Top Banner
PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security • Building Layout • Specific CBR Attack Prevention Recommendations • Securing Outdoor-Air Intakes • Ventilation and Filtration • Emergency Plans, Policies, and Procedures
24

PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Mar 28, 2015

Download

Documents

Zoie Roback
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

PowerPoint® PresentationPowerPoint® Presentation

Chapter 14Chapter 14Homeland SecurityHomeland Security

Homeland Security • Building Layout • Specific CBR Attack Prevention

Recommendations • Securing Outdoor-Air Intakes • Ventilation and Filtration •

Emergency Plans, Policies, and Procedures

Homeland Security • Building Layout • Specific CBR Attack Prevention

Recommendations • Securing Outdoor-Air Intakes • Ventilation and Filtration •

Emergency Plans, Policies, and Procedures

Page 2: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

PowerPoint® PresentationPowerPoint® Presentation

Chapter 14Chapter 14Homeland SecurityHomeland Security

Homeland Security • Building Layout • Specific CBR Attack Prevention

Recommendations • Securing Outdoor-Air Intakes • Ventilation and Filtration •

Emergency Plans, Policies, and Procedures

Homeland Security • Building Layout • Specific CBR Attack Prevention

Recommendations • Securing Outdoor-Air Intakes • Ventilation and Filtration •

Emergency Plans, Policies, and Procedures

Page 3: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Because the U.S. Department of Homeland Security (DHS) houses the Federal Emergency Management Agency (FEMA), the DHS is responsible for preparedness, response, and recovery to natural disasters as well as man-made events.

Because the U.S. Department of Homeland Security (DHS) houses the Federal Emergency Management Agency (FEMA), the DHS is responsible for preparedness, response, and recovery to natural disasters as well as man-made events.

Page 4: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

A CBR attack employs chemical, biological, or radiological (CBR) agents to strike a building or area.

A CBR attack employs chemical, biological, or radiological (CBR) agents to strike a building or area.

Page 5: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

The airflow patterns and dynamics in a building are of particular concern, specifically the heating, ventilating, and air conditioning (HVAC) systems of a building as an entry point and distribution system for hazardous contaminants, particularly CBR agents.

The airflow patterns and dynamics in a building are of particular concern, specifically the heating, ventilating, and air conditioning (HVAC) systems of a building as an entry point and distribution system for hazardous contaminants, particularly CBR agents.

Page 6: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

When sufficient questions or surprises arise from a building walk-through, an independent evaluation by a qualified HVAC professional is used to establish a useful baseline.

When sufficient questions or surprises arise from a building walk-through, an independent evaluation by a qualified HVAC professional is used to establish a useful baseline.

Page 7: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Poorly executed efforts and security measures to protect a building from a CBR attack can have adverse effects on a building’s indoor air quality.

Poorly executed efforts and security measures to protect a building from a CBR attack can have adverse effects on a building’s indoor air quality.

Page 8: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Physical security measures such as locking the doors to mechanical rooms are low cost, but other physical security measures such as increased security personnel or packaged X-ray equipment are more costly.

Physical security measures such as locking the doors to mechanical rooms are low cost, but other physical security measures such as increased security personnel or packaged X-ray equipment are more costly.

Page 9: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Securing the outdoor-air intakes is a critical line of defense in limiting an external CBR attack on a building. Outside-air intakes must be located to allow for security.

Securing the outdoor-air intakes is a critical line of defense in limiting an external CBR attack on a building. Outside-air intakes must be located to allow for security.

Page 10: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

When relocation of outdoor-air intakes is not feasible, intake extensions can be used to extend or enclose intakes in order to improve security without creating adverse effects on HVAC system performance.

When relocation of outdoor-air intakes is not feasible, intake extensions can be used to extend or enclose intakes in order to improve security without creating adverse effects on HVAC system performance.

Page 11: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Outside-air intakes have hoods sloped at 45° and a mesh screen that is used to prevent objects from being thrown into the intake.

Outside-air intakes have hoods sloped at 45° and a mesh screen that is used to prevent objects from being thrown into the intake.

Page 12: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Perimeter barriers such as iron fencing or other barriers that do not obscure visual detection of terrorist activities prevent public access to outdoor-air intake areas.

Perimeter barriers such as iron fencing or other barriers that do not obscure visual detection of terrorist activities prevent public access to outdoor-air intake areas.

Page 13: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

All outdoor-air intake buffer zones must be monitored by physical security, closed-circuit television (CCTV), security lighting, or intrusion-detection sensors.

All outdoor-air intake buffer zones must be monitored by physical security, closed-circuit television (CCTV), security lighting, or intrusion-detection sensors.

Page 14: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Access to secure areas of a building must be strictly controlled by key locks, keycards, or key-coded doors with the access to keys, keycards, and key codes strictly maintained.

Access to secure areas of a building must be strictly controlled by key locks, keycards, or key-coded doors with the access to keys, keycards, and key codes strictly maintained.

Page 15: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

To prevent the widespread dispersion of a contaminant released within a building’s lobby, mailroom, or loading dock area, the HVAC system for these areas must be isolated.

To prevent the widespread dispersion of a contaminant released within a building’s lobby, mailroom, or loading dock area, the HVAC system for these areas must be isolated.

Page 16: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Return-air grills must be inaccessible yet in an observable location, have increased security presence via more security personnel or security cameras, and have all furniture and visual obstructions removed from areas near return-air grills.

Return-air grills must be inaccessible yet in an observable location, have increased security presence via more security personnel or security cameras, and have all furniture and visual obstructions removed from areas near return-air grills.

Page 17: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Information on building mechanical, electrical, vertical transport, fire and life-safety, and emergency operation systems must be strictly controlled.

Information on building mechanical, electrical, vertical transport, fire and life-safety, and emergency operation systems must be strictly controlled.

Page 18: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Many building automation systems have the capability to regulate airflow and pressures or shut down an HVAC system within a building in the event of an outdoor CBR emergency.

Many building automation systems have the capability to regulate airflow and pressures or shut down an HVAC system within a building in the event of an outdoor CBR emergency.

Page 19: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Manipulation of a building’s HVAC system could minimize the spread of a CBR agent. Building personnel must be trained to recognize a terrorist attack quickly and to know when to initiate certain control measures, such as maintaining pressure in stairwells, unless the stairwell is known to be the source of the CBR agent.

Manipulation of a building’s HVAC system could minimize the spread of a CBR agent. Building personnel must be trained to recognize a terrorist attack quickly and to know when to initiate certain control measures, such as maintaining pressure in stairwells, unless the stairwell is known to be the source of the CBR agent.

Page 20: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Particulate air filters used for biological and radiological particles are not effective for gases and vapors typically used in chemical attacks. Gases and vapors require adsorbent filters that contain activated carbon or another adsorbent-type medium.

Particulate air filters used for biological and radiological particles are not effective for gases and vapors typically used in chemical attacks. Gases and vapors require adsorbent filters that contain activated carbon or another adsorbent-type medium.

Page 21: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Filter efficiency increases as a filter loads with contaminants.

Filter efficiency increases as a filter loads with contaminants.

Page 22: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Nonducted return-air systems commonly use hallways or spaces above dropped ceilings as return-air paths or plenums.

Nonducted return-air systems commonly use hallways or spaces above dropped ceilings as return-air paths or plenums.

Page 23: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

Damper and smoke damper leakage ratings are available from manufacturers’ specifications, Underwriters Laboratory (UL), and the Air Movement and Control Association International, Inc. (AMCA).

Damper and smoke damper leakage ratings are available from manufacturers’ specifications, Underwriters Laboratory (UL), and the Air Movement and Control Association International, Inc. (AMCA).

Page 24: PowerPoint ® Presentation Chapter 14 Homeland Security Homeland Security Building Layout Specific CBR Attack Prevention Recommendations Securing Outdoor-

Chapter 14–Homeland SecurityChapter 14–Homeland Security

A shelter-in-place is a small, interior room of a building with few or no windows where individuals can take refuge.

A shelter-in-place is a small, interior room of a building with few or no windows where individuals can take refuge.