    Dead-Tank Oil Circuit Breaker 

    Recommended Tests:Power-Factor Time & TravelContact Resistance

    CGE, 253 kV

    type FKG

  • 8/19/2019 Oil Circuit Breakers PF Test

    3/35

    In Simplified Terms:

    Two Bushings Per Phase

    Contact Assembl !"nterru#ter$

    O#erating Rod !%ertical or Rotar$

    "nsulated uide Assembl !O#erating Rod$

    A %olume o' Oil

    Tank (iner 

    Oil Circuit Breaker Tests

  • 8/19/2019 Oil Circuit Breakers PF Test

    4/35

    Dead Tank OilCircuit Breaker

    Bushings

    uide Assembl

    Tank (iner 

    Contact Assembl

    !"nterru#ter$ (i't Rod

    Oil

    (i't Rod uide

  • 8/19/2019 Oil Circuit Breakers PF Test

    5/35

     

    ) Overall Circuit Breaker Test  a* +i, O#en Breaker !+T$

      b* Three Closed Breaker !+T$) Tank (oss "nde,

    ) Bushing Tests

    ) Oil +am#le Test

    ) iscellaneous

    ) Diagnostic

    Doble Recommended Tests!inimum$

  • 8/19/2019 Oil Circuit Breakers PF Test

    6/35

    Breaker Voltage Rating Test Voltage

    ./-k% and Above .0

    1*2 and 1*/ k% /

    /-k% and Below 2

    Recommended Doble Test %oltagesOil Circuit Breakers

  • 8/19/2019 Oil Circuit Breakers PF Test

    7/35

    Overall Test ProcedureOil Circuit Breakers

    Test

    No.

    Breaker 

    Position

    Test

    Mode

    Bushing

    Energized

    Bushing

    Floating1 OPEN GS 1 2

    2 OPEN GS 2 1

    3 OPEN GS 3 !

    ! OPEN GS ! 3

    5 OPEN GS 5 "

    " OPEN GS " 5

    # C$OSE% GS 1 & 2 '

    ( C$OSE% GS 3 & ! '

    ) C$OSE% GS 5 & " '

  • 8/19/2019 Oil Circuit Breakers PF Test

    8/35

    O#en Circuit Breaker Test

    +tresses3 .$ . Bushing

    2$ . "nterru#ter 

    4$ (i't Rod uide

    5$ To# o' (i't Rod !uide

    Assembl$

    +T round

    " &6 eter  round (ead

    7% (ead

    No Low Voltage Lead Reuired

  • 8/19/2019 Oil Circuit Breakers PF Test

    9/35

  • 8/19/2019 Oil Circuit Breakers PF Test

    10/35

    Closed Breaker Test

    +tresses3 .$ 2 Bushing

    2$ (ower (i't Rod

    4$ Oil

    5$ Tank (iner 

    +T round

    " &6 eter  round (ead

    7% (ead

    Oil

  • 8/19/2019 Oil Circuit Breakers PF Test

    11/35

    Closed Breaker Test

    a8or Contribution o' 6atts-(oss3

     Bushing !2$ Oil

     (ower (i't-Rod Tank (iner 

    (esser Contribution o' 6atts-(oss3

     Contact Assembl !"nterru#ter$ (i't-Rod uide

  • 8/19/2019 Oil Circuit Breakers PF Test

    12/35

    Tank (oss "nde,! T(" $

    )Bushings Com#rise the (argest Portion o' the Oil

    Circuit Breaker "nsulation +stem

    )A Bad Bushing 6ill Be "ndicated in the O#en and

    Closed Breaker Tests*

    )To Anal:e the Condition o' the "nternal Parts o' the

    OCB; Tank (oss "nde, !T("$ was Develo#ed

    T(" < Closed Breaker 6atts - !Σ O#en Breaker 6atts $

    !For =ach Phase$

  • 8/19/2019 Oil Circuit Breakers PF Test

    13/35

  • 8/19/2019 Oil Circuit Breakers PF Test

    14/35

    Tank (oss "nde,3 Com#onent Failures

    TLI < (ower (i't Rod> Oil >Tank (iner - 2 "nterru#ters - (i't Rod

      uides - 2 To# o' (i't Rods

    6hat would ha##en to T(" i'3

    6ater Content o' the Oil "ncreases@** Carbon is Collecting on the "nterru#ters@ Tank (iner Becomes +aturated 6ith 6ater 

    (i't Rod uide is Deteriorating Due to Corona Activit@ 

  • 8/19/2019 Oil Circuit Breakers PF Test

    15/35

    uideline Tank-(oss "nde,es !T("$Oil Circuit Breakers

    Tank (oss "nde,

    Above Between -.0 m6 -.0 m6 to >1*/ m6 Between >1*/ m6 Above

     -./ m6 and -./ m% and >./ m6 >./ m6

    Above Between -0*.0 6 -0*.0 6 to >0*0/ 6 Between >0*0/ 6 Above

    -0*20 6 and -0*20 6 and >0*.0 6 >0*.0 6

    "nvestigate Retest ?ormal 'or most Retest "nvestigate

    "mmediatel on a more breaker t#es* Place on a more "mmediatel

      'reuent basis* on a normal routine 'reuent basis*

    test schedule*

    (i't-Rod guide assembl; contact (i't rod; Tank Oil; tank  assembl !"nterru#ter$; and u##er liner; and au,iliar contact

     #ortion o' li't rod* su##ort insulation*

    2*/ k%

    .0 k%

  • 8/19/2019 Oil Circuit Breakers PF Test

    16/35

    Calculating Tank (oss "nde,

    TLI# $ CB%& ' (OB%)*OB%!+ $ ,-!./ ' (,-)/)* ,-!!&+ $ ' ,-)0!%

    TLIB $ CB%1 ' (OB%.*OB%2+ $ ,-!)2 ' (,-!&)* ,-),/+ $ ' ,-)/.%

    TLIC $ CB%3 ' (OB%0*OB%/+ $ ,-)0. ' (,-,&)* ,-,3)+ $ ' ,-,,3%

  • 8/19/2019 Oil Circuit Breakers PF Test

    17/35

    Analsis o'

    Oil Circuit Breaker Condition

  • 8/19/2019 Oil Circuit Breakers PF Test

    18/35

    Check "' Breaker O#erated

  • 8/19/2019 Oil Circuit Breakers PF Test

    19/35

    Bushing Problem Found

    = T#e 9 Bushings

  • 8/19/2019 Oil Circuit Breakers PF Test

    20/35

    Bushing Problem Found

    = T#e 9 Bushings

  • 8/19/2019 Oil Circuit Breakers PF Test

    21/35

    Check Condition o' Bushings

    ) Bus"ings Comprise t"e Largest 4ortion of

    t"e Oil Circuit Breaker Insulation S5stem

    ) # Bad Bus"ing %ill S"ow 6p in Bot" t"eOpen and Closed Circuit Breaker Tests

  • 8/19/2019 Oil Circuit Breakers PF Test

    22/35

    Tank-(oss "nde,

    EXAMPLE # 1 I (A! "atts PF

    1 ($%en! 1.1&' '.' '.)1

    * ($%en! 1.1&' '.' '.)1

    (+losed! *.,'' '.11 '.&'

    TLI $ ,-)) ' (,-,& * ,-,&+ $ ' ,-,. watts

    Comments: Test results are normal-

  • 8/19/2019 Oil Circuit Breakers PF Test

    23/35

    78ample 9! "!mA$ 6atts PF

    .!OP=?$ .*./ 0*01 0*.

    2!OP=?$ .*2 0*22 .*4

    1!C(O+=D$ 2*4 0*.4 0*/

    T(" < 0*.4 - !0*01 > 0*22$ < -0*.

    Comments3

    7igh ?egative T(" E6et "nterru#ter on Bushing ?o* 2

    or 7igh (osses ?ear Bushing ?o* 2

    a be the (i't Rod uide Assembl

    7igh Power Factor on Bushing ?o* 2; Test Bushing to Con'irm

    Tank-(oss "nde,

  • 8/19/2019 Oil Circuit Breakers PF Test

    24/35

    78ample 9. "!mA$ 6atts PF

    .!OP=?$ .*./ 0*01 0*.

    2!OP=?$ .*2 0*22 .*4

    1!C(O+=D$ 2*4/ 0*2 .*..

    T(" < 0*2 - !0*01 > 0*22$ < -0*04

    Comments3

     ?ormal T("

    Bushing ?o* 2 a Be Contaminated*

    Test Bushing to Con'irm*

    Tank-(oss "nde,

    k d

  • 8/19/2019 Oil Circuit Breakers PF Test

    25/35

    78ample 92 "!mA$ 6atts PF

    .!OP=?$ .*2 0*./ .*2/

    2!OP=?$ .*2 0*./ .*2/

    1!C(O+=D$ 2*4 0*.. 0*5

    T(" < 0*.. - !0*./ > 0*./$ < -0*.G

    Comments3

    7igh ?egative T("

    Bushing a Be OH -Test to Con'irm

    Possible Problems3)Deteriorated O#erating-Rod uide

    )9##er Portion o' (i't Rod)Contaminated "nterru#ter Assemblies

    Tank-(oss "nde,

    T k ( " d = l DTA

  • 8/19/2019 Oil Circuit Breakers PF Test

    26/35

    Tank-(oss "nde, =,am#le - DTA

    eneral =lectric

    FH-../-/000-I

    4 Tanks

    Oil Ci i B k T +

  • 8/19/2019 Oil Circuit Breakers PF Test

    27/35

    easure "; 6 and PF

    Calculate Tank-(oss "nde, !T("$

    T(" < Closed OCB 6atts - +um 2 O#en OCB 6atts

    PF Corrected 9sing Bushing T#e and Ambient

    Tem#erature

    "nter#ret Test Results on a Per Phase Basis

    Oil Circuit Breaker Test +ummar

    6 d d O h " l i b

  • 8/19/2019 Oil Circuit Breakers PF Test

    28/35

    6ood and Other "nsulating embers

    )The "nsulating Pro#erties o' 6ood or Other

    "nsulating embers Can Be easured

    )This Dielectric easurement is a %aluable Tool6hen "nvestigating 7igh Power Factors From Other

    Dielectric Tests)=,am#le3 7igh ?egative T(" 6hich a "ndicate

    a Breaker (i't Rod Problem

  • 8/19/2019 Oil Circuit Breakers PF Test

    29/35

    6 d d Oth " l ti b

  • 8/19/2019 Oil Circuit Breakers PF Test

    30/35

    6sed

    Breaker (i't-Rods3

    0*20 6attsJ4 K .0 k%

    =9 .2*/ 6J4 K 2*/ k%

    Plastic Coated embers3

    0*./ 6attsJ4 K .0 k%

    =9 LG*/ 6J4 K 2*/ k%

    New or 78cellent Condition

    0*02 6attsJ4 K .0 k%

    =9 L. 6J4 K 2*/ k%

    6ood and Other "nsulating embers

    Recommended 4ower actor Test Limits3

    " t t " ti ti T t

  • 8/19/2019 Oil Circuit Breakers PF Test

    31/35

    "nterru#ters - "nvestigative Tests

    7ouseholdTin-Foil

    Bushing

    oveable Contact3 =nergi:e 'or TestBreaker Closed

    Bare 6ireTo 7old Foil

    in Place

    (% (ead !9+T$

    " t t " ti ti T t

  • 8/19/2019 Oil Circuit Breakers PF Test

    32/35

      4ower actors for Interrupters  (;eneral ;uideline+

    ood3 .0-40

    MuestionableJre area3 40-/0

    Bad3 N/0

    )Alternate Test ethod3

    6ra# Additional Tin Foil Around the Bottom o' the"nterru#ter 6ith the Breaker in the O#en Position

    "nterru#ters - "nvestigative Tests

    R l T t

  • 8/19/2019 Oil Circuit Breakers PF Test

    33/35

    Recloser Tests

    )Reclosers Are Tested as Oil Circuit Breakers

    )"' 9ne,#ected Results are Obtained; Recloser a

    7ave a Resistor Assembl Between (ower Bushing

    Terminals)Per'orm Alternate Tests .- b uarding One

    Bushing and =nergi:ing the O##osite Bushing on the

    +ame Phase

    )Alternate Tests "nclude Three 9+T Tests - One PerPhase

    Alt t R l T t .

  • 8/19/2019 Oil Circuit Breakers PF Test

    34/35

    +T uard

    "&6 eter  round (ead

    7igh %oltage (ead

    +tresses . Bushing

    (ow %oltage (ead

    uard

    Alternate Recloser Tests .-

    Alt t R l T t .0 .2

  • 8/19/2019 Oil Circuit Breakers PF Test

    35/35

    Alternate Recloser Tests .0-.2

    9+T

    "&6 eter 

    round (ead

    7igh %oltage (ead

    +tresses "nterru#ter

    Assembl

    (ow %oltage (ead

    uard