Page 1: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Pressure Control

Liquid Level

Control

Temperature

Control

Glycol Pump

ControlValves

Page 2: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Temperature Controllers

Page 3: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Indirect Thermostat

T12

Negative feedback forlinear output 5 to 30 psi air or

gas supply pressure

Stainless steel housing

Bi-metal sensing elementfor accurate control

Output pressure proportionateto temperature at any setting

Single adjustment overWide temperature range: T 12 -30 to 400oF HT 12 -30 to 700oF

Page 4: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

? Direct or Indirect ?

Direct Mode Indirect Mode

Rising Temperature Rising Temperature

Rising Output Falling Output

Direct Indirect

Page 5: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Indirect Thermostat

Indirect

Page 6: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Thermostat with Separable Socket

Maximum Working Pressure

Without Separable Socket 500 psiWith Separable Socket 4000 psiWith Special Separable Socket 7000 psi

Page 7: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Direct Acting Thermostat

T 12DASupply Output

Direct

Page 8: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

T 12DA Thermostat

Output

Supply

Indirect

Reversed for Indirect Throttle Mode

Page 9: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

High Temperature Thermostat

HT 12Output

Supply

Indirect

Page 10: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Direct Snap Thermostat

T 12S

OutputSupply

Direct

Page 11: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Indirect Snap Thermostat

T 12DASOutput

Supply

Indirect

Page 12: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Indirect Throttle Thermostat

T 12T

Output

Supply

Indirect

Page 13: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Direct Throttle Thermostat

T 12TDA

Output

Supply

Direct

Page 14: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Direct Semi-Throttle Thermostat

T 12DAT

Output

Supply

Direct

Page 15: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Indirect High Temperature Shut-Down

T 12MOutput

SupplyIndirect

Page 16: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Direct Low Temperature Shut-Down

T 12DAM

Output

SupplyDirect

Page 17: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

High Temperature Pilot Guard

HT 12PG

Output

Supply

Direct

Page 18: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Typical Installation

High temperatureshutdown thermostat

Burner controlthermostat

Safety shutdown

valve

Burnervalve

Main burner

Pilot

Pilot GuardthermostatInstrument Gas

Page 19: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

High temperatureshutdown thermostat

Burner controlthermostat

Safety shutdown

valve

Burnervalve

Main burner

Pilot

Pilot Guardthermostat

Instrument Gas

Low liquid shutdown pilot

Typical Burner Control Installation

Page 20: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Trouble Shooting

SYMPTOM CAUSE

• Erratic temperature changes

•Continuous venting

• Bent sensing element (element should be centered in base and should “ring”)

• Incomplete immersion of probe

•Dirty pilot plug seat•Hole in diaphragm•Weak pilot plug spring•Faulty ‘O’ ring

Page 21: Pressure Control Liquid Level Control Temperature Control Glycol Pump Control Valves.

Trouble Shooting

• To check small seat: increase temperature setting several degrees and see if venting stops.

• To check large seat: decrease temperature setting several degrees and see if venting stops.

• Replace pilot plug and seats if unable to stop venting by cleaning seats.