of the 600V rec-tifier. Press Reset, restart air con-ditioning
Engine overheating(400Hz/28VDC OFF)
Solid Engine notstopped
Wait for the engine to cool. PressReset Restart the 400Hz or 28Vdcgeneration.
Engine overheating(PCA OFF)
Solid Engine notstopped
Wait for the engine to cool. PressReset Restart the air conditioning.
– 127 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Contact the engine manufacturer for all SPN/IMF codes
MOTOR
Fault description onthe display
Start-Resetindi-catorlight
Generatorstatus
Action
Oil pressure Solid Enginestopped
Check the oil level, check for leaks,check the condition of the oil circuit,press Reset, restart the start-up cy-cle
Engine temperature Solid Enginestopped
Let cool, check water level, checkfor leaks, check the coolant circuit,restart the start-up cycle
Low water level Solid Enginestopped
Let cool, check the coolant circuit,top up the water, restart the start-up cycle
Clogged air filter Solid Enginestoppedr
Check the condition of the filter,restart the start-up cycle
Oil level Solid Enginestopped
Check oil level, check for leaks, pressReset, restart the start-up cycle
Presence of water in fuel Solid Enginestopped
Remove the water using a diesel pre-filter
SPN Unknown Solid Enginestopped
Press the message to access theSPN/FMI. Correct the problem.Press Reset, restart the start-up cy-cle
1st low fuel level thresh-old (20%)
Solid Fuel levelalert light
None, the group can continue to op-erate
2nd low fuel levelthreshold (5%)
Solid Fuel levelalert light,Enginestopped
Restart is prevented. Add morethan 50% of the fuel capacity.Restart the start-up cycle
The total disconnection of the ignition may sometimes be necessary to allow the resetting of afaulty engine:
– Switch off the ignition
– Switch on the ignition
– Press Reset
– Restart the start-up cycle
– 128 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
ELECTRIC
Fault description onthe display
Start-Resetindi-catorlight
Generatorstatus
Action
Battery charging alter-nator fault
Solid Enginestopped
Press Reset, restart the start-up cy-cle
Help diagrams
5 possible types of malfunction are explained below:
• SITUATION 1 : Power-up faultSTOP-ON-START switch in the ON position: nothing happens.
• SITUATION 2 : Starting faultThe message ”Waiting for start” is displayed. After having put the STOP-ON-START switchin the START position, the engine does not start.
• SITUATION 3 : Engine faultThe unit is operating. Problem: the generator stops, the FAULT indicator comes on, an enginefault is indicated on the display
• SITUATION 4 : 400Hz distribution faultThe unit is operating. Problem: the unit stops or continues to operate, the FAULT indicatorcomes on, a 400Hz distribution fault is shown on the display. Do not rearm.
• SITUATION 5 : 28V distribution faultUnit generating 28V Problem: the FAULT indicator illuminates, the 28V contactor opens, a28V distribution fault is shown on the display, the engine continues to run.
RECOMMENDATIONS
Please contact GUINAULT Customer Service for all repair work. Ensure that these problems arenot caused by an engine fault (please refer to the engine owner’s manual supplied with the unit). Ifan electronic card needs to be changed, please contact Guinault Customer Service for its testing orrepair. In case of engine failure (loss of power, malfunction), refer to the engine operating manual.Whatever the problem, it must be addressed by a highly skilled technician.
ALL REPAIR WORK on the engine beam, open body, runningengine, is prohibited for all non-qualified people.
Materials needed:
• Set of mechanic tools
– 129 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
• Universal multimeter
• Set of electrical tools
Take all necessary precautions, and locate the various elements before performing any maintenanceon the group.
BEFORE STARTING ANY WORK ON THE UNIT; DISCONNECTTHE BATTERIES.
– 130 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
SITUATION 1 : Power-up faultSTOP / ON / START switch at the ON position: Nothing happens
– 131 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
SITUATION 2 : The engine will not startThe STOP-ON-START warning light is switched on after the voltage is switched on, the display
indicates ”Waiting for start”. Once the switch is in the START position, the engine does not start.
– 132 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
SITUATION 3 : Engine faultThe unit is operating.Problem: The unit stops, an engine fault appears on the screen (type SPN/FMI)
– 133 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– 134 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– 135 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
SITUATION 4 : 400Hz faultThe unit has started, its no-load voltage is 200V (P/P)/400Hz, 400Hz distribution is active.
Problem: The 400Hz distribution stops and the unit stops (1) or the unit works (2)
Under and over-voltage faults can occur during operating cycles.
– 136 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– 137 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– 138 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
SITUATION 5 : 28V distribution faultUnit generating 28V Problem: Opening of the switch 28V, the distribution indicator is turned off,
the ”default” indicator illuminates.
Under and over voltage faults can occur during the authorisedoperating cycles (strong load impact (under voltage) orload shedding
(over voltage)). Check the condition of the 28V current limiter.
– 139 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
– 140 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
3.3.3 Troubleshooting chart
Default on the MRS16 display
When a default occurs with the engine, the ”ENGINE FAILURE” red lamp of the operating stationlights on. In order to identify the code corresponding to the current problem, the user must consultthe alarm menu of the MRS 16 display (figure 3.20). If a ”Wrn ECu Alarm” occurs on the alarm list,the user must consult the ECU Alarm list menu.
Figure 3.20: MRS 16 Engine Monitoring System
Based on the code, the user must go to the corresponding board in the troubleshooting chart. Onevery board, information is presented in three categories:
• Cause
• Type
• Solution
When it is appropriate, the solution is presented through a tree. When the problem is solved, resetthe MRS 16 (reset button on the electrical cabinetof the engine).
– 141 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Table 3.5: Troubleshooting chart for engine failure
Eng Cool Temp Wrn
CAUSE: High water temperature, engine too hot
TYPE: Engine default causing a stop
SOLUTION: - Turn off the general start button.- Wait for the refreshing of the engine.- Control the level of cooling liquid in the tank.- Retry to start.- Check if the fan of the radiator is working.
Oil Press Wrn
CAUSE: Oil pressure is smaller than Wrn Oil press setpoint.
TYPE: Warning
SOLUTION: - Control the oil level.- Control the pressostat.- If necessary, reload oil.
Oil Press Sd
CAUSE: Oil pressure is smaller than Sd Oil press setpoint.
TYPE: Engine default causing a stop
SOLUTION: See Oil Press Wrn.
Eng Cool Temp Sd
CAUSE: Water temperature is greater than Sd Water temp.
TYPE: Engine default causing a stop.
SOLUTION: - Turn off the general start button.- Wait for the refreshing of the engine.- Control the level of liquid cooling in the tank.- Retry to start.- Check if the fan of the radiator is working.
– 142 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Fuel level Wrn
CAUSE: Fuel level is smaller than Wrn fuel level setpoint (25%).
TYPE: Warning
SOLUTION: Refill the tank if necessary.
Fuel level Sd
CAUSE: Fuel level is smaller than Sd fuel level setpoint (10%).
TYPE: Shutdown
SOLUTION: Refill the tank if necessary.
Battery voltage <,>
CAUSE: Battery voltage is out of limits given by Batt overvolt and Batt un-dervolt setpoints.
TYPE: Warning
SOLUTION: - Check the alternator of the engine.- Check the main features of the battery.- Reload if necessary.- Retry to start.
Battery flat Sd
CAUSE: If the controller switches off during starting sequence due to badbattery condition, it doesn’t try to start again and activates thisprotection.
TYPE: Engine default causing a stop.
SOLUTION: See Battery voltage
Start failed
CAUSE: Gen-set start failed.
TYPE: Engine default causing a stop.
SOLUTION: Check the alternator.
– 143 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
EmergencyStop Sd
CAUSE: If the input Emergency stop is opened, shutdown is immediately ac-tivated.
TYPE: Engine default causing a stop.
SOLUTION: - Turn off the general start button.- Control all the securities before disengaging emergency button.- Retry yo start and check all the unit.
ChrgAlternFail Wrn
CAUSE: Failure of the alternator for charging the battery.
TYPE: Warning
SOLUTION: - Check the alternator.- Check the battery.- Check the wires.
Air Filter Sd
CAUSE: The air pressostat of the engine filter switched on.
TYPE: Engine default causing a stop
SOLUTION: - Remove filter for cleaning or replacement.- Check the wires.
Water in Fuel
CAUSE: Water presence in fuel filter.
TYPE: Engine default causing a stop.
SOLUTION: - Drain the fuel filter.- Check the wires.
Coolant Level
CAUSE: The coolant level sensor switched on.
TYPE: Engine default causing a stop.
SOLUTION: - Control the level liquid in the radiator and reload.- Check the wires.
– 144 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Default on the PLC display
This section presents the required solutions when the ”AIR SUPPLY FAILURE” lamp lights on. Onevery board of the table 3.6, information is presented through three categories:
• Cause
• Type
• Solution
When it is appropriate, the solution is presented through a tree. When the problem is solved, resetthe PLC (Reset/Maintenance button).
– 145 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Table 3.6: Troubleshooting chart for unit failures
D001
CAUSE: Failure comes from the speed controller of the blower SC1
TYPE: Stop of the unit in all mode
SOLUTION: look at the alarme on the speed controller by the PLC display (SeeChapter 2)
.
D002
CAUSE: Failure comes from the PTC probe
TYPE: Stop of the unit in all mode
SOLUTION: - Wait until the temperature inside the unit goes down.- Restart the unit.- If the default occurs again, contact Guinault-Lebrun
– 146 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D003
CAUSE: The air pressure switch (PSH3) switched on
TYPE: Stop of the unit in all mode
SOLUTION:
Is the air pressureswitch activated onthe speed controllerscreen on the PLC ?
The default is fixed. Reset thePLC with the maintenancebutton and reboot the unitin the selected mode. Checkif the default occurs again
and in which condition.
YES
Is cable 53 well connectedaccording to the Guinault-
Lebrun drawing andis it in a good state?
Check the wiring atthe terminal number
12 and 18 of the speedcontroller SC 1. If the
problem goes on, contactGuinault-Lebrun .
YE
S
Connect the ca-ble correctly and
replace it, if needed.
NO
NO
– 147 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D004
CAUSE: The circuit breaker QD1 switched off (blower protection device).
TYPE: Stop of the unit in all mode
SOLUTION:
Did the circuit breakerQD1 switched off?
Reset the circuit breaker.Reset thePLC. Restart the group measuring
the current value consumed bythe frequency driver (after thecircuit breaker).If the problem
goes on, contact Guinault-Lebrun .
YES
Is the auxiliary contact on the circuitbreaker QD1 working properly? (mea-
sure with a ohm-meter, off power)
Check the wiringof the PLC card
DM72F0, terminal11. If the problemgoes on, contact
Guinault-Lebrun .
YE
S
Replace theauxiliary
contact of thecircuit breaker.
NO
NO
D005
CAUSE: The PLC did not receive the information that the speed controllerSC1 started even though it asked for it.
TYPE: Stop of the unit in all mode
SOLUTION:
Is speed controller under power?
Start the unit in ventilationmode. Check the proper work-
ing of CAN communication BUS(contact Guinault-Lebrun )
YES
Check the circuit breakerQD1. If the problem goes on,
contact Guinault-Lebrun .
NO
– 148 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D009
CAUSE: The PLC detected a default on the Danfoss regulator (AKCC750).
TYPE: Stop of the unit in cooling mode
SOLUTION:
Is light n°5 of thefirst DM72FO card
of the PLC on?
The default disappeared.Reset the PLC with the
maintenance buttonand restart the unit
in the selection mode.Check if the default
comes back and underwhich circumstances.
YES
Check if the contacton the terminals 39
and 41 of the regulatorAKCC750 is openen.
Default of theAKCC750.
Check the pres-sure sensor PT3.
Check for over heating.Check the expansionvalves EV5, 6 and 7(adjust if necessary).
YE
S
Check the wiringbetween the PLCand the AKCC750
regulator at theterminals 39 and 41of the regulator. Is
there a problem there?
Correctthe wiring.
YE
S
Check the wiringof the PLC card
DM72FO. Ifthe problem
goes on, contactGuinault-Lebrun .
NO
NO
NO
– 149 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D010
CAUSE: One of the circuit breaker QM2A or QM2B switched off (compressorprotection device).
TYPE: Stop of the unit in cooling mode
SOLUTION:
Did the circuitbreaker QM2A or
QM2B switched off?
Reset the circuit breaker.Reset the PLC.
Restart the group measur-ing the current value con-
sumed by the frequency driver(after the circuit breaker).
If the problem goes on, con-tact Guinault-Lebrun .
YES
Is the auxiliary contact on thecircuit breaker QM2A or QM2B
working properly? (measurewith a ohm-meter, off power)
Check the wiringof the PLC card
DM72F0, terminal21. If the problemgoes on, contact
Guinault-Lebrun .
YE
S
Replace the aux-iliary contact of
the circuit breaker.
NO
NO
D011
CAUSE: The PLC detected a shortage of compressor oil.
TYPE: Stop of the unit in cooling mode
SOLUTION: - Reset the unit.- Check the auxiliary contacts of the contactors.- Control the oil level through the sightglass on the compressor.- Fill up if necessary.
– 150 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D012
CAUSE: The PLC did not receive the information that the compressor con-tactors started even though it commanded it.
TYPE: Stop of the unit in cooling mode
SOLUTION:
Check the KM2A and KM2B contactors.Check the auxiliary contacts of the con-tactors. Is there a problem with these?
Replace the defective part
YES
Reset the PLC and restart in coolingmode. Do the contactors turn on? Both?
Problem in the commandof the wiring. Check
the wiring between thecontactor wiring and theexit card of the contactorand the PLC exit card.If the problem goes on,
contact Guinault-Lebrun
YE
S
Is light 0 of thesecond card DI12DEduring the 5 secondsbefore the default?
Problem of infor-mation return ofthe PLC. Check
the wiring betweenthe auxiliary con-tact and the PLC.
If the problemgoes on, contactGuinault-Lebrun
YE
S
Problemwith the
PLC.ContactGuinault-Lebrun
NO
NO
NO
– 151 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D013
CAUSE: The PLC detected a default on the Danfoss economizer regulator(AKCC550)
TYPE: Stop of the unit in cooling mode
SOLUTION:
Is light 6 on the on theDM72FO card of the PLC on?
Check if the contact on theterminals 7 and 9 of the
regulator AKCC550 is open.
Check the wiringbetween the OTB andthe AKCC550 regu-lator at terminals 7
and 9 of the regulator.If problem goes on con-tact Guinault-Lebrun ?
YE
S
Default of theAKCC550.
Send the code dis-played on the screenof the AKCC550 toGuinault-Lebrun .
NO
YES
The default disappeared. Reset thePLC with the maintenance button
and restart the unit with the selectionmode. Check if the default occurs
again and under which circumstances.
NO
D014
CAUSE: The PLC reduced the capacity of the compressor to limit the currentconsumption.
TYPE: Information
SOLUTION: This is no default. The PLC limits the use of the unit under thenormal working conditions.
– 152 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D015
CAUSE: Failure comes from the speed controller of the condenser SC3
TYPE: Stop of the unit in cooling mode
SOLUTION: look at the alarm on the speed controller by the PLC display (SeeChapter 2)
.
D016
CAUSE: The QD3 circuit breaker switched off.
TYPE: Stop of the unit in cooling mode
SOLUTION:
Did the QD3 circuitbreaker switch off?
Restart the QD3 circuit breaker.Reset the PLC.
Restart the group measuring thevalue of the current consumed by
the frequency driver SC3 (after thecircuit breaker). If the problemgoes, contact Guinault-Lebrun .
YES
Does the auxiliary contactQD3 work well? (measure
with a ohm-meter off power)
Check the wiringat the PLC card
DM72F0 terminal12. If the problemgoes on, contact
Guinault-Lebrun .
YE
S
Replace the QD3auxiliary contact.
NO
NO
– 153 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D019
CAUSE: The number of successive start of the compressor is larger than 6 inan hour.
TYPE: Stop of the unit in cooling mode
SOLUTION: - Reset the unit.- Restart the unit.- Check the low pressure.- Check that there is no leak in the cooling circuit.- If the problem goes on, contact Guinault-Lebrun .
– 154 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
D020
CAUSE: The PLC detected a default with the internal protection of the com-pressor (Kriwan).
TYPE: Stop of the unit in cooling mode.
SOLUTION:
Is light 9 of the first card(DI12DE) of the PLC on?
The default is no morethere. Reset and check
the compressor working.If the problem goees on,contact Guinault-Lebrun
YES
Cut the current with theIs1 for 10 seconds. Reset
the Is1 and the PLC.Is the default still there
Check the wiringsbetween second cardDI12DE and connec-tions x3-1 and x3-2
Check cable LEB36. Ifthe problem goes on,
contact Guinault-Lebrun
YE
S
The default is no morethere. Reset and check
the compressor working.If the problem goes on,
contact Guinault-Lebrun
NO
NO
D021
CAUSE: The PLC detected a default with the high pressure pressure swtitch.
TYPE: Stop of the unit in cooling mode.
SOLUTION: - Reset the HP pressure switch (black button).- Reset the PLC.- Restart the unit → Check the operating pressure values.- Identify when the default occurs again.- Contact Guinault-Lebrun .
– 155 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Cooling Mode
That section presents a non-exhaustive list of problems that can occur when the unit is in coolingmode and their solution.
Cooling compressor fails to start (red lamp is off).
Is the fan in operation
Check the circuitbreaker for the opera-tion of the PLC QD10
YES
Is there a partial or com-plete loss of refrigerant charge.
Check the pressure onthe manometers PI1
and PI2. This pressuremust be up to 2,5 Bar topermit the operation ofthe compressor.Repair
leak and recharge system.
YE
S
Is there a defaulton the pressure
sensor PT4?
Check the valueof the PT4 onthe PLC and
compare with themanometer PI2.
YE
S
See nextPage.
NO
NO
NO
– 156 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Suction pressuretoo low (internalpressure switch).
Automatic restartof the compressorwhen the pressureis up to 1,5 bar.
YES
Waiting for short delay?Automatic restartof the compressorafter 2 minutes.
NO
Noisy compressor.
Is one or more expansionvalve in ”open” position (in-
dicated by abnormallycold suction line)?).
Check superheat.Adjust or replacevalve. Control the
operation of the directexpansion regulator.
YES
If electrical repair has beenmade to unit, check compres-sor electrical power 3-phase
for proper phase connections.
NO
– 157 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
System cooling output poor.
Is there flash gas inliquid refrigerant line(indicated by a foamyor bubbly sight glass)?
Locate and repair leakin refrigerant system.Recharge refrigerant
to proper levels.
YES
Is the electronic expansionvalve not running correctly?
Control the opera-tion of the direct
expansion regulator.
YE
S
Is the drier/strainerclogged (feels cool
to the touch)?
Replacedrier/strainer
YE
S
See nextPage.
NO
NO
NO
– 158 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Is the evaporator coil dirty?
Clean coil.
YES
High ambient temperature(more than 40oC)
and/or air flow too high.
NO
Discharge pressure too high.
Is the condenserair flow too low?
Check speed controllerof the condenser.
chack fan operation.clean coil if required
YES
Is there air or any other non-condensable gas in system?
Evacuate system andrecharge. Install
new drier/strainer.
YE
S
If there is an over-charge of refrigerant,
purge or removeexcess from highside of system.
NO
NO
– 159 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Discharge pressure too low.
Is there a Lack of refrigerant (in-dicated by bubbles in sight glass)?
Repair leak and recharge system.
YE
S
Suction pressure too high.
Is the expansion valve not running correctly?
Repair or replace valve, if necessary.Controlthe operation of the direct expansion regulator.
YE
S
– 160 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Suction pressure too low.
Is there a lack of refrigerant(flash gas in liquid refrigerant
line indicated by a foamyor bubbly sight glass)?
Repair leakand recharge.
YES
Is the drier/strainer clogged(feels cool to the touch)?
Replacedrier/strainer.
YE
S
Is the expansionvalve not running
correctly?
Replace valveif necessary.Control theoperation ofthe directexpansionregulator.
YE
S
Is the Air sideof coil dirty?
Cleancoil.
YE
S
If the air flowis too low,
check the airflow at theunit outlet.
NO
NO
NO
NO
– 161 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Ventilation mode
The fan is running but the operation is not correct :- Air flow too low- Vibrations- Abnormal noise
– 162 –
Prope
rty o
f Am
erica
n Airli
nes
Operating ManualGF10 COMBOV. August 2016 Confidential
Maintenance
Operating modes starting
Engine is running and voltage is good but it is impossible to start the unit’s operatingmodes (cooling or ventilation).
Is the circuitbreaker of the
PLC off (QD10)?
Engage thecircuit breaker ofthe PLC. Check
the intensity.
YES
Are the fuses ofthe current trans-
former burnt?
Replace by new fuses (4AaM). Check the intensity.
YE
S
Is the circuitbreaker 220
V off (QD4)?
Engagethe circuit
breaker220 V.
Check theintensity.
YE
S
If the PLC isfaulty (red lamp inthe PLC), then :- Cut the circuit
breaker of the PLC.- Retry to engage
this circuit breaker.- If the PLC is
always in default, itmust be replaced.
NO
NO
NO
– 163 –
Prope
rty o
f Am
erica
n Airli
nes